SECTION 21 13 17 Page 1
JOINT BASE LEWIS – McCHORD DESIGN STANDARDS
SECTION 21 13 17.00 10 - DRY PIPE SPRINKLER SYSTEM, FIRE PROTECTION
Design Requirements
a. The governing primary code document is UFC 3-600-01; the secondary governing code document is applicable chapters of the NFPA 13.
b. All designs shall be reviewed by the Joint Base Lewis-McChord Public
Works life safety systems manager and approved by Joint Base Lewis-
McChord Public Works. All new construction installations, remodel and retrofit work requires inspection and acceptance by the Joint Base
Lewis-McChord Public Works. All acceptance testing shall be coordinated with the Fire Prevention and Inspection Branch of the DES and the Joint
Base Lewis-McChord Emergency Command Center to ensure availability of personnel to support operational testing.
c. Final acceptance testing must be scheduled 7 to 10 days prior to day of testing.
d. New pipe schedule designed systems are not acceptable, all new systems shall be hydraulically designed.
e. Plastic pipe is only acceptable in residential occupancies. However, plastic pipe is discouraged for use in any application given the military environment it is subjected to, and is not allowed when exposed and subjected to physical damage.
f. Grooved joints and fittings shall not be installed in concealed locations. This applies to inaccessible locations like inside walls. It does not apply to accessible locations like above drop ceilings.
g. All system valves require tamper switches, excluding post indicator valves.
h. Back Flow Preventers require testing by a Washington State certified
BPA tester. The tester shall complete and submit the required Joint
Base Lewis-McChord BPA form linked to this design standard. The BPA shall be installed by a certified, licensed installer. Reduced pressure
BPA's are not acceptable. Flushing the BPA is required after installation. Acceptable backflow preventers are listed on the
Washington Dept. of Health approved backflow preventer list. The backflow preventer specific make, model, design, size, and approved installed orientation must match the approved list.
i. Residential sprinklers and intermediate level rack sprinklers shall be fast response type.
j. All designs shall be reviewed, approved, stamped, and signed by the
Fire Protection Specialist prior to submitting for government approval.
k. Preliminary and Final Acceptance Testing shall be witnessed by the Fire
Protection Specialist. The USACE representative and/or DPW representatives shall be invited to attend and witness, but are not required to be present.
l. The Joint Base Lewis-McChord Public Works Water and