ATTACHMENT A - SAMPLE REPORT.pdf
PDF 383 KB Posted
- Solicitation number
- 36C25225Q0042
About this file
This document is a Test & Balance Report for the VA Hospital - 5th Floor - Electrophysiology Lab project located in Milwaukee, WI. The report certifies that the systems have been balanced to their optimum performance capabilities, and includes details on the air change and room pressure tests, as well as the air distribution test results for the AHU-1 system serving the 5th floor.
The related federal contract opportunity is for Solicitation Number 36C25225Q0042, "H141--TEST & BALANCE CRITICAL CARE AREAS BASE + 4 OYS", issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12. The contractor shall provide labor, supervision, materials and equipment to clean grilles and fan systems, conduct Air Change (ACH) Testing, and replace filters at the Edward Hines Jr VA Hospital in Hines, IL.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25225Q0042_2.docx | DOCX document | |
| S02 36C25225Q0042_2.pdf | ||
| ATTACHMENT B - NDA VA-0752.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T E S T & B A L A N C E R E P O R T
Project Name: VA Hospital – 5th Floor – Electrophysiology Lab Location: Milwaukee, WI Architect: N.A.
Engineer: PSJ Engineering Mechanical Contractor: N.A.
Project Number: 118-332
This is to certify that . has balanced the systems described herein to their optimum performance capabilities. The testing and balancing have been performed in accordance with TABB recommended procedures and principles and the results of these tests are herein recorded.
03/20/19 Dated
Randall Staron Accustar Air Balance, Inc.
TABB Supervisor
BB000051S
March 31, 2021 Printed: 02/18/2019
Date 03/20/19
Project Name: VA Hospital – 5th Floor – Electrophysiology Lab System Name: AHU-1 Floor Number 5th
A I R C H A N G E A N D R O O M P R E S S U R E T E S T S H E E T
Room Use Supply CFM Exhaust CFM Room Air Changes Per Hr Room Number Design Actual Design Actual Volume FT Design Actual Pressure
5535 EP Lab 1750 1874 1500 1156 4850 21.6 23.2 POS
Remarks
VHAMIWMaviS Text Box in.
w.c.
VHAMIWMaviS
List code and/or industry standard tested to (NFPA, FGI, etc.
Date 03/20/19
Project Name: VA Hospital – 5th Floor – Electrophysiology Lab System Name: AHU-1 Floor Number 5th
A I R D I S T R I B U T I O N T E S T S H E E T
Terminal Room Terminal Factor Design Test - FPM or CFM Final Number Number Type Size FPM CFM Test 1 Test 2 Test 3 FPM CFM
Supply 1750 1874
1 EP Lab SW 48” x 4” 1.0 - - 93 93
2 EP Lab SW 48” x 4” 1.0 - - 119 119
3 EP Lab SW 48” x 4” 1.0 - - 165 165
4 EP Lab SW 48” x 4” 1.0 - - 157 157
5 EP Lab SW 48” x 4” 1.0 - - 174 174
6 EP Lab SW 48” x 4” 1.0 - - 173 173
7 EP Lab CD 36” x 24” 1.0 - - 205 205
8 EP Lab CD 36” x 24” 1.0 - - 200 200
9 EP Lab CD 36” x 24” 1.0 - - 194 194
10 EP Lab CD 36” x 24” 1.0 - - 138 138
11 EP Lab CD 24” x 24” 1.0 - - 160 160
12 EP Lab CD 24” x 24” 1.0 - - 96 96
13 Control Rm CD 24” x 24” 1.0 - - 311 311
Exhaust
1 EP Lab LLE 24” x 12” 1.1 - - 502 552
2 EP Lab LLE 24” x 12” 1.1 - - 549 604
3 Control Rm EG 24” x 24” 1.1 - - 307 338
Remarks
VHAMIWMaviS
List code and/or industry standard tested to (NFPA, FGI, etc.