This is an inventory spreadsheet attachment supporting an RFQ for annual backflow inspection and repair services at the VA Maine Healthcare System Togus Medical Center. The spreadsheet serves as a pricing template and line item detail document for the solicitation, outlining the required supplies and services that vendors must quote against.
The solicitation (36C24126Q0744) is a set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) with a NAICS code of 238220 and a small business size standard of $19 Million. The work involves backflow device inspection and preventive maintenance in accordance with the Statement of Work (SOW) across a base year (Item 0001) and two optional years (OY1 and OY2, Items 1001-2003). For OY1 and OY2 periods, vendors must provide pricing for inspection and preventive maintenance services along with contingency amounts not-to-exceed $10,000 for backflow device repairs and $5,000 for backflow device replacement per year. The inventory spreadsheet captures the itemized breakdown necessary for vendors to submit complete quotes, with quantity of one year per line item and unit pricing to be provided by offerors.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| FAR 852.219-75-Limitation on Subcontracting.pdf | ||
| Attachment 4 - Spec Sheet.pdf | ||
| Attachment 2 - Campus Map - Togus.pdf | ||
| Attachment 1 - VA BFP Testing Forms.pdf | ||
| Attachment 3 - PG-18-10 Section 4.10.pdf | ||
| 36C24126Q0744.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EQUIPMENT
EE # Manufacturer Equipment Name Model Serial Type of BFP tc={DB278E7A-BBEF-476E-8DFD-8E78C5735BB6}: [Threaded comment]
Your version of Excel allows you to read this threaded comment; however, any edits to it will get removed if the file is opened in a newer version of Excel. Learn more: https://go.microsoft.com/fwlink/?linkid=870924
Comment:
Reduced Pressure Zone Assembly (RPZ or RPZA) Double Check Valve Assembly (DCVA or DCA) Pressure Vacuum Breaker (PVB)
| Atmospheric Vacuum Breaker (AVB) | Acquisition/ Installation Date | Room | Building | Test Date | Pass | Fail | Corrective Action | PM/Work Order Number | Notes, Date Replaced/Rebuild | Tech initials | ||||
| 11478 | WILKINS DIV OF ZURN INDUSTRIES INC | BACKFLOW PREVENTOR | 575A | W29214 | E254 | 200 | 2024-03-13 | X | Rebuild or Replaced | |||||
| 16021 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6335 | 1999-06-04 | 001 | 204 | 2024-03-13 | X | |||||
| 16022 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6319 | 1999-06-04 | 001 | 204 | 2024-03-13 | X | |||||
| 16026 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6645 | 1999-06-04 | 001 | 207 | 2024-03-13 | X | Replaced | ||||
| 16027 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6556 | 1999-06-04 | 001 | 207 | 2024-03-13 | X | Replaced | ||||
| 16028 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6324 | 1999-06-04 | 001 | 206 | 2024-03-13 | X | Replaced | ||||
| 16029 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6330 | 1999-06-04 | 001 | 206 | 2024-03-13 | X | Replaced | ||||
| 34556 | FLOWMATIC | BACKFLOW PREVENTOR | RPZE | G8736 | 001 | 232 | 2024-03-13 | X | Rebuild or Replaced | |||||
| 34134 | FLOWMATIC | BACKFLOW PREVENTOR | RPZE | G4891 | 2009-12-01 | 001 | 232 | 2024-03-13 | X | Rebuild or Replaced | ||||
| 16023 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6334 | 1999-06-04 | 100 | 202 | 2024-03-14 | X | Replaced | ||||
| 16024 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6645 | 1999-06-04 | 001 | 201 | 2024-03-14 | X | |||||
| 16030 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6331 | 1999-06-04 | 001 | 205 | 2024-03-14 | X | |||||
