This notice provides details for an upcoming Design-Build solicitation for infrastructure upgrades at a Department of Veterans Affairs medical center. The solicitation will require relocating or remodeling approximately 44 telecommunications rooms and one data center to meet Electronic Health Records Modernization standards. Offerors will need to provide all labor, materials, and services for design, construction, and project closeout on a firm-fixed-price basis. The project value is estimated between $10-20 million. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and issued in May 2021, with a performance period of around 540 days from notice to proceed. Questions must be submitted in writing by the specified date.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VISN 21 CM/PM Electronic Health

Records Modernization (EHRM) PHASE I Support Task

PO# 612C209

Central California Health Care System Fresno VA Medical Center

Merced Community Based Outpatient Clinic

Oakhurst CBOC

Tulare CBOC

Visalia Home-Based Primary Care (HBPC)

Fresno VA Administrat ive Office

Ta b l e o f C o n t e n t s

Project TeamContributors

Vicinity Map/Building Addresses

Campus Map / Building Information

Campus and Interbuilding Fiber Backbone

VAMC Fiber Distances

VAMC Fiber Distances

Door Security Requirements

Fresno VAMC - Bldg. 1

Sub-Basement

Basement

First Floor Plan

Second Floor Plan

Third Floor Plan

Fourth Floor Plan

Fifth Floor Plan

Sixth Floor Plan

Seventh Floor Plan

Fresno VAMC – Bldg. 2

First Floor Plan

Fresno VAMC – Bldg. 3

First Floor Plan

Fresno VAMC – Bldg. 24

Second Floor Plan

Fresno VAMC – Bldg. 25

First Floor Plan

Fresno VAMC – Bldg. 27

Second Floor Plan

Fresno VAMC – Bldg. 28

First Floor Plan

Fresno VAMC – Bldg. 31

First Floor Plan

Identification of Network Spaces

Network Spaces: (cont’d)

Off Campus Locations:

Fresno VAMC – Bldg. 32

First Floor Plan

Fresno VAMC – Bldg. 34

First Floor Plan

Second Floor Plan

Fresno VAMC – OPC

Basement Plan

First Floor Plan

Second Floor Plan

Third Floor Plan

Fresno VAMC – Bldg. LC2

First Floor Plan

M Street

9th Floor Plan

Merced CBOC

First Floor Plan

Oakhurst CBOC

First Floor Plan

Tulare CBOC

First Floor Plan

*Visalia Home-Based Primary Care (HBPC)

Drawing Not Available

Network Space Design

Bldg. 1:

B2A08

Design Matrix

Enlarged Plan – Existing

Bldg. 1:

B1A13

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

B1B06

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

B1B14A

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

Dumbwaiter Area - Basement

Design Matrix

Enlarged Plan – Existing

Bldg. 1:

Dumbwaiter Area – 1st Floor

Design Matrix

Enlarged Plan – Existing

Bldg. 1:

Dumbwaiter Area – 2nd Floor

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

Dumbwaiter Area – 3rd Floor

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

3A11

Design Matrix

Enlarged Plan – Existing

Bldg. 1:

Dumbwaiter Area – 4th Floor

Design Matrix

Enlarged Plan – Existing

Bldg. 1:

Dumbwaiter Area – 5th Floor

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

Dumbwaiterr Area – 6th Floor

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

7A07F

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

7B02

Design Matrix

Enlarged Plan - Existing

Bldg. 2:

SP4

Design Matrix

Enlarged Plan - Existing

Bldg. 3:

22A

Design Matrix

Enlarged Plan - Existing

Network Space Design (cont’d)

Ta b l e o f C o n t e n t s

Bldg. 24:

2A017

Design Matrix

Enlarged Plan - Existing

Bldg. 25:

1A18

Design Matrix

Enlarged Plan – Existing

Bldg. 27:

2C05

Design Matrix

Enlarged Plan – Existing

Bldg. 28:

1E17

Design Matrix

Enlarged Plan – Existing

Bldg. 31:

1A17

Design Matrix

Enlarged Plan – Existing

Bldg. 31:

1B19

Design Matrix

Enlarged Plan – Existing

Bldg. 31:

1C16

Design Matrix

Enlarged Plan – Existing

Bldg. 32:

