Attachment_4_142010-26-0063.pdf
PDF 516 KB Posted
- Solicitation number
- 1305M326Q0394
About this file
Record Drawing Summary
This is a Trane record drawing (as-built documentation) dated March 16, 2016, for the NOAA Weather Station project in Charleston, South Carolina. The project was prepared for Carolina Comfort Solutions (2006 Rockland Road, Columbia, SC 29210) and sold through the Trane Sales Office in West Columbia, South Carolina. The Trane project team included Account Manager Kent Koehn, Project Manager Jeff Kindle, and Designer Jan Van Sise.
The drawing set comprises 19 sheets documenting a complete HVAC control system installation, including a system controller (SC-1), three air handling units (AHU-1, AHU-2, AHU-3) with UC600 controllers, ten electric duct heaters (EDH-1 through EDH-10) with UC210 controllers, and associated expansion modules (XM30-1, XM32-2). The system incorporates BACNET MS/TP communication architecture, 24 VAC power distribution via transformers (TX-2 through TX-6), damper actuators, temperature and humidity sensors, differential pressure switches, current sensors, relays, and zone control devices from vendors including Trane, Belimo, and Kele. Wiring specifications detail analog input/output limits (0-10 VDC at 300 feet maximum, 0-20 mA at 1,000 feet maximum), BACNET communication cable requirements (shielded twisted pair, 18 AWG minimum, 4,000-foot maximum distance), and installation standards compliance with the National Electrical Code and local building codes. The bill of materials lists 59 components across all system elements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_1305M326Q0394_Amd_0001.pdf | ||
| Attachment_6_142010-26-0063.pdf | ||
| Attachment_5_142010-26-0063.pdf | ||
| Charleston_WD_2015-4427.txt | TXT text file | |
| Hampton_WD_2015-4441.txt | TXT text file | |
| Attachment_3_142010-26-0063.pdf | ||
| Attachment_8_142010-26-0063.pdf | ||
| Attachment_7_142010-26-0063.pdf | ||
| Attachment_1_142010-26-0063.pdf | ||
| Attachment_2_142010-26-0063.pdf | ||
| Sol_1305M326Q0394.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Record Drawing Date: March 16, 2016
Project Number:
Project Name:
NOAA Weather Station
CHARLESTON, SC
Customer P.O. Number:
Customer Project Number:
Prepared For:
Carolina Comfort Solutions
2006 ROCKLAND RD.
COLUMBIA, SC 29210
Sold To:
Trane Sales Office:
COLUMBIA MAIN OFFICE
111 LOTT COURT
WEST COLUMBIA, SC 29169
Phone: 803-936-4700 Fax:
Web:
Architect:
Mechanical Contractor:
Mechanical Engineer:
Trane Contracting Team:
Account Manager: Kent Koehn kkoehn@trane.com
Project Manager: Jeff Kindle jeff.kindle@trane.com
Designed By: Jan Van Sise jcvansise@trane.com
TITLE PAGE
1NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
THIS DRAWING SET IS THE PROPERTY OF
TRANE. DESIGN INFORMATION, DRAWINGS,
DETAILS OR SPECIFICATION DATA MAY NOT BE
REPRODUCED OR DUPLICATED NOR MAY ANY
WORK BE EXECUTED HEREFROM WITHOUT THE
WRITTEN AUTHORIZATION OF TRANE.
NOAA Weather Station
CHARLESTON, SC
SALESPERSON:
Kent Koehn
PROJECT MANAGER:
Jeff Kindle
DESIGNED BY:
Jan Van Sise
TRANE PROJECT TEAM
Carolina Comfort Solutions
2006 ROCKLAND RD.
COLUMBIA, SC 29210
Customer Contact
DRAWING INDEX
2NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
DRAWING
NUM BER
DRAWING TITLE REVISION LEVEL REVISION DATE COM M ENTS
1 TITLE PAGE AS-BUILT DRAWING 2/24/2016
2 DRAWING INDEX AS-BUILT DRAWING 2/24/2016
3 LEGEND AS-BUILT DRAWING 2/24/2016
4 COM M UNICATION RISER AS-BUILT DRAWING 2/24/2016
5 SYSTEM CONTROLLER SC - 1 WIRING DETAIL AS-BUILT DRAWING 2/24/2016
6 AHU-1 FLOW DIAGRAM AS-BUILT DRAWING 2/24/2016
7 AHU-1 UC600-1 WIRING DETAIL AS-BUILT DRAWING 2/24/2016
8 AHU - 1 XM 30 - 1 WIRING DETAIL AS-BUILT DRAWING 2/24/2016
9 AHU - 1 XM 32 - 2 WIRING DETAIL AS-BUILT DRAWING 2/24/2016
10 AHU-2 FLOW DIAGRAM AS-BUILT DRAWING 2/24/2016
11 AHU-2 UC600-2 WIRING DETAIL AS-BUILT DRAWING 2/24/2016
12 AHU-3 FLOW DIAGRAM AS-BUILT DRAWING 2/24/2016
13 AHU-3 UC600-3 WIRING DETAIL AS-BUILT DRAWING 2/24/2016
14 CONDENSING UNIT WIRING AS-BUILT DRAWING 2/24/2016
15 EDH 1 - 3, 9 - 10 UC210 WIRING DETAIL AS-BUILT DRAWING 2/24/2016
16 EDH 4 - 8 UC210 WIRING DETAIL AS-BUILT DRAWING 2/24/2016
17 DETAIL SHEET # 1 AS-BUILT DRAWING 2/24/2016
18 DETAIL SHEET # 2 AS-BUILT DRAWING 2/24/2016
19 BILL OF M ATERIALS AS-BUILT DRAWING 2/24/2016
INDEX OF CONTROL SYSTEM DRAWINGS
LEGEND
3NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
Symbol Legend
AIR FLOW STATION
AFS
AIR FLOW STATION, FAN
MOUNTED
AFS
ALARM, BELL
ALM
ALARM, STROBE
ALM
ALARM, PIEZIO
ALM
BLENDER, AIR
BURNER, FUEL-FIRED
DIRECT COIL, COAXIAL
COIL, CHW, DX, HW,
STEAM, ETC.
