This notice provides details for an upcoming Design-Build solicitation for infrastructure upgrades at a Department of Veterans Affairs medical center. The solicitation will require relocating or remodeling approximately 44 telecommunications rooms and one data center to meet Electronic Health Records Modernization standards. Offerors will need to provide all labor, materials, and services for design, construction, and project closeout on a firm-fixed-price basis. The project value is estimated between $10-20 million. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and issued in May 2021, with a performance period of around 540 days from notice to proceed. Questions must be submitted in writing by the specified date.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VISN 21 CM/PM Electronic Health
Records Modernization (EHRM) PHASE I Support Task
PO# 612C209
Central California Health Care System Fresno VA Medical Center
Merced Community Based Outpatient Clinic
Oakhurst CBOC
Tulare CBOC
Visalia Home-Based Primary Care (HBPC)
Fresno VA Administrat ive Office
Ta b l e o f C o n t e n t s
Project TeamContributors
Vicinity Map/Building Addresses
Campus Map / Building Information
Campus and Interbuilding Fiber Backbone
VAMC Fiber Distances
VAMC Fiber Distances
Door Security Requirements
Fresno VAMC - Bldg. 1
Sub-Basement
Basement
First Floor Plan
Second Floor Plan
Third Floor Plan
Fourth Floor Plan
Fifth Floor Plan
Sixth Floor Plan
Seventh Floor Plan
Fresno VAMC – Bldg. 2
First Floor Plan
Fresno VAMC – Bldg. 3
First Floor Plan
Fresno VAMC – Bldg. 24
Second Floor Plan
Fresno VAMC – Bldg. 25
First Floor Plan
Fresno VAMC – Bldg. 27
Second Floor Plan
Fresno VAMC – Bldg. 28
First Floor Plan
Fresno VAMC – Bldg. 31
First Floor Plan
Identification of Network Spaces
Network Spaces: (cont’d)
Off Campus Locations:
Fresno VAMC – Bldg. 32
First Floor Plan
Fresno VAMC – Bldg. 34
First Floor Plan
Second Floor Plan
Fresno VAMC – OPC
Basement Plan
First Floor Plan
Second Floor Plan
Third Floor Plan
Fresno VAMC – Bldg. LC2
First Floor Plan
M Street
9th Floor Plan
Merced CBOC
First Floor Plan
Oakhurst CBOC
First Floor Plan
Tulare CBOC
First Floor Plan
*Visalia Home-Based Primary Care (HBPC)
Drawing Not Available
Network Space Design
Bldg. 1:
B2A08
Design Matrix
Enlarged Plan – Existing
Bldg. 1:
B1A13
Design Matrix
Enlarged Plan - Existing
Bldg. 1:
B1B06
Design Matrix
Enlarged Plan - Existing
Bldg. 1:
B1B14A
Design Matrix
Enlarged Plan - Existing
Bldg. 1:
Dumbwaiter Area - Basement
Design Matrix
Enlarged Plan – Existing
Bldg. 1:
Dumbwaiter Area – 1st Floor
Design Matrix
Enlarged Plan – Existing
Bldg. 1:
Dumbwaiter Area – 2nd Floor
Design Matrix
Enlarged Plan - Existing
Bldg. 1:
Dumbwaiter Area – 3rd Floor
Design Matrix
Enlarged Plan - Existing
Bldg. 1:
3A11
Design Matrix
Enlarged Plan – Existing
Bldg. 1:
Dumbwaiter Area – 4th Floor
Design Matrix
Enlarged Plan – Existing
Bldg. 1:
Dumbwaiter Area – 5th Floor
Design Matrix
Enlarged Plan - Existing
Bldg. 1:
Dumbwaiterr Area – 6th Floor
Design Matrix
Enlarged Plan - Existing
Bldg. 1:
7A07F
Design Matrix
Enlarged Plan - Existing
Bldg. 1:
7B02
Design Matrix
Enlarged Plan - Existing
Bldg. 2:
SP4
Design Matrix
Enlarged Plan - Existing
Bldg. 3:
22A
Design Matrix
Enlarged Plan - Existing
Network Space Design (cont’d)
Ta b l e o f C o n t e n t s
Bldg. 24:
2A017
Design Matrix
Enlarged Plan - Existing
Bldg. 25:
1A18
Design Matrix
Enlarged Plan – Existing
Bldg. 27:
2C05
Design Matrix