WH109

Design Matrix

Enlarged Plan – Existing

Bldg. 34:

Design Matrix

Enlarged Plan – Existing

Bldg. 34:

Design Matrix

Enlarged Plan – Existing

Bldg. LC2:

LC2-28

Design Matrix

Enlarged Plan – Existing

Bldg. OPC:

B1C15/S0G13A

Design Matrix

Enlarged Plan – Existing

Network Space Design (cont’d)

Bldg. OPC:

1C45

Design Matrix

Enlarged Plan – Existing

Bldg. OPC:

2C15D

Design Matrix

Enlarged Plan – Existing

Bldg. OPC:

3C13 & 3C14

Design Matrix

Enlarged Plan – Existing

Ta b l e o f C o n t e n t s

Network Space Design (cont’d)

Off Campus Locations

Merced CBOC:

Design Matrix

Enlarged Plan – Existing

Oakhurst CBOC:

Design Matrix

Enlarged Plan – Existing

Tulare CBOC:

2A17

Design Matrix

Enlarged Plan – Existing

Visalia HBPC:

SV20

Design Matrix

Enlarged Plan – N/A

M Street:

Design Matrix

Enlarged Plan – Existing

Appendix A – Power Installation Example

Appendix B – Compliance Requirements

Appendix C – Rack Labeling Standard

Appendix

P R O J E C T C O N TA C T D I R E C T O R Y

Concourse Federal Group

123 S. Royal Street Alexandria, Virginia 22314

Tim Hower, Project Manager .........................................................................................thower@concousefederal.com

Lorena Alvarez.................................................................................................................IaIvarez@concousefederaI.com

Mike Olson .................................................................................................................... molson@concousefederal.com

Marshall Contino, Concourse A|E Vice President ........................................................ mcontino@concousefederal.com

DHE Engineering 3300 N. Central Ave. 3300 Tower Suite, 1520, Phoenix, AZ 85012

Rick Seger P.E., Principal, Electrical Engineer................................................................rseger@dheeng.com

Kory Young, EIT, Senior Mechanical Engineer.................................................................kyoung@dheeng.com

Central California Health Care System

Travis Horn, Chief Engineer............................................................................................Travis.Horn@va.gov

Calvin Parret, Chief of Projects….....................................................................................Calvin.Parret@va.gov

Ron Mills, Area Manager................................................................................................Ron.Mills@va.gov

Kenneth T. Brister, IT Specialist.......................................................................................Kenneth.Brister@va.gov

V i c i n i t y M a p B u i l d i n g A d d r e s s e s

F r e s n o V A M e d i c a l C e n t e r ( V A M C )

2 6 1 5 E . C l i n t o n A v e n u e

F r e s n o , C A 9 3 7 0 3

M e r c e d C o m m u n i t y B a s e d

O u t p a t i e n t C l i n i c ( C B O C )

3 4 0 E a s t Y o s e m i t e A v e .

S u i t e D

M e r c e d , C A 9 5 3 4 0 - 9 1 6 7

O a k h u r s t C B O C

4 0 5 9 7 W e s t l a k e D r i v e

O a k h u r s t , C A 9 3 6 4 4 - 9 0 2 4

T u l a r e C B O C

1 0 5 0 N o r t h C h e r r y S t r e e t

T u l a r e , C A 9 3 2 7 4 - 2 2 5 1

V i s a l i a H o m e - B a s e d P r i m a r y C a r e

( H B P C )

5 3 0 0 W . T u l a r e A v e .

