Attachment 5 - Trailer Disconnect.pdf
PDF 935 KB Posted
- Attached to
- Mobile Office Trailers
- Solicitation number
- 663
- Issued by
- Idaho
About this file
This document is an electrical design specification and installation manual for a mobile office trailer disconnect and power system modification project in Salmon, Idaho, prepared by Myers Architecture and Anderson Interior Design Historic Preservation for the Idaho Transportation Department (ITD). The specification outlines comprehensive requirements for furnishing and installing a complete electrical system including general power, lighting, and communications system raceway, with a fire alarm system to be designed and built by the electrical contractor and communications cabling provided by the owner. The project involves installation of a 100-ampere trailer disconnect with pin and sleeve connections, a 200-ampere panelboard within the trailer, and a 100-ampere non-fused disconnect switch in a NEMA 3R enclosure, along with associated conduit, wiring, outlets, and grounding systems. The document specifies that electrical work must comply with the National Electrical Code, OSHA, International Building and Fire Codes, NFPA standards, and all applicable state and local codes, with the electrical contractor responsible for arranging inspections and paying all associated license, permit, and inspection fees. A site visit is required of all bidders prior to bid submission, and all work must be completed to the owner's satisfaction with a one-year guarantee period following the certificate of final payment.
The specifications establish strict material requirements mandating new, UL-labeled components including stranded copper conductors (minimum #12 AWG), THWN insulation for wet locations and THHN for dry locations, galvanized or cadmium-plated steel outlet boxes, specification-grade 20-amp 125-volt wiring devices with matching coverplates, and panelboards manufactured by Square D, General Electric, Siemens, or Eaton/Cutler Hammer. Outdoor raceways must utilize rigid steel or intermediate metal conduit, while indoor installations may use electrical metallic tubing or rigid steel conduit depending on exposure conditions. The contractor must submit seven copies of complete shop drawings and materials lists within fourteen days of contract award, identify all proposed deviations from specifications, provide three copies of operations and maintenance manuals, and deliver one clean legible copy of as-built drawings indicating any deviations from the initial design. The document includes detailed keynotes for equipment specifications such as Appleton pin and sleeve receptacles and connectors rated for 100-amp and 200-amp capacities at 125/250 volts, and establishes color-coding requirements for both 480/277-volt and 208/120-volt electrical systems throughout the installation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 4 - Technical Drawings.pdf | ||
| ITB663 - Attachment 2 - Bid Schedule.xlsx | XLSX spreadsheet | |
| ITB # 663 Mobile Office Trailer Admin Doc.docx | DOCX document | |
| Section 67-2302 – Idaho State Legislature (1).pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL &
MECHANICAL
LEGEND &
ABBREVIATIONS
E0.0
SHEET TITLE:
ARCH.
JOB
NUMBER:
REVISION DATE
SA
LM
O N
, I D
A H
O
PR
O
JE
C
T N
A M
E:
CONTRACTOR SHALL VERIFY
ALL DIMENSIONS & CONDITIONS
SHOWN or IMPLIED
23606-23A
February 2024
A
IA
N
C
RB
SI
D
SHEET
ISSUED
DATE:
SHEET
IT
D
D
SA
LM
O N
JO
B
TR
A
IL
ER
DRAWING SCALE APPLIES
TO 22" X 34" SHEET SIZE
CLIENT
PROJ.
NUMBER:
DO NOT DISTRIBUTE PARTIAL SETS OF
DRAWINGS or SPECIFICATIONS
M y e rs
A rc hi te ct ur e
A n d e r s o n
In te rio r D es ig n
H ist or ic P re se rv at io n
So ut h M ai n
St re et
Po ca te llo , I d ah o
T el
(2
) 2
F ax
(2
) 2
/02
/20
:04
IA
N
BR
OW
N G:
\C
LIE
NT
S\
IT
D\
IT
D2
4-
IT
D
TR
AI
LE
R
EX
TE
NS
IO
N
CO
RD
D
ES
IG
N\
DE
SI
GN
\E
LE
CT
RI
CA
L\E
0.0
LE
GE
ND
JO
B
TR
AI
LE
R.
DW
G
1. COLOR CODE WIRES AS FOLLOWS:
2. ELECTRICAL DEVICES AND LINEWORK ARE SHOWN
BOLD FOR NEW, BOLD/DASHED FOR DEMO &
RELOCATED AND MEDIUM/DASHED FOR EXISTING.
3. DIMENSIONED LENGTHS SHALL TAKE PRECEDENCE
OVER SCALED LENGTHS.
4. FURNISH AND INSTALL A COMPLETE ELECTRICAL
SYSTEM AS DEPICTED FROM THE PLANS AND
SPECIFICATIONS. COMPLETE AS NOTED OR IMPLIED,
NOT LIMITED TO WHAT IS SHOWN.
5. COORDINATE ALL DEVICE/EQUIPMENT LOCATIONS
AND SPECIFIC REQUIREMENTS WITH MECHANICAL
TRADE PRIOR TO ROUGH-IN.