C
C
CONTROL POINT
CS - CURRENT SENSOR
CSR - CURRENT
SENSOR W/RELAY
CS OR CSR
DAMPER, OPPOSED OR
PARALLEL
D
TRAQ DAMPER
D
ACTUATOR, DAMPER
DA
SENSOR, DIFFERENTIAL
PRESSURE
DPS
AIR DIFFERENTIAL
SWITCH OR SENSOR
DPS, DPT
DIFFERENTIAL
PRESSURE SWITCH OR
SENSOR
DPT, DPS
H L EXCHANGER, FUEL FIRE
HEAT
EXCHANGER, FLUID
HEAT FAN OR PUMP
FAN, ROOF TOP FILTER, AIR FILTER, AIR BAG FILTER, AIR HEPA
FILTER, AIR ROLL SWITCH, FLOAT
FLT
FIRESTAT
FS
SENSOR, FLOW
FS
HEATER, ELECTRIC
DUCT
SENSOR, ROOM STATIC
PRESSURE
HDW
TUBE, STATIC
PRESSURE
HDW
SENSOR, DUCT
HUMIDITY AND
TEMPERATURE
HE, TEH
SENSOR, HUMIDITY OR
TEMPERATURE AND
HUMIDITY
HE, TEH
SENSOR, INDOOR AIR
QUALITY
IAQ
SENSOR, INDOOR AIR
QUALITY (CO2)
IRQ
THERMOSTAT, LOW
LIMIT
LLT
STARTER, MOTOR
MS
SENSOR, OCCUPANCY
OCC
TRANSMITTER,
PRESSURE
PT
RELAY
R
RELAY, SOCKET
R
SENSOR, OUTDOOR
PRESSURE
RB
SWITCH, RESET
STATION
RST
DETECTOR, SMOKE
SD
SEQUENCER
SEQ
SWITCH
SW
ON
OFF
SOLENOID, AIR
SOL
SWITCH, BUTTON
SW
THERMOSTAT, WALL
T
COMPOUND, THERMAL
TC
SENSOR, AVERAGING
TEMPERATURE
TE
SENSOR, STRAP ON
TEMPERATURE
TE
SWITCH, ROTARY
SW
HEAT COOL
AUTO
SENSOR,
TEMPERATURE
TE
SENSOR, ZONE
TE
TIMER, ELECTRONIC
WALL
TMR
TIMER, WALL
TMR
WELL, THERMAL
TW
TRANSFORMER
TX
LIGHT, ULTRAVIOLET
UV
VALVE, 2-WAY COIL
VAL
VALVE, 3-WAY COIL
VAL
VALVE, DUCT
HUMIDIFIER
VAL
VARIABLE FREQUENCY
DRIVE
VFD
Wiring and Project NotesWiring and Project Notes
ELECTRICAL CONTRACTOR FOR TRANE:
1. REFER TO DEVICE INSTALLATION MANUALS FOR SPECIFIC WIRING REQUIREMENTS.
2. FIELD WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE, STATE AND
LOCAL BUILDING CODES, AND DIVISION 16 OF SPECIFICATIONS.
3. TAG ALL CONTROL WIRING AT EACH END OF THE CABLE OR WIRE PER TAGS SHOWN IN
ATTACHED DRAWINGS.
4. AVOID OVER TIGHTENING CABLE TIES AND OTHER FORMS OF CABLE WRAPS. THIS CAN
DAMAGE THE WIRES INSIDE THE CABLES.
5. DO NOT CABLE TIE TO INSULATED WATER, STEAM OR OTHER LINES.
6. IN OPEN PLENUMS, AVOID RUNNING WIRE NEAR LIGHTING BALLASTS, ESPECIALLY THOSE
USING 277 VAC.
7. ALL PANELS AND FIELD DEVICES LISTED IN THIS DOCUMENT ARE TO BE INSTALLED BY
CONTROLS ELECTRICAL SUBCONTRACTOR UNLESS OTHERWISE NOTED ON DRAWINGS.
8. MOUNT ALL ROOM SENSORS AND SWITCHES AS SHOWN ON THE CONSTRUCTION
DOCUMENTS, UNLESS OTHERWISE DIRECTED IN WRITING BY THE OWNER AND/OR ENGINEER.
9. FLEXIBLE CONDUIT IS NOT TO EXCEED 24” IN LENGTH.
10. CONTROL PANELS ARE NOT TO BE USED AS JUNCTION BOXES OR RACEWAYS. WIRING
THAT DOES NOT TERMINATE IN A CONTROL PANEL IS NOT TO BE RUN WITHIN THE PANEL.
11. BINARY INPUT LIMITS: 1000 FT (300 M).
12. 0~10 VDC ANALOG INPUT LIMITS: 300 FT (100 M).
13. 0~20 MA ANALOG INPUT LIMITS: 1000 FT (300 M).
14. VARIABLE RESISTANCE ANALOG INPUT LIMITS: 300 FT (100 M).
15. ANALOG OUTPUT LIMITS: 1000 FT (300 M).
16. BINARY OUTPUT LIMITS: 1000 FT (300 M).
17. WIRING POWER FROM THE AC OUT TERMINALS TO POWER ANALOG INPUT DEVICES WILL
CAUSE IMMEDIATE CONTROLLER FAILURE IF INPUT DEVICE USES HALF-WAVE RECTIFICATION.
WHEN UNSURE, USE A SEPARATE POWER SUPPLY FOR DEVICE.
18. GENERAL COMMUNICATION GUIDE: DO NOT RUN COMMUNICATION LINK WIRING IN THE
SAME CONDUIT OR WIRE BUNDLE WITH AC-POWER WIRES (INCLUDING CONDUCTORS
RUNNING FROM TRIAC-TYPE OUTPUTS). KEEP POLARITY CONSISTENT THROUGHOUT THE
SITE. MAKE SURE THAT THE 24 VAC POWER SUPPLIES ARE CONSISTENT IN HOW THEY ARE
GROUNDED. AVOID SHARING 24 VAC BETWEEN CONTROLLERS. USE ONLY ONE TYPE OF
COMMUNICATION CABLE; DO NOT MIX CABLE. IF AN EXISTING JOB USED ALTERNATE CABLE,
CONTINUE USING THE SAME CABLE AFTER APPROVAL FROM THE PROJECT MANAGER.
19. BACNET MS/TP COMMUNICATION CABLE MUST BE SHIELDED TWISTED PAIR, 18 AWG
MINIMUM, STRANDED, TINNED COPPER CONDUCTORS. SHIELD MUST BE CONTINUOUS
THROUGHOUT, ISOLATED FROM OTHER CONDUCTORS OR GROUND, AND GROUNDED AT THE
SYSTEM CONTROLLER ONLY. MAXIMUM CAPACITANCE BETWEEN CONDUCTORS IS 24
PICOFARADS PER FOOT. MAXIMUM DISTANCE IS 4000 FT (1372 M). MAXIMUM OF 60 TRANE
DEVICES PER LINK BUT LESS WHEN COMBINED WITH NON-TRANE DEVICES. EXPANSION
MODULE LINK LIMIT IS 656 FT (200 M). A TRACER BACNET TERMINATOR IS REQUIRED AT EACH
END OF THE COMMUNICATION LINK. TOPOLOGY MUST BE DAISY CHAINED.
20. LONTALK (COMM 5) COMMUNICATION CABLE MUST BE LEVEL 4 UNSHIELDED, 22 AWG WITH
MAXIMUM CAPACITANCE BETWEEN CONDUCTORS OF 17 PICOFARADS PER FOOT. MAXIMUM
DISTANCE IS 4500 FT (1400 M). MAXIMUM DEVICES IS 60 DEVICES WITHOUT REPEATER AND
120 WITH REPEATER. ONE REPEATER PER LINK CAN BE USED FOR AN ADDITIONAL 4500 FT
(1400 M), 60 DEVICES. EX2 LINK LIMIT IS 1000 FT (300 M). CCP III LINK LIMIT IS 3500 FT (1090 M).