V i s a l i a , C A 9 3 2 7 7

F r e s n o V A A d m i n i s t r a t i v e O f f i c e

8 5 5 M S t r e e t

S u i t e 9 7 0

F r e s n o , C A 9 3 7 2 1

2 3

C a m p u s M a p – F r e s n o V A M e d i c a l C e n t e r

B u i l d i n g I n f o r m a t i o n

N O

R T

H F

R E

S N

O S

T R

E E

T

N O

R T

H A

N G

U S

S T

R E

E T

EAST HARVARD AVENUE

CLINTON AVENUE

Bldg. # Bldg. Name TR Qty Levels

1 Main Hospital 12 9

2 Boiler Plant 1 1

3 Engineering 1 1

24 Liberty Bldg. 1 4

25 Mental Health Freedom Bldg. 1 2

27 Mental Health Independence Bldg. 1 2

28 CLC Expansion Bldg. 1 1

31 Community Living Center 3 1

32 Warehouse 1 2

34 Mental Health Valor Bldg. 2 2

LC-2 LC-2 1 1

OPC Outpatient Clinic 4 4

Bldg. # Bldg. Name Data Ctr Levels

1 Main Hospital 1 9

LC-2

OPC

C A M P U S A N D I N T E R B U I L D I N G F I B E R B AC K B O N E

N O

R T

H F

R E

S N

O S

T R

E E

T

N O

R T

H A

N G

U S

S T

R E

E T

EAST HARVARD AVENUE

CLINTON AVENUE

CURRENT FIBER RUN

CONDUIT STUB UP

ABOVE GRADE INTO A

PULL BOX AND ENTERS

BUILDING

VAMC FIBER DISTANCES

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

VAMC Fresno

Building Floor Room

Distance (Ft.) from New Fiber Hub (old PBX)

Fiber Type Notes

Interior - 4" EMT

Exterior -Concrete

Encased 4" PVC or HDPE with (4) 1" Interducts

1 SB B2A08 280 0 24 strand multimode

1 B B1A13 20 0 24 strand multimode PBX

1 B B1B07 (?) 260 0 24 strand multimode New TR - Dumbwaiter area

1 B B1B06 3350 0 24 strand multimode Electrical Vault

1 B B1B14A 330 0 24 strand multimode Server Room

1 B B1A01.2 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 1 1B06I 250 0 24 strand multimode New TR - Dumbwaiter area

1 1 1A15D 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 1 AB01A 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 1 1B17 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 2 2B11 270 0 24 strand multimode New TR - Dumbwaiter area

1 2 2A19 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 2 2B17 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 3 3B07 320 0 24 strand multimode New TR - Dumbwaiter area

1 3 3A11 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 3 3B09D 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 4 4B10 325 0 24 strand multimode New TR - Dumbwaiter area

1 4 4A31 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 4 4B42 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 5 5B11 310 0 24 strand multimode New TR - Dumbwaiter area

1 5 5A42 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 5 5B46 0 24 strand multimode Abandon - New TR in dumbwaiter area

1 6 6A38 0 24 strand multimode Abandon - Move to expanded 6B10/6B11

1 6 6B10 310 0 24 strand multimode Room Expanded into Dumbwaiter Area

1 7 7A07F 230 0 24 strand multimode

1 7 7B02 340 0 24 strand multimode Room Expanded

CREATE REDUNDANT WAN PATH – ASSUME 1350’-0”

CONCRETE ENCASED 4” PVC OR HDPE WITH (4) 1” INTERDUCTS.

VAMC FIBER DISTANCES

FRESNO MEDICAL CENTER

VAMC Fresno

Building Floor Room

Distance (Ft.) from New Fiber Hub (old PBX)

Fiber Type Notes

Interior - 4" EMT

Exterior -Concrete

Encased 4" PVC or HDPE with (4) 1" Interducts

2 1 SP4 70 400 24 strand multimode

3 1 22A 190 200 24 strand multimode

24 1 2A17 145 40 24 strand multimode

25 1 1A18 30 260 24 strand multimode

27 2 2C05 165 500 24 strand singlemode

28 1 1E17 225 535 24 strand singlemode

31 1 1A17 120 480 24 strand singlemode

31 2 1B19 120 490 24 strand singlemode

31 3 1C16 135 540 24 strand singlemode

32 1 WH109 222 0 24 strand multimode

34 1 122 65 350 24 strand singlemode

34 1 228 430 0 24 strand singlemode

LC2 1 LC2-28 130 400 24 strand singlemode

OPC 1 B1C15/S0G13A 400 0 24 strand singlemode

OPC 1 B1C16 410 0 24 strand singlemode

OPC 1 1C45 414 0 24 strand singlemode

OPC 1 2C15D 429 0 24 strand singlemode

OPC 1 3C13/3C14 444 0 24 strand singlemode

DOOR SECURITY REQUIREMENTS

FRESNO MEDICAL CENTER

I D E N T I F I C AT I O N O F N E T WO R K S PAC E S

BLDG: 1

LEVEL: SUB-BASEMENT

SCALE: 1/32” = 1’-0”

