Attachment A - Electrical Power Distribution Equipment and Cables Inventory.pdf

PDF 241 KB Posted

Attached to
H361--Electrical Power Distribution System Inspection Federal contract opportunity
Solicitation number
36C25222Q0262
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12

About this file

This document includes an attachment and solicitation related to an electrical power distribution system inspection contract opportunity. The attachment provides an inventory of electrical equipment and components to be maintained, inspected, and tested under the scope of work. This includes various switchgear assemblies, transformers, switches, circuit breakers, protective relays, cables, grounding systems, and panelboards located across multiple buildings on site. The solicitation seeks a contractor to provide all labor, materials, supplies, equipment, management and supervision needed to inspect, test and adjust the entire electrical power distribution system at the VA Illiana Health Care Center in Danville, Illinois, in accordance with the statement of work and delivery schedule. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12.

View the file

Other files for this federal contract opportunity

Other files attached to H361--Electrical Power Distribution System Inspection, newest first.
File Type Posted
Attachment E - Vermilion County WD 2015-5021 (Rev-16) dated 12.27.2021.pdf PDF
Attachment B - VHA Directive 1028 Facility Electrical Power Systems.pdf PDF
Attachment C - Electrical Drawings.zip ZIP file
Attachment D - VA Notice of Limitations on Subcontracting Form.pdf PDF
S02 - 36C25222Q0262_1 Final.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment A - Inventory of Electrical Power Distribution Equipment and Cables to be

Maintained, Inspected, and/or Tested Under This Scope of Work

1) Switchgear Assemblies, Low-Voltage.

Location Device ID Current Rating

B14 MDP 1200

B58 Switchgear 58 3200

B98 B98 Service (indoor) 2000

B98 B98 Service (outdoor) 2000

B98 B98 Service (outdoor) 2000

B104 104 Switchboard 1200

B140 MDP 1200

2) Transformers, Liquid-Filled.

Transformer kVA Primary Secondary Circuit

T/13 225 4,160 V 208 V 2

T/14 500 4,160 V 208 V 2

T/19 150 4,160 V 208 V 9

T/22 225 4,160 V 208 V 4

T/26

(old T/48)

300 4,160 V 208 V 9

T/30 112.5 4,160 V 208 V 9

T/33 150 4,160 V 208 V 9

T/33A 75 4,160 V 208 V 9

T/39/40 75 4,160 V 208 V 9

T/49 75 4,160 V 208 V 9

T/58A 2,000 4,160 V 480 V 3

T/58B 300 4,160 V 480 V 9

T/60 112.5 4,160 V 208 V 2

T/64/72 225 4,160 V 208 V 9

T/68 75 4,160 V 208 V 9

T/93 150 4,160 V 208 V 2

T/98 1,500 4,160 V 480 V 3

T/100 300 4,160 V 480 V 3

T/101 1,000 4,160 V 480 V 6

T/102 1,000 4,160 V 480 V 5

T/103 1,000 4,160 V 480 V 7

T/104 2,000 4,160 V 480 V 8

T/125 300 4,160 V 208 V 8

T/128/129 300 4,160 V 208 V 2

T/130 150 4,160 V 208 V 2

T/131 150 4,160 V 208 V 2

T/132/133 750 4,160 V 208 V 2

T/140 500 4160 V 208 V 9

3) Switches, Bolted-Pressure, Low-Voltage.

Location Device ID Ampacity

B14 Main 1200

4) Switches, Air, Medium-Voltage, Metal-Enclosed.

Switch Circuit

SW-MH46 2

S&C PMH-9 2

SW-MH26-A 3

SW-MH26-B 4

SW-MH28-A 3

SW-MH28-B 4

SW-MH49-A 3

SW-MH49-B 4

SW-MH34A 8

SW-MH22-A 9

SW-MH43 9

SW-MH25 9

SW-MH48 9

SW-MH54 2

5) Circuit Breakers, Air, Insulated-Case/ Molded-Case.