Enlarged Plan – Existing
Bldg. 28:
1E17
Design Matrix
Enlarged Plan – Existing
Bldg. 31:
1A17
Design Matrix
Enlarged Plan – Existing
Bldg. 31:
1B19
Design Matrix
Enlarged Plan – Existing
Bldg. 31:
1C16
Design Matrix
Enlarged Plan – Existing
Bldg. 32:
WH109
Design Matrix
Enlarged Plan – Existing
Bldg. 34:
Design Matrix
Enlarged Plan – Existing
Bldg. 34:
Design Matrix
Enlarged Plan – Existing
Bldg. LC2:
LC2-28
Design Matrix
Enlarged Plan – Existing
Bldg. OPC:
B1C15/S0G13A
Design Matrix
Enlarged Plan – Existing
Network Space Design (cont’d)
Bldg. OPC:
1C45
Design Matrix
Enlarged Plan – Existing
Bldg. OPC:
2C15D
Design Matrix
Enlarged Plan – Existing
Bldg. OPC:
3C13 & 3C14
Design Matrix
Enlarged Plan – Existing
Ta b l e o f C o n t e n t s
Network Space Design (cont’d)
Off Campus Locations
Merced CBOC:
Design Matrix
Enlarged Plan – Existing
Oakhurst CBOC:
Design Matrix
Enlarged Plan – Existing
Tulare CBOC:
2A17
Design Matrix
Enlarged Plan – Existing
Visalia HBPC:
SV20
Design Matrix
Enlarged Plan – N/A
M Street:
Design Matrix
Enlarged Plan – Existing
Appendix A – Power Installation Example
Appendix B – Compliance Requirements
Appendix C – Rack Labeling Standard
Appendix
P R O J E C T C O N TA C T D I R E C T O R Y
Concourse Federal Group
123 S. Royal Street Alexandria, Virginia 22314
Tim Hower, Project Manager .........................................................................................thower@concousefederal.com
Lorena Alvarez.................................................................................................................IaIvarez@concousefederaI.com
Mike Olson .................................................................................................................... molson@concousefederal.com
Marshall Contino, Concourse A|E Vice President ........................................................ mcontino@concousefederal.com
DHE Engineering 3300 N. Central Ave. 3300 Tower Suite, 1520, Phoenix, AZ 85012
Rick Seger P.E., Principal, Electrical Engineer................................................................rseger@dheeng.com
Kory Young, EIT, Senior Mechanical Engineer.................................................................kyoung@dheeng.com
Central California Health Care System
Travis Horn, Chief Engineer............................................................................................Travis.Horn@va.gov
Calvin Parret, Chief of Projects….....................................................................................Calvin.Parret@va.gov
Ron Mills, Area Manager................................................................................................Ron.Mills@va.gov
Kenneth T. Brister, IT Specialist.......................................................................................Kenneth.Brister@va.gov
V i c i n i t y M a p B u i l d i n g A d d r e s s e s
F r e s n o V A M e d i c a l C e n t e r ( V A M C )
2 6 1 5 E . C l i n t o n A v e n u e
F r e s n o , C A 9 3 7 0 3
M e r c e d C o m m u n i t y B a s e d
O u t p a t i e n t C l i n i c ( C B O C )
3 4 0 E a s t Y o s e m i t e A v e .
S u i t e D
M e r c e d , C A 9 5 3 4 0 - 9 1 6 7
O a k h u r s t C B O C
4 0 5 9 7 W e s t l a k e D r i v e
O a k h u r s t , C A 9 3 6 4 4 - 9 0 2 4
T u l a r e C B O C
1 0 5 0 N o r t h C h e r r y S t r e e t
T u l a r e , C A 9 3 2 7 4 - 2 2 5 1
V i s a l i a H o m e - B a s e d P r i m a r y C a r e
( H B P C )
5 3 0 0 W . T u l a r e A v e .
