Attachment_4_142010-26-0063.pdf

PDF 516 KB Posted

Attached to
NWS HVAC PREVENTIVE MAINTENANCE (PM) WFO AND NEXRA
Solicitation number
1305M326Q0394
Issued by

About this file

Record Drawing Summary

This is a Trane record drawing (as-built documentation) dated March 16, 2016, for the NOAA Weather Station project in Charleston, South Carolina. The project was prepared for Carolina Comfort Solutions (2006 Rockland Road, Columbia, SC 29210) and sold through the Trane Sales Office in West Columbia, South Carolina. The Trane project team included Account Manager Kent Koehn, Project Manager Jeff Kindle, and Designer Jan Van Sise.

The drawing set comprises 19 sheets documenting a complete HVAC control system installation, including a system controller (SC-1), three air handling units (AHU-1, AHU-2, AHU-3) with UC600 controllers, ten electric duct heaters (EDH-1 through EDH-10) with UC210 controllers, and associated expansion modules (XM30-1, XM32-2). The system incorporates BACNET MS/TP communication architecture, 24 VAC power distribution via transformers (TX-2 through TX-6), damper actuators, temperature and humidity sensors, differential pressure switches, current sensors, relays, and zone control devices from vendors including Trane, Belimo, and Kele. Wiring specifications detail analog input/output limits (0-10 VDC at 300 feet maximum, 0-20 mA at 1,000 feet maximum), BACNET communication cable requirements (shielded twisted pair, 18 AWG minimum, 4,000-foot maximum distance), and installation standards compliance with the National Electrical Code and local building codes. The bill of materials lists 59 components across all system elements.

View the file

Other files

File Type Posted
Sol_1305M326Q0394_Amd_0001.pdf PDF
Attachment_6_142010-26-0063.pdf PDF
Attachment_5_142010-26-0063.pdf PDF
Charleston_WD_2015-4427.txt TXT text file
Hampton_WD_2015-4441.txt TXT text file
Attachment_3_142010-26-0063.pdf PDF
Attachment_8_142010-26-0063.pdf PDF
Attachment_7_142010-26-0063.pdf PDF
Attachment_1_142010-26-0063.pdf PDF
Attachment_2_142010-26-0063.pdf PDF
Sol_1305M326Q0394.pdf PDF
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Record Drawing Date: March 16, 2016

Project Number:

Project Name:

NOAA Weather Station

CHARLESTON, SC

Customer P.O. Number:

Customer Project Number:

Prepared For:

Carolina Comfort Solutions

2006 ROCKLAND RD.

COLUMBIA, SC 29210

Sold To:

Trane Sales Office:

COLUMBIA MAIN OFFICE

111 LOTT COURT

WEST COLUMBIA, SC 29169

Phone: 803-936-4700 Fax:

Web:

Architect:

Mechanical Contractor:

Mechanical Engineer:

Trane Contracting Team:

Account Manager: Kent Koehn kkoehn@trane.com

Project Manager: Jeff Kindle jeff.kindle@trane.com

Designed By: Jan Van Sise jcvansise@trane.com

TITLE PAGE

1NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

THIS DRAWING SET IS THE PROPERTY OF

TRANE. DESIGN INFORMATION, DRAWINGS,

DETAILS OR SPECIFICATION DATA MAY NOT BE

REPRODUCED OR DUPLICATED NOR MAY ANY

WORK BE EXECUTED HEREFROM WITHOUT THE

WRITTEN AUTHORIZATION OF TRANE.

NOAA Weather Station

CHARLESTON, SC

SALESPERSON:

Kent Koehn

PROJECT MANAGER:

Jeff Kindle

DESIGNED BY:

Jan Van Sise

TRANE PROJECT TEAM

Carolina Comfort Solutions

2006 ROCKLAND RD.

COLUMBIA, SC 29210

Customer Contact

DRAWING INDEX

2NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

DRAWING

NUM BER

DRAWING TITLE REVISION LEVEL REVISION DATE COM M ENTS

1 TITLE PAGE AS-BUILT DRAWING 2/24/2016

2 DRAWING INDEX AS-BUILT DRAWING 2/24/2016

3 LEGEND AS-BUILT DRAWING 2/24/2016

4 COM M UNICATION RISER AS-BUILT DRAWING 2/24/2016

5 SYSTEM CONTROLLER SC - 1 WIRING DETAIL AS-BUILT DRAWING 2/24/2016

6 AHU-1 FLOW DIAGRAM AS-BUILT DRAWING 2/24/2016

7 AHU-1 UC600-1 WIRING DETAIL AS-BUILT DRAWING 2/24/2016

8 AHU - 1 XM 30 - 1 WIRING DETAIL AS-BUILT DRAWING 2/24/2016

9 AHU - 1 XM 32 - 2 WIRING DETAIL AS-BUILT DRAWING 2/24/2016

10 AHU-2 FLOW DIAGRAM AS-BUILT DRAWING 2/24/2016

11 AHU-2 UC600-2 WIRING DETAIL AS-BUILT DRAWING 2/24/2016

12 AHU-3 FLOW DIAGRAM AS-BUILT DRAWING 2/24/2016

13 AHU-3 UC600-3 WIRING DETAIL AS-BUILT DRAWING 2/24/2016

14 CONDENSING UNIT WIRING AS-BUILT DRAWING 2/24/2016

15 EDH 1 - 3, 9 - 10 UC210 WIRING DETAIL AS-BUILT DRAWING 2/24/2016

16 EDH 4 - 8 UC210 WIRING DETAIL AS-BUILT DRAWING 2/24/2016

17 DETAIL SHEET # 1 AS-BUILT DRAWING 2/24/2016

18 DETAIL SHEET # 2 AS-BUILT DRAWING 2/24/2016

19 BILL OF M ATERIALS AS-BUILT DRAWING 2/24/2016

INDEX OF CONTROL SYSTEM DRAWINGS

LEGEND

3NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

Symbol Legend

AIR FLOW STATION

AFS

AIR FLOW STATION, FAN

MOUNTED

AFS

ALARM, BELL

ALM

ALARM, STROBE

ALM

ALARM, PIEZIO

ALM

BLENDER, AIR

BURNER, FUEL-FIRED

DIRECT COIL, COAXIAL

COIL, CHW, DX, HW,

STEAM, ETC.