| 16031 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6548 | 1999-06-04 | 001 | 205 | 2024-03-14 | X | Replaced | ||||
| ????? | 2024-03-14 | X | Replaced | |||||||||||
| 16040 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6321 | 1999-06-04 | 001A | 248 | 2024-03-14 | X | Replaced | ||||
| 34594 | FLOWMATIC | BACKFLOW PREVENTOR | RPZE | G6251 | 2010-07-01 | 001 | 202 | 2024-03-14 | X | Replaced | ||||
| 16035 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6329 | 1999-06-04 | 004 | 209 | 2024-03-15 | X | |||||
| 16036 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6333 | 1999-06-04 | 004 | 209 | 2024-03-15 | X | |||||
| 16037 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6366 | 1999-06-04 | 029 | 200 | 2024-03-15 | X | Needs to be Replaced | ||||
| 16038 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6325 | 1999-06-04 | 029 | 200 | 2024-03-15 | X | Needs to be Replaced | ||||
| 16034 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6550 | 1999-06-04 | 001 | 210 | 2024-03-17 | X | Replaced | ||||
| 11479 | WILKINS DIV OF ZURN INDUSTRIES INC | BACKFLOW PREVENTOR | 575A | W29226 | E400 | 200 | 2024-03-18 | X | ||||||
| 11480 | FEBCO SALES INC. | BACKFLOW PREVENTOR | 825Y | MM3192 | 569 | 200 | 2024-03-18 | X | ||||||
| 11481 | FEBCO SALES INC. | BACKFLOW PREVENTOR | 825Y | AM3245 | 609 | 200 | 2024-03-18 | X | Rebuild or Replaced | |||||
| 11482 | FEBCO SALES INC. | BACKFLOW PREVENTOR | 825Y | AM3232 | 650 | 200 | 2024-03-18 | X | Rebuild or Replaced | |||||
| 33958 | FLOWMATIC | BACKFLOW PREVENTOR | RPZE | F3445 | 2010-05-09 | E219 | 200 | 2024-03-18 | X | Needs to be Replaced | ||||
| 34554 | FLOWMATIC | BACKFLOW PREVENTOR | RPZE | J1579 | 2010-06-10 | E400 | 200 | 2024-03-18 | X | |||||
| 40918 | FLOWMATIC | BACKFLOW PREVENTER | RPZII | J3930 | 2012-11-11 | 329 | 200 | 2024-03-18 | X | Rebuild or Replaced | ||||
| 40919 | FLOWMATIC | BACKFLOW PREVENTER | RPZII | J3932 | 2012-11-11 | 332B | 200 | 2024-03-18 | X | |||||
| 40920 | FLOWMATIC | BACKFLOW PREVENTER | RPZII | J3931 | 2012-11-11 | 332B | 200 | 2024-03-18 | X | Rebuild or Replaced | ||||
| 40923 | FLOWMATIC | BACKFLOW PREVENTER | RPZII | J3955 | 2011-09-01 | 314 | 200 | 2024-03-18 | X | |||||
| 47667 | FLOWMATIC | BACKFLOW PREVENTER | RPZE | G5360 | 2015-06-15 | 400A | 200 | 2024-03-18 | X | |||||
| 16033 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6538 | 1999-06-04 | 001 | 210 | 2024-03-19 | X | Replaced | ||||
| 32206 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A4916 | 001 | BQ69 | 2024-03-19 | X | ||||||
| 32209 | FLOWMATIC | BACKFLOW PREVENTOR | RPZE | G4673 | 2009-04-09 | 001 | 203 | 2024-03-19 | X | Rebuild or Replaced | ||||
| 32210 | FLOWMATIC | BACKFLOW PREVENTOR | rpze | g4665 | 2009-04-09 | 001 | 203 | 2024-03-19 | X | Rebuild or Replaced | ||||
| 34551 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | D0255 | 2010-08-08 | 001 | 232 | 2024-03-19 | X | Rebuild or Replaced | Turned in?? 03/08/2010 | |||
| 34595 | FLOWMATIC | BACKFLOW PREVENTOR | RPZE | G3946 | 2010-07-01 | 001 | 235 | 2024-03-19 | X | Rebuild or Replaced | ||||
| 34596 | FLOWMATIC | BACKFLOW PREVENTOR | RPZE | G3996 | 2010-07-01 | 001 | 235 | 2024-03-19 | X | |||||
| 56446 | FLOWMATIC | BACKFLOW PREVENTER | DCVE | T9400 | 2024-03-19 | X | Rebuild or Replaced | |||||||
| 34598 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | M0531\ | 109A | 232 | 2024-03-24 | X | ||||||
| 16054 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A4902 | 1999-06-04 | 001 | BQ19 | 2024-04-08 | X | |||||
| 34559 | FLOWMATIC | BACKFLOW PREVENTOR | DCVE | H6562 | 001 | BQ18 | 2024-04-08 | X | Rebuild or Replaced | |||||