V i s a l i a , C A 9 3 2 7 7
F r e s n o V A A d m i n i s t r a t i v e O f f i c e
8 5 5 M S t r e e t
S u i t e 9 7 0
F r e s n o , C A 9 3 7 2 1
2 3
C a m p u s M a p – F r e s n o V A M e d i c a l C e n t e r
B u i l d i n g I n f o r m a t i o n
N O
R T
H F
R E
S N
O S
T R
E E
T
N O
R T
H A
N G
U S
S T
R E
E T
EAST HARVARD AVENUE
CLINTON AVENUE
Bldg. # Bldg. Name TR Qty Levels
1 Main Hospital 12 9
2 Boiler Plant 1 1
3 Engineering 1 1
24 Liberty Bldg. 1 4
25 Mental Health Freedom Bldg. 1 2
27 Mental Health Independence Bldg. 1 2
28 CLC Expansion Bldg. 1 1
31 Community Living Center 3 1
32 Warehouse 1 2
34 Mental Health Valor Bldg. 2 2
LC-2 LC-2 1 1
OPC Outpatient Clinic 4 4
Bldg. # Bldg. Name Data Ctr Levels
1 Main Hospital 1 9
LC-2
OPC
C A M P U S A N D I N T E R B U I L D I N G F I B E R B AC K B O N E
N O
R T
H F
R E
S N
O S
T R
E E
T
N O
R T
H A
N G
U S
S T
R E
E T
EAST HARVARD AVENUE
CLINTON AVENUE
CURRENT FIBER RUN
CONDUIT STUB UP
ABOVE GRADE INTO A
PULL BOX AND ENTERS
BUILDING
VAMC FIBER DISTANCES
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
VAMC Fresno
Building Floor Room
Distance (Ft.) from New Fiber Hub (old PBX)
Fiber Type Notes
Interior - 4" EMT
Exterior -Concrete
Encased 4" PVC or HDPE with (4) 1" Interducts
1 SB B2A08 280 0 24 strand multimode
1 B B1A13 20 0 24 strand multimode PBX
1 B B1B07 (?) 260 0 24 strand multimode New TR - Dumbwaiter area
1 B B1B06 3350 0 24 strand multimode Electrical Vault
1 B B1B14A 330 0 24 strand multimode Server Room
1 B B1A01.2 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 1 1B06I 250 0 24 strand multimode New TR - Dumbwaiter area
1 1 1A15D 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 1 AB01A 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 1 1B17 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 2 2B11 270 0 24 strand multimode New TR - Dumbwaiter area
1 2 2A19 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 2 2B17 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 3 3B07 320 0 24 strand multimode New TR - Dumbwaiter area
1 3 3A11 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 3 3B09D 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 4 4B10 325 0 24 strand multimode New TR - Dumbwaiter area
1 4 4A31 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 4 4B42 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 5 5B11 310 0 24 strand multimode New TR - Dumbwaiter area
1 5 5A42 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 5 5B46 0 24 strand multimode Abandon - New TR in dumbwaiter area
1 6 6A38 0 24 strand multimode Abandon - Move to expanded 6B10/6B11
1 6 6B10 310 0 24 strand multimode Room Expanded into Dumbwaiter Area
1 7 7A07F 230 0 24 strand multimode
1 7 7B02 340 0 24 strand multimode Room Expanded
CREATE REDUNDANT WAN PATH – ASSUME 1350’-0”
CONCRETE ENCASED 4” PVC OR HDPE WITH (4) 1” INTERDUCTS.
VAMC FIBER DISTANCES
FRESNO MEDICAL CENTER
VAMC Fresno
Building Floor Room
Distance (Ft.) from New Fiber Hub (old PBX)
Fiber Type Notes
Interior - 4" EMT
Exterior -Concrete
Encased 4" PVC or HDPE with (4) 1" Interducts
2 1 SP4 70 400 24 strand multimode
3 1 22A 190 200 24 strand multimode
24 1 2A17 145 40 24 strand multimode
25 1 1A18 30 260 24 strand multimode
27 2 2C05 165 500 24 strand singlemode
28 1 1E17 225 535 24 strand singlemode
31 1 1A17 120 480 24 strand singlemode
31 2 1B19 120 490 24 strand singlemode
31 3 1C16 135 540 24 strand singlemode
32 1 WH109 222 0 24 strand multimode
34 1 122 65 350 24 strand singlemode
34 1 228 430 0 24 strand singlemode
LC2 1 LC2-28 130 400 24 strand singlemode
OPC 1 B1C15/S0G13A 400 0 24 strand singlemode
OPC 1 B1C16 410 0 24 strand singlemode
OPC 1 1C45 414 0 24 strand singlemode
OPC 1 2C15D 429 0 24 strand singlemode
OPC 1 3C13/3C14 444 0 24 strand singlemode
DOOR SECURITY REQUIREMENTS
FRESNO MEDICAL CENTER
I D E N T I F I C AT I O N O F N E T WO R K S PAC E S
BLDG: 1
LEVEL: SUB-BASEMENT
SCALE: 1/32” = 1’-0”
DATE: 12/14/2020
N
EXPAND IN PLACE
STORAGE
ROOM B2A08
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
EXISTING TR LOCATION(S)
FRESNO MEDICAL CENTER
N
REMEDIATE IN PLACE
TELECOMMUNICATION ROOM
ROOM B1A13
REMEDIATE IN PLACE
SERVER ROOM
ROOM B1B14A
ABANDON
TELE ROOM B1A01.2
RELOCATE TO DUMBWAITER AREA
REMEDIATE IN PLACE
ELECTRICAL
ROOM B1B06
NEW TR ROOM
EXISTING DUMBWAITER AREA
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 1
LEVEL: BASEMENT
SCALE: 1/32” = 1’-0”
DATE: 12/14/2020
Pneumatic Tube System
The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require
110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three
(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.