C

C

CONTROL POINT

CS - CURRENT SENSOR

CSR - CURRENT

SENSOR W/RELAY

CS OR CSR

DAMPER, OPPOSED OR

PARALLEL

D

TRAQ DAMPER

D

ACTUATOR, DAMPER

DA

SENSOR, DIFFERENTIAL

PRESSURE

DPS

AIR DIFFERENTIAL

SWITCH OR SENSOR

DPS, DPT

DIFFERENTIAL

PRESSURE SWITCH OR

SENSOR

DPT, DPS

H L EXCHANGER, FUEL FIRE

HEAT

EXCHANGER, FLUID

HEAT FAN OR PUMP

FAN, ROOF TOP FILTER, AIR FILTER, AIR BAG FILTER, AIR HEPA

FILTER, AIR ROLL SWITCH, FLOAT

FLT

FIRESTAT

FS

SENSOR, FLOW

FS

HEATER, ELECTRIC

DUCT

SENSOR, ROOM STATIC

PRESSURE

HDW

TUBE, STATIC

PRESSURE

HDW

SENSOR, DUCT

HUMIDITY AND

TEMPERATURE

HE, TEH

SENSOR, HUMIDITY OR

TEMPERATURE AND

HUMIDITY

HE, TEH

SENSOR, INDOOR AIR

QUALITY

IAQ

SENSOR, INDOOR AIR

QUALITY (CO2)

IRQ

THERMOSTAT, LOW

LIMIT

LLT

STARTER, MOTOR

MS

SENSOR, OCCUPANCY

OCC

TRANSMITTER,

PRESSURE

PT

RELAY

R

RELAY, SOCKET

R

SENSOR, OUTDOOR

PRESSURE

RB

SWITCH, RESET

STATION

RST

DETECTOR, SMOKE

SD

SEQUENCER

SEQ

SWITCH

SW

ON

OFF

SOLENOID, AIR

SOL

SWITCH, BUTTON

SW

THERMOSTAT, WALL

T

COMPOUND, THERMAL

TC

SENSOR, AVERAGING

TEMPERATURE

TE

SENSOR, STRAP ON

TEMPERATURE

TE

SWITCH, ROTARY

SW

HEAT COOL

AUTO

SENSOR,

TEMPERATURE

TE

SENSOR, ZONE

TE

TIMER, ELECTRONIC

WALL

TMR

TIMER, WALL

TMR

WELL, THERMAL

TW

TRANSFORMER

TX

LIGHT, ULTRAVIOLET

UV

VALVE, 2-WAY COIL

VAL

VALVE, 3-WAY COIL

VAL

VALVE, DUCT

HUMIDIFIER

VAL

VARIABLE FREQUENCY

DRIVE

VFD

Wiring and Project NotesWiring and Project Notes

ELECTRICAL CONTRACTOR FOR TRANE:

1. REFER TO DEVICE INSTALLATION MANUALS FOR SPECIFIC WIRING REQUIREMENTS.

2. FIELD WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE, STATE AND

LOCAL BUILDING CODES, AND DIVISION 16 OF SPECIFICATIONS.

3. TAG ALL CONTROL WIRING AT EACH END OF THE CABLE OR WIRE PER TAGS SHOWN IN

ATTACHED DRAWINGS.

4. AVOID OVER TIGHTENING CABLE TIES AND OTHER FORMS OF CABLE WRAPS. THIS CAN

DAMAGE THE WIRES INSIDE THE CABLES.

5. DO NOT CABLE TIE TO INSULATED WATER, STEAM OR OTHER LINES.

6. IN OPEN PLENUMS, AVOID RUNNING WIRE NEAR LIGHTING BALLASTS, ESPECIALLY THOSE

USING 277 VAC.

7. ALL PANELS AND FIELD DEVICES LISTED IN THIS DOCUMENT ARE TO BE INSTALLED BY

CONTROLS ELECTRICAL SUBCONTRACTOR UNLESS OTHERWISE NOTED ON DRAWINGS.

8. MOUNT ALL ROOM SENSORS AND SWITCHES AS SHOWN ON THE CONSTRUCTION

DOCUMENTS, UNLESS OTHERWISE DIRECTED IN WRITING BY THE OWNER AND/OR ENGINEER.

9. FLEXIBLE CONDUIT IS NOT TO EXCEED 24” IN LENGTH.

10. CONTROL PANELS ARE NOT TO BE USED AS JUNCTION BOXES OR RACEWAYS. WIRING

THAT DOES NOT TERMINATE IN A CONTROL PANEL IS NOT TO BE RUN WITHIN THE PANEL.

11. BINARY INPUT LIMITS: 1000 FT (300 M).

12. 0~10 VDC ANALOG INPUT LIMITS: 300 FT (100 M).

13. 0~20 MA ANALOG INPUT LIMITS: 1000 FT (300 M).

14. VARIABLE RESISTANCE ANALOG INPUT LIMITS: 300 FT (100 M).

15. ANALOG OUTPUT LIMITS: 1000 FT (300 M).

16. BINARY OUTPUT LIMITS: 1000 FT (300 M).

17. WIRING POWER FROM THE AC OUT TERMINALS TO POWER ANALOG INPUT DEVICES WILL

CAUSE IMMEDIATE CONTROLLER FAILURE IF INPUT DEVICE USES HALF-WAVE RECTIFICATION.

WHEN UNSURE, USE A SEPARATE POWER SUPPLY FOR DEVICE.

18. GENERAL COMMUNICATION GUIDE: DO NOT RUN COMMUNICATION LINK WIRING IN THE

SAME CONDUIT OR WIRE BUNDLE WITH AC-POWER WIRES (INCLUDING CONDUCTORS

RUNNING FROM TRIAC-TYPE OUTPUTS). KEEP POLARITY CONSISTENT THROUGHOUT THE

SITE. MAKE SURE THAT THE 24 VAC POWER SUPPLIES ARE CONSISTENT IN HOW THEY ARE

GROUNDED. AVOID SHARING 24 VAC BETWEEN CONTROLLERS. USE ONLY ONE TYPE OF

COMMUNICATION CABLE; DO NOT MIX CABLE. IF AN EXISTING JOB USED ALTERNATE CABLE,

CONTINUE USING THE SAME CABLE AFTER APPROVAL FROM THE PROJECT MANAGER.

19. BACNET MS/TP COMMUNICATION CABLE MUST BE SHIELDED TWISTED PAIR, 18 AWG

MINIMUM, STRANDED, TINNED COPPER CONDUCTORS. SHIELD MUST BE CONTINUOUS

THROUGHOUT, ISOLATED FROM OTHER CONDUCTORS OR GROUND, AND GROUNDED AT THE

SYSTEM CONTROLLER ONLY. MAXIMUM CAPACITANCE BETWEEN CONDUCTORS IS 24

PICOFARADS PER FOOT. MAXIMUM DISTANCE IS 4000 FT (1372 M). MAXIMUM OF 60 TRANE

DEVICES PER LINK BUT LESS WHEN COMBINED WITH NON-TRANE DEVICES. EXPANSION

MODULE LINK LIMIT IS 656 FT (200 M). A TRACER BACNET TERMINATOR IS REQUIRED AT EACH

END OF THE COMMUNICATION LINK. TOPOLOGY MUST BE DAISY CHAINED.

20. LONTALK (COMM 5) COMMUNICATION CABLE MUST BE LEVEL 4 UNSHIELDED, 22 AWG WITH

MAXIMUM CAPACITANCE BETWEEN CONDUCTORS OF 17 PICOFARADS PER FOOT. MAXIMUM

DISTANCE IS 4500 FT (1400 M). MAXIMUM DEVICES IS 60 DEVICES WITHOUT REPEATER AND

120 WITH REPEATER. ONE REPEATER PER LINK CAN BE USED FOR AN ADDITIONAL 4500 FT

(1400 M), 60 DEVICES. EX2 LINK LIMIT IS 1000 FT (300 M). CCP III LINK LIMIT IS 3500 FT (1090 M).