CIRCUIT CONCEALED IN
CEILING OR WALL.
3/4"C-2#12,1#12G UNO.
CIRCUIT CONCEALED IN
FLOOR OR UNDERGROUND.
3/4"C-2#10,1#10G UNO.
CONDUIT STUBBED OR SLEEVE,
CAPPED, AND MARKED WITH PULL CORD
BRANCH PANEL.
CIRCUIT BREAKER. SIZE
AND TYPE AS SPECIFIED
JUNCTION BOX.
FLUSH MOUNTED
PANELBOARD/ENCLOSURE.
NON-FUSED DISCONNECT
SWITCH. SIZE AS INDICATED,
NEMA 1 UNO, 3 POLE UNO.
TRANSFORMER.
DUPLEX OUTLET. +18" AFF UNO.
T
3/4"C 2#12:C-1
1#12:GND
CONDUCTOR
QUANTITY
GROUNDING
CONDUCTOR
SIZE
RACEWAY SIZE
CONDUCTOR SIZE
CIRCUIT NUMBER
PANEL
FOURPLEX OUTLET. +18" AFF UNO.
METER AND BASE
PANEL
FINISH FLOOR
18"
46" 56"
78" 90"
FUSED DISCONNECT SWITCH.
SIZE AS INDICATED, NEMA 1
UNO, 3 POLE UNO.
SERVICE GROUND. GROUND PER NEC
ARTICLE 250
120V TWIST LOCK RECEPTACLE.TL
T
POWER SYSTEM DEVICE SYMBOLS
GFI OUTLET. +18" AFF UNO.
GFI OUTLET. ABOVE COUNTER
FOURPLEX GFI OUTLET. +18" AFF UNO.
EQUIPMENT CONNECTION
CIRCUIT WIRING SYMBOLS
ONE-LINE DIAGRAM SYMBOLS
CONDUCTORS
PHASE A
PHASE B
PHASE C
NEUTRAL
GROUND
120/208V
BLACK
RED
BLUE
WHITE
GREEN
480/277V
BROWN
ORANGE
YELLOW
GRAY
GREEN
DEDICATED SIMPLEX GFCI OUTLET. +18"
AFF UNO.
CONDUIT AND WIRE SIZE CALLOUT.####
TRANSFORMER
DETAILS
1 TYPICAL HEIGHTS DETAIL
---- SCALE: NTS
A AMPERES
AC ABOVE COUNTER; REFER
TO ARCHITECTURAL
ELEVATIONS FOR REQUIRED
HEIGHT.
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AF AMPERE FRAME
AHJ AUTHORITY HAVING
JURISDICTION
AT AMP TRIP
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CO CONDUIT ONLY, PROVIDE
PULL-LINE
Cu COPPER
CW COLD WATER
DC DIRECT CURRENT
DIA DIAMETER
(E) EXISTING
EF EXHAUST FAN
EMT ELECTRICAL MAGNETIC TUBING
F FUSE
FVNR FULL VOLTAGE NON-REVERSING
G/GND GROUND
GFI GROUND FAULT INTERRUPTION
GFP GROUND FAULT PROTECTION
HH HANDHOLE
HP HORSE POWER
IC INTERRUPTING CAPACITY
J/JB JUNCTION BOX
KAIC KILO-AMP INTERRUPTING
CURRENT
KW KILO-WATT
KVA KILO-VOLT AMPERE
MB MAIN BREAKER
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MLO MAIN LUGS ONLY
MS MOTOR STARTER
(N) NEW
N NEUTRAL
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NTS NOT TO SCALE
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
P PHASE
PC PHOTOCELL
PVC POLYVINYL CHLORIDE
RCPT RECEPTACLE
(R) RELOCATED
RE: REFER TO
RPVC RIGID PVC (SCHEDULE 80)
SER SERVICE ENTRANCE RATED
SPST SINGLE POLE SINGLE THROW
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
V VOLT
VA VOLT AMPERE
WP WEATHER PROOF/NEMA 3R
XFMR TRANSFORMER
ABBREVIATIONS & DESCRIPTIONS
PIN & SLEEVE CONNECTION
DOUBLE-POLE DOUBLE-THROW
DISCONNECT
100 A CORD MODIFICATION 2-27-24
02-27-2024
AutoCAD SHX Text A
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL
SPECIFICATIONS
E0.1
SHEET TITLE:
ARCH.
JOB
NUMBER:
REVISION DATE
SA
LM
O N
, I D
A H
O
PR
O
JE
C
T N
A M
E:
CONTRACTOR SHALL VERIFY
ALL DIMENSIONS & CONDITIONS
SHOWN or IMPLIED
23606-23A
D
SHEET
ISSUED
DATE:
SHEET
IT
D
D
SA
LM
O N
JO
B
TR
A
IL
ER
DRAWING SCALE APPLIES
TO 22" X 34" SHEET SIZE
CLIENT
PROJ.