105 OHMS, 1%, ¼ WATT TERMINATION RESISTORS ARE REQUIRED AT EACH END FOR LEVEL 4
WIRE AND 82 OHMS, 1%, ¼ WATT AT EACH END FOR 18 AWG SHIELDED (PURPLE) WIRE.
TOPOLOGY MUST BE DAISY CHAINED.
21. COMM 3 AND COMM 4 COMMUNICATION CABLE MUST BE SHIELDED TWISTED PAIR, 18AWG
MINIMUM, STRANDED, TINNED COPPER CONDUCTORS. SHIELD MUST BE CONTINUOUS
THROUGHOUT, ISOLATED FROM OTHER CONDUCTORS OR GROUND, AND GROUNDED AT BCU
ONLY. MAXIMUM CAPACITANCE BETWEEN CONDUCTORS IS 24 PICOFARADS PER FOOT.
MAXIMUM DISTANCE IS 5000 FT (1715 M). UNDER CERTAIN CONDITIONS, TERMINATION
RESISTORS ARE REQUIRED ON A COMM 3 COMMUNICATION LINK.
22. ETHERNET LAN COMMUNICATION CABLE MAXIMUM DISTANCE IS 295 FT (90 M) PLUS 33 FT
(10 M) FOR PATCH CABLES.
MECHANICAL CONTRACTOR:
1. DAMPERS ARE TO BE INSTALLED BY SHEET METAL CONTRACTOR UNLESS OTHERWISE
NOTED.
2. CONTROL VALVES AND ACCESSORIES INSTALLED DIRECTLY INTO PIPING (SENSOR WELLS,
THREADOLETS, ETC.) ARE TO BE INSTALLED BY MECHANICAL CONTRACTOR.
3. FLOW DIAGRAMS SHALL NOT BE A GUIDE FOR PIPE AND VALVE INSTALLATION. REFER TO
THE VALVE MANUFACTURER’S INSTALLATION INSTRUCTIONS FOR INSTALLATION GUIDANCE.
FIELD WIRING NOTE:
D
WHT
BLK
D
WHT
BLK
SOLID LINES: NOT
WIRED BY FIELD
DASHED LINES:
WIRED BY FIELD
BLK
WHT
121 37
2TB
WIRED BY FACTORY WIRED BY FIELD
FIELD MOUNTED
CONTROLLER
FACTORY
TERMINAL
CABLE
TAG
FACTORY MOUNTED DEVICE WITH FIELD MOUNTED CONTROLLE R:
D
CABLE MATRIX NOTES:
KEEP ALL COMMUNICATION LINK WIRING IN A DAISY CHAIN CONFIGURATION. ALL CABLE WIRING MUST BE TRANE RECOMMENDED WIRING , ESPECIALLY COMMUNICATION CABLES. CONTACT TRANE FOR RECOMMENDED CABLES
AND SPECIFICATIONS.
Cable MatrixCable Matrix
* When ordering cable specify jacket color. Part numbers are subject to change without notice.
CT
052003
TRANE NUMBER*
A WHT, BLK
DESCRIPTION
18/2 TWIST SHLD PURPLE COMM CABLE
105500C WHT, BLK22/2 TWIST NON-SHLD BLUE COMM CABLE
002320D WHT, BLK18/2 TWIST SHLD PLEN WHITE CABLE
002330E WHT, BLK, RED18/3 TWIST SHLD PLEN WHITE CABLE
002340F WHT, BLK, RED, GRN18/4 TWIST SHLD PLEN WHITE CABLE
J WHT, BLK1 PAIR #14 THHN STRANDED IN CONDUIT
L ETHERNET RG58 THNNET PLEN CABLE
555619M ETHERNET CAT-5 PLEN CABLE
002352O WHT, BLK, RED, ORN, YEL, GRN, BLU, BRN18/8 TWIST SHLD PLEN WHITE CABLE
106502P WHT, BLK22/2 TWIST SHLD PLEN ORANGE COMM CABLE
WIRE COLORS
761360Q WHT, BLK16/2 SOLID RED SMOKE DETECTOR CABLE
5100012C WHT, RED18/2 SOLID PLENUM THERMOSTAT CABLE
51002-043C WHT, RED, GRN18/3 SOLID PLENUM THERMOSTAT CABLE
5100045C WHT, RED, GRN, YEL, BLU18/5 SOLID PLENUM THERMOSTAT CABLE
5100078C WHT, RED GRN, YEL, BLU, ORN, BLK, BRN18/8 SOLID PLENUM THERMOSTAT CABLE
10C WHT, RED, GRN, YEL, BLU, ORN, BLK, BRN, GRY, PNK18/10 SOLID PLENUM THERMOSTAT CABLE
12C 18/12 SOLID PLENUM THERMOSTAT CABLE
B FACTORY PROVIDED CABLE
WHT, RED, GRN, YEL, BLU, ORN, BLK, BRN, GRY, PNK, PUR, TAN
CABLE INFORMATION SHAPE (CIS):
EACH CABLE CONNECTION HAS A CIS WHICH PROVIDES SOME OR ALL OF THE INFORMATION INDICATED BELOW:
WIRE COLOR
OR POLARITY
SHIELD
CONFIGURATION
CABLE TYPE FROM
CABLE MATRIX
CABLE
NUMBER
DEVICE TAG AND
POINT DESCRIPTION
END DEVICE DETAIL
REFERENCE INSET & PAGE
B
CSR-3 CONDENSER PUMP STATUS
D
WHT
BLK TAPE SHLD
SHIELDING NOTE:
D
WHT
BLK TAPE SHLD
D
WHT
BLK
ATTACH ALL SHIELDS TO
COMMON AS SHOWN
TAPE OFF SHIELD
AT DEVICE
FACTORY
PROVIDED
AND WIRED
DEVICE
Field, Factory And Existing Device Note:
EXISTING
DEVICE
FIELD WIRED
DEVICE (FIELD
OR FACTORY
PROVIDED)
D
FACT
10D
EXST
RISER 'WIRING BY' NOTE:
EC - ELECTRICAL CONTRACTOR
ESC - ELECTRICAL SUBCONTRACTOR
OTHERS
TRANE
EXIST - EXISTING POWER
CONTROLLER
PAGE
NUMBER
CABLE TYPE
FROM
CABLE MATRIX
DEVICE TAG
FLOW SHAPE NOTES:
D 10
TE - 1
CABLE TAG
480 VAC
BY EC
AHU - X
ADDRESS
WCI
AHU - X
WIRELESS
COMMUNICATION
INTERFACE
DISPLAYING
SUBNET NUMBER
COMMUNICATION RISER
4NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
SYSTEM CONTROLLER
FIELD LOCATE
120 VAC
BY ESC
SC - 1
AHU-1
120 VAC
BY ESC
UC600 - 1
AHU-2
120 VAC
BY ESC
UC600 - 2
AHU-3
120 VAC
BY ESC
UC600 - 3
TO
OWNER'S
LAN
M
A
EDH - 10
24 VAC
BY ESC
EDH - 10
EDH - 9
24 VAC
BY ESC
EDH - 9
EDH - 4
24 VAC
BY ESC
EDH - 4
EDH - 3
24 VAC
BY ESC
EDH - 3
EDH - 8
24 VAC
BY ESC
EDH - 8
EDH - 7
24 VAC
BY ESC
EDH - 7
EDH - 6
24 VAC
BY ESC
EDH - 6
EDH - 5
24 VAC
BY ESC
EDH - 5
EDH - 1
24 VAC
BY ESC
EDH - 1
EDH - 2
24 VAC
BY ESC
EDH - 2
D
24 VAC FROM TRANS-
FORMER TX - 3
24 VAC FROM TRANS-
FORMER TX - 4
D
TAG QTY VENDOR PART NO DESCRIPTION
ENC - 4 1 TRANE X13651559010 ENC, TRACER UC M EDIUM , 120 VAC OUTLET
SC - 1 1 TRANE BM SC000AAA01100 TRACER SC
SFT - 1 1 TRANE BM CF000AAA0AE00 TRACER SC15 SOFTWARE
TBT - 2 1 TRANE X13651524-01 TRANE BACNET TERM INATOR (2/PKG)
BILL OF M ATERIALSTYPICAL FOR 1
(SYSTEM CONTROLLER)
SYSTEM CONTROLLER SC - 1 WIRING DETAIL
5NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
4 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE
DEVICE INSTALLATION LITERATURE.