DATE: 12/14/2020

N

EXPAND IN PLACE

STORAGE

ROOM B2A08

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

EXISTING TR LOCATION(S)

FRESNO MEDICAL CENTER

N

REMEDIATE IN PLACE

TELECOMMUNICATION ROOM

ROOM B1A13

REMEDIATE IN PLACE

SERVER ROOM

ROOM B1B14A

ABANDON

TELE ROOM B1A01.2

RELOCATE TO DUMBWAITER AREA

REMEDIATE IN PLACE

ELECTRICAL

ROOM B1B06

NEW TR ROOM

EXISTING DUMBWAITER AREA

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 1

LEVEL: BASEMENT

SCALE: 1/32” = 1’-0”

DATE: 12/14/2020

Pneumatic Tube System

The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require

110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three

(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS EITHER PHEUMATIC TUBE

STATIONS OR GENERAL STORAGE. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PATCH AND REPAIR FLOORS

• PATCH, REPAIR AND PAINT WALLS

• PROVIDE NEW DROP-IN CEILING

• PROVIDE NEW LIGHTING

N

ABANDON

COMM ROOM 1A15D

RELOCATE TO DUMBWAITER AREA

ABANDON

COMM ROOM 1B17

RELOCATE TO DUMBWAITER AREA

ABANDON

COMM ROOM 1B01A

RELOCATE TO DUMBWAITER AREA

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

NEW TR ROOM

EXISTING DUMBWAITER AREA

NEW PNEUMATIC TUBE STOP

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 1

LEVEL: 1

SCALE: 1/32” = 1’-0”

DATE: 12/14/2020

Pneumatic Tube System

The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require

110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three

(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS EITHER PHEUMATIC TUBE

STATIONS OR GENERAL STORAGE. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PATCH AND REPAIR FLOORS

• PATCH, REPAIR AND PAINT WALLS

COMM 2B17

RELOCATE TO

DUMBWAITER AREA

EXISTING SPACE TO BE POTENTIAL SITE

FOR PNEUMATIC TUBE STOP

N

ABANDON

COMM 2A19

RELOCATE TO DUMBWAITER AREA

EXISTING SPACE TO BE POTENTIAL

SITE FOR PNEUMATIC TUBE STOP

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

NEW TR ROOM

EXISTING DUMBWAITER AREA

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 1

LEVEL: 2

SCALE: 1/32” = 1’-0”

DATE: 12/14/2020

Pneumatic Tube System

The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require

110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three

(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS EITHER PHEUMATIC TUBE

STATIONS OR GENERAL STORAGE. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PATCH AND REPAIR FLOORS

• PATCH, REPAIR AND PAINT WALLS

COMM ROOM 3B09D

RELOCATE TO

DUMBWAITER AREA

EXISTING SPACE TO BE POTENTIAL SITE

FOR PNEUMATIC TUBE STOP

N

REMEDIATE IN PLACE

COMM ROOM 3A11

EXISTING SPACE TO BE POTENTIAL SITE

FOR PNEUMATIC TUBE STOP

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

NEW TR ROOM

EXISTING DUMBWAITER AREA

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 1

LEVEL: 3

SCALE: 1/32” = 1’-0”

DATE: 12/14/2020

Pneumatic Tube System

The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require

110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three

(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS EITHER PHEUMATIC TUBE

STATIONS OR GENERAL STORAGE. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PATCH AND REPAIR FLOORS

• PATCH, REPAIR AND PAINT WALLS

COMM ROOM 4B42

RELOCATE TO DUMBWAITER AREA

EXISTING SPACE TO BE POTENTIAL SITE

FOR PNEUMATIC TUBE STOP

N

ABANDON

COMM ROOM 4A31

RELOCATE TO DUMBWAITER AREA

EXISTING SPACE TO BE POTENTIAL SITE

FOR PNEUMATIC TUBE STOP

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

NEW TR ROOM

EXISTING DUMBWAITER AREA

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 1

LEVEL: 4

SCALE: 1/32” = 1’-0”

