This document provides details for a federal contract opportunity for architectural and engineering services. The Department of Veterans Affairs Technology Acquisition Center Austin is seeking statements of qualifications from Service-Disabled Veteran-Owned Small Businesses by May 15, 2021 for design services related to infrastructure upgrades at the Central Alabama Veterans Health Care System campus in Montgomery, Alabama. The project scope involves upgrading electrical, IT, and other systems to allow for a new Electronic Health Record Modernization system and has an estimated construction value between $10-20 million. Statements of qualifications will be evaluated based on experience with similar healthcare IT and infrastructure projects, professional qualifications, capacity to complete the work within 183 calendar days, past performance, and local market knowledge. Discussions will be held with the most highly qualified firms to further evaluate their qualifications before final selection and contract award by July 2021.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HEFP/10NA5G/29APR20
SOCAMES 6 Design Alert 1
Problem
During a recent construction activity of cable upgrades to an existing telecommunication room (TR) at an Initial Operating Capability (IOC) site, it was discovered during cable testing procedures that some of the cables being upgraded were greater in length to the end user device than standards allows.
Background
ANSI/TIA-568.D, “Balanced Twisted-Pair Telecommunications Cabling and Components” (Sep 2018) version of industry standards for telecommunication room fixed cabling installation, limits the total length of a network Unshielded Twisted Pair (UTP) cable segment to 100 meters. The 100 meters is broken down as 10 meters for patch cables and 90 meters for total fixed cabling. Cable length requires a three-dimensional assessment to ensure that the fixed cables being installed do not exceed the specified UTP cable segment of 90 meters of fixed cable length.
There are several scenarios that require an assessment to occur to ensure that a telecommunication rooms UTP cable segments do not exceed 90 meters.
Scenario 1: The installation of a new telecommunication room to serve an area.
Scenario 2: The relocation of an existing telecommunication room to serve an area.
Scenario 3: The installation of new cabling upgrades in a telecommunication room that will remain in place to serve an area.
Scenario 4: An existing telecommunication room that will not receive any cabling upgrades.
Solution
To ensure that an assessment is performed for each of the four telecommunication room scenarios listed above, our office in conjunction with the SD-DCIE team is providing a recommended three-dimensional estimation approach that can be shared with your respective facility leads and design team to verify all telecommunication rooms do not exceed the specified UTP cable segment of 90 meters.
Step 1: Ensure you have an accurate floor plan that depicts the locations of the telecommunication rooms serving the facility.
Step 2: Utilizing AutoCAD or rule, center on the location of the telecommunication room being assessed.
From the center of the room project out lines, 80 meters in length from that point, in the plan north, south, east and west respectively.
Step 3: At the end each of the 80 meters lines created, connect a line 45 degrees from that point out to the next end point creating a diamond.
Step 4: Validate that all areas served by that telecommunication room fall within the parameters of the diamond overlay.
HEFP/10NA5G/29APR20
Step 5: If the area served by that telecommunication room is within the diamond overlay then the distance, as provided by the estimation tool, is adequate for that telecommunication room.
Step 6: If the area served by that telecommunication room is outside the diamond overlay then the distance, as provided by the estimation tool, is inadequate for that telecommunication room and further investigation is required by electronically testing the cable lengths to see if they pass or physical measurement. Any UTP cabling that does not pass testing protocols and is too long will need to have further design considerations to remedy the distance issue.
Notes
Since it is necessary to account for vertical cable distance, installation of slack for bypassing obstructions, cable management, bend radii and other in-situ obstacles 80 meters is utilized instead of the 90 meters acceptable length. This is to provide a realistic estimation of coverage of the representative telecommunication room.
This estimation tool is a recommended approach to validate fixed cable lengths meet the standards.
Designers and installers remain responsible for ensuring actual cable distances do not exceed the limits in the standards.
Below is a diagram of an example demonstrating the use of the estimation tool.