| 16042 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6541 | 1999-06-04 | 001 | 240 | 2024-04-10 | X | |||||
| 16043 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A4883 | 1999-06-04 | 105 | 211 | 2024-04-10 | X | Rebuild or Replaced | ||||
| 51289 | WATTS | BACKFLOW PREVENTOR | LF009QT | 56052 | 2016-08-01 | 252 | 206 | 2024-04-10 | X | |||||
| 51290 | WATTS | BACKFLOW PREVENTOR | LF009M3QT | 93638 | 2016-08-01 | 402 | 206 | 2024-04-10 | X | Rebuild or Replaced | ||||
| 51291 | WATTS | BACKFLOW PREVENTOR | LF009M3QT | 88243 | 2016-08-01 | 402 | 206 | 2024-04-10 | X | |||||
| 51292 | WATTS | BACKFLOW PREVENTOR | 2F009M3QT | 93633 | 2016-08-01 | 402 | 206 | 2024-04-10 | X | Relief did not open @ 2 PSI Min | ||||
| 51293 | WATTS | BACKFLOW PREVENTOR | LF009M3QT | 89163 | 2016-08-01 | 402 | 206 | 2024-04-10 | X | Rebuild or Replaced | ||||
| 32198 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A4937 | 001 | BQ20 | 2024-04-18 | X | ||||||
| 16020 | MILES LAB/AMES LAB TEK | BACKFLOW PREVENTOR | 2000SS | 2CN1229 | 1999-06-04 | 100 | 238 | 2024-07-07 | X | |||||
| 33955 | FLOWMATIC | BACKFLOW PREVENTOR | DCVE | H6974 | 2010-04-09 | 001 | BQ32 | 2024-07-09 | X | Bad first check??? | ||||
| 14732 | FLOWMATIC | BACKFLOW PREVENTER | RPZ | B5643 | 1998-01-01 | 100 | 245 | 2025-07-07 | X | |||||
| 14733 | FLOWMATIC | BACKFLOW PREVENTER | RPZ | B5457 | 1998-01-01 | 245 | 245 | 2025-07-07 | X | Rebuild or Replaced | ||||
| 16048 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A4517 | 1999-06-04 | 001 | BQ15 | 2025-07-07 | X | |||||
| 16049 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A4498 | 1999-06-04 | 001 | BQ16 | 2025-07-07 | X | |||||
| 16058 | WATTS REGULATOR CO | BACKFLOW PREVENTOR | 009 | 4750 | 1999-06-04 | 100 | 238 | 2025-07-07 | X | down stream valve failed - need to Replaced and retest | ||||
| 33960 | WATTS REGULATOR CO | BACKFLOW PREVENTOR | 009 | 30927 | 2010-05-09 | 100 | 238 | 2025-07-07 | X | |||||
| 33956 | AMES CONTROL | BACKFLOW PREVENTOR | DC 200 | JC-0527 | 2010-04-09 | 001 | 210 | 2025-07-08 | x | Both checks failed | ||||
| 40917 | WATTS REGULATOR CO | BACKFLOW PREVENTER | 009M2 | 304541 | 2012-11-01 | 100 | 238 | 2025-07-08 | X | |||||
| 54548 | WILKINS DIV OF ZURN INDUSTRIES | BACKFLOW PREVENTER | 975xl2 | 4594712 | 2018-08-01 | 100 | 239 | 2025-07-08 | X | |||||
| 16044 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A4918 | 1999-06-04 | 001 | BQ04A | 2025-07-09 | X | |||||
| 16045 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A929 | 1999-06-04 | 001 | BQ03A | 2025-07-09 | X | Rebuild or Replaced | Bad first check?? | |||
| 32208 | AMES CONTROL | BACKFLOW PREVENTOR | 200B DC | 26235 | 001 | BQ03A | 2025-07-09 | X | ||||||
| 57134 | WILKINS DIV OF ZURN INDUSTRIES | BACKFLOW PREVENTER | 350XL | H663113 | 2019-03-01 | 001 | 203 | 2025-07-09 | X | |||||
| 16047 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A4468 | 1999-06-04 | 001 | BQ01 | 2025-07-10 | X | |||||
| 32196 | FLOWMATIC | BACKFLOW PREVENTER | RPZ II | B1255 | 2025-07-10 | X | ||||||||
| 44698 | FLOWMATIC | BACKFLOW PREVENTER | RPZE | J1634 | 2011-11-01 | 001 | 206 | 2025-07-10 | X | |||||
| 52137 | WILKINS DIV OF ZURN INDUSTRIES INC | BACKFLOW PREVENTER | 975XL2 | 3979392 | 2017-01-01 | 401 | 207 | 2025-07-10 | X | |||||
| 16046 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A1607 | 1999-06-04 | 001 | BQ02 | 2025-07-11 | X | |||||
| 16050 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | 4491 | 1999-06-04 | 000 | STATION | 2025-09-17 | X | |||||
| 749 | HERSEY PRODUCTS, INC. | BACKFLOW PREVENTER | FRP11 | 9248 | 1984-01-01 | 001 | 207 | No Longer there - Remove from list | ||||||