DATE: 12/14/2020

Pneumatic Tube System

The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require

110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three

(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS EITHER PHEUMATIC TUBE

STATIONS OR GENERAL STORAGE. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PATCH AND REPAIR FLOORS

• PATCH, REPAIR AND PAINT WALLS

COMM ROOM 5B46

EXISTING SPACE TO BE POTENTIAL SITE

FOR PNEUMATIC TUBE STOP

N

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

NEW TR ROOM

EXISTING DUMBWAITER AREA

ABANDON

COMM ROOM 5A42

RELOCATE TO DUMBWAITER AREA

EXISTING SPACE TO BE POTENTIAL SITE

FOR PNEUMATIC TUBE STOP

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 1

LEVEL: 5

SCALE: 1/32” = 1’-0”

DATE: 12/14/2020

Pneumatic Tube System

The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require

110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three

(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS EITHER PHEUMATIC TUBE

STATIONS OR GENERAL STORAGE. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PATCH AND REPAIR FLOORS

• PATCH, REPAIR AND PAINT WALLS

EXPAND IN PLACE

COMM ROOM 6B10

EXPAND INTO DUMBWAITER AREA

N

ABANDON

COMM ROOM 6A38

RELOCATE TO DUMBWAITER AREA

EXISTING SPACE TO BE POTENTIAL SITE

FOR PNEUMATIC TUBE STOP

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

NEW TR ROOM

EXISTING DUMBWAITER AREA

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 1

LEVEL: 6

SCALE: 1/32” = 1’-0”

DATE: 12/14/2020

Pneumatic Tube System

The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require

110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three

(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS EITHER PHEUMATIC TUBE

STATIONS OR GENERAL STORAGE. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PATCH AND REPAIR FLOORS

• PATCH, REPAIR AND PAINT WALLS

REMEDIATE IN PLACE

COMM ROOM

7B02

N

REMEDIATE IN PLACE

COMM ROOM

7A07F

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

EXISTING DUMBWAITER AREA

AVAILABLE FOR MECH. SPACE

IF NEEDED

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 1

LEVEL: 7

SCALE: 1/32” = 1’-0”

DATE: 12/14/2020

NOTE:

ALL ABANDONED TR ROOMS ARE TO BE

REPURPOSED AS EITHER PHEUMATIC TUBE

STATIONS OR GENERAL STORAGE. MINIMUM

REQUIREMENTS FOR TR ROOMS TO BE

ABANDONED:

• REMOVE ALL IT EQUIPMENT

• SEAL ALL PENETRATIONS IN ACCORDANCE

WITH FIRE REQUIREMENTS

• PATCH AND REPAIR FLOORS

• PATCH, REPAIR AND PAINT WALLS

SP4 (CABINET ON NORTH WALL)

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 2

LEVEL: 1

SCALE: 1/32” = 1’-0”

DATE: 12/14/2020

TELE. CLOSET

22A

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 3

LEVEL: 1

COMM

2A17

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

NOTE: REMOVE EXISTING CABLING

& EQUIPMENT FROM THE 3rd

FLOOR, ROOM 3A20

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 24

LEVEL: 2

SCALE: 1/16” = 1’-0”

COMM CLOSET

1A18

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 25

LEVEL: 1

DATA

2C05

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 27

LEVEL: 2

TELE/DATA ROOM

1E17

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 28

LEVEL: 1

COMM ROOM

1B19

EXPAND IN PLACE

COMM ROOM

1A17

REMEDIATE IN PLACE

COMM ROOM

1C16

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

NOTE: ROOMS NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 31

LEVEL: 1

CABINET

WH109

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 32

LEVEL: 1

TELE/DATA

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 34

LEVEL: 1

TELE/DATA

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 34

LEVEL: 2

RELOCATE

TELEPHONE CLOSET B1C15

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

NEW TELEPHONE CLOSET

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: OPC

LEVEL: BASEMENT

COMM

1C45

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: OPC

LEVEL: 1

COMM

2C15D

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: OPC

LEVEL: 2

COMM

3C13 & 3C14

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: OPC

LEVEL: 3

COMM CLOSET

LC2-28

EXISTING TR LOCATION(S)

VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM

FRESNO MEDICAL CENTER

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: LC2

LEVEL: 1

I D E N T I F I C AT I O N O F O F F C A M P U S N E T WO R K S PAC E S

FRESNO

REMEDIATE IN PLACE

IT

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: M STREET

LEVEL: 9

FRESNO

N

REMEDIATE IN PLACE

IT

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: MERCED CBOC

LEVEL: 1

FRESNO

REMEDIATE IN PLACE

IT

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: OAKHURST CBOC

LEVEL: 1

FRESNO

N

EXPAND IN PLACE

IT

SV20

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: TULARE CBOC

LEVEL: 1

N E T WO R K S PAC E D E S I G N

B2A08

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: SUB-BASEMENT

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

ROOM NO. B2A08 STORAGE

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated HVAC unit X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Cooling inadequate There is no air condition in this room X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special

Telecommunications Systems Design

Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat X

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 27

Approximate total cable length = 4207.5'

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X Inadequate rack space for new equipment provide new rack as required.

REMOVE PORTION OF

EXISTING WALL.

INSTALL NEW DOOR.

NEW WALL

APPROX. SIZE

8’-3” x 10’-2”

NOTE: This is a small 1/2 rack mounted on the wall of a large storage room. The mechanical yard is referred to as "the moat" where you can place a condensing unit.

EMS STORAGE

(CURRENT LOCATION

OF COMM B2A08)

COMM ROOM

(RENOVATED)

B1A13

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: BASEMENT

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

PROVIDE NEW WALL

& NEW 4’ DOOR

TO CREATE ROOM

FOR A NEW FIBER

HUB

TELECOMMUNICATION

ROOM

B1A13

NEW FIBER HUB

ROOM NO. B1A13 TELEPHONE/ELECTRICAL CLOSET (VA ER RENOVATION)

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated HVAC unit

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Cooling inadequate

Room is warm. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above. X

Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS X

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X

Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough

X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special

Telecommunications Systems Design

Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat

X

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Micro condensate pump

Commercial condensate pump

X

Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X

Inadequate rack space for new equipment provide new rack as required.

B1B06

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: BASEMENT

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

ELECTRICAL

B1B06

ROOM NO. B1B06 ELECTRICAL

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA

L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

Cooling inadequate There is no air condition in this room Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications

Systems Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

Inadequate fiber optic cabling to TR Install new as required

X Remote Controlled battery thermostat Wired thermostat

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Micro condensate pump Commercial condensate pump Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new provide new rack as required.Note: UPS "big blue" is not being monitored.

B1B14A

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: BASEMENT

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

SERVER ROOM

B1B14A

ROOM NO. B1B14A SERVER ROOM

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

Cooling inadequate There is no air condition in this room X Insufficient Central UPS power backup.

Design Build contractor to determine size of Central UPS.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing Telecom Main

Ground Bar (TMGB) Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs three (3) new temperature monitoring sensors per rack, three (3) humidity sensor, and controls from BMS

X

Inadequate grounding connections to metal objects in date canter.

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion X

No telecommunications bonding backbone to other

TR grounding bars

Provide grounding conductor to nearest

TR per VA Telecommunications and

Special Telecommunications Systems

Design Manual

No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X

No redundant fiber optic cable feeds entering the building on opposite faces.

Install new as required

Remote Controlled battery thermostat Wired thermostat

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = TBD

Approximate total cable length = TBD'

Micro condensate pump

Commercial condensate pump Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment

DUMBWAITER AREA

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: BASEMENT

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

NEW TR ROOM

DUMBWAITER AREA

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Provide 2-ton DX Liebert Mini Mate-

2 with I-COM. Condensing unit on ground floor or roof.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

Cooling inadequate

Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA Telecommunications and Special

Telecommunications Systems Design

Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

X Remote Controlled battery thermostat Wired thermostat X

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 80

Approximate total cable length = 10,900'

X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X Inadequate rack space for new equipment

NEW TR IN DUMBWAITER AREA

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: 1

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

NEW WALL

NEW TR ROOM

DUMBWAITER AREA

NEW TR IN DUMBWAITER AREA (ROOM NO. 1B17 COMM ABANDONED)

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Provide 2-ton DX Liebert Mini Mate-

2 with I-COM. Condensing unit on ground floor or roof.