NOTE:
ALL ABANDONED TR ROOMS ARE TO BE
REPURPOSED AS EITHER PHEUMATIC TUBE
STATIONS OR GENERAL STORAGE. MINIMUM
REQUIREMENTS FOR TR ROOMS TO BE
ABANDONED:
• REMOVE ALL IT EQUIPMENT
• SEAL ALL PENETRATIONS IN ACCORDANCE
WITH FIRE REQUIREMENTS
• PATCH AND REPAIR FLOORS
• PATCH, REPAIR AND PAINT WALLS
• PROVIDE NEW DROP-IN CEILING
• PROVIDE NEW LIGHTING
N
ABANDON
COMM ROOM 1A15D
RELOCATE TO DUMBWAITER AREA
ABANDON
COMM ROOM 1B17
RELOCATE TO DUMBWAITER AREA
ABANDON
COMM ROOM 1B01A
RELOCATE TO DUMBWAITER AREA
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
NEW TR ROOM
EXISTING DUMBWAITER AREA
NEW PNEUMATIC TUBE STOP
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 1
LEVEL: 1
SCALE: 1/32” = 1’-0”
DATE: 12/14/2020
Pneumatic Tube System
The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require
110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three
(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.
NOTE:
ALL ABANDONED TR ROOMS ARE TO BE
REPURPOSED AS EITHER PHEUMATIC TUBE
STATIONS OR GENERAL STORAGE. MINIMUM
REQUIREMENTS FOR TR ROOMS TO BE
ABANDONED:
• REMOVE ALL IT EQUIPMENT
• SEAL ALL PENETRATIONS IN ACCORDANCE
WITH FIRE REQUIREMENTS
• PATCH AND REPAIR FLOORS
• PATCH, REPAIR AND PAINT WALLS
COMM 2B17
RELOCATE TO
DUMBWAITER AREA
EXISTING SPACE TO BE POTENTIAL SITE
FOR PNEUMATIC TUBE STOP
N
ABANDON
COMM 2A19
RELOCATE TO DUMBWAITER AREA
EXISTING SPACE TO BE POTENTIAL
SITE FOR PNEUMATIC TUBE STOP
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
NEW TR ROOM
EXISTING DUMBWAITER AREA
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 1
LEVEL: 2
SCALE: 1/32” = 1’-0”
DATE: 12/14/2020
Pneumatic Tube System
The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require
110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three
(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.
NOTE:
ALL ABANDONED TR ROOMS ARE TO BE
REPURPOSED AS EITHER PHEUMATIC TUBE
STATIONS OR GENERAL STORAGE. MINIMUM
REQUIREMENTS FOR TR ROOMS TO BE
ABANDONED:
• REMOVE ALL IT EQUIPMENT
• SEAL ALL PENETRATIONS IN ACCORDANCE
WITH FIRE REQUIREMENTS
• PATCH AND REPAIR FLOORS
• PATCH, REPAIR AND PAINT WALLS
COMM ROOM 3B09D
RELOCATE TO
DUMBWAITER AREA
EXISTING SPACE TO BE POTENTIAL SITE
FOR PNEUMATIC TUBE STOP
N
REMEDIATE IN PLACE
COMM ROOM 3A11
EXISTING SPACE TO BE POTENTIAL SITE
FOR PNEUMATIC TUBE STOP
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
NEW TR ROOM
EXISTING DUMBWAITER AREA
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 1
LEVEL: 3
SCALE: 1/32” = 1’-0”
DATE: 12/14/2020
Pneumatic Tube System
The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require
110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three
(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.