SC - 1
LOCATION:
SYSTEM
CONTROLLED:
FIELD LOCATE
SYSTEM CONTROLLER
B
A
GND
LO
N
GND
B A
C N
E T
M S
T P
L
IN
K
GND
U S
B H
O S
T E
T H
E R
N E
T
N
T W
O R
K
E T
H E
R N
T
N
T
W O
R K
B
A C
N E
T R
S -2
IO
IO
I
LINK 2
SC TRANE
MODEM IOIOI
1 2
A B
LON
A B
LON
LINK 1
LINK 1
LINK 2
ADDRESS
L1 L2 MODEM
LINK
ACT
LON
TX
RX
SERVICE
STATUS
TX
RX
IMCIOIOI 1 2
SERVICE TOOL
B A
C N
E T
M S
T P
L
IN
K
M O
D E
M
INSTALL BACNET TERMINATOR AT THE
BEGINNING AND AT THE END OF THIS
LINK.
INSTALL BACNET
TERMINATOR AND
CONNECT TO POWER
INSTALL 105 OHM RESISTOR AT THE
BEGINNING AND AT THE END OF THIS LINK.
24 VDC
GND
IM
C
24 VDC
GND
IM
C
GND
GND
24 VAC
24 VACO
U
T X
F M
R
NOT USED
MSTP1
A
SEE RISER WHT
BLK
SHLD
BLU
GRN
TBTBACNET TERMINATOR
NOT USED
NOT USED
NOT USED
M
CAT5 TO OWNER'S LAN
NOT USED
CON - 1 +
IMC
- IMCIMC
VDC
VDC
IMC
PM014 TRANE
PM - 1
XFMR
VAC
OUT
VAC
SFT - 1
TBT - 2
LINK 1
A
GRN
ENC - 4
TX - 2
24 VAC
HE - 1, TEH - 3 2 TRANE X1379044401 3% ROOM RH SENS, TEM P
TE - 1 1 TRANE 4190-1046 TEM P SENS, AVG, BALCO, 22FT
TE - 2 1 TRANE 41901133 TEM P SENS, DUCT/ IMM , THERM 6 IN
TEH - 1, TEH - 2 2 TRANE 4190-7020 3% DUCT RH SENS, TEM P
DA - 1, DA - 2 2 BELIM O AF24-SR US ACT PROP 24VAC SR 133IN-LB
CS - 1 1 KELE RIBXGA CUR SW, 0.75-150A, SPLIT, NO
DPS - 1 1 KELE P32AC-2 DIFF PRES SW, 0.05-5 IN WC
R - Y1, R - 4 2 KELE RIBU2C RLY DPDT, LED, 10-30 VAC/DC/120 VAC
R - Y2 1 KELE RIBU1C RLY SPDT, LED, 10-30 VAC/DC/120 VAC
TE - 17 1 KELE ST-M P3-X25 STRAP-ON 10K NTC THERM ISTOR
BILL OF M ATERIALS
AHU-1 FLOW DIAGRAM
6NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
AHU - 1
RA
SAOA
C
DX
FILTER
N.C.
N.O.
7E
DA - 1
E
DA - 2
D 7
DPS - 1
H L
ACU - 1
D
R - Y1
COOL 1
R
D
R - Y2
COOL 2
R
INTLK
SD - 1
INTLK
SD - 2
1 EXISTING SMOKE DETECTORS ARE HARDWIRED TO FAN STARTER FOR SHUTDOWN.
D
D 7
TEH - 1
D
D 7
TEH - 2
D 7
TE - 1
D 7
TE - 2
7D
S/S
R - 4
D 7
113STS
CS - 1
STARTER HUM - 1
3 EXISTING HUMIDIFIER INTERLOCK/SAFETY CONTROLS ARE EXISTING (NOT SHOWN).
D 7
HE - 1
SPACE HUMIDITY SENSOR
OPERATIONS RM. 109
SEQUENCE OF OPERATION:
AIR HANDLING UNITS AHU-1 & AHU-2:
AHU-1 & 2 SERVE THE OPERATIONS AREA AND ARE OPERATED ON A 24 HOUR SCHEDULE. ONLY ONE AIR HANDLING UNIT SHALL OPERATE, AND THE NON-OPERATING UNIT SHALL SERVE AS A BACKUP. THE BACKUP UNIT SHALL BE STARTED AUTOMATICALLY UPON FAILURE OF THE OTHER UNIT. AHU-1 & 2 SHALL BE PROGRAMMED TO ALTERNATE TO MAINTAIN EQUAL RUN TIME. THE SUPPLY AIR FAN SHALL RUN CONTINUOUSLY. A SUPPLY AIR TEMPERATURE SENSOR SHALL STAGE THE AIR COOLED CONDENSING UNIT (ACU) TO MAINTAIN 55 DEG. F DISCHARGE AIR TEMPERATURE. THE SUPPLY AIR TEMPERATURE SHALL BE RESET TO SATISFY THE ROOM TEMPERATURE SENSOR WITH THE MAXIMUM COOLING DEMAND. AN OUTSIDE AIR ECONOMIZER CYCLE SHALL BE PROVIDED WITH COMPARATIVE ENTHALPY CONTROL. A MIXED AIR TEMPERATURE SENSOR SHALL MODULATE THE OUTSIDE AND RETURN AIR DAMPERS DURING THE ECONOMIZER CYCLE. MINIMUM OUTSIDE AIR SHALL BE PROVIDED WHEN THE UNIT IS NOT IN THE ECONOMIZER CYCLE. HUMIDITY SHALL BE CONTROLLED BY THE SPACE HUMIDITY SENSOR.
HEATING IS PROVIDED BY INDIVIDUAL ELECTRIC DUCT HEATERS (EDH). SMOKE DETECTORS IN THE SUPPLY AND RETURN AIR DUCTWORK SHALL DE-ENERGIZE THE SUPPLY AIR FAN UPON SENSING SMOKE. UPON LOSS OF COMMERCIAL POWER, THE AIR HANDLING UNIT SHALL BE PROGRAMMED FOR A TIMED DELAY RESTART. ELECTRIC
DUCT HEATER EDH-2 SHALL NOT OPERATE ON EMERGENCY POWER.