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

Cooling inadequate

Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above. X

Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X

Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough

X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Ground cable leaves room. Verify where this goes. If not provide grounding cable to

MDF ground bar.

X UPS Central Monitoring BACnet conversion

X

No telecommunications bonding backbone to other TR grounding bars

Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat

X

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

440Approximate total cable length =

59,400'

Micro condensate pump Commercial condensate pump

X

Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X

Inadequate rack space for new

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: 2

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

NEW TR ROOM

EXPAND ROOM

INTO 2B03

REMOVE EXISTING DOOR.

INFILL OPENING.

EXISTING STORAGE

ROOM

2B03

NEW TR IN DUMBWAITER AREA (ROOM NO. 2B17 COMM ABANDONED)

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Provide 2-ton DX Liebert Mini Mate-

2 with I-COM or Liebert PDX with I-

COM. Contractor to verify refrigerant lines. Condensing unit on ground floor or roof.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

Cooling inadequate

Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Ground cable leaves room. Verify where this goes. If not provide grounding cable to

MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat X

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 300

Approximate total cable length = 40,000'

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X Inadequate rack space for new

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: 3

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

NEW TR ROOM

NEW TR IN DUMBWAITER AREA (ROOM NO. 3A11 COMM ABANDONED)

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Provide 2-ton DX Liebert Mini Mate-

2 with I-COM. Condensing unit on roof.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

Cooling inadequate

Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special

Telecommunications Systems Design Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Ground cable leaves room. Verify where this goes. If not provide grounding cable to MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA

Telecommunications and Special Telecommunications

Systems Design Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat X

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A. Approximate number of cables = 185 Approximate total cable length =

25,000'

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-

80M)

X Inadequate rack space for new

3A11

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: 3

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

ROOM NO. 3A11 COMM

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated HVAC unit Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

X Cooling inadequate

Room is warm. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Ground cable leaves room. Verify where this goes. If not provide grounding cable to

MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat X

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 72

Approximate total cable length = 11880'

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

Inadequate rack space for new equipment

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: 4

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

NEW TR ROOM

EXPAND INTO

OFFICE 4B09

NEW TR IN DUMBWAITER AREA (ROOM NO. 4B42 COMM ABANDONED)

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Provide 2-ton DX Liebert Mini Mate-

2 with I-COM. Condensing unit on roof.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

Cooling inadequate

Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Ground cable leaves room. Verify where this goes. If not provide grounding cable to

MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat X

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 230

Approximate total cable length = 31,000'

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X Inadequate rack space for new

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: 5

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

NEW TR ROOM

NEW TR IN DUMBWAITER AREA (ROOM NO. 5A42 COMM ABANDONED)

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate

Provide 2-ton DX Liebert Mini Mate-

2 with I-COM. Condensing unit on roof.

X Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

Cooling inadequate

Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Ground cable leaves room. Verify where this goes. If not provide grounding cable to

MDF ground bar.

X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars

Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

X No condensate leak detection Needs condensate leak detection

C A

B

LI

N G

X Inadequate fiber optic cabling to TR Install new as required

Remote Controlled battery thermostat Wired thermostat X

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables = 210

Approximate total cable length = 28,100'

Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed

292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)

X Inadequate rack space for new

FRESNO MEDICAL CENTER

BLDG: 1

LEVEL: 6

SCALE: 1/4” = 1’-0”

DATE: 12/14/2020

N

NEW TR ROOM.

EXPAND INTO

EXISTING

COMM RM

NEW TR IN DUMBWAITER AREA (ROOM NO. 6B10)

C O

O

LI

N G

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

E

LE

C T

R

IC

A L

"X' EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Provide 2-ton VRF system with

BACnet communication X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire NEMA L21-

30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone

PDU

Cooling inadequate

Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from

BMS

X Missing grounding bus bar Install copper grounding bus bar

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per VA

Telecommunications and Special

Telecommunications Systems Design

Manual

Piping over equipment Relocate piping or pipe trough X

TR ground bar not connected to

Telecom Main Ground Bar (TMGB) in the data room

Ground cable leaves room.