NUMBER:
DO NOT DISTRIBUTE PARTIAL SETS OF
DRAWINGS or SPECIFICATIONS
M y e rs
A rc hi te ct ur e
A n d e r s o n
In te rio r D es ig n
H ist or ic P re se rv at io n
So ut h M ai n
St re te llo , I d ah o
T el
(2
) 2
) 2
/02
/20
:04
IA
N
BR
OW
N G:
\C
LIE
NT
S\
IT
D\
IT
D2
4-
IT
D
TR
AI
LE
R
EX
TE
NS
IO
N
CO
RD
D
ES
IG
N\
DE
SI
GN
\E
LE
CT
RI
CA
L\E
0.1 S
PE
C.
DW
G
ELECTRICAL SHEET SPECIFICATIONS
PART 1 - GENERAL
1.1 SCOPE OF WORK
FURNISH AND INSTALL ALL MATERIALS AND EQUIPMENT AND
PROVIDE ALL ASSOCIATED LABOR REQUIRED AND NECESSARY TO
COMPLETE THE WORK INTENDED BY OR INFERRED FROM THIS
SHEET SPECIFICATION AND DRAWING PACKAGE, AND ALL OTHER
WORK AND OR MISCELLANEOUS ITEMS, NOT SPECIFICALLY
MENTIONED, BUT REASONABLY INFERRED FOR A COMPLETE
INSTALLATION, INCLUDING ALL ACCESSORIES AND APPURTENANCES
REQUIRED FOR TESTING OF THE SYSTEM. IT IS THE INTENT OF THE
DRAWINGS AND SPECIFICATIONS THAT ALL SYSTEMS BE COMPLETE
AND READY FOR OPERATION. THIS PROJECT INCLUDES GENERAL
POWER, LIGHTING, AND COMMUNICATIONS SYSTEM RACEWAY. FIRE
ALARM SYSTEM, IF REQUIRED, IS TO BE DESIGN/BUILD BY
ELECTRICAL CONTRACTOR. COMMUNICATIONS SYSTEM CABLING
AND HEAD-END EQUIPMENT IS BY OWNER.
1.2 CODE COMPLIANCE
ALL WORK AND MATERIALS SHALL COMPLY WITH LATEST RULES,
CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE
MOST CURRENT ADOPTED VERSIONS OF OSHA, THE NATIONAL
ELECTRICAL CODE, INTERNATIONAL BUILDING AND FIRE CODES,
NFPA, AND OTHER APPLICABLE STATE AND LOCAL CODES, LAWS AND
REGULATIONS. CODE COMPLIANCE IS MANDATORY. NOTHING IN
THESE DRAWINGS AND SPECIFICATIONS PERMITS WORK NOT
CONFORMING TO THESE CODES. WHERE WORK IS SHOWN TO
EXCEED MINIMUM CODE REQUIREMENTS, COMPLY WITH DRAWINGS
AND SPECIFICATIONS.
1.3 LICENSE, FEES AND PERMITS
ELECTRICAL CONTRACTOR IS TO ARRANGE FOR REQUIRED
INSPECTIONS AND PAY ALL LICENSE, PERMIT AND INSPECTION FEES.
1.4 CONDITIONS AT SITE
VISIT TO SITE IS REQUIRED OF ALL BIDDERS PRIOR TO SUBMISSION
OF BID. ALL BIDDERS WILL BE HELD TO HAVE FAMILIARIZED
THEMSELVES WITH ALL DISCERNIBLE CONDITIONS AND NO EXTRA
PAYMENT WILL BE ALLOWED FOR WORK REQUIRED BECAUSE OF
THESE CONDITIONS, WHETHER SPECIFICALLY MENTIONED OR NOT.
LINES OF OTHER SERVICES THAT ARE DAMAGED AS A RESULT OF
THIS WORK SHALL PROMPTLY BE REPAIRED AT NO EXPENSE TO THE
OWNER TO COMPLETE SATISFACTION OF THE OWNER.
1.5 SAFETY
THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY
RESPONSIBLE FOR CONDITIONS OF THE JOB SITE, INCLUDING
SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE
OF THE WORK. CONTRACTOR SHALL HAVE AN ESTABLISHED SAFETY
PLAN THAT ALL EMPLOYEES ARE TRAINED ON.
1.6 GUARANTEE
GUARANTEE THE INSTALLATION FREE FROM DEFECTS OF
WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER
DATE OF CERTIFICATE OF FINAL PAYMENT AND PROMPTLY REMEDY
ANY DEFECTS DEVELOPING DURING THIS PERIOD, WITHOUT CHARGE.
1.7 SUBSTITUTIONS
WHEREVER POSSIBLE, MORE THAN ONE MANUFACTURER HAS BEEN
LISTED FOR VARIOUS ITEMS OF EQUIPMENT, ANY ONE OF WHICH
WILL BE ACCEPTABLE. BASE THE BID ON USE OF MATERIALS
SPECIFIED. IF, AFTER AWARD OF THE CONTRACT, A SUBSTITUTE IS
PROPOSED, THE REQUEST FOR PERMISSION TO SUBSTITUTE SHALL
BE ACCOMPANIED WITH A STATEMENT OF THE AMOUNT OF MONEY
TO BE RETURNED TO THE CONTRACT IF THE SUBSTITUTION IS
PERMITTED. THE OWNER IS THE SOLE JUDGE OF ACCEPTABILITY OF
PROPOSED SUBSTITUTIONS, IF A SUBSTITUTE ITEM IS PERMITTED,
AND ANY REDESIGN EFFORT IS THEREBY NECESSITATED, THE
REQUIRED REDESIGN SHALL BE AT THE CONTRACTOR'S EXPENSE.
