This document appears to be a technical specification for the ULTRA XV High Efficiency V-Cell air filter product. The ULTRA XV filter is described as offering high MERV 15/16+ efficiency with very low initial resistance, resulting in significant energy savings compared to other similar efficiency filters. Key details include:
The ULTRA XV filter uses a new "ULTRA media" that provides HEPA-like efficiency at a fraction of the pressure drop. It can achieve MERV 15 or MERV 16+ efficiency while maintaining an initial resistance as low as 0.24" WG. This low resistance can translate to up to 55% reduction in energy usage compared to other high-efficiency filters. The filter is also very durable, with a burst strength exceeding 25" WG. Overall, the ULTRA XV is positioned as an energy-efficient, high-performance filter option that can help achieve LEED credits.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26225Q0070 0002.docx | DOCX document | |
| 36C26225Q0070 0001.docx | DOCX document | |
| 36C26225Q0070_1.docx | DOCX document | |
| Attachment 2 Evaluation.docx | DOCX document | |
| Attachment 4 SDVOSB Certification.docx | DOCX document | |
| Attachment 7 Tri Dek C Carbon Panel Link Filters.docx | DOCX document | |
| Attachment 3 Notice of Total SetAside for Certified SDVOSB.docx | DOCX document | |
| Attachment 6 Tri Cell IV II Thin Line Mini Pleat Air Filters.docx | DOCX document | |
| Attachment 10 WLAVA MAP.pdf | ||
| Attachment 9 INVENTORY.xlsx | XLSX spreadsheet | |
| Attachment 5 SYN PAC E High Efficiency Synthetic Bag Filter.docx | DOCX document | |
| Attachment 1 ADDENDUM Instructions to Offerors.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ULTRA XV
High Efficiency V-Cell
High Efficiency V-Cell Filter
Energy Savings 0.70.68
ENERGY SAVINGS
0.58 0.58 0.53 0.37 0.24
0.6Initial Resistance ["W.G.]
0.5
0.4TRI-CELL R MERV 14
SYN-PAC R MERV 14
TRI-CELL ASHRAE MERV 14
PREDATOR II MERV 14
0.3PREDATOR
8-Panel MERV 14
0.2ULTRA XV M 15
0.1
ULTRA™ MEDIA
ULTRA media is a new generation of media that offers unmatched and innovative performance with MERV 16+, MERV 15 and MERV 13 efficiency with ultra low resistance (0.31” WG on a MERV 15) - creating a new industry benchmark for efficiency and energy savings. ULTRA media has proven itself in testing utilizing the ASHRAE
52.2 Appendix J test method.
The ULTRA MERV 16+ media provides near HEPA performance at a fraction of thepressure drop which equals to energy ULTRA™ MEDIA savings. The reduction on pressure drop is greater than 50% which could translate into significant energy savings. Low pressure drop is not all the ULTRA media offers - also ultra-high efficiency with results on the ASHRAE 52.2 showing HEPA-like efficiencies.
ENERGY SAVINGS
The ULTRA XV filter offers many features that will benefit a ‘Green Initiative Program’ - these include: Energy Savings, LEED® IEQ Credit, Longer Service Life, etc. Lower Resistance leads to INITIAL RESISTANCE energy savings in almost all applications - the chart (above) compares filters of similar efficiencies and shows the dra- matic difference the ULTRA XV delivers. That is a reduction of up to 55% in resistance which translates into Energy Savings.
In a recent study actual energy savings of 40% was documented using this new media. All ULTRA XV filters will help to achieve valuable LEED points under the Indoor Environmental Quality for reduction of particles in air distribution.
INITIAL EFFICIENCY
@ 0.3 micron of various air filtration products
70PREDATOR
8-Panel MERV 14
ULTRA XV M 15
60TRI-CELL R MERV 14
SYN-PAC R MERV 14
TRI-CELL ASHRAE MERV 14
PREDATOR II MERV 14
ULTRA XV after test was suspended at 25” WG with NO air bypass.
EFFICIENCY
Tri-Dim’s ULTRA media achieves and maintains a MERV 15 efficiency when tested under the new Appendix J of ASHRAE 52.2. The chart lower right shows the initial efficiency on 0.3 micron particles on filters of similar efficiencies (these are the same filters in the Resistance Chart on the previous page). Again there is a dramatic difference. This difference can best be shown by particle penetration. A filter that is 70% efficient on 0.3 micron particles will let 30,000 particles pass through the filter for every 100,000 particles that challenge the filter. The ULTRA XV, that is 86% efficient on 0.3 micron particles, will reduce that amount by over 50% to only 14,000 particles. A little difference in efficiency can have a huge impact on the number of airborne particles.
STRENGTH
The strength and durability of a filter is a key performance charac- teristic because resistance and test performance have little value if the filter will not hold up under demanding applications.
Tri-Dim has extensively tested the ULTRA media for strength and durability. The ULTRA XV filter was subjected to a Breach or Burst Strength test - the test consists of the filter being challenged by a combination of water and test dust until air bypass can be detected
- that is filter failure. Traditional V-Bank filters constructed with fiberglass media experience failure at 10” WG but the ULTRA media test was suspended after 25” WG with no air bypass /filter failure documenting the strength of the ULTRA XV.
ULTRA XV
Technical Data
SPECIFICATIONS
| Specifications |
| ULTRA XV |
| Media |
| Hybrid |
Frame Single Header - All Plastic Frame Double Header, Metal Wrap Contains Recylced Content
Efficiency ASHRAE 52.2 (ASHRAE 52.1 Equivalent)
MERV 13 (80-85%)
MERV 15 (90-95%)
MERV 16+ (99%+)
Initial Resistance @ 500 FPM (2.54 m/sec)
MERV 13: 0.21” WG (52 PA)
MERV 15: 0.24” WG (60 PA)
MERV 16: 0.49” WG (122 PA)
| Final Resistance |
| 1.5” WG (373 PA) |
| Burst Strength |
| + 25” WG (+ 6220 PA) |
| Temperature Limit |
| 160°F (71°C) |
| Meets Requirements |
| ANSI/UL-900 |
Tri-Dim Filter Corporation is committed to continual product development – all descriptions, specifications and performance data are subject to change without notice. Tri-Dim products are manufactured to exacting criteria – there can be a ±5% variance in filter performance.LOCAL REPRESENTATIVE
Tel: 800-458-9835 info@tridim.com tridim.com mann-hummel.com 1900-8 0120 © MANN+HUMMEL GmbH image6.png image7.png image8.png image9.png image10.png image11.png image12.png image13.png image14.png image15.png image16.png image17.png image18.jpeg image19.png image20.png image21.png image22.png image23.png image24.png image25.png image26.png image27.png image28.png image29.png image30.png image31.png image32.png image33.png image1.jpeg image2.png image3.png image4.png image5.png
File details come from the government source that posted it. Updated .