HUMIDIFIER:
THE HUMIDIFIER SHALL NOT BE ALLOWED TO OPERATE UNLESS THE AIR HANDLING UNIT SUPPLY AIR FAN IS IN OPERATION. AN AIRFLOW SWITCH SHALL DE-ENERGIZE THE HUMIDIFIER UPON LOSS OF AIRFLOW. THE STEAM SOLENOID VALARE INTERLOCKED TO OPEN WHEN THE CORRESPONDING AIR HANDLING UNIT IS IN OPERATION. THE SPACE HUMIDITY SENSOR SHALL MODULATR THE HUMIDIFIER. WHEN THE HUMIDIFIER IS ENERGIZED, THE SUPPLY AIR TEMPERATURE SHALL BE RESET TO 65 DEG. F. WHEN THE HUMIDIFIER IS DE-ENERGIZED, SUPPLY AIR TEMPERATURE SHALL BE SET BACK TO 55 DEG. F.A SIGNAL FROM THE DUCT MOUNTED HIGH LIMIT HUMIDITY
SENSOR SHALL DE-ENERGIZE THE HUMIDIFIER.
D7
TE - 17
D 8
TEH - 3
D
DATA ROOM
TEMP/HUMIDITY SENSOR
D 7
CS - 2
AHU-1 UC600-1 WIRING DETAIL
7NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
TAG QTY VENDOR PART NO DESCRIPTION
UC600 - 1 1 TRANE BM UC600AAA0100011UC600 CONTROLLER, FRAM E M OUNT
BILL OF M ATERIALS
UC600 - 1
LOCATION:
SYSTEM
CONTROLLED:
AHU-1
IMC IMC
P1
MBUS
TX
RX
SERVICE
TRANEUC600
ADDRESS
BO1 BO2 BO3 BO4
UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8
VAC
VAC
VAC
MBUS VDC LINK IMC
VDC
AO3
UI11
AO2
UI10
AO1
UI9
AO6
UI14
AO5
UI13
AO4
UI12
BO3BO2BO1 BO4
IMC
LINK
ACT
x100 x10 x1
SERVICE TOOL
UI8
P I1
UI7
UI6
UI5
UI4
UI3
UI2
UI1
LI
N
K
V D
C
IM
C
LI
N K
V A
C
+24
V D
C
-24
V A
C X
F R
M
M B
U S
AO2/UI10
AO1/UI9
BO4
BO3
BO2
BO1
E T
H E
R N
E T
N E
T W
O R
K
AO6/UI14
AO5/UI13
AO4/UI12
AO3/UI11
1ADDRESS
BRN
BRN
SHLD
D
CS - 2 ACU -1 STATUS
A
WHT
BLK
SHLD
D
CS - 1 SUPPLY FAN STATUS
H
WHT
BLK
SHLD
D
TE - 1 MIXED AIR TEMP (BALCO)
G
WHT
BLK
SHLD
D
DPS - 1 FILTER STATUS
E
WHT
BLK
SHLD
D
TEH - 2 OUTSIDE AIR TEMPERATURE
E
GRN
RED
SHLD
D
TEH - 2 OUTSIDE AIR HUMIDITY
E
WHT
BLK
SHLD
D
TEH - 1 RETURN AIR TEMPERATURE
E
GRN
RED
SHLD
D
TEH - 1 RETURN AIR HUMIDITY
MSTP1
A
SEE RISER WHT
BLK
MSTP1
A
SEE RISER WHT
BLKSHLD
TX - 1
24VAC120 VAC
BY ESC
NOT USED
C
WHT
BLK
SHLD
D
TE - 2 DISCHARGE AIR TEMP
B
WHT
BLK
SHLD
D
HE - 1 SPACE HUMIDITY SENSOR (4-20 MA)
WHT
BLK
SHLD
175 GENERATOR RUN STATUS
WHT
BLK
SHLD
D
TE - 17 CIRCUIT 1 SUCTION TEMPERATURE
WHT
BLK
SHLDRED
E
DA - 1 (F/17); DA - 2 (F/17)
B
WHT
GRN
SHLD
D
R - Y2 COOLING STAGE 2
A
RED
BLK
SHLD
D
R - Y1 COOLING STAGE 1 & LLSV
WHT
BLK
SHLD
D
R - 4 SUPPLY FAN START/STOP
GRN 1
TYPICAL FOR 1
(AHU-1)
1 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE
DEVICE INSTALLATION LITERATURE.
OA/RA DAMPERS
AHU - 1
LOC
XM30 - 1
LOC
XM
AHU - 1
XM32 - 2
LOC
XM
XM 30 - 1 1 TRANE X13651537010 4 POINT UI/AO EXPANSION M ODULE
BILL OF M ATERIALSTYPICAL FOR 1
(AHU - 1)
U I/A
O
IM
C
IM
C
+ IM
C
24 V D
C
IM
C
T X
R X
S E
R V
IC
E
T R A N E
X M
A D
D R
E S
S
UI 4
UI 3
UI 2
UI 1
XM30 - 1
LOCATION:
SYSTEM
CONTROLLED:
AHU - 1
1ADDRESS
B
BLK
WHT
SHLD
D
TEH - 3 DATA ROOM HUMIDITY
B
BLK
WHT
SHLD
D
TEH - 3 DATA ROOM TEMPERATURE
COMM COMM LINK FROM UC600
COMM EXP COMM TO XM32 - 2
AHU - 1 XM30 - 1 WIRING DETAIL
8NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
CRAC UNIT #2 FAILURE
CRAC UNIT #1 FAILURE
XM 32 - 2 1 TRANE X13651563010 4 POINT BO EXPANSION M ODULE
BILL OF M ATERIALSTYPICAL FOR 1
(AHU - 1)
XM32 - 2
LOCATION:
SYSTEM
CONTROLLED:
AHU - 1
2ADDRESS
IM
C
IM
C
IM
C
T X
R X
S E
R V
IC
E
T R A N E
X M
A D
D R
E S
S
C
NC
NO
+ IM
C
24 V D
C
C
NC
NO
C
NC
NO
C
NC
NO
B O
B
O
B O
B
O
B O
B
O
B O
B
O
COMM EXP COMM FROM XM30 - 1
AHU - 1 XM32 - 2 WIRING DETAIL
9NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
R - 2
R - 1
TX - 18
R - 1
1 2CRAC-1
R - 2
1 2CRAC-2
TE - 1 1 TRANE 4190-1046 TEM P SENS, AVG, BALCO, 22FT
TE - 2 1 TRANE 41901133 TEM P SENS, DUCT/ IM M , THERM 6 IN
TEH - 1, TEH - 2 2 TRANE 4190-7020 3% DUCT RH SENS, TEM P
DA - 1, DA - 2 2 BELIM O AF24-SR US ACT PROP 24VAC SR 133IN-LB
CS - 1 1 KELE RIBXGA CUR SW, 0.75-150A, SPLIT, NO
DPS - 1 1 KELE P32AC-2 DIFF PRES SW, 0.05-5 IN WC
R - Y1, R - 4 2 KELE RIBU2C RLY DPDT, LED, 10-30 VAC/DC/120 VAC
R - Y2 1 KELE RIBU1C RLY SPDT, LED, 10-30 VAC/DC/120 VAC
TE - 19 1 KELE ST-M P3-X25 STRAP-ON 10K NTC THERM ISTOR
BILL OF M ATERIALS
AHU-2 FLOW DIAGRAM
10NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
AHU - 2
RA
SAOA
C
DX
FILTER
N.C.