1.8 SHOP DRAWINGS AND MATERIALS LISTS
SUBMIT TO THE OWNER, SEVEN (7) COPIES OF COMPLETE SHOP
DRAWINGS AND MATERIALS LISTS FOR REVIEW WITHIN FOURTEEN
(14) DAYS AFTER AWARD OF CONTRACT, ALL PROPOSED DEVIATIONS
FROM SPECIFICATIONS MUST BE CLEARLY LISTED UNDER A
PROMINENT HEADING ENTITLED "DEVIATIONS".
1.9 WORKMANSHIP
ONLY QUALITY WORKMANSHIP WILL BE ACCEPTED. HAPHAZARD OR
POOR INSTALLATION PRACTICE WILL BE CAUSE FOR REJECTION OF
WORK.
1.10 COORDINATION
COORDINATE WORK WITH OTHER TRADES TO AVOID CONFLICT AND
TO PROVIDE CORRECT ROUGH-IN AND CONNECTION FOR EQUIPMENT
FURNISHED BY OTHER TRADES THAT REQUIRE ELECTRICAL
CONNECTIONS. VERIFY EQUIPMENT DIMENSIONS AND
REQUIREMENTS WITH PROVISIONS SPECIFIED UNDER THIS SECTION.
CHECK ACTUAL JOB CONDITIONS BEFORE FABRICATING WORK.
REPORT NECESSARY CHANGES IN TIME TO PREVENT NEEDLESS
WORK AND OR DELAYS.
1.11 CUTTING AND PATCHING
ALL CUTTING AND PATCHING REQUIRED FOR WORK OF THIS DIVISION
IS INCLUDED HEREIN. COORDINATION WITH GENERAL CONTRACTOR
AND OTHER TRADES IS IMPERATIVE.
1.12 SITE CLEANUP
A. AFTER ALL OTHER WORK HAS BEEN ACCOMPLISHED, CLEAN
ALL EXPOSED CONDUIT, FIXTURES, EQUIPMENT AND
SUPPORTS. TOUCH UP PAINT ON ANY EQUIPMENT SCRAPED
OR SCRATCHED DURING CONSTRUCTION. DAMAGED
EQUIPMENT CAUSED BY THIS CONTRACTOR WILL BE
REPLACED.
B. LEAVE ALL AREAS INVOLVING ELECTRICAL WORK IN A
CONDITION SATISFACTORY TO THE OWNER. REMOVE ALL
CRATES, CARDBOARD, PACKING MATERIAL, WASTE MATERIAL,
AND OTHER DEBRIS LEFT OVER FROM CONSTRUCTION DAILY.
PART 2 - PRODUCTS
2.1 MATERIAL APPROVAL
ALL MATERIALS MUST BE NEW AND BEAR U.L. LABEL. MATERIALS
THAT ARE NOT COVERED BY UL TESTING STANDARDS SHALL BE
TESTED AND APPROVED BY AN INDEPENDENT TESTING LABORATORY
OF A GOVERNMENTAL AGENCY APPROVED BY THE AUTHORITY
HAVING JURISDICTION.
2.2 WIRES AND CABLES
A. CONDUCTORS FOR 600V SYSTEMS AND BELOW SHALL BE
STRANDED COPPER (UNLESS NOTED OTHERWISE), #12 AWG
MINIMUM.
B. INSULATION SHALL BE THWN FOR WET LOCATIONS AND THHN
FOR DRY LOCATIONS.
2.3 OUTLET BOXES, JUNCTION AND PULL BOXES
A. OUTLET BOXES SHALL BE GALVANIZED OR CADMIUM PLATED
STEEL SIZED AS PER N.E.C. OR AS NOTED. UTILIZE
RESIDENTIAL-GRADE PLASTIC HANGER BOXES FOR
NETWORK/COMMUNICATIONS CONNECTION POINTS. USE FOUR
(4) INCH SQUARE OCTAGON BOX FOR FIXTURES AND TILE TYPE
DEVICE BOXES.
2.4 WIRING DEVICES
A. PROVIDE AND INSTALL ALL WIRING DEVICES WITH
COVERPLATES AS NOTED ON THE PLANS. DEVICES AND
COVER PLATES SHALL MATCH THE EXISTING COLOR AND TYPE.
B. DEVICES: WALL SWITCHES AND CONVENIENCE OUTLETS SHALL
BE RATED FOR 20-AMP, 125-VOLT (NEMA 5-20 ANSI C73.12 UL
498) SPECIFICATION GRADE DEVICES EXCEPT AS NOTED.