NOTE:
ALL ABANDONED TR ROOMS ARE TO BE
REPURPOSED AS EITHER PHEUMATIC TUBE
STATIONS OR GENERAL STORAGE. MINIMUM
REQUIREMENTS FOR TR ROOMS TO BE
ABANDONED:
• REMOVE ALL IT EQUIPMENT
• SEAL ALL PENETRATIONS IN ACCORDANCE
WITH FIRE REQUIREMENTS
• PATCH AND REPAIR FLOORS
• PATCH, REPAIR AND PAINT WALLS
COMM ROOM 4B42
RELOCATE TO DUMBWAITER AREA
EXISTING SPACE TO BE POTENTIAL SITE
FOR PNEUMATIC TUBE STOP
N
ABANDON
COMM ROOM 4A31
RELOCATE TO DUMBWAITER AREA
EXISTING SPACE TO BE POTENTIAL SITE
FOR PNEUMATIC TUBE STOP
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
NEW TR ROOM
EXISTING DUMBWAITER AREA
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 1
LEVEL: 4
SCALE: 1/32” = 1’-0”
DATE: 12/14/2020
Pneumatic Tube System
The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require
110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three
(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.
NOTE:
ALL ABANDONED TR ROOMS ARE TO BE
REPURPOSED AS EITHER PHEUMATIC TUBE
STATIONS OR GENERAL STORAGE. MINIMUM
REQUIREMENTS FOR TR ROOMS TO BE
ABANDONED:
• REMOVE ALL IT EQUIPMENT
• SEAL ALL PENETRATIONS IN ACCORDANCE
WITH FIRE REQUIREMENTS
• PATCH AND REPAIR FLOORS
• PATCH, REPAIR AND PAINT WALLS
COMM ROOM 5B46
EXISTING SPACE TO BE POTENTIAL SITE
FOR PNEUMATIC TUBE STOP
N
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
NEW TR ROOM
EXISTING DUMBWAITER AREA
ABANDON
COMM ROOM 5A42
RELOCATE TO DUMBWAITER AREA
EXISTING SPACE TO BE POTENTIAL SITE
FOR PNEUMATIC TUBE STOP
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 1
LEVEL: 5
SCALE: 1/32” = 1’-0”
DATE: 12/14/2020
Pneumatic Tube System
The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require
110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three
(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.
NOTE:
ALL ABANDONED TR ROOMS ARE TO BE
REPURPOSED AS EITHER PHEUMATIC TUBE
STATIONS OR GENERAL STORAGE. MINIMUM
REQUIREMENTS FOR TR ROOMS TO BE
ABANDONED:
• REMOVE ALL IT EQUIPMENT
• SEAL ALL PENETRATIONS IN ACCORDANCE
WITH FIRE REQUIREMENTS
• PATCH AND REPAIR FLOORS
• PATCH, REPAIR AND PAINT WALLS
EXPAND IN PLACE
COMM ROOM 6B10
EXPAND INTO DUMBWAITER AREA
N
ABANDON
COMM ROOM 6A38
RELOCATE TO DUMBWAITER AREA
EXISTING SPACE TO BE POTENTIAL SITE
FOR PNEUMATIC TUBE STOP
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
NEW TR ROOM
EXISTING DUMBWAITER AREA
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 1
LEVEL: 6
SCALE: 1/32” = 1’-0”
DATE: 12/14/2020
Pneumatic Tube System
The pneumatic tube system in Building 1 will have eight (8) stations. Each station will require
110v/1p/60hz at 5 amps. The tubing will consist of 6” diameter tubing. There will be a minimum of three
(3) transfer stations and one (1) blower. Provide electrical power to blower, data cables, and update system (graphics, room names, room numbers, and software) for the pneumatic tube front end workstation.
