This document is a detailed engineering layout drawing for a Jensen Precast vault assembly (Part Number 200061707) designed for Puget Sound Energy (PSE) specification 7663200. The vault is a precast concrete structure measuring 5078x44 inches, with two primary components: a rectangular bottom section knockout sump (Part Number 2000617041, weighing 6,716.878 lbs) and a slab top (Part Number 2000617061, weighing 3,218.276 lbs). The total assembly weighs approximately 9,933.61 lbs and is designed for a 5.0' burial depth, meeting ASTM C857 and ACI 318 standards with an AASHTO HS20-44 loading specification. Key features include a 36x72 galvanized steel H-20 rated hatch, multiple unistrut mounting points, ground rod knockouts, pulling irons, and utility markings, with each component labeled with manufacturer, date of manufacture, and weight. The design is currently not yet approved by the agency and requires further consultation with Jensen Precast for complete product information.

View the file

Other files

File Type Posted
Attachment 2 - Drawing.pdf PDF
Attachment 1 - Meak Solutions Quote.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ISO LAYOUT

BILL OF MATERIALS

WEIGHT (LBS)DESCRIPTIONPART NUMBERQTYITEM

6716.878Vault 5078x44 Rect. Bottom Section Knockout Sump20006170411

3218.276Vault 5078x13 Slab Top 3672"C20006170612

7.

id w

SHEET:

REV:

A-4

9/13/2021 10/17/2022MODIFIED:CREATED:

PART NUMBER: DRAWN BY:

DESCRIPTION:

Vault 5078 Layout Assembly

AGENCY SPEC:AGENCY:

DESIGN SPEC: LOADING SPEC:

BURY DEPTH:

WWW.JENSENPRECAST.COM

0.0' - 0.0' to Top

WATER LEVEL:

A-16 (AASHTO HS20-44)

5.0' APPROX. WEIGHT: 9933.61 Lbs

200061707 T.Larson

ASTM C857,ACI 318

©2022 Jensen Precast- All rights reserved.

All materials appearing as Jensen Precast documents and the like are proprietary work product and are protected under U.S. copyright and other laws.

Unless in conjunction with business conducted with Jensen Precast, any use of Jensen Precast work product without express, written consent is prohibited, and recipient is prohibited from distributing any and all work product to non-approved third parties under penalty of civil action.

LAYOUT REVIEW

DESIGN NOTES

■ DESIGNED TO MEET SPECIFICATIONS OF PUGENT SOUND ENERGY (PSE) 7663200.

NOT YET APPROVED BY AGENCY.

■ FOR COMPLETE DESIGN AND PRODUCT INFORMATION CONTACT JENSEN PRECAST.

CHANGE HISTORY

NO. DESCRIPTION DATE BY

1 DRAWING CREATED 3/29/2022 T.Larson

36x72 GALVANIZED STEEL HATCH:

H-20 RATED, SPRING ASSISTED,

180° CAPABLE, DIAMOND PLATE

STANDARD, TRAXPLATE OPTIONAL

EACH PIECE

LABELED WITH

MANUFACTURER,

DATE OF MANUFACTURE,

AND WEIGHT

PLAN VIEW

SECTION A-A SECTION B-B

PLAN VIEW

(SHOWING INSIDE FLOOR)

A

A

B B

7.

id w

SHEET:

REV:

A-4

9/13/2021 10/17/2022MODIFIED:CREATED:

PART NUMBER: DRAWN BY:

DESCRIPTION:

Vault 5078 Layout Assembly

AGENCY SPEC:AGENCY:

DESIGN SPEC: LOADING SPEC:

BURY DEPTH:

WWW.JENSENPRECAST.COM

0.0' - 0.0' to Top

WATER LEVEL:

A-16 (AASHTO HS20-44)

5.0' APPROX. WEIGHT: 9933.61 Lbs

200061707 T.Larson

ASTM C857,ACI 318

©2022 Jensen Precast- All rights reserved.

All materials appearing as Jensen Precast documents and the like are proprietary work product and are protected under U.S. copyright and other laws.

Unless in conjunction with business conducted with Jensen Precast, any use of Jensen Precast work product without express, written consent is prohibited, and recipient is prohibited from distributing any and all work product to non-approved third parties under penalty of civil action.

LAYOUT DRAWING

GRD

88"

60"

60"

12"

48"

70" 9"9"

11 3/8"

37 1/4"

11 3/8"

18"X24"

KNOCKOUT

2 EACH ON

ALL WALLS

13/16"x1-5/8"

UNISTRUT

1 EACH SIDE WALL

72" LONG

13/16"x1-5/8"

UNISTRUT

1 EACH SIDE WALL

24" LONG

13/16"x1-5/8"

UNISTRUT

1 EACH END WALL

36" LONG

Ø0.5" GALV

PULLING IRON (x4)

13"

13"

11"

18"

30"

16" 16" 26" 26" n1 1/2"

LIFT HOLE

1 EACH SIDE WALL

5" 50" 5"

60"

5" 78" 5"

88"

48"

21 1/2"

TYP.

35 1/2"

TYP.

32"

TYP.

18"

TYP.

n2" GROUND ROD

KNOCKOUT (x2) n12"x2.5"

SUMP

4"

1/2"x36" BRASS

GROUND INSERT

1 EACH ON

SIDE WALLS

WITH PROTECTIVE

CAPS

UTILITY MARKING

OF "POWER"

WITH 2 INCH

LETTER HEIGHT

Ø3/4" RECESSED

ZINC PLATED

THREADED INSERT

LIFTERS (x4)

55 1/2"

25 FT - #3

REBAR FOR

GROUNDING

13"

"GRD" LABELED

ADJACENT TO

GROUNDING

INSERTS