105 OHMS, 1%, ¼ WATT TERMINATION RESISTORS ARE REQUIRED AT EACH END FOR LEVEL 4

WIRE AND 82 OHMS, 1%, ¼ WATT AT EACH END FOR 18 AWG SHIELDED (PURPLE) WIRE.

TOPOLOGY MUST BE DAISY CHAINED.

21. COMM 3 AND COMM 4 COMMUNICATION CABLE MUST BE SHIELDED TWISTED PAIR, 18AWG

MINIMUM, STRANDED, TINNED COPPER CONDUCTORS. SHIELD MUST BE CONTINUOUS

THROUGHOUT, ISOLATED FROM OTHER CONDUCTORS OR GROUND, AND GROUNDED AT BCU

ONLY. MAXIMUM CAPACITANCE BETWEEN CONDUCTORS IS 24 PICOFARADS PER FOOT.

MAXIMUM DISTANCE IS 5000 FT (1715 M). UNDER CERTAIN CONDITIONS, TERMINATION

RESISTORS ARE REQUIRED ON A COMM 3 COMMUNICATION LINK.

22. ETHERNET LAN COMMUNICATION CABLE MAXIMUM DISTANCE IS 295 FT (90 M) PLUS 33 FT

(10 M) FOR PATCH CABLES.

MECHANICAL CONTRACTOR:

1. DAMPERS ARE TO BE INSTALLED BY SHEET METAL CONTRACTOR UNLESS OTHERWISE

NOTED.

2. CONTROL VALVES AND ACCESSORIES INSTALLED DIRECTLY INTO PIPING (SENSOR WELLS,

THREADOLETS, ETC.) ARE TO BE INSTALLED BY MECHANICAL CONTRACTOR.

3. FLOW DIAGRAMS SHALL NOT BE A GUIDE FOR PIPE AND VALVE INSTALLATION. REFER TO

THE VALVE MANUFACTURER’S INSTALLATION INSTRUCTIONS FOR INSTALLATION GUIDANCE.

FIELD WIRING NOTE:

D

WHT

BLK

D

WHT

BLK

SOLID LINES: NOT

WIRED BY FIELD

DASHED LINES:

WIRED BY FIELD

BLK

WHT

121 37

2TB

WIRED BY FACTORY WIRED BY FIELD

FIELD MOUNTED

CONTROLLER

FACTORY

TERMINAL

CABLE

TAG

FACTORY MOUNTED DEVICE WITH FIELD MOUNTED CONTROLLE R:

D

CABLE MATRIX NOTES:

KEEP ALL COMMUNICATION LINK WIRING IN A DAISY CHAIN CONFIGURATION. ALL CABLE WIRING MUST BE TRANE RECOMMENDED WIRING , ESPECIALLY COMMUNICATION CABLES. CONTACT TRANE FOR RECOMMENDED CABLES

AND SPECIFICATIONS.

Cable MatrixCable Matrix

* When ordering cable specify jacket color. Part numbers are subject to change without notice.

CT

052003

TRANE NUMBER*

A WHT, BLK

DESCRIPTION

18/2 TWIST SHLD PURPLE COMM CABLE

105500C WHT, BLK22/2 TWIST NON-SHLD BLUE COMM CABLE

002320D WHT, BLK18/2 TWIST SHLD PLEN WHITE CABLE

002330E WHT, BLK, RED18/3 TWIST SHLD PLEN WHITE CABLE

002340F WHT, BLK, RED, GRN18/4 TWIST SHLD PLEN WHITE CABLE

J WHT, BLK1 PAIR #14 THHN STRANDED IN CONDUIT

L ETHERNET RG58 THNNET PLEN CABLE

555619M ETHERNET CAT-5 PLEN CABLE

002352O WHT, BLK, RED, ORN, YEL, GRN, BLU, BRN18/8 TWIST SHLD PLEN WHITE CABLE

106502P WHT, BLK22/2 TWIST SHLD PLEN ORANGE COMM CABLE

WIRE COLORS

761360Q WHT, BLK16/2 SOLID RED SMOKE DETECTOR CABLE

5100012C WHT, RED18/2 SOLID PLENUM THERMOSTAT CABLE

51002-043C WHT, RED, GRN18/3 SOLID PLENUM THERMOSTAT CABLE

5100045C WHT, RED, GRN, YEL, BLU18/5 SOLID PLENUM THERMOSTAT CABLE

5100078C WHT, RED GRN, YEL, BLU, ORN, BLK, BRN18/8 SOLID PLENUM THERMOSTAT CABLE

10C WHT, RED, GRN, YEL, BLU, ORN, BLK, BRN, GRY, PNK18/10 SOLID PLENUM THERMOSTAT CABLE

12C 18/12 SOLID PLENUM THERMOSTAT CABLE

B FACTORY PROVIDED CABLE

WHT, RED, GRN, YEL, BLU, ORN, BLK, BRN, GRY, PNK, PUR, TAN

CABLE INFORMATION SHAPE (CIS):

EACH CABLE CONNECTION HAS A CIS WHICH PROVIDES SOME OR ALL OF THE INFORMATION INDICATED BELOW:

WIRE COLOR

OR POLARITY

SHIELD

CONFIGURATION

CABLE TYPE FROM

CABLE MATRIX

CABLE

NUMBER

DEVICE TAG AND

POINT DESCRIPTION

END DEVICE DETAIL

REFERENCE INSET & PAGE

B

CSR-3 CONDENSER PUMP STATUS

D

WHT

BLK TAPE SHLD

SHIELDING NOTE:

D

WHT

BLK TAPE SHLD

D

WHT

BLK

ATTACH ALL SHIELDS TO

COMMON AS SHOWN

TAPE OFF SHIELD

AT DEVICE

FACTORY

PROVIDED

AND WIRED

DEVICE

Field, Factory And Existing Device Note:

EXISTING

DEVICE

FIELD WIRED

DEVICE (FIELD

OR FACTORY

PROVIDED)

D

FACT

10D

EXST

RISER 'WIRING BY' NOTE:

EC - ELECTRICAL CONTRACTOR

ESC - ELECTRICAL SUBCONTRACTOR

OTHERS

TRANE

EXIST - EXISTING POWER

CONTROLLER

PAGE

NUMBER

CABLE TYPE

FROM

CABLE MATRIX

DEVICE TAG

FLOW SHAPE NOTES:

D 10

TE - 1

CABLE TAG

480 VAC

BY EC

AHU - X

ADDRESS

WCI

AHU - X

WIRELESS

COMMUNICATION

INTERFACE

DISPLAYING

SUBNET NUMBER

COMMUNICATION RISER

4NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

SYSTEM CONTROLLER

FIELD LOCATE

120 VAC

BY ESC

SC - 1

AHU-1

120 VAC

BY ESC

UC600 - 1

AHU-2

120 VAC

BY ESC

UC600 - 2

AHU-3

120 VAC

BY ESC

UC600 - 3

TO

OWNER'S

LAN

M

A

EDH - 10

24 VAC

BY ESC

EDH - 10

EDH - 9

24 VAC

BY ESC

EDH - 9

EDH - 4

24 VAC

BY ESC

EDH - 4

EDH - 3

24 VAC

BY ESC

EDH - 3

EDH - 8

24 VAC

BY ESC

EDH - 8

EDH - 7

24 VAC

BY ESC

EDH - 7

EDH - 6

24 VAC

BY ESC

EDH - 6

EDH - 5

24 VAC

BY ESC

EDH - 5

EDH - 1

24 VAC

BY ESC

EDH - 1

EDH - 2

24 VAC

BY ESC

EDH - 2

D

24 VAC FROM TRANS-

FORMER TX - 3

24 VAC FROM TRANS-

FORMER TX - 4

D

TAG QTY VENDOR PART NO DESCRIPTION

ENC - 4 1 TRANE X13651559010 ENC, TRACER UC M EDIUM , 120 VAC OUTLET

SC - 1 1 TRANE BM SC000AAA01100 TRACER SC

SFT - 1 1 TRANE BM CF000AAA0AE00 TRACER SC15 SOFTWARE

TBT - 2 1 TRANE X13651524-01 TRANE BACNET TERM INATOR (2/PKG)

BILL OF M ATERIALSTYPICAL FOR 1

(SYSTEM CONTROLLER)

SYSTEM CONTROLLER SC - 1 WIRING DETAIL

5NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

4 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE

DEVICE INSTALLATION LITERATURE.

SC - 1

LOCATION:

SYSTEM

CONTROLLED:

FIELD LOCATE

SYSTEM CONTROLLER

B

A

GND

LO

N

GND

B A

C N

E T

M S

T P

L

IN

K

GND

U S

B H

O S

T E

T H

E R

N E

T

N

T W

O R

K

E T

H E

R N

T

N

T

W O

R K

B

A C

N E

T R

S -2

IO

IO

I

LINK 2

SC TRANE

MODEM IOIOI

1 2

A B

LON

A B

LON

LINK 1

LINK 1

LINK 2

ADDRESS

L1 L2 MODEM

LINK

ACT

LON

TX

RX

SERVICE

STATUS

TX

RX

IMCIOIOI 1 2

SERVICE TOOL

B A

C N

E T

M S

T P

L

IN

K

M O

D E

M

INSTALL BACNET TERMINATOR AT THE

BEGINNING AND AT THE END OF THIS

LINK.

INSTALL BACNET

TERMINATOR AND

CONNECT TO POWER

INSTALL 105 OHM RESISTOR AT THE

BEGINNING AND AT THE END OF THIS LINK.

24 VDC

GND

IM

C

24 VDC

GND

IM

C

GND

GND

24 VAC

24 VACO

U

T X

F M

R

NOT USED

MSTP1

A

SEE RISER WHT

BLK

SHLD

BLU

GRN

TBTBACNET TERMINATOR

NOT USED

NOT USED

NOT USED

M

CAT5 TO OWNER'S LAN

NOT USED

CON - 1 +

IMC

- IMCIMC

VDC

VDC

IMC

PM014 TRANE

PM - 1

XFMR

VAC

OUT

VAC

SFT - 1

TBT - 2

LINK 1

A

GRN

ENC - 4

TX - 2

24 VAC

HE - 1, TEH - 3 2 TRANE X1379044401 3% ROOM RH SENS, TEM P

TE - 1 1 TRANE 4190-1046 TEM P SENS, AVG, BALCO, 22FT

TE - 2 1 TRANE 41901133 TEM P SENS, DUCT/ IMM , THERM 6 IN

TEH - 1, TEH - 2 2 TRANE 4190-7020 3% DUCT RH SENS, TEM P

DA - 1, DA - 2 2 BELIM O AF24-SR US ACT PROP 24VAC SR 133IN-LB

CS - 1 1 KELE RIBXGA CUR SW, 0.75-150A, SPLIT, NO

DPS - 1 1 KELE P32AC-2 DIFF PRES SW, 0.05-5 IN WC

R - Y1, R - 4 2 KELE RIBU2C RLY DPDT, LED, 10-30 VAC/DC/120 VAC

R - Y2 1 KELE RIBU1C RLY SPDT, LED, 10-30 VAC/DC/120 VAC

TE - 17 1 KELE ST-M P3-X25 STRAP-ON 10K NTC THERM ISTOR

BILL OF M ATERIALS

AHU-1 FLOW DIAGRAM

6NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

AHU - 1

RA

SAOA

C

DX

FILTER

N.C.

N.O.

7E

DA - 1

E

DA - 2

D 7

DPS - 1

H L

ACU - 1

D

R - Y1

COOL 1

R

D

R - Y2

COOL 2

R

INTLK

SD - 1

INTLK

SD - 2

1 EXISTING SMOKE DETECTORS ARE HARDWIRED TO FAN STARTER FOR SHUTDOWN.

D

D 7

TEH - 1

D

D 7

TEH - 2

D 7

TE - 1

D 7

TE - 2

7D

S/S

R - 4

D 7

113STS

CS - 1

STARTER HUM - 1

3 EXISTING HUMIDIFIER INTERLOCK/SAFETY CONTROLS ARE EXISTING (NOT SHOWN).

D 7

HE - 1

SPACE HUMIDITY SENSOR

OPERATIONS RM. 109

SEQUENCE OF OPERATION:

AIR HANDLING UNITS AHU-1 & AHU-2:

AHU-1 & 2 SERVE THE OPERATIONS AREA AND ARE OPERATED ON A 24 HOUR SCHEDULE. ONLY ONE AIR HANDLING UNIT SHALL OPERATE, AND THE NON-OPERATING UNIT SHALL SERVE AS A BACKUP. THE BACKUP UNIT SHALL BE STARTED AUTOMATICALLY UPON FAILURE OF THE OTHER UNIT. AHU-1 & 2 SHALL BE PROGRAMMED TO ALTERNATE TO MAINTAIN EQUAL RUN TIME. THE SUPPLY AIR FAN SHALL RUN CONTINUOUSLY. A SUPPLY AIR TEMPERATURE SENSOR SHALL STAGE THE AIR COOLED CONDENSING UNIT (ACU) TO MAINTAIN 55 DEG. F DISCHARGE AIR TEMPERATURE. THE SUPPLY AIR TEMPERATURE SHALL BE RESET TO SATISFY THE ROOM TEMPERATURE SENSOR WITH THE MAXIMUM COOLING DEMAND. AN OUTSIDE AIR ECONOMIZER CYCLE SHALL BE PROVIDED WITH COMPARATIVE ENTHALPY CONTROL. A MIXED AIR TEMPERATURE SENSOR SHALL MODULATE THE OUTSIDE AND RETURN AIR DAMPERS DURING THE ECONOMIZER CYCLE. MINIMUM OUTSIDE AIR SHALL BE PROVIDED WHEN THE UNIT IS NOT IN THE ECONOMIZER CYCLE. HUMIDITY SHALL BE CONTROLLED BY THE SPACE HUMIDITY SENSOR.