N.O.
11E
DA - 1
E
DA - 2
D 11
DPS - 1
H L
ACU - 1
D
R - Y1
COOL 1
R
D
R - Y2
COOL 2
R
INTLK
SD - 1
INTLK
SD - 2
1 EXISTING SMOKE DETECTORS ARE HARDWIRED TO FAN STARTER FOR SHUTDOWN.
2 CONNECT TO CONTACTS OF EXISTING STATUS RELAY.
D
D 11
TEH - 1
D
D 11
TEH - 2
D 11
TE - 1
D 11
TE - 2
11D
S/S
R - 4
D 11
142STS
CS - 1
STARTER HUM - 1
3 EXISTING HUMIDIFIER INTERLOCK/SAFETY CONTROLS ARE EXISTING (NOT SHOWN).
D11
TE - 19
D 11
CS - 3
AHU-2 UC600-2 WIRING DETAIL
11NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
TAG QTY VENDOR PART NO DESCRIPTION
UC600 - 2 1 TRANE BM UC600AAA0100011UC600 CONTROLLER, FRAM E M OUNT
BILL OF M ATERIALS
UC600 - 2
LOCATION:
SYSTEM
CONTROLLED:
AHU-2
IMC IMC
P1
MBUS
TX
RX
SERVICE
TRANEUC600
ADDRESS
BO1 BO2 BO3 BO4
UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8
VAC
VAC
VAC
MBUS VDC LINK IMC
VDC
AO3
UI11
AO2
UI10
AO1
UI9
AO6
UI14
AO5
UI13
AO4
UI12
BO3BO2BO1 BO4
IMC
LINK
ACT
x100 x10 x1
SERVICE TOOL
UI8
P I1
UI7
UI6
UI5
UI4
UI3
UI2
UI1
LI
N
K
V D
C
IM
C
LI
N K
V A
C
+24
V D
C
-24
V A
C X
F R
M
M B
U S
AO2/UI10
AO1/UI9
BO4
BO3
BO2
BO1
E T
H E
R N
E T
N E
T W
O R
K
AO6/UI14
AO5/UI13
AO4/UI12
AO3/UI11
2ADDRESS
BRN
BRN
SHLD
D
CS - 3 ACU -2 STATUS
A
WHT
BLK
SHLD
D
CS - 1 SUPPLY FAN STATUS
H
WHT
BLK
SHLD
D
TE - 1 MIXED AIR TEMP (BALCO)
G
WHT
BLK
SHLD
D
DPS - 1 FILTER STATUS
E
WHT
BLK
SHLD
D
TEH - 2 OUTSIDE AIR TEMPERATURE
E
GRN
RED
SHLD
D
TEH - 2 OUTSIDE AIR HUMIDITY
E
WHT
BLK
SHLD
D
TEH - 1 RETURN AIR TEMPERATURE
E
GRN
RED
SHLD
D
TEH - 1 RETURN AIR HUMIDITY
MSTP1
A
SEE RISER WHT
BLK
MSTP1
A
SEE RISER WHT
BLKSHLD
NOT USED
C
WHT
BLK
SHLD
D
TE - 2 DISCHARGE AIR TEMP
WHT
BLK
SHLD
D
TE - 19 CIRCUIT 1 SUCTION TEMPERATURE
WHT
BLK
SHLDRED
E
DA - 1 (F/17); DA - 2 (F/17)
B
WHT
GRN
SHLD
D
R - Y2 COOLING STAGE 2
RED
BLK
SHLD
D
R - Y1 COOLING STAGE 1 & LLSV
WHT
BLK
SHLD
D
R - 4 SUPPLY FAN START/STOP
GRN 1
TYPICAL FOR 1
(AHU-2)
1 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE
DEVICE INSTALLATION LITERATURE.
OA/RA DAMPERS
TX - 5
24VAC120 VAC
BY ESC
TE - 1 1 TRANE 4190-1046 TEMP SENS, AVG, BALCO, 22FT
TE - 2, TE - 3, TE - 21 3 TRANE 41901133 TEMP SENS, DUCT/IM M , THERM 6 IN
DA - 1, DA - 2 2 BELIMO AF24-SR US ACT PROP 24VAC SR 133IN-LB
CS - 1 1 KELE RIBXGA CUR SW, 0.75-150A, SPLIT, NO
DPS - 1 1 KELE P32AC-2 DIFF PRES SW, 0.05-5 IN WC
R - Y1, R - 4 2 KELE RIBU2C RLY DPDT, LED, 10-30 VAC/DC/120 VAC
R - Y2 1 KELE RIBU1C RLY SPDT, LED, 10-30 VAC/DC/120 VAC
TE - 22 1 KELE ST-M P3-X25 STRAP-ON 10K NTC THERM ISTOR
BILL OF M ATERIALS
AHU-3 FLOW DIAGRAM
12NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
AHU - 3
RA
SAOA
C
DX
FILTER
N.C.
N.O.
13E
DA - 1
E
DA - 2
D 13
DPS - 1
H L
ACU - 1
D
R - Y1
COOL 1
R
INTLK
SD - 1
INTLK
SD - 2
1 EXISTING SMOKE DETECTORS ARE HARDWIRED TO FAN STARTER FOR SHUTDOWN.
2 CONNECT TO CONTACTS OF EXISTING STATUS RELAY.
D 13
TE - 1
D 13
TE - 2
13D
S/S
R - 4
D 13
171STS
CS - 1
STARTER
D 13
TE - 3
SEQUENCE OF OPERATION:
AIR HANDLING UNIT AHU-3:
AHU-3 SERVES THE ADMINISTRATION AREA AND OPERATES ON AN 8 HOUR SCHEDULE WITH NIGHT SETBACK. THE
OPERATION OF AHU-3 IS SIMILAR TO AHU-1 AND AHU-2 WITH THE FOLLOWING EXCEPTIONS:
(1) OUTSIDE AIR ECONOMIZER CYCLE IS CONTROLLED BY OUTSIDE AIR TEMPERATURE.
(2) NO HUMIDITY CONTROL.
AHU-3, ACU-3 AND ASSOCIATED ELECTRIC DUCT HEATERS SHALL NOT OPERATE ON EMERGENCY POWER. UPON RESTORATION OF COMMERCIAL POWER, AHU-3 ACU-3 AND ASSOCIATED ELECTRIC DUCT HEATERS SHALL RETURN TO NORMAL OPERATING MODE. THE AIR HANDLING UNIT SHALL BE PROGRAMMED FOR A TIMED DELAY RESTART.
