This document is a salient characteristics and specifications sheet for an Emergency Lighting Panel issued by the Missouri Basin Region Bureau of Reclamation under Solicitation 140R6026Q0054.

The specification details a FastLite Model FST emergency lighting panel manufactured by Controlled Power Company, with power ratings ranging from 525W to 2.2KW at unity power factor. The system accepts single-phase electrical input at 120V, 277V, or 347V at 60Hz with programmable voltage range capability, and provides matching output voltages with ±5% regulation during full battery discharge across rated loads. Key operational features include a 2-millisecond transfer time to and from battery power, 60Hz frequency stability at ±0.5% during battery operation, and overload capability up to 400% for 4 cycles during battery mode, with peak 1500% inrush rating for LED fixtures. The battery system employs valve-regulated sealed lead acid technology with NFPA 101 compliant automatic self-testing and manual push-to-test capability, providing 90-minute minimum runtime with 12-hour recharge time. The unit achieves up to 98.8% efficiency and includes optional surge protection devices. Communications are supported through an LED display panel or advanced Intellistat TS color touchscreen monitor with USB serial interface and hardwired relay contacts for alarm and battery test functions. Environmental specifications indicate operating temperature range of 20-30 degrees Celsius for optimal battery performance, storage capability at -20 degrees Celsius, and operation up to 6,600 feet elevation without derating. The panel measures 26" W x 53" H and weighs 1,100 pounds, with UL924 and CSA C22.2 certifications, NFPA 101/111 compliance, and ISO 9001:2015 quality certification.

View the file

Other files for this federal contract opportunity

Other files attached to MTE Emergency Lighting, newest first.
File Type Posted
Sol_140R6026Q0054_Amd_0001.pdf PDF
Attachment_B_-_Solicitation_140R6026Q0054_-_Amendment_0001_-_Question_and_Answer_0001.pdf PDF
Combined_Synp_Solicitation_-_140R6026Q0054_-_MTE_Emergency_Lighting.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Emergency Lighting Panel Salient Characteristics / Specifications

Brand Name: FastLite Model: FST (525W-2.2KW) Manufacturer: Controlled Power Company

Power:

Ratings: (kVA/kW) .525, .750, 1.1, 1.44, 1.5, 1.7, 2, 2.2 at

1.0 (unity) power factor Topology: Fast-transfer, high-efficiency

Electrical Input:

Nominal Voltage: 120V, 277V or 347V, 1 Phase, 60Hz Voltage Range: Programmable +/- 10% or +10%, -15% (without battery usage) Operating Frequency: 60 Hz +/-5% from nominal System AIC Rating: 5k AIC standard; 65k AIC optional

Electrical Output:

Nominal Voltage: 120V, 277V or 347V, 1 Phase, 60Hz Voltage Regulation: +/-5% from nominal during full battery discharge, no load to full rated load Transfer Time: 2 msec to and from battery, under any loading conditions Frequency: 60 Hz +/-0.5% while in battery operation mode Overload: Up to: 110% for 2 minutes, 125% for 30 seconds, 150% for 10 seconds, 400% for 4 cycles while in battery operation mode LED Inrush Rating: Peak overload capability of 1500% when fed from AC power or on battery, to accommodate inrush current from LED fixtures/drivers Voltage Distortion: 3% THD, while on battery with a linear load Efficiency: Up to 98.8%

Battery:

Type: Valve-regulated, sealed lead acid, maintenance free Testing: NFPA 101 compliant automatic self-testing, manual push-to-test feature Runtimes: 90 minutes minimum Nominal Voltage: 96 VDC or 10B VDC, dependent on output wattage rating and runtime Charger: 3 stage, 3.5 amps, temp condensated Recharge Time: 12-hour recharge, UL and CSA compliant

Certifications:

Safety: UL924 Listed – Emergency Lighting Equip

C-UL Listed to CSA C22.2 No. 141-15 UL 924 Listed – Auxiliary Lighting and Power Equip NFPA 101, 111, NEC, IBC and local codes

EMI Compliance: FCC Class A limits, 47 C.F.R. Part 15, Subparts A, B

Quality: ISO 9001:2015

General:

Diagnostics: Periodic and annual self-test, including weekly diagnostic Electrical Configurations: “Normally On” output and

“Normally Off/Switched” output Output Surge Protection: Optional Surge Protection Device (SPD) Output Distribution: 1 output circuit breaker or monitored, fused switch Dimensions/Weights: 26” W X 53” H / 1,100 lbs

Communications:

Basic Monitor: LED display panel to indicate systems status and battery condition Intellistat TS Monitor: Monitor with high resolution, color touchscreen display for monitoring system status and parameters Network/Web Interface: Intellistat TS Communication Port: Serial communications via USB. Interface application software to comply with NFPA 101 7.9.3.1.3 Relay Interface: Form C :General Alarm” contacts and “Battery Test Active” contacts. All relay contacts provided via hardwired terminal strip. Contacts rated for 1A at 30VDC or 120VAC.

Environmental:

Operating Temps: 20 degree C to 30 degree C for UL 924 and C-UL listed models, optimum battery performance and life at 25 degree C Storage Temps: Inverter at -20 degree C for 6 months before charging is required, for each 9 degree C rise, reduce storage time by half Relative Humidity: 0-95% non-condensing Audible Noise: 45 dB typical Elevation: 6600 feet (2000 meters) without derating

Solicitation: 140R6026Q0054 Attachment A Missouri Basin Region Bureau of Reclamation