NOTE:
ALL ABANDONED TR ROOMS ARE TO BE
REPURPOSED AS EITHER PHEUMATIC TUBE
STATIONS OR GENERAL STORAGE. MINIMUM
REQUIREMENTS FOR TR ROOMS TO BE
ABANDONED:
• REMOVE ALL IT EQUIPMENT
• SEAL ALL PENETRATIONS IN ACCORDANCE
WITH FIRE REQUIREMENTS
• PATCH AND REPAIR FLOORS
• PATCH, REPAIR AND PAINT WALLS
REMEDIATE IN PLACE
COMM ROOM
7B02
N
REMEDIATE IN PLACE
COMM ROOM
7A07F
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
EXISTING DUMBWAITER AREA
AVAILABLE FOR MECH. SPACE
IF NEEDED
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 1
LEVEL: 7
SCALE: 1/32” = 1’-0”
DATE: 12/14/2020
NOTE:
ALL ABANDONED TR ROOMS ARE TO BE
REPURPOSED AS EITHER PHEUMATIC TUBE
STATIONS OR GENERAL STORAGE. MINIMUM
REQUIREMENTS FOR TR ROOMS TO BE
ABANDONED:
• REMOVE ALL IT EQUIPMENT
• SEAL ALL PENETRATIONS IN ACCORDANCE
WITH FIRE REQUIREMENTS
• PATCH AND REPAIR FLOORS
• PATCH, REPAIR AND PAINT WALLS
SP4 (CABINET ON NORTH WALL)
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 2
LEVEL: 1
SCALE: 1/32” = 1’-0”
DATE: 12/14/2020
TELE. CLOSET
22A
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 3
LEVEL: 1
COMM
2A17
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
NOTE: REMOVE EXISTING CABLING
& EQUIPMENT FROM THE 3rd
FLOOR, ROOM 3A20
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 24
LEVEL: 2
SCALE: 1/16” = 1’-0”
COMM CLOSET
1A18
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 25
LEVEL: 1
DATA
2C05
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 27
LEVEL: 2
TELE/DATA ROOM
1E17
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 28
LEVEL: 1
COMM ROOM
1B19
EXPAND IN PLACE
COMM ROOM
1A17
REMEDIATE IN PLACE
COMM ROOM
1C16
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
NOTE: ROOMS NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 31
LEVEL: 1
CABINET
WH109
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 32
LEVEL: 1
TELE/DATA
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 34
LEVEL: 1
TELE/DATA
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: 34
LEVEL: 2
RELOCATE
TELEPHONE CLOSET B1C15
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
NEW TELEPHONE CLOSET
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: OPC
LEVEL: BASEMENT
COMM
1C45
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: OPC
LEVEL: 1
COMM
2C15D
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: OPC
LEVEL: 2
COMM
3C13 & 3C14
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: OPC
LEVEL: 3
COMM CLOSET
LC2-28
EXISTING TR LOCATION(S)
VA CENTRAL CALIFORNIA HEALTHCARE SYSTEM
FRESNO MEDICAL CENTER
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: LC2
LEVEL: 1
I D E N T I F I C AT I O N O F O F F C A M P U S N E T WO R K S PAC E S
FRESNO
REMEDIATE IN PLACE
IT
NOTE: ROOM NOT VISITED BY RFP DEVELOPER.
SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: M STREET
LEVEL: 9
FRESNO
N
REMEDIATE IN PLACE
IT
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: MERCED CBOC
LEVEL: 1
FRESNO
REMEDIATE IN PLACE
IT
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: OAKHURST CBOC
LEVEL: 1
FRESNO
N
EXPAND IN PLACE
IT
SV20
LEGEND
LOCATION OF EXISTING
TR /DC
POTENTIAL LOCATION
FOR RELOCATED TR
BLDG: TULARE CBOC
LEVEL: 1
N E T WO R K S PAC E D E S I G N
B2A08
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: SUB-BASEMENT
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
ROOM NO. B2A08 STORAGE
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Needs dedicated HVAC unit X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Cooling inadequate There is no air condition in this room X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special
Telecommunications Systems Design
Manual
X No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
Remote Controlled battery thermostat Wired thermostat X
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 27
Approximate total cable length = 4207.5'
Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
X Inadequate rack space for new equipment provide new rack as required.
REMOVE PORTION OF
EXISTING WALL.
INSTALL NEW DOOR.
NEW WALL
APPROX. SIZE
8’-3” x 10’-2”
NOTE: This is a small 1/2 rack mounted on the wall of a large storage room. The mechanical yard is referred to as "the moat" where you can place a condensing unit.