| 835 | WATTS REGULATOR CO | BACKFLOW PREVENTER | 909 | 120328 | 1983-01-01 | 012 | 203 | No Longer there - Remove from list | ||||||
| 4282 | NEPTUNE WATER METER | BACKFLOW PREVENTER | 575 | MCB18803 | 100 | 222 | Out of Service | |||||||
| 14729 | FLOWMATIC | BACKFLOW PREVENTER | RPZ | H2888 | 1997-01-01 | 615 | 200 | |||||||
| 14731 | WATTS REGULATOR CO | BACKFLOW PREVENTER | 009 | 57086 | 1997-01-01 | 512A | 200 | |||||||
| 16041 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B6658 | 1999-06-04 | 001 | 212 | |||||||
| 16051 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A4958 | 1999-06-04 | 105A | 221 | |||||||
| 16052 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | 4924 | 1999-06-04 | 001 | BQ32 | |||||||
| 16053 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | 4934 | 1999-06-04 | 001 | BQ27 | |||||||
| 16055 | FLOWMATIC | BACKFLOW PREVENTOR | DCV | A4915 | 1999-06-04 | 001 | BQ18 | No Longer there - Replaced By EE34559 | ||||||
| 16892 | FLOWMATIC | BACKFLOW PREVENTER | RPZ | B9470 | 2000-08-16 | 001 | 206 | |||||||
| 32199 | FLOWMATIC | BACKFLOW PREVENTOR | RPZE | F8351 | 2009-04-06 | 001 | 245 | No Longer In Service | ||||||
| 32200 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | D0263 | 2009-04-09 | 100 | 249 | |||||||
| 32201 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B5833 | 001 | 200 | Unable to test - Line not in service | |||||||
| 32203 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ | B5822 | 029 | 200 | Unable to test - Line not in service | |||||||
| 32205 | FLOWMATIC | BACKFLOW PREVENTOR | RPZE | G3509 | 2009-04-09 | 100 | 245 | No Longer In Service | ||||||
| 32207 | WATTS REGULATOR CO | BACKFLOW PREVENTOR | 007M2QT DC | 49782 | 131 | 209 | ||||||||
| 33957 | AMES CONTROL | BACKFLOW PREVENTOR | DC 200 | ID-1395 | 2010-04-09 | 116 | linco | |||||||
| 33961 | WATTS REGULATOR CO | BACKFLOW PREVENTOR | 009 | 31047 | 2010-04-09 | 100 | 238 | Could not test due to port issues | ||||||
| 34553 | FLOWMATIC | BACKFLOW PREVENTOR | RPZ 3/4 | J1584 | 2008-06-01 | 100 | 222 | No Longer In Service | ||||||
| 34555 | AMES COLT | BACKFLOW PREVENTOR | DC | JJ0422 | 2009-12-01 | 001 | BQ01 | |||||||
| 40915 | WATTS REGULATOR CO | BACKFLOW PREVENTER | 009M3 | 338926 | 2012-11-01 | 100 | 239 | Remove from list no longer there | ||||||
| 40916 | WATTS REGULATOR CO | BACKFLOW PREVENTER | 0093M | 360355 | 2012-11-01 | 100 | 239 | Remove from list no longer there | ||||||
| 40921 | FLOWMATIC | BACKFLOW PREVENTER | RPZII | G9831 | 2009-06-01 | 200 | 232 | |||||||
| 40922 | FLOWMATIC | BACKFLOW PREVENTER | RPZII | G9829 | 2009-06-01 | 200 | 232 | |||||||
| 40924 | FLOWMATIC | BACKFLOW PREVENTER | RPZII | J3927 | 2012-09-01 | 305A | 200 | Could not be tested - No water supply | ||||||
| 49430 | WILKINS DIV OF ZURN INDUSTRIES | BACKFLOW PREVENTER | 975XL2 | 4226753 | 2016-08-04 | E142 | 200 | |||||||
| 51576 | WATTS | BACKFLOW PREVENTER | LF909 | 19388 | Roof | 200 | ||||||||
| 51638 | WILKINS DIV OF ZURN INDUSTRIES INC | BACKFLOW PREVENTER | 975XL2 | 4334410 | 2017-08-01 | 620A | 200 | |||||||
| 54598 | WILKINS DIV OF ZURN INDUSTRIES INC | BACKFLOW PREVENTER | 975XL2 | 4594537 | 2018-09-01 | 100 | 239 | Could not test - Locked Out | ||||||
| 58260 | WILKINS DIV OF ZURN INDUSTRIES INC | BACKFLOW PREVENTOR | 950XLT | 4274062 | 2019-10-01 | 111 | 300 | |||||||
| 58261 | WATTS | BACKFLOW PREVENTOR RPZ | LF009M2QT | 124683 | 2019-10-01 | 111 | 300 | |||||||
| 58262 | FEBCO SALES INC. | BACKFLOW PREVENTOR | 825Y | 44131 | 2019-10-01 | 111 | 300 |
Reduced Pressure Zone Assembly (RPZ or RPZA) Double Check Valve Assembly (DCVA or DCA) Pressure Vacuum Breaker (PVB) Atmospheric Vacuum Breaker (AVB)