D 13
TE - 21
D13
TE - 22
D
R - Y2
COOL 2
R
D 13
CS - 4
AHU-3 UC600-3 WIRING DETAIL
13NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
TAG QTY VENDOR PART NO DESCRIPTION
ENC - 2 1 TRANE X13651552010 ENC, TRACER UC LARGE, 120 VAC OUTLET
UC600 - 3 1 TRANE BM UC600AAA0100011UC600 CONTROLLER, FRAM E M OUNT
BILL OF M ATERIALS
UC600 - 3
LOCATION:
SYSTEM
CONTROLLED:
AHU-3
IMC IMC
P1
MBUS
TX
RX
SERVICE
TRANEUC600
ADDRESS
BO1 BO2 BO3 BO4
UI1 UI2 UI3 UI4 UI5 UI6 UI7 UI8
VAC
VAC
VAC
MBUS VDC LINK IMC
VDC
AO3
UI11
AO2
UI10
AO1
UI9
AO6
UI14
AO5
UI13
AO4
UI12
BO3BO2BO1 BO4
IMC
LINK
ACT
x100 x10 x1
SERVICE TOOL
UI8
P I1
UI7
UI6
UI5
UI4
UI3
UI2
UI1
LI
N
K
V D
C
IM
C
LI
N K
V A
C
+24
V D
C
-24
V A
C X
F R
M
M B
U S
AO3/UI11
AO2/UI10
AO1/UI9
BO4
BO3
BO2
BO1
E T
H E
R N
E T
N E
T W
O R
K
AO6/UI14
AO5/UI13
AO4/UI12
3ADDRESS
BRN
BRN
SHLD
D
CS - 4 ACU - 3 STATUS
A
WHT
BLK
SHLD
D
CS - 1 SUPPLY FAN STATUS
H
WHT
BLK
SHLD
D
TE - 1 MIXED AIR TEMP (BALCO)
G
WHT
BLK
SHLD
D
DPS - 1 FILTER STATUS
WHT
BLK
SHLD
D
TE - 3 OUTSIDE AIR TEMP
MSTP1
A
SEE RISER WHT
BLK
MSTP1
A
SEE RISER WHT
BLKSHLD
TX - 6
24VAC120 VAC
BY ESC
NOT USED
C
WHT
BLK
SHLD
D
TE - 2 DISCHARGE AIR TEMP
WHT
BLK
SHLD
D
TE - 21 RETURN AIR TEMPERATURE
WHT
BLK
SHLD
D
TE - 22 SUCTION TEMPERATURE
WHT
BLK
SHLDRED
E
DA - 1 (F/17); DA - 2 (F/17)
WHT
BLK
SHLD
D
R - Y2 COOLING STAGE 2
A
WHT
BLK
SHLD
D
R - Y1 COOLING STAGE 1 & LLSV
WHT
BLK
SHLD
D
R - 4 SUPPLY FAN START/STOP
ENC - 2
GRN 1
TYPICAL FOR 1
(AHU-3)
1 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE
DEVICE INSTALLATION LITERATURE.
OA/RA DAMPERS
CONDENSING UNIT WIRING
14NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
Y2
R
Y1
C
CU
R - Y2
R - Y1
LLSV
ORG
RED
YEL
PUR
EDH 1 - 3, 9 - 10 UC210 WIRING DETAIL
15NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
TAG QTY VENDOR PART NO DESCRIPTION
EDH - 1 5 TRANE X13651610010 UC210 VAV, FLOW SENS, M TG
TE - 32 5 TRANE 41901129 TEM P SENS, DUCT, THERM , 4 IN
TE - 33 5 TRANE X1351152701 TEM P SENS ZONE THERM O/U SP
BILL OF M ATERIALS
TYPICAL FOR 5
(EDH - 1, EDH - 2, EDH - 3, EDH - 9,
EDH - 10)
1 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE
DEVICE INSTALLATION LITERATURE.
EDH
SUPPLY
AIR
AIR
FLOW
VCEF
GND
24VAC
GND
24VAC
BO1
24VAC
BO2
24VAC
BO3
AO1
GND
AO2
GND
AI1
GND
AI2
AI3
GND
BI1
UI1
UI2
GND
GND
LI
N
K
LI
N
K
LI
N
K
LI
N
K
V
D C
G N
D
IM
C
IM
C
V
D C
G N
D
IM
C
IM
C x10 x10 x1
ADDRESS
J15
J16
J17
J18
J19
J20
J21
J22
J23
J26
J27
J28
J29
J1
J2
J3
J4
J5
CLS
OPN
24VAC
GND
24VAC
GND
EDH - 1
LOCATION:
SYSTEM
CONTROLLED:
EDH - 1
24 VAC
BY ESC
GRN
GND1
WHT325HEAT SCR SIGNAL
D BLKTAPE SHLD
C
WHT
TAPE SHLD
326 TE - 33 ZONE SENSOR TEMPERATURE
EBLK
RED
D
WHT
TAPE SHLD
327 TE - 32 DISCHARGE AIR TEMPERATURE
DBLK
COMM
A
SEE COMM RISER PAGE WHT
BLK
COMM
A
SEE COMM RISER PAGE WHT
BLK
SHLD
FROM TX-3 & TX-4
SEE COMM RISER PAGE
D
D 15
TE - 32
E 15
TE - 33
ZONE SENSOR
SEQUENCE OF OPERATION:
WHEN SPACE HEATING IS REQUIRED AS DETERMINED BY THE
ZONE THERMOSTAT THE CONTROLLER SHALL MODULATE THE
HEAT TO CONTROL THE DISCHARGE AIR TEMPERATURE EQUAL
TO THE DISCHARGE AIR HEATING SETPOINT. (100 DEG. ADJ.)
EDH 4 - 8 UC210 WIRING DETAIL
16NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
TAG QTY VENDOR PART NO DESCRIPTION
EDH - 4 5 TRANE X13651610010 UC210 VAV, FLOW SENS, M TG
TE - 30 5 TRANE 41901129 TEM P SENS, DUCT, THERM , 4 IN
TE - 31 5 TRANE X1351152701 TEM P SENS ZONE THERM O/U SP
BILL OF M ATERIALS
TYPICAL FOR 5
(EDH - 4, EDH - 8, EDH - 7, EDH - 6,
EDH - 5)
1 DEVICE MUST BE GROUNDED WITH FACTORY PROVIDED GROUND WIRE AS DETAILED IN THE
DEVICE INSTALLATION LITERATURE.