EMS STORAGE
(CURRENT LOCATION
OF COMM B2A08)
COMM ROOM
(RENOVATED)
B1A13
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: BASEMENT
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
PROVIDE NEW WALL
& NEW 4’ DOOR
TO CREATE ROOM
FOR A NEW FIBER
HUB
TELECOMMUNICATION
ROOM
B1A13
NEW FIBER HUB
ROOM NO. B1A13 TELEPHONE/ELECTRICAL CLOSET (VA ER RENOVATION)
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Needs dedicated HVAC unit
X
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Cooling inadequate
Room is warm. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above. X
Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS X
Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
X
Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough
X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X UPS Central Monitoring BACnet conversion
X
No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special
Telecommunications Systems Design
Manual
X No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
Remote Controlled battery thermostat Wired thermostat
X
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Micro condensate pump
Commercial condensate pump
X
Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
X
Inadequate rack space for new equipment provide new rack as required.
B1B06
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: BASEMENT
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
ELECTRICAL
B1B06
ROOM NO. B1B06 ELECTRICAL
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
Cooling inadequate Needs dedicated HVAC unit Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA
L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU
Cooling inadequate There is no air condition in this room Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X UPS Central Monitoring BACnet conversion No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special Telecommunications
Systems Design Manual
X No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
Inadequate fiber optic cabling to TR Install new as required
X Remote Controlled battery thermostat Wired thermostat
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Micro condensate pump Commercial condensate pump Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
Inadequate rack space for new provide new rack as required.Note: UPS "big blue" is not being monitored.
B1B14A
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: BASEMENT
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
SERVER ROOM
B1B14A
ROOM NO. B1B14A SERVER ROOM
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
Cooling inadequate Needs dedicated HVAC unit X
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU
Cooling inadequate There is no air condition in this room X Insufficient Central UPS power backup.
Design Build contractor to determine size of Central UPS.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
X Missing Telecom Main
Ground Bar (TMGB) Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs three (3) new temperature monitoring sensors per rack, three (3) humidity sensor, and controls from BMS
X
Inadequate grounding connections to metal objects in date canter.
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough
X UPS Central Monitoring BACnet conversion X
No telecommunications bonding backbone to other
TR grounding bars
Provide grounding conductor to nearest
TR per VA Telecommunications and
Special Telecommunications Systems
Design Manual
No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
X
No redundant fiber optic cable feeds entering the building on opposite faces.
Install new as required
Remote Controlled battery thermostat Wired thermostat
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = TBD
Approximate total cable length = TBD'
Micro condensate pump
Commercial condensate pump Horizontal cable run not to exceed 292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
Inadequate rack space for new equipment
DUMBWAITER AREA
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: BASEMENT
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
NEW TR ROOM
DUMBWAITER AREA
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate
Provide 2-ton DX Liebert Mini Mate-
2 with I-COM. Condensing unit on ground floor or roof.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
Cooling inadequate
Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Provide grounding cable to MDF ground bar.
X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars
Provide grounding conductor to nearest TR per VA Telecommunications and Special
Telecommunications Systems Design
Manual
X No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
X Remote Controlled battery thermostat Wired thermostat X
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 80
Approximate total cable length = 10,900'
X Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
X Inadequate rack space for new equipment
NEW TR IN DUMBWAITER AREA
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: 1
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
NEW WALL
NEW TR ROOM
DUMBWAITER AREA
NEW TR IN DUMBWAITER AREA (ROOM NO. 1B17 COMM ABANDONED)
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate
Provide 2-ton DX Liebert Mini Mate-
2 with I-COM. Condensing unit on ground floor or roof.
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
Cooling inadequate
Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above. X
Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
X
Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough
X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Ground cable leaves room. Verify where this goes. If not provide grounding cable to
MDF ground bar.
X UPS Central Monitoring BACnet conversion
X
No telecommunications bonding backbone to other TR grounding bars
Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
X No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
Inadequate fiber optic cabling to TR Install new as required
Remote Controlled battery thermostat Wired thermostat
X
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables =
440Approximate total cable length =
59,400'
Micro condensate pump Commercial condensate pump
X
Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
X
Inadequate rack space for new
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: 2
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
NEW TR ROOM
EXPAND ROOM
INTO 2B03
REMOVE EXISTING DOOR.
INFILL OPENING.
EXISTING STORAGE
ROOM
2B03
NEW TR IN DUMBWAITER AREA (ROOM NO. 2B17 COMM ABANDONED)
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate
Provide 2-ton DX Liebert Mini Mate-
2 with I-COM or Liebert PDX with I-
COM. Contractor to verify refrigerant lines. Condensing unit on ground floor or roof.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
Cooling inadequate
Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Ground cable leaves room. Verify where this goes. If not provide grounding cable to
MDF ground bar.