Location Device ID Trip Rating

B14 Chiller 400

B14 Generator 350

B14 Transfer Switch 400

B19 Main 400

B26 Main 400

B30 Main 400

B58 Generator 800

B60 Main 600

B64/72 Generator 150

B64/72 Main 600

B98 Generator 800

B125 Main 800

B128/129 Generator 800

B128/129 Main 800

B128/129 North 400

B128/129 South 400

B128/129 Spare 400

B130 Main 400

B130 Generator 250

B131 Main 400

B131 Generator 250

B132/133 Generator 600

B140 Generator 400

B140 Generator 100

B140 Generator 100

B140 Main 400

B140 Main 100

B140 Main 100

6) Circuit Breakers, Draw-Out Air, Low-Voltage Power.

Location Device ID Frame Size

B58 58/DP1 800

B58 Alt Source 3200

B58 Bus Duct 800

B58 Chiller CK-1 800

B58 Chiller CK-2 800

B58 58/DP2 800

B58 58/K1 800

B58 Main 3200

B58 MCC-P1 800

B58 MCC-P2 800

B58 58/MSR 800

B58 58/NDP 800

B98 DP-A 600

B98 DP-B 600

B98 DP-C 600

B98 B-PH 600

B98 DSB 1600

B98 Main 3000

B98 MCC 225

B98 MCC 2 800

B98 New Main 2000

B98 Trane Ckt #1 600

B98 Trane Ckt #2 600A

B98 ATS 1 600

B98 ATS 2 600

B101 ATS 101 600

B101 DS-206 800

B101 Main 1600

B101 MCC 600

B101 MDP 600

B101 Spare 600

B101 T-1 600

B101 T-2 600

B101 T-3 600

B101 T-4 600

B101 T-5 600

B101 T-6 600

B102 Chiller 800

B102 Main 1600

B102 MCC 600

B102 PA 6 600

B102 PB 600

B102 Spare 600

B102 MCC 600

B103 PE 600

B103 EMN 800

B103 Main 1600

B103 PF 600

B103 Spare 600

B104 Alt Source 3200

B104 FDR Trane Chiller 600

B104 EM #1 B102 600

B104 EM #2 B103 600

B104 EM #3 B101 600

B104 EM #4 B104 600

B104 FDR EMN 600

B104 EP B125 800

B104 FDR 1 600

B104 FDR 2 600

B104 FDR 3 600

B104 FDR 4 600

B104 FDR 5 600

B104 FDR 6 600

B104 Generator 1400

B104 New Main 3200

B104 Old Main 1600

B104 Panel NX 800

B140 Panel 1N1 200

B140 Panel 1N2 100

B140 Panel 1N3 100

B140 Panel 1N4 100

B140 Panel 2N1 200

B140 Panel 1ER1 400

B140 Panel 1CR1 100

B140 Panel 1LS1 100

B140 Panel SPD 60

7) Protective Relays, Electronic, Medium-Voltage.

Location Device ID Description

B99 RLY-102A GE MULTILIN 350

B99 RLY-104B GE MULTILIN 350

B99 RLY-109A GE MULTILIN 350

B99 RLY-F1 GE MULTILIN 350

B99 RLY-F2 GE MULTILIN 350

B99 RLY-F3 GE MULTILIN 350

B99 RLY-F4 GE MULTILIN 350

B99 RLY-F5 GE MULTILIN 350

B99 RLY-F6 GE MULTILIN 350

B99 RLY-F7 GE MULTILIN 350

B99 RLY-F8 GE MULTILIN 350

B99 RLY-F9 GE MULTILIN 350

B99 RLY-MAIN-1 GE MULTILIN 750

B99 RLY-MAIN-2 GE MULTILIN 750

B99 RLY-TIE GE MULTILIN 750

B99 RLY-UTILITY BASLER BE1-50/51B, Series 100

8) Facility Grounding Systems.

Buildings 14, 19, 22/69, 25, 49, 58, 60, 64/72, 93, 98, 99, 101, 102, 103, 104, 125, 128, 129, 130, 131, 132, 133, 140, 211, 212, 214, & 216.