RESIDENTIAL GRADE DEVICES ARE NOT PERMITTED.
C. PROVIDE FACTORY-FABRICATED WIRING DEVICES, IN TYPES,
AND ELECTRICAL RATINGS FOR APPLICATIONS INDICATED AND
COMPLYING WITH NEMA STDS. PUB. NO. WD1.
D. PROVIDE WIRING DEVICES (OF PROPER VOLTAGE RATING) AS
FOLLOWS:
MFGR C.O.'S 1-POLE 3-WAY 4-WAY W/PILOT
HUBBELL 5362 L 1221 L 1223 L 1234 L 1221-P1 L
P&S 5362 L 20AC1 L 20AC3 L 20AC4 L 20AC1-CPL
LEVITON 5362 L 1223 L 1223 L 1224 L
E. COVER PLATES: ALL DEVICES SHALL HAVE COVERPLATES.
THEY SHALL HAVE A PLAIN FLAT SURFACE WITH BEVELED
EDGES COMPATIBLE WITH THE DEVICE. THE COVER PLATES IN
THE SHOP, PARTS, TOOL ROOM AND FIRE RISER ROOM SHALL
BE STAINLESS STEEL. COVER PLATES IN ALL OFFICE TYPE
AREAS, SHOWROOM, RESTROOM AND HALLWAYS SHALL BE
HIGHLY IMPACT RESISTANT (NYLON OR LEXAN) AND SHALL
MATCH THE COLOR OF THE ASSOCIATED DEVICE.
F. EMPTY BOXES: SHALL BE COVERED WITH MATCHING
COVERPLATES. PROVIDE HARDWARE AS NEEDED.
G. EXTERIOR DEVICES SHALL BE 20A GFCI TYPE WITH
WATERPROOF HIGHLY IMPACT RESISTANT WHILE IN USE TYPE
COVER.
H. PIN & SLEEVE RECEPTACLES AND CONNECTORS:
1. 240/120V SINGLE PHASE, 100A AND 200A PIN AND SLEEVE
RECEPTACLES AND CONNECTORS. COMPLY WITH UL/CSA.
I. PRODUCTS INCORPORATED INTO THE WORK:
1. 200A: APPLETON 3W, 4P, 2" HUB, SPRING DOOR RECEPTACLE
WITH ADJA MOUNTING BOX AND CLAMPING RING PLUG.
2.100A: APPLETON 3W, 4P, 1-1/2" HUB, RECEPTACLE WITH AJA
MOUNTING BOX AND CLAMPING RING PLUG.
3. APPROVED EQUALS.
2.5 WIRE CONNECTORS
I. FOR WIRE SIZES #8 AWG AND SMALLER: INSULATED PRESSURE
TYPE (WITH LIVE SPRING) RATED 105°C, 600V, FOR BUILDING
WIRING AND 1000V IN FIXTURES, SCOTCHLOK OR IDEAL.
J. FOR WIRE SIZES #6 AWG AND LARGER: T&B OR EQUIVALENT
COMPRESSION TYPE WITH 3M #33+ OR PLYMOUTH "SLIPKNOT
GREY" TAPE INSULATION.
2.6 PANELBOARD
PANELBOARDS SHALL BE AS MANUFACTURED BY SQUARE D,
GENERAL ELECTRIC, SIEMENS, OR EATON/CUTLER HAMMER.
PROVIDE PANELBOARDS AS INDICATED ON SCHEDULES, WITH THE
FOLLOWING FEATURES: TINNED ALUMINUM BUS (98 PERCENT
CONDUCTIVITY), MECHANICAL-TYPE MAIN AND NEUTRAL LUGS,
NEUTRAL BUS RATED 100 PERCENT OF PHASE BUS, GROUND BUS
BONDED TO ENCLOSURE, BOLT-ON MOLDED-CASE
THERMAL-MAGNETIC BREAKERS.
2.7 RACEWAYS
A. OUTDOORS:
EXPOSED: RIGID STEEL OR INTERMEDIATE METAL CONDUIT
CONCEALED: RIGID STEEL OR INTERMEDIATE METAL CONDUIT
UNDERGROUND: RIGID NON-METALLIC CONDUIT
TO VIBRATING EQUIPMENT: LIQUID-TIGHT FLEXIBLE METAL CONDUIT
B. INDOORS:
EXPOSED: ELECTRICAL METALLIC TUBING, RIGID STEEL CONDUIT,
PVC-COATED RIGID STEEL CONDUIT
CONCEALED: ELECTRIC METALLIC TUBING, METAL CLAD (WHERE
ALLOWED BY AHJ)
DAMP OR WET LOCATIONS: RIGID STEEL CONDUIT
TO VIBRATING EQUIPMENT: FLEXIBLE METAL CONDUIT
PART 3 - EXECUTION
3.1 - GENERAL
A. ELECTRIC SYSTEM LAYOUTS INDICATED ON THE DRAWINGS
ARE GENERALLY DIAGRAMMATIC, BUT SHALL BE FOLLOWED AS
CLOSELY AS ACTUAL CONSTRUCTION AND WORK OF OTHER
TRADES WILL PERMIT.