X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars
Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
X No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
Remote Controlled battery thermostat Wired thermostat X
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 300
Approximate total cable length = 40,000'
Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
X Inadequate rack space for new
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: 3
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
NEW TR ROOM
NEW TR IN DUMBWAITER AREA (ROOM NO. 3A11 COMM ABANDONED)
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate
Provide 2-ton DX Liebert Mini Mate-
2 with I-COM. Condensing unit on roof.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU
Cooling inadequate
Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA Telecommunications and Special
Telecommunications Systems Design Manual
Piping over equipment Relocate piping or pipe trough X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Ground cable leaves room. Verify where this goes. If not provide grounding cable to MDF ground bar.
X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars
Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA
Telecommunications and Special Telecommunications
Systems Design Manual
X No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
Remote Controlled battery thermostat Wired thermostat X
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A. Approximate number of cables = 185 Approximate total cable length =
25,000'
Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-
80M)
X Inadequate rack space for new
3A11
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: 3
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
ROOM NO. 3A11 COMM
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Needs dedicated HVAC unit Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
X Cooling inadequate
Room is warm. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Ground cable leaves room. Verify where this goes. If not provide grounding cable to
MDF ground bar.
X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars
Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
X No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
Remote Controlled battery thermostat Wired thermostat X
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 72
Approximate total cable length = 11880'
Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
Inadequate rack space for new equipment
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: 4
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
NEW TR ROOM
EXPAND INTO
OFFICE 4B09
NEW TR IN DUMBWAITER AREA (ROOM NO. 4B42 COMM ABANDONED)
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate
Provide 2-ton DX Liebert Mini Mate-
2 with I-COM. Condensing unit on roof.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
Cooling inadequate
Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Ground cable leaves room. Verify where this goes. If not provide grounding cable to
MDF ground bar.
X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars
Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
X No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
Remote Controlled battery thermostat Wired thermostat X
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 230
Approximate total cable length = 31,000'
Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
X Inadequate rack space for new
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: 5
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
NEW TR ROOM
NEW TR IN DUMBWAITER AREA (ROOM NO. 5A42 COMM ABANDONED)
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate
Provide 2-ton DX Liebert Mini Mate-
2 with I-COM. Condensing unit on roof.
X Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
Cooling inadequate
Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Ground cable leaves room. Verify where this goes. If not provide grounding cable to
MDF ground bar.
X UPS Central Monitoring BACnet conversion X No telecommunications bonding backbone to other TR grounding bars
Ground cable leaves room. Verify where this goes. If not provide grounding conductor to nearest TR per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
X No condensate leak detection Needs condensate leak detection
C A
B
LI
N G
X Inadequate fiber optic cabling to TR Install new as required
Remote Controlled battery thermostat Wired thermostat X
Horizontal and/or patch data cabling below minimum Cat 5e.
Replace all cabling with Cat 6A.
Approximate number of cables = 210
Approximate total cable length = 28,100'
Micro condensate pump Commercial condensate pump X Horizontal cable run not to exceed
292 feet
Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-260' (70-80M)
X Inadequate rack space for new
FRESNO MEDICAL CENTER
BLDG: 1
LEVEL: 6
SCALE: 1/4” = 1’-0”
DATE: 12/14/2020
N
NEW TR ROOM.
EXPAND INTO
EXISTING
COMM RM
NEW TR IN DUMBWAITER AREA (ROOM NO. 6B10)
C O
O
LI
N G
"X" EXISTING ISSUES RECOMMENDED SOLUTIONS
E
LE
C T
R
IC
A L
"X' EXISTING ISSUES RECOMMENDED SOLUTIONS
X Cooling inadequate Provide 2-ton VRF system with
BACnet communication X
Insufficient redundant power connections for network equipment.
Provide (2) 30A, 208V, 5 wire NEMA L21-
30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone
PDU
Cooling inadequate
Room is hot. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.
X Insufficient UPS power backup.
Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.
X Room Temperature/Humidity
Monitoring Inadequate
Room needs new COMBINATION temperature and humidity monitoring and/or controls from
BMS
X Missing grounding bus bar Install copper grounding bus bar
X Rack Temperature/Humidity
Monitoring Inadequate
Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS
X Inadequate grounding connections to metal objects in TR
Provide bonding conductors to non-energized metal surfaces per VA
Telecommunications and Special
Telecommunications Systems Design
Manual
Piping over equipment Relocate piping or pipe trough X
TR ground bar not connected to
Telecom Main Ground Bar (TMGB) in the data room
Ground cable leaves room.