9) Medium-Voltage Cables

Cable From To Size

Circuit #2 B99 Main Sub T/14, T/48, T/60, T/93, T/128/129, T/130/131, T/132/133

4/0

Circuit #3 B99 Main Sub T/58A 500 MCM

Circuit #4 B99 Main Sub T/98 500 MCM

Circuit #5 B99 Main Sub T/102 4/0

T/103 – T/102 T/103 T/102 4/0

Circuit #6 B99 Main Sub T/101 4/0

T/101 – T/104 T/101 T/104 4/0

Circuit #7 B99 Main Sub T/103 4/0

Circuit #8 B99 Main Sub T/104 4/0

Circuit #9 B99 Main Sub T/26 4/0

T/64/72 – T/26 T/64/72 T/26 4/0

T/19 – T/68 T/19 T/68 4/0

T/30 – T/39/40 T/30 T/39/40 4/0

T/49 – T/33A T/49 T/33A 4/0

SW-MH22A –

T/140

SW-MH22A T/140 4/0

T/58B – T/30 T/58B T/30 4/0

T/64/72 –

T/58B

T/64/72 T/58B 4/0

T/64/72 – T/49 T/64/72 T/49 4/0

*T/99 – B99

Main Sub

T/99 B99 Main Sub *

* T/99 (69 kV / 4.16 kV) and cables to B99 Main Substation busway is owned by Ameren Illinois. Contractor shall coordinate with Ameren.

10) Panelboards & Disconnects (Inspection Only).