B. CONSULT ALL OTHER DRAWINGS. VERIFY SCALES AND REPORT
ANY DIMENSIONAL DISCREPANCIES OR OTHER CONFLICTS TO
ARCHITECT BEFORE SUBMITTING BID.
C. ALL HOME RUNS ARE INDICATED AS STARTING FROM THE
DEVICE NEAREST THE PANEL AND CONTINUING IN THE
GENERAL DIRECTION OF THAT PANEL. CONTINUE SUCH
CIRCUITS TO THE PANEL AS THOUGH THE ROUTES WERE
COMPLETELY INDICATED.
D. AVOID CUTTING AND BORING HOLES THROUGH STRUCTURE OR
STRUCTURAL MEMBERS WHEREVER POSSIBLE. OBTAIN PRIOR
APPROVAL OF ARCHITECT AND CONFORM TO ALL STRUCTURAL
REQUIREMENTS WHEN CUTTING OR BORING THE STRUCTURE
IS NECESSARY AND PERMITTED.
3.2 - ELECTRICAL GROUNDING
GROUND ALL ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC
ARTICLE 250. IN ADDITION PROVIDE A SEPARATE GROUND WIRE FOR
ALL FEEDERS AND BRANCH CIRCUITS.
3.3 - ELECTRICAL EQUIPMENT INSTALLATION
A. HEAD ROOM MAINTENANCE: IF MOUNTING HEIGHTS OR OTHER
LOCATION CRITERIA ARE NOT INDICATED, ARRANGE AND
INSTALL COMPONENTS AND EQUIPMENT TO PROVIDE THE
MAXIMUM POSSIBLE HEADROOM.
B. MATERIALS AND COMPONENTS: INSTALL LEVEL, PLUMB, AND
PARALLEL AND PERPENDICULAR TO OTHER BUILDING SYSTEMS
AND COMPONENTS, UNLESS OTHERWISE INDICATED.
C. EQUIPMENT: INSTALL TO FACILITATE SERVICE, MAINTENANCE,
AND REPAIR OR REPLACEMENT OF COMPONENTS. CONNECT
FOR EASE OF DISCONNECTING, WITH MINIMUM INTERFERENCE
WITH OTHER INSTALLATIONS.
D. RIGHT OF WAY: COORDINATE INSTALLATION OF ELECTRICAL
DEVICES WITH OTHER TRADES.
3.4 - RACEWAY AND CABLE INSTALLATION
RACEWAY:
A. ABOVE GRADE: RIGID STEEL OR IMC IN WET LOCATIONS,
WHERE SUBJECT TO MECHANICAL DAMAGE AND IN CONCRETE
OR BLOCK WALLS, EMT IN OTHER LOCATIONS WHERE
PERMITTED BY CODE. METAL CLAD ONLY WHERE ALLOWED BY
LOCAL AUTHORITY HAVING JURISDICTION.
B. CONCEAL RACEWAYS AND CABLES WITHIN FINISHED WALLS,
CEILINGS, AND FLOORS, UNLESS OTHERWISE INDICATED.
C. INSTALL RACEWAYS AND CABLES AT LEAST SIX (6) INCHES
AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR
HOT-WATER PIPES. LOCATE HORIZONTAL RACEWAY RUNS
ABOVE WATER AND STEAM PIPING.
D. USE TEMPORARY RACEWAY CAPS TO PREVENT FOREIGN
MATTER FROM ENTERING.
E. MAKE CONDUIT BENDS AND OFFSETS SO INSIDE DIAMETER IS
NOT REDUCED. KEEP LEGS OF BENDS IN THE SAME PLANE AND
STRAIGHT LEGS OFFSETS PARALLEL, UNLESS OTHERWISE
INDICATED.
F. USE RACEWAY FITTINGS AND CABLE FITTINGS COMPATIBLE
WITH RACEWAYS AND CABLES AND SUITABLE FOR THIS
APPLICATION AND LOCATION.
G. INSTALL RACEWAYS EMBEDDED IN SLABS IN MIDDLE THIRD OF
SLAB THICKNESS WHERE PRACTICAL, AND LEAVE AT LEAST
1-INCH OF CONCRETE COVER.
H. SECURE RACEWAYS TO REINFORCING RODS TO PREVENT
SAGGING OR SHIFTING DURING CONCRETE PLACEMENT.
I. SPACE RACEWAYS LATERALLY TO PREVENT VOIDS IN
CONCRETE.
J. INSTALL CONDUIT LARGER THAN 1-INCH TRADE SIZE PARALLEL
TO OR AT RIGHT ANGLES TO MAIN REINFORCEMENT. WHERE
CONDUIT IS AT RIGHT ANGLES TO REINFORCEMENT, PLACE
CONDUIT CLOSE TO SLAB SUPPORT.
K. TRANSITION FROM NONMETALLIC TUBING TO RIGID STEEL
CONDUIT, OR IMC BEFORE RISING ABOVE FLOOR.