EDH
SUPPLY
AIR
AIR
FLOW
GND
24VAC
GND
24VAC
BO1
24VAC
BO2
24VAC
BO3
AO1
GND
AO2
GND
AI1
GND
AI2
AI3
GND
BI1
UI1
UI2
GND
GND
LI
N
K
LI
N
K
LI
N
K
LI
N
K
V
D C
G N
D
IM
C
IM
C
V
D C
G N
D
IM
C
IM
C x10 x10 x1
ADDRESS
J15
J16
J17
J18
J19
J20
J21
J22
J23
J26
J27
J28
J29
J1
J2
J3
J4
J5
CLS
OPN
24VAC
GND
24VAC
GND
EDH - 4
LOCATION:
SYSTEM
CONTROLLED:
EDH - 4
24 VAC
BY ESC
GRN
GND1
WHT305HEAT STAGE 2
D BLKTAPE SHLD
WHT306HEAT STAGE 1
D
BLK
TAPE SHLD
C
WHT
TAPE SHLD
309 TE - 31 ZONE SENSOR TEMPERATURE
EBLK
RED
D
WHT
TAPE SHLD
310 TE - 30 DISCHARGE AIR TEMPERATURE
DBLK
COMM
A
SEE COMM RISER PAGE WHT
BLK
COMM
A
SEE COMM RISER PAGE WHT
BLK
SHLD
D 16
TE - 30
D
D
E 16
TE - 31
ZONE SENSOR
2 CONTROLLER OUTPUTS SWITCH COMMON SIDE OF CIRCUIT.
SEQUENCE OF OPERATION:
WHEN SPACE HEATING IS REQUIRED AS DETERMINED BY THE
ZONE THERMOSTAT THE CONTROLLER SHALL STAGE THE
HEAT TO CONTROL THE DISCHARGE AIR TEMPERATURE EQUAL
TO THE DISCHARGE AIR HEATING SETPOINT. (100 DEG. ADJ.)
FROM TX-3 & TX-4
SEE COMM RISER PAGE
DETAIL SHEET #1
17NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
CURRENT OPERATED SWITCH, SPILT-CORE, ADJ. TRIP,
LEDS
RIBXGA
KELE
A
UNK
UNK
STATUS
COMMON
WHT
BLK
SENSOR ZONE RH +/- 3% AND TEMP
X1379044401
TRANE
B
- GRN
RED +24VDC
4-20mA SIGNAL
T T
WHT
BLK
TEMP SIGNAL
TEMP COMMON
TRANE
ZONE SENSOR THERM + SETPOINT + OCC/UNOC
C
WHT
BLK
ZONE TEMP
COMMON
3 RED SETPOINT
X1351152701
OCC
SETPOINT
UNOCC
SENSOR TEMP 4" DUCT THERM
41901129
TRANE
D
RED WHT TEMP
GRN BLK COMMON
SENSOR DUCT RH +/- 3% AND TEMP
4190-7020
TRANE
E
TT
GRN
RED
GRN 4-20mA SIGNAL
+ 24VDC
BLK
WHT
COMMON
TEMP
ACTUATORS MOD, 24VAC/DC, 133 IN-LB
BELIMO
AF24-SR US
F
HOT (2)
COM (1)
RED
BLK
INPUT (3) WHT
24 VAC
COMMON
2-10VDC SIGNAL
OUTPUT (5) NOT USED
SWITCH AIR DP P32 0.05-5"
P32AC-2
KELE
G
Y
B
R BLK COMMON
WHT NO - CLOSE ON RISE
HIGH
PRESSURE
LOW
PRESSURE
SIDEFRONT
SENSOR TEMP DUCT 22 FT. AVG BALCO
4190-1046
TRANE
H
BLK WHT TEMP
BLK BLK COMMON
DETAIL SHEET #2
18NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
DUAL DPDT RELAY
KELE
RIBU2C
A
WHT/YEL
ORN
YEL
BLU
WHT/BLU
BLK
BLK
WHT
BRN
PUR
GRY NOT USED
WHT
BLK
WHT
NOT USED
10-30VAC/DC
CONTACT #1, NO
CONTACT #1, COMMON
CONTACT #2, NO
CONTACT #2, COMMON
WHT/BLK NOT USED
10-30VAC/DC COMMON
WHT/PUR
GRY/WHT
BLK
WHT/RED
R E
LA
Y
WHT 10-30VAC/DC
NOT USED
10-30VAC/DC COMMON
R E
LA
Y
SPDT RELAY
KELE
RIBU1C
B
WHT/YEL
ORN
YEL
COIL, COMMON
BLU
CONTACTS, NO
CONTACTS, COM
CONTACTS, NC
WHT/BLK
WHT/BLU
COIL, 120VAC
COIL 10-30VAC/VDC
NOT USED
WHT
RED
BLK
BLK
WHT CONTROLLER OUTPUT
CONTROLLER COMMON
DEVICE
DEVICE
DEVICE
SENSOR TEMP 6" DUCT/IMM THERM
41901133
TRANE
C
RED WHT TEMP
GRN BLK COMMON
BILL OF MATERIALS
19NOAA_CHS.AXD
K KOEHN J VAN SISE
INSTALLATION DRAWING 1/6/2016 JVS
AS-BUILT DRAWING 2/24/2016 JP
SALESPERSON:
FILE
NAME:
NUM. REVISION DATE: BY:
DESIGNED BY: CHECKED BY:
NOAA WEATHER STATION
CHARLESTON, SC
PROJECT:
803-936-4700
WEST COLUMBIA, SC 29169
111 LOTT COURT
COLUMBIA MAIN OFFICE
DWG:
PROJECT ID:CID: PID:
TAG PREFIX QTY VENDOR PART NO DESCRIPTION
TE 3 TRANE 4190-1046 TEMP SENS, AVG, BALCO, 22FT
TEH 4 TRANE 4190-7020 3% DUCT RH SENS, TEMP
TE 10 TRANE 41901129 TEMP SENS, DUCT, THERM, 4 IN
TE 5 TRANE 41901133 TEMP SENS, DUCT/IMM, THERM 6 IN
SFT 1 TRANE BMCF000AAA0AE00 TRACER SC15 SOFTWARE
SC 1 TRANE BMSC000AAA01100 TRACER SC
UC600 3 TRANE BMUC600AAA0100011 UC600 CONTROLLER, FRAME MOUNT
TE 10 TRANE X1351152701 TEMP SENS ZONE THERM O/U SP
TBT 1 TRANE X13651524-01 TRANE BACNET TERMINATOR (2/PKG)
XM30 1 TRANE X13651537010 4 POINT UI/AO EXPANSION MODULE
ENC 1 TRANE X13651552010 ENC, TRACER UC LARGE, 120 VAC OUTLET
ENC 1 TRANE X13651559010 ENC, TRACER UC MEDIUM, 120 VAC OUTLET
XM32 1 TRANE X13651563010 4 POINT BO EXPANSION MODULE
EDH 10 TRANE X13651610010 UC210 VAV, FLOW SENS, MTG
HE, TEH 2 TRANE X1379044401 3% ROOM RH SENS, TEMP
DA 6 BELIMO AF24-SR US ACT PROP 24VAC SR 133IN-LB
DPS 3 KELE P32AC-2 DIFF PRES SW, 0.05-5 IN WC
R 3 KELE RIBU1C RLY SPDT, LED, 10-30 VAC/DC/120 VAC
R 6 KELE RIBU2C RLY DPDT, LED, 10-30 VAC/DC/120 VAC
CS 3 KELE RIBXGA CUR SW, 0.75-150A, SPLIT, NO
TE 3 KELE ST-MP3-X25 STRAP-ON 10K NTC THERMISTOR
BILL OF MATERIALS