Building Equipment ID Volts Size

B14 14/EM 208/120 400

B14 14/MDP 208/120 1200

B14 ATS 208/120 400

B14 T/14 Chiller Disconnect 600 400

B19 T/19 Main Disconnect 600 400

B19 19/MDP1 208/120 400

B19 19/MDP2 208/120 225

B19 19/MDP3 208/120 400

B22 22/MDP-1 (Left) 480 400

B22 22/MDP-2 (Right) 480 400

B25 25/MDP 208/120 400

B33 33/DP-1 208/120 600

B33 33/DP-2 208/120 400

B49 49/MDP 208/120 400

B58 58/MDP 480/277 600

B58 58/H 480/277 400

B58 58/DP2 480/277 250

B58 58/DP1 480/277 600

B58 Chiller Compressor 1&2 480 400

B58 Chiller Compressor 3&4 480 600

B58 58/NE 240/120 400

B58 58/EP4 480/277 250

B60 60/MDP1 208/120 400

B60 60/MDP2 208/120 225

B64 64/MDP 208/120 600

B68 68/MDP1 208/120 200

B93 93/MDP 208/120 400

B93 T1 Primary Disconnect 600 200

B93 T1 Secondary Disconnect 240 60

B98 Main Switchgear 480/277 3000

B98 98/DP-C 480/277 400

B98 98/EDP1 480/277 400

B98 98/EDP2 480/277 400

B98 98/ATS-1 480 400

B98 98/ATS-2 480 400

B98 98/ATS-3 480 400

B98 98/EMCC1 480 600

B98 98/EMCC2 480 600

B98 98/MCC1 480 600

B98 98/MCC2 480 600

B98 98/BPH 480/277 400

B98 98/2DP-A 480/277 400

B98 98/2DP-B 480/277 400

B98 98/DSB 480/277 1200

B98 98/2RP-A1 208/120 250

B98 98/2RP-A2 208/120 250

B98 98/2RP-A3 208/120 250

B98 98/2RP-B1 208/120 250

B98 98/2RP-B2 208/120 250

B98 98/2RP-B3 208/120 250

B98 2DP-A T1 Sec Disconnect 240 400

B98 2DP-B T2 Sec Disconnect 240 400

B98 Trane Ckt #1 Disconnect 480 800

B98 Trane Ckt #2 Disconnect 480 400

B101 101/EMCCA 480 N/L

B101 101/EMCCB 480 N/L

B101 101/MCC 480 N/L

B101 101/MDP-1 480/277 600

B101 101-1 480/277 800

B101 Main Switchgear 480/277 2000

B101 101/A1-A 208/120 250

B101 101/B1-A 208/120 250

B101 101/C1-A 208/120 250

B101 101/F1 480 800

B101 T1 Primary Disconnect 480 200

B101 T1 Sec Disconnect 240 100

B101 T2 Primary Disconnect 480 200

B101 T2 Sec Disconnect 240 100

B101 T3 Primary Disconnect 480 200

B101 T3 Sec Disconnect 240 100

B101 T4 Primary Disconnect 480 200

B101 T4 Sec Disconnect 240 100

B101 T5 Disconnect 480 200

B101 T6 Disconnect 480 200

B102 Main Switchboard 480/277 2000

B102 102/PA 480/277 600

B102 102/PAA 480/277 400

B102 Panel PB 480/277 600

B102 102/J5 208/120 250

B102 102/J6 208/120 250

B102 102/J7 208/120 250

B102 102/SK3 208/120 400

B102 102/EMA2 480 400

B102 102/PP1 480/277 400

B102 102/PP2 480/277 400

B102 102/PP3 480/277 400

B102 102/PP4 480/277 400

B102 102/A 208/120 250

B102 102/B 208/120 250

B102 102/AB 208/120 250

B102 102/C 208/120 250

B102 102/CD 208/120 250

B102 102/E 208/120 250

B102 102/F 208/120 250

B102 102/EF 208/120 250

B102 102/G 208/120 250

B102 102/H 208/120 250

B102 102/GH 208/120 250

B102 102/EAMLS 480/277 250

B102 102/EMACE 480/277 250

B102 102/EMBLS 480/277 250

B102 102/EMBCE 480/277 250

B102 102/MCC 480 N/L

B102 102/EMCC 480 N/L

B102 102/MDP1 480/277 800

B102 102/EDP 480 N/L

B103 Main Switchboard 480/277 1600

B103 103/PF 480/277 600

B103 103/MDP1 480/277 N/L

B103 103/EMCC 480/277 N/L

B103 103/MCC 480/277 600

B104 Main Switchboard 480/277 3200

B104 104/P2 480/277 600

B104 104/EMDP-2 480/277 400

B104 104/EMDP3 208/120 350

B125 125/MDP 208/120 800

B128/129 MDP1 208/120 800

B128/129 EMDP 208/120 400

B128 Panel A-1 208/120 400

B128 Panel A-2 208/120 400

B128 Panel EM-1 208/120 250

B128 Panel EM-2 208/120 250

B129 Panel A-1 208/120 400

B129 Panel A-2 208/120 400

B129 Panel EM-1 208/120 250

B129 Panel EM-2 208/120 250

B130 Panel EDP 208/120 250

B130 Panel NRP1 208/120 150

B130 Panel NRP2 208/120 150

B130 Panel NRP3 208/120 150

B130 Panel ELRP 208/120 150

B130 Panel EPP1 208/120 100

B130 Panel EPP2 208/120 150

B131 Panel EDP 208/120 250

B131 Panel NRP1 208/120 150

B131 Panel NRP2 208/120 150

B131 Panel NRP3 208/120 150

B131 Panel ELRP 208/120 150

B131 Panel EPP1 208/120 100

B131 Panel EPP2 208/120 150

B132 MDP 208/120 600

B133 MDP 208/120 600

B211 211-BP0 480/277 200

B211 211-BP1 208/120 110

B212 212-BP0 480/277 200

B212 212-BP1 208/120 110

B214 214-BP0 480/277 150

B214 214-BP1 208/120 110

B216 216-BP0 480/277 150

B216 216-BP1 208/120 110

B140 AHU-1 208 100

B140 AHU-2 208 60

B140 CU-1A 208 100

B140 CU-1B 208 100

B140 CU-2 208 100

B140 BPP-1 208 100

B140 HU-1A 208 100

B140 HU-1B 208 100

End of Attachment A