L. MAKE EXPOSED BENDS FOR BANKED RUNS FROM SAME
CENTERLINE IN ORDER THAT BENDS ARE PARALLEL. USE
FACTORY ELBOWS ONLY WHERE ELBOWS CAN BE INSTALLED
PARALLEL; OTHERWISE, PROVIDE FIELD BENDS FOR
EXPOSED PARALLEL RACEWAYS.
CABLES:
A. INSTALL PULL WIRES IN EMPTY RACEWAYS. USE NO. 14 AWG
ZINC-COATED STEEL OR MONOFILAMENT PLASTIC LINE WITH
NOT LESS THAN 200-LB TENSILE STRENGTH. LEAVE AT LEAST
12-INCHES OF SLACK AT EACH END OF PULL WIRE.
B. INSTALL TELEPHONE AND SIGNAL SYSTEM RACEWAYS, 2-INCH
TRADE SIZE AND SMALLER, IN MAXIMUM LENGTHS OF 150 FEET
(45 M) AND WITH A MAXIMUM OF TWO 90-DEGREE BENDS OR
EQUIVALENT. SEPARATE LENGTHS WITH PULL OR JUNCTION
BOXES WHERE NECESSARY TO COMPLY WITH THESE
REQUIREMENTS, IN ADDITION TO REQUIREMENTS ABOVE.
C. CONNECT MOTORS AND EQUIPMENT SUBJECT TO VIBRATION,
NOISE TRANSMISSION, OR MOVEMENT WITH A MAXIMUM OF
72-INCH FLEXIBLE CONDUIT. INSTALL LFMC IN WET OR DAMP
LOCATIONS. INSTALL A SEPARATE GROUND CONDUCTOR
ACROSS FLEXIBLE CONNECTIONS.
D. SET FLOOR BOXES LEVEL AND TRIM AFTER INSTALLATION TO
FIT FLUSH TO FINISHED FLOOR SURFACE.
E. CONDUCTORS: TYPE THHN/THWN INSULATED CONDUCTORS IN
RACEWAY.
F. INSTALL SPLICES AND TAPS THAT ARE COMPATIBLE WITH
CONDUCTOR MATERIAL AND THAT POSSESS EQUIVALENT OR
BETTER MECHANICAL STRENGTH AND INSULATION RATINGS
THAN UNSPLICED CONDUCTORS.
G. INSTALL WIRING AT OUTLETS WITH AT LEAST 12 INCHES OF
SLACK CONDUCTOR AT EACH OUTLET.
H. CONNECT OUTLET AND COMPONENT CONNECTIONS TO WIRING
SYSTEMS AND TO GROUND. TIGHTEN ELECTRICAL
CONNECTORS AND TERMINALS, ACCORDING TO
MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES.
IF MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED,
USE THOSE SPECIFIED IN UL 486A.
3.5 IDENTIFICATION
A. PROVIDE ENGRAVED 3 LAYER LAMINATE PLASTIC NAMEPLATES
FOR PANELBOARDS, DISCONNECT SWITCHES AND ALL SIMILAR
DEVICES.
B. COLOR-CODE 480/277-VOLT SYSTEM THREE PHASE SERVICE,
FEEDERS, AND BRANCH-CIRCUIT CONDUCTORS THROUGHOUT
THE SECONDARY ELECTRICAL SYSTEM AS FOLLOWS:
1. PHASE A: BROWN
2. PHASE B: ORANGE
3. PHASE C: YELLOW
4. NEUTRAL: GRAY
5. GROUND: GREEN WITH YELLOW STRIPE
C. COLOR-CODE 208/120-VOLT SYSTEM THREE PHASE SERVICE,
FEEDERS, AND BRANCH-CIRCUIT CONDUCTORS THROUGHOUT
THE SECONDARY ELECTRICAL SYSTEM AS FOLLOWS:
1. PHASE A: BLACK
2. PHASE B: RED
3. PHASE C: BLUE
4. NEUTRAL: WHITE
5. GROUND: GREEN
3.7 OPERATING AND MAINTENANCE INSTRUCTIONS
(O+M MANUAL)
PREPARE THREE (3) COPIES FOR ALL EQUIPMENT.
3.8 RECORD AS-BUILTS
PROVIDE (1) CLEAN, LEGIBLE COPY OF DRAWINGS TO ENGINEER
INDICATING ALL DEVIATIONS FROM INITIAL DESIGN (AS-BUILT
CONDITIONS).