HEATING IS PROVIDED BY INDIVIDUAL ELECTRIC DUCT HEATERS (EDH). SMOKE DETECTORS IN THE SUPPLY AND RETURN AIR DUCTWORK SHALL DE-ENERGIZE THE SUPPLY AIR FAN UPON SENSING SMOKE. UPON LOSS OF COMMERCIAL POWER, THE AIR HANDLING UNIT SHALL BE PROGRAMMED FOR A TIMED DELAY RESTART. ELECTRIC

DUCT HEATER EDH-2 SHALL NOT OPERATE ON EMERGENCY POWER.

HUMIDIFIER:

THE HUMIDIFIER SHALL NOT BE ALLOWED TO OPERATE UNLESS THE AIR HANDLING UNIT SUPPLY AIR FAN IS IN OPERATION. AN AIRFLOW SWITCH SHALL DE-ENERGIZE THE HUMIDIFIER UPON LOSS OF AIRFLOW. THE STEAM SOLENOID VALARE INTERLOCKED TO OPEN WHEN THE CORRESPONDING AIR HANDLING UNIT IS IN OPERATION. THE SPACE HUMIDITY SENSOR SHALL MODULATR THE HUMIDIFIER. WHEN THE HUMIDIFIER IS ENERGIZED, THE SUPPLY AIR TEMPERATURE SHALL BE RESET TO 65 DEG. F. WHEN THE HUMIDIFIER IS DE-ENERGIZED, SUPPLY AIR TEMPERATURE SHALL BE SET BACK TO 55 DEG. F.A SIGNAL FROM THE DUCT MOUNTED HIGH LIMIT HUMIDITY

SENSOR SHALL DE-ENERGIZE THE HUMIDIFIER.

D7

TE - 17

D 8

TEH - 3

D

DATA ROOM

TEMP/HUMIDITY SENSOR

D 7

CS - 2

AHU-1 UC600-1 WIRING DETAIL

7NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

TAG QTY VENDOR PART NO DESCRIPTION

UC600 - 1 1 TRANE BM UC600AAA0100011UC600 CONTROLLER, FRAM E M OUNT

BILL OF M ATERIALS

UC600 - 1

LOCATION:

SYSTEM

CONTROLLED:

AHU-1

IMC IMC

P1

MBUS

TX

RX

SERVICE

TRANEUC600

ADDRESS

BO1 BO2 BO3 BO4

UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8

VAC

VAC

VAC

MBUS VDC LINK IMC

VDC

AO3

UI11

AO2

UI10

AO1

UI9

AO6

UI14

AO5

UI13

AO4

UI12

BO3BO2BO1 BO4

IMC

LINK

ACT

x100 x10 x1

SERVICE TOOL

UI8

P I1

UI7

UI6

UI5

UI4

UI3

UI2

UI1

LI

N

K

V D

C

IM

C

LI

N K

V A

C

+24

V D

C

-24

V A

C X

F R

M

M B

U S

AO2/UI10

AO1/UI9

BO4

BO3

BO2

BO1

E T

H E

R N

E T

N E

T W

O R

K

AO6/UI14

AO5/UI13

AO4/UI12

AO3/UI11

1ADDRESS

BRN

BRN

SHLD

D

CS - 2 ACU -1 STATUS

A

WHT

BLK

SHLD

D

CS - 1 SUPPLY FAN STATUS

H

WHT

BLK

SHLD

D

TE - 1 MIXED AIR TEMP (BALCO)

G

WHT

BLK

SHLD

D

DPS - 1 FILTER STATUS

E

WHT

BLK

SHLD

D

TEH - 2 OUTSIDE AIR TEMPERATURE

E

GRN

RED

SHLD

D

TEH - 2 OUTSIDE AIR HUMIDITY

E

WHT

BLK

SHLD

D

TEH - 1 RETURN AIR TEMPERATURE

E

GRN

RED

SHLD

D

TEH - 1 RETURN AIR HUMIDITY

MSTP1

A

SEE RISER WHT

BLK

MSTP1

A

SEE RISER WHT

BLKSHLD

TX - 1

24VAC120 VAC

BY ESC

NOT USED

C

WHT

BLK

SHLD

D

TE - 2 DISCHARGE AIR TEMP

B

WHT

BLK

SHLD

D

HE - 1 SPACE HUMIDITY SENSOR (4-20 MA)

WHT

BLK

SHLD

175 GENERATOR RUN STATUS

WHT

BLK

SHLD

D

TE - 17 CIRCUIT 1 SUCTION TEMPERATURE

WHT

BLK

SHLDRED

E

DA - 1 (F/17); DA - 2 (F/17)

B

WHT

GRN

SHLD

D

R - Y2 COOLING STAGE 2

A

RED

BLK

SHLD

D

R - Y1 COOLING STAGE 1 & LLSV

WHT

BLK

SHLD

D

R - 4 SUPPLY FAN START/STOP

GRN 1

TYPICAL FOR 1

(AHU-1)

1 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE

DEVICE INSTALLATION LITERATURE.

OA/RA DAMPERS

AHU - 1

LOC

XM30 - 1

LOC

XM

AHU - 1

XM32 - 2

LOC

XM

XM 30 - 1 1 TRANE X13651537010 4 POINT UI/AO EXPANSION M ODULE

BILL OF M ATERIALSTYPICAL FOR 1

(AHU - 1)

U I/A

O

IM

C

IM

C

+ IM

C

24 V D

C

IM

C

T X

R X

S E

R V

IC

E

T R A N E

X M

A D

D R

E S

S

UI 4

UI 3

UI 2

UI 1

XM30 - 1

LOCATION:

SYSTEM

CONTROLLED:

AHU - 1

1ADDRESS

B

BLK

WHT

SHLD

D

TEH - 3 DATA ROOM HUMIDITY

B

BLK

WHT

SHLD

D

TEH - 3 DATA ROOM TEMPERATURE

COMM COMM LINK FROM UC600

COMM EXP COMM TO XM32 - 2

AHU - 1 XM30 - 1 WIRING DETAIL

8NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

CRAC UNIT #2 FAILURE

CRAC UNIT #1 FAILURE

XM 32 - 2 1 TRANE X13651563010 4 POINT BO EXPANSION M ODULE

BILL OF M ATERIALSTYPICAL FOR 1

(AHU - 1)

XM32 - 2

LOCATION:

SYSTEM

CONTROLLED:

AHU - 1

2ADDRESS

IM

C

IM

C

IM

C

T X

R X

S E

R V

IC

E

T R A N E

X M

A D

D R

E S

S

C

NC

NO

+ IM

C

24 V D

C

C

NC

NO

C

NC

NO

C

NC

NO

B O

B

O

B O

B

O

B O

B

O

B O

B

O

COMM EXP COMM FROM XM30 - 1

AHU - 1 XM32 - 2 WIRING DETAIL

9NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

R - 2

R - 1

TX - 18

R - 1

1 2CRAC-1

R - 2

1 2CRAC-2

TE - 1 1 TRANE 4190-1046 TEM P SENS, AVG, BALCO, 22FT

TE - 2 1 TRANE 41901133 TEM P SENS, DUCT/ IM M , THERM 6 IN

TEH - 1, TEH - 2 2 TRANE 4190-7020 3% DUCT RH SENS, TEM P

DA - 1, DA - 2 2 BELIM O AF24-SR US ACT PROP 24VAC SR 133IN-LB

CS - 1 1 KELE RIBXGA CUR SW, 0.75-150A, SPLIT, NO

DPS - 1 1 KELE P32AC-2 DIFF PRES SW, 0.05-5 IN WC

R - Y1, R - 4 2 KELE RIBU2C RLY DPDT, LED, 10-30 VAC/DC/120 VAC

R - Y2 1 KELE RIBU1C RLY SPDT, LED, 10-30 VAC/DC/120 VAC

TE - 19 1 KELE ST-M P3-X25 STRAP-ON 10K NTC THERM ISTOR

BILL OF M ATERIALS

AHU-2 FLOW DIAGRAM

10NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

AHU - 2

RA

SAOA

C

DX

FILTER

N.C.