3.9 STRUT CHANNEL -
MANUFACTURERS
SUBJECT TO COMPLIANCE WITH REQUIREMENTS SET
FORTH IN THE DRAWINGS, PROVIDE PRODUCTS BY
ONE OF THE FOLLOWING:
1. UNISTRUT
2. COOPER B-LINE
3. ALLIED TUBE & CONDUIT
4. THOMAS & BETTS
5. WESANCO
6. GS GLOBAL METAL
7. APPROVED EQUAL
END OF SECTION
February 2024
100 A CORD MODIFICATION 2-27-24
02-27-2024
(N)125/250V, 100A PIN &
SLEEVE CONNECTION
100A NON-FUSED
TRAILER DISCONNECT
(W) 125/250V, 100A PIN
& SLEEVE
CONNECTION
TO ALTERNATE
POWER
(E) 200A PANELBOARD
TRAILER
(E) EQUIPMENT RACK
(E) DATA BOX
EXISTING TRAILER HITCH
LOCATE ELECTRICAL
EQUIPMENT SUCH THAT
CLEARANCE IS MAINTAINED
EXISTING AC UNIT
KEEP ELECTRICAL
EQUIPMENT CLEAR
ELECTRICAL
DETAILS
E5.0
SHEET TITLE:
ARCH.
JOB
NUMBER:
REVISION DATE
SA
LM
O N
, I D
A H
O
PR
O
JE
C
T N
A M
E:
CONTRACTOR SHALL VERIFY
ALL DIMENSIONS & CONDITIONS
SHOWN or IMPLIED
23606-23A
D
SHEET
ISSUED
DATE:
SHEET
IT
D
D
SA
LM
O N
JO
B
TR
A
IL
ER
DRAWING SCALE APPLIES
TO 22" X 34" SHEET SIZE
CLIENT
PROJ.
NUMBER:
DO NOT DISTRIBUTE PARTIAL SETS OF
DRAWINGS or SPECIFICATIONS
M y e rs
A rc hi te ct ur e
A n d e r s o n
In te rio r D es ig n
H ist or ic P re se rv at io n
So ut h M ai n
St re te llo , I d ah o
T el
(2
) 2
) 2
/02
/20
:07
IA
N
BR
OW
N G:
\C
LIE
NT
S\
IT
D\
IT
D2
4-
IT
D
TR
AI
LE
R
EX
TE
NS
IO
N
CO
RD
D
ES
IG
N\
DE
SI
GN
\E
LE
CT
RI
CA
L\E
5.0 D
ET
AI
LS
T
RA
ILE
R.
DW
G
1 TRAILER ELEVATION DETAIL
E5.0 SCALE: NTS
1. DOUBLE-POLE DOUBLE-THROW SWITCH 100A. NEMA 3R
ENCLOSURE REQUIRED.
2. APPLETON ADJA10034-150 (RECEPTACLE). NEMA 3R
RATED.
3. APPLETON ADJA10034-150RS (RECEPTACLE). NEMA 3R
RATED.
4. APPLETON AP10034E (PLUG). NEMA 3R RATED.
5. APPLETON AP10034ERS (PLUG). NEMA 3R RATED.
6. TF KABLE W4-4 50'-0" TYPE W PORTABLE POWER CABLE.
KEYNOTES: #
February 2024
A. MAINTAIN NEC REQUIRED WORKING CLEARANCES FOR ALL
PANELS AND DISCONNECTS
B. ADDITIONAL LOADS NOT TO EXCEED 100 AMPS.
SHEET NOTES:
G N
(E)400A/2P
(E)PANELBOARD
400A, 120/240V
1Φ, 3W
(N)TRAILER
DISCONNECT
100A/2P
(E)100A/2P
(E)200A/2P
(E)PIN &
SLEEVE 100A
(E)PIN &
SLEEVE 200A
(N)2"C - 3#3, 1#8G
(E)PANELBOARD
200A, 120/240V
FUTURE
CONNECTION
(FUTUR)PIN &
SLEEVE 200A
(N)PIN &
SLEEVE 100A
(N)#4, TYPE W CABLE
(FUTURE) #1/0, TYPE W CABLE
SINGLE-LINE
DIAGRAM
E6.0
SHEET TITLE:
ARCH.
JOB
NUMBER:
REVISION DATE
SA
LM
O N
, I D
A H
O
PR
O
JE
C
T N
A M
E:
CONTRACTOR SHALL VERIFY
ALL DIMENSIONS & CONDITIONS
SHOWN or IMPLIED
23606-23A
D
SHEET
ISSUED
DATE:
SHEET
IT
D
D
SA
LM
O N
JO
B
TR
A
IL
ER
DRAWING SCALE APPLIES
TO 22" X 34" SHEET SIZE
CLIENT
PROJ.
NUMBER:
DO NOT DISTRIBUTE PARTIAL SETS OF
DRAWINGS or SPECIFICATIONS
M y e rs
A rc hi te ct ur e
A n d e r s o n
In te rio r D es ig n
H ist or ic P re se rv at io n
So ut h M ai n
St re te llo , I d ah o
T el
(2
) 2
) 2
/02
/20
:04
IA
N
BR
OW
N G:
\C
LIE
NT
S\
IT
D\
IT
D2
4-
IT
D
TR
AI
LE
R
EX
TE
NS
IO
N
CO
RD
D
ES
IG
N\
DE
SI
GN
\E
LE
CT
RI
CA
L\E
6.0 S
IN
GL
E-
LIN
E
DI
AG
RA
M.
DW
G
1 SINGLE-LINE DIAGRAM
E6.0 SCALE: NTS
February 2024