N.O.

11E

DA - 1

E

DA - 2

D 11

DPS - 1

H L

ACU - 1

D

R - Y1

COOL 1

R

D

R - Y2

COOL 2

R

INTLK

SD - 1

INTLK

SD - 2

1 EXISTING SMOKE DETECTORS ARE HARDWIRED TO FAN STARTER FOR SHUTDOWN.

2 CONNECT TO CONTACTS OF EXISTING STATUS RELAY.

D

D 11

TEH - 1

D

D 11

TEH - 2

D 11

TE - 1

D 11

TE - 2

11D

S/S

R - 4

D 11

142STS

CS - 1

STARTER HUM - 1

3 EXISTING HUMIDIFIER INTERLOCK/SAFETY CONTROLS ARE EXISTING (NOT SHOWN).

D11

TE - 19

D 11

CS - 3

AHU-2 UC600-2 WIRING DETAIL

11NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

TAG QTY VENDOR PART NO DESCRIPTION

UC600 - 2 1 TRANE BM UC600AAA0100011UC600 CONTROLLER, FRAM E M OUNT

BILL OF M ATERIALS

UC600 - 2

LOCATION:

SYSTEM

CONTROLLED:

AHU-2

IMC IMC

P1

MBUS

TX

RX

SERVICE

TRANEUC600

ADDRESS

BO1 BO2 BO3 BO4

UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8

VAC

VAC

VAC

MBUS VDC LINK IMC

VDC

AO3

UI11

AO2

UI10

AO1

UI9

AO6

UI14

AO5

UI13

AO4

UI12

BO3BO2BO1 BO4

IMC

LINK

ACT

x100 x10 x1

SERVICE TOOL

UI8

P I1

UI7

UI6

UI5

UI4

UI3

UI2

UI1

LI

N

K

V D

C

IM

C

LI

N K

V A

C

+24

V D

C

-24

V A

C X

F R

M

M B

U S

AO2/UI10

AO1/UI9

BO4

BO3

BO2

BO1

E T

H E

R N

E T

N E

T W

O R

K

AO6/UI14

AO5/UI13

AO4/UI12

AO3/UI11

2ADDRESS

BRN

BRN

SHLD

D

CS - 3 ACU -2 STATUS

A

WHT

BLK

SHLD

D

CS - 1 SUPPLY FAN STATUS

H

WHT

BLK

SHLD

D

TE - 1 MIXED AIR TEMP (BALCO)

G

WHT

BLK

SHLD

D

DPS - 1 FILTER STATUS

E

WHT

BLK

SHLD

D

TEH - 2 OUTSIDE AIR TEMPERATURE

E

GRN

RED

SHLD

D

TEH - 2 OUTSIDE AIR HUMIDITY

E

WHT

BLK

SHLD

D

TEH - 1 RETURN AIR TEMPERATURE

E

GRN

RED

SHLD

D

TEH - 1 RETURN AIR HUMIDITY

MSTP1

A

SEE RISER WHT

BLK

MSTP1

A

SEE RISER WHT

BLKSHLD

NOT USED

C

WHT

BLK

SHLD

D

TE - 2 DISCHARGE AIR TEMP

WHT

BLK

SHLD

D

TE - 19 CIRCUIT 1 SUCTION TEMPERATURE

WHT

BLK

SHLDRED

E

DA - 1 (F/17); DA - 2 (F/17)

B

WHT

GRN

SHLD

D

R - Y2 COOLING STAGE 2

RED

BLK

SHLD

D

R - Y1 COOLING STAGE 1 & LLSV

WHT

BLK

SHLD

D

R - 4 SUPPLY FAN START/STOP

GRN 1

TYPICAL FOR 1

(AHU-2)

1 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE

DEVICE INSTALLATION LITERATURE.

OA/RA DAMPERS

TX - 5

24VAC120 VAC

BY ESC

TE - 1 1 TRANE 4190-1046 TEMP SENS, AVG, BALCO, 22FT

TE - 2, TE - 3, TE - 21 3 TRANE 41901133 TEMP SENS, DUCT/IM M , THERM 6 IN

DA - 1, DA - 2 2 BELIMO AF24-SR US ACT PROP 24VAC SR 133IN-LB

CS - 1 1 KELE RIBXGA CUR SW, 0.75-150A, SPLIT, NO

DPS - 1 1 KELE P32AC-2 DIFF PRES SW, 0.05-5 IN WC

R - Y1, R - 4 2 KELE RIBU2C RLY DPDT, LED, 10-30 VAC/DC/120 VAC

R - Y2 1 KELE RIBU1C RLY SPDT, LED, 10-30 VAC/DC/120 VAC

TE - 22 1 KELE ST-M P3-X25 STRAP-ON 10K NTC THERM ISTOR

BILL OF M ATERIALS

AHU-3 FLOW DIAGRAM

12NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

AHU - 3

RA

SAOA

C

DX

FILTER

N.C.

N.O.

13E

DA - 1

E

DA - 2

D 13

DPS - 1

H L

ACU - 1

D

R - Y1

COOL 1

R

INTLK

SD - 1

INTLK

SD - 2

1 EXISTING SMOKE DETECTORS ARE HARDWIRED TO FAN STARTER FOR SHUTDOWN.

2 CONNECT TO CONTACTS OF EXISTING STATUS RELAY.

D 13

TE - 1

D 13

TE - 2

13D

S/S

R - 4

D 13

171STS

CS - 1

STARTER

D 13

TE - 3

SEQUENCE OF OPERATION:

AIR HANDLING UNIT AHU-3:

AHU-3 SERVES THE ADMINISTRATION AREA AND OPERATES ON AN 8 HOUR SCHEDULE WITH NIGHT SETBACK. THE

OPERATION OF AHU-3 IS SIMILAR TO AHU-1 AND AHU-2 WITH THE FOLLOWING EXCEPTIONS:

(1) OUTSIDE AIR ECONOMIZER CYCLE IS CONTROLLED BY OUTSIDE AIR TEMPERATURE.

(2) NO HUMIDITY CONTROL.

AHU-3, ACU-3 AND ASSOCIATED ELECTRIC DUCT HEATERS SHALL NOT OPERATE ON EMERGENCY POWER. UPON RESTORATION OF COMMERCIAL POWER, AHU-3 ACU-3 AND ASSOCIATED ELECTRIC DUCT HEATERS SHALL RETURN TO NORMAL OPERATING MODE. THE AIR HANDLING UNIT SHALL BE PROGRAMMED FOR A TIMED DELAY RESTART.

D 13

TE - 21

D13

TE - 22

D

R - Y2

COOL 2

R

D 13

CS - 4

AHU-3 UC600-3 WIRING DETAIL

13NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

TAG QTY VENDOR PART NO DESCRIPTION

ENC - 2 1 TRANE X13651552010 ENC, TRACER UC LARGE, 120 VAC OUTLET

UC600 - 3 1 TRANE BM UC600AAA0100011UC600 CONTROLLER, FRAM E M OUNT

BILL OF M ATERIALS

UC600 - 3

LOCATION:

SYSTEM

CONTROLLED:

AHU-3

IMC IMC

P1

MBUS

TX

RX

SERVICE

TRANEUC600

ADDRESS

BO1 BO2 BO3 BO4

UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8

VAC

VAC

VAC

MBUS VDC LINK IMC

VDC

AO3

UI11

AO2

UI10

AO1

UI9

AO6

UI14

AO5

UI13

AO4

UI12

BO3BO2BO1 BO4

IMC

LINK

ACT

x100 x10 x1

SERVICE TOOL

UI8

P I1

UI7

UI6

UI5

UI4

UI3

UI2

UI1

LI

N

K

V D

C

IM

C

LI

N K

V A

C

+24

V D

C

-24

V A

C X

F R

M

M B

U S

AO3/UI11

AO2/UI10

AO1/UI9

BO4

BO3

BO2

BO1

E T

H E

R N

E T

N E

T W

O R

K

AO6/UI14

AO5/UI13

AO4/UI12

3ADDRESS

BRN

BRN

SHLD

D

CS - 4 ACU - 3 STATUS

A

WHT

BLK

SHLD

D

CS - 1 SUPPLY FAN STATUS

H

WHT

BLK

SHLD

D

TE - 1 MIXED AIR TEMP (BALCO)

G

WHT

BLK

SHLD

D

DPS - 1 FILTER STATUS

WHT

BLK

SHLD

D

TE - 3 OUTSIDE AIR TEMP

MSTP1

A

SEE RISER WHT

BLK

MSTP1

A

SEE RISER WHT

BLKSHLD

TX - 6

24VAC120 VAC

BY ESC

NOT USED

C

WHT

BLK

SHLD

D

TE - 2 DISCHARGE AIR TEMP

WHT

BLK

SHLD

D

TE - 21 RETURN AIR TEMPERATURE

WHT

BLK

SHLD

D

TE - 22 SUCTION TEMPERATURE

WHT

BLK

SHLDRED

E

DA - 1 (F/17); DA - 2 (F/17)

WHT

BLK

SHLD

D

R - Y2 COOLING STAGE 2

A

WHT

BLK

SHLD

D

R - Y1 COOLING STAGE 1 & LLSV

WHT

BLK

SHLD

D

R - 4 SUPPLY FAN START/STOP

ENC - 2

GRN 1

TYPICAL FOR 1

(AHU-3)

1 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE

DEVICE INSTALLATION LITERATURE.

OA/RA DAMPERS

CONDENSING UNIT WIRING

14NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

Y2

R

Y1

C

CU

R - Y2

R - Y1

LLSV

ORG

RED

YEL

PUR

EDH 1 - 3, 9 - 10 UC210 WIRING DETAIL

15NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

TAG QTY VENDOR PART NO DESCRIPTION

EDH - 1 5 TRANE X13651610010 UC210 VAV, FLOW SENS, M TG

TE - 32 5 TRANE 41901129 TEM P SENS, DUCT, THERM , 4 IN

TE - 33 5 TRANE X1351152701 TEM P SENS ZONE THERM O/U SP

BILL OF M ATERIALS

TYPICAL FOR 5

(EDH - 1, EDH - 2, EDH - 3, EDH - 9,

EDH - 10)

1 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE

DEVICE INSTALLATION LITERATURE.

EDH

SUPPLY

AIR

AIR

FLOW

VCEF

GND

24VAC

GND

24VAC

BO1

24VAC

BO2

24VAC

BO3

AO1

GND

AO2

GND

AI1

GND

AI2

AI3

GND

BI1

UI1

UI2

GND

GND

LI

N

K

LI

N

K

LI

N

K

LI

N

K

V

D C

G N

D

IM

C

IM

C

V

D C

G N

D

IM

C

IM

C x10 x10 x1

ADDRESS

J15

J16

J17

J18

J19

J20

J21

J22

J23

J26

J27

J28

J29

J1

J2

J3

J4

J5

CLS

OPN

24VAC

GND

24VAC

GND

EDH - 1

LOCATION:

SYSTEM

CONTROLLED:

EDH - 1

24 VAC

BY ESC

GRN

GND1

WHT325HEAT SCR SIGNAL

D BLKTAPE SHLD

C

WHT

TAPE SHLD

326 TE - 33 ZONE SENSOR TEMPERATURE

EBLK

RED

D

WHT

TAPE SHLD

327 TE - 32 DISCHARGE AIR TEMPERATURE

DBLK

COMM

A

SEE COMM RISER PAGE WHT

BLK

COMM

A

SEE COMM RISER PAGE WHT

BLK

SHLD

FROM TX-3 & TX-4

SEE COMM RISER PAGE

D

D 15

TE - 32

E 15

TE - 33

ZONE SENSOR

SEQUENCE OF OPERATION:

WHEN SPACE HEATING IS REQUIRED AS DETERMINED BY THE

ZONE THERMOSTAT THE CONTROLLER SHALL MODULATE THE

HEAT TO CONTROL THE DISCHARGE AIR TEMPERATURE EQUAL

TO THE DISCHARGE AIR HEATING SETPOINT. (100 DEG. ADJ.)

EDH 4 - 8 UC210 WIRING DETAIL

16NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

TAG QTY VENDOR PART NO DESCRIPTION

EDH - 4 5 TRANE X13651610010 UC210 VAV, FLOW SENS, M TG

TE - 30 5 TRANE 41901129 TEM P SENS, DUCT, THERM , 4 IN

TE - 31 5 TRANE X1351152701 TEM P SENS ZONE THERM O/U SP

BILL OF M ATERIALS

TYPICAL FOR 5

(EDH - 4, EDH - 8, EDH - 7, EDH - 6,

EDH - 5)

1 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE

DEVICE INSTALLATION LITERATURE.

EDH

SUPPLY

AIR

AIR

FLOW

GND

24VAC

GND

24VAC

BO1

24VAC

BO2

24VAC

BO3

AO1

GND

AO2

GND

AI1

GND

AI2

AI3

GND

BI1

UI1

UI2

GND

GND

LI

N

K

LI

N

K

LI

N

K

LI

N

K

V

D C

G N

D

IM

C

IM

C

V

D C

G N

D

IM

C

IM

C x10 x10 x1

ADDRESS

J15

J16

J17

J18

J19

J20

J21

J22

J23

J26

J27

J28

J29

J1

J2

J3

J4

J5

CLS

OPN

24VAC

GND

24VAC

GND

EDH - 4

LOCATION:

SYSTEM

CONTROLLED:

EDH - 4

24 VAC

BY ESC

GRN

GND1

WHT305HEAT STAGE 2

D BLKTAPE SHLD

WHT306HEAT STAGE 1

D

BLK

TAPE SHLD

C

WHT

TAPE SHLD

309 TE - 31 ZONE SENSOR TEMPERATURE

EBLK

RED

D

WHT

TAPE SHLD

310 TE - 30 DISCHARGE AIR TEMPERATURE

DBLK

COMM

A

SEE COMM RISER PAGE WHT

BLK

COMM

A

SEE COMM RISER PAGE WHT

BLK

SHLD

D 16

TE - 30

D

D

E 16

TE - 31

ZONE SENSOR

2 CONTROLLER OUTPUTS SWITCH COMMON SIDE OF CIRCUIT.

SEQUENCE OF OPERATION:

WHEN SPACE HEATING IS REQUIRED AS DETERMINED BY THE

ZONE THERMOSTAT THE CONTROLLER SHALL STAGE THE

HEAT TO CONTROL THE DISCHARGE AIR TEMPERATURE EQUAL

TO THE DISCHARGE AIR HEATING SETPOINT. (100 DEG. ADJ.)

FROM TX-3 & TX-4

SEE COMM RISER PAGE

DETAIL SHEET #1

17NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

CURRENT OPERATED SWITCH, SPILT-CORE, ADJ. TRIP,

LEDS

RIBXGA

KELE

A

UNK

UNK

STATUS

COMMON

WHT

BLK

SENSOR ZONE RH +/- 3% AND TEMP

X1379044401

TRANE

B

- GRN

RED +24VDC

4-20mA SIGNAL

T T

WHT

BLK

TEMP SIGNAL

TEMP COMMON

TRANE

ZONE SENSOR THERM + SETPOINT + OCC/UNOC

C

WHT

BLK

ZONE TEMP

COMMON

3 RED SETPOINT

X1351152701

OCC

SETPOINT

UNOCC

SENSOR TEMP 4" DUCT THERM

41901129

TRANE

D

RED WHT TEMP

GRN BLK COMMON

SENSOR DUCT RH +/- 3% AND TEMP

4190-7020

TRANE

E

TT

GRN

RED

GRN 4-20mA SIGNAL

+ 24VDC

BLK

WHT

COMMON

TEMP

ACTUATORS MOD, 24VAC/DC, 133 IN-LB

BELIMO

AF24-SR US

F

HOT (2)

COM (1)

RED

BLK

INPUT (3) WHT

24 VAC

COMMON

2-10VDC SIGNAL

OUTPUT (5) NOT USED

SWITCH AIR DP P32 0.05-5"

P32AC-2

KELE

G

Y

B

R BLK COMMON

WHT NO - CLOSE ON RISE

HIGH

PRESSURE

LOW

PRESSURE

SIDEFRONT

SENSOR TEMP DUCT 22 FT. AVG BALCO

4190-1046

TRANE

H

BLK WHT TEMP

BLK BLK COMMON

DETAIL SHEET #2

18NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

DUAL DPDT RELAY

KELE

RIBU2C

A

WHT/YEL

ORN

YEL

BLU

WHT/BLU

BLK

BLK

WHT

BRN

PUR

GRY NOT USED

WHT

BLK

WHT

NOT USED

10-30VAC/DC

CONTACT #1, NO

CONTACT #1, COMMON

CONTACT #2, NO

CONTACT #2, COMMON

WHT/BLK NOT USED

10-30VAC/DC COMMON

WHT/PUR

GRY/WHT

BLK

WHT/RED

R E

LA

Y

WHT 10-30VAC/DC

NOT USED

10-30VAC/DC COMMON

R E

LA

Y

SPDT RELAY

KELE

RIBU1C

B

WHT/YEL

ORN

YEL

COIL, COMMON

BLU

CONTACTS, NO

CONTACTS, COM

CONTACTS, NC

WHT/BLK

WHT/BLU

COIL, 120VAC

COIL 10-30VAC/VDC

NOT USED

WHT

RED

BLK

BLK

WHT CONTROLLER OUTPUT

CONTROLLER COMMON

DEVICE

DEVICE

DEVICE

SENSOR TEMP 6" DUCT/IMM THERM

41901133

TRANE

C

RED WHT TEMP

GRN BLK COMMON

BILL OF MATERIALS

19NOAA_CHS.AXD

K KOEHN J VAN SISE

INSTALLATION DRAWING 1/6/2016 JVS

AS-BUILT DRAWING 2/24/2016 JP

SALESPERSON:

FILE

NAME:

NUM. REVISION DATE: BY:

DESIGNED BY: CHECKED BY:

NOAA WEATHER STATION

CHARLESTON, SC

PROJECT:

803-936-4700

WEST COLUMBIA, SC 29169

111 LOTT COURT

COLUMBIA MAIN OFFICE

DWG:

PROJECT ID:CID: PID:

TAG PREFIX QTY VENDOR PART NO DESCRIPTION

TE 3 TRANE 4190-1046 TEMP SENS, AVG, BALCO, 22FT

TEH 4 TRANE 4190-7020 3% DUCT RH SENS, TEMP

TE 10 TRANE 41901129 TEMP SENS, DUCT, THERM, 4 IN

TE 5 TRANE 41901133 TEMP SENS, DUCT/IMM, THERM 6 IN

SFT 1 TRANE BMCF000AAA0AE00 TRACER SC15 SOFTWARE

SC 1 TRANE BMSC000AAA01100 TRACER SC

UC600 3 TRANE BMUC600AAA0100011 UC600 CONTROLLER, FRAME MOUNT

TE 10 TRANE X1351152701 TEMP SENS ZONE THERM O/U SP

TBT 1 TRANE X13651524-01 TRANE BACNET TERMINATOR (2/PKG)

XM30 1 TRANE X13651537010 4 POINT UI/AO EXPANSION MODULE

ENC 1 TRANE X13651552010 ENC, TRACER UC LARGE, 120 VAC OUTLET

ENC 1 TRANE X13651559010 ENC, TRACER UC MEDIUM, 120 VAC OUTLET

XM32 1 TRANE X13651563010 4 POINT BO EXPANSION MODULE

EDH 10 TRANE X13651610010 UC210 VAV, FLOW SENS, MTG

HE, TEH 2 TRANE X1379044401 3% ROOM RH SENS, TEMP

DA 6 BELIMO AF24-SR US ACT PROP 24VAC SR 133IN-LB

DPS 3 KELE P32AC-2 DIFF PRES SW, 0.05-5 IN WC

R 3 KELE RIBU1C RLY SPDT, LED, 10-30 VAC/DC/120 VAC

R 6 KELE RIBU2C RLY DPDT, LED, 10-30 VAC/DC/120 VAC

CS 3 KELE RIBXGA CUR SW, 0.75-150A, SPLIT, NO

TE 3 KELE ST-MP3-X25 STRAP-ON 10K NTC THERMISTOR

BILL OF MATERIALS

File details come from the government source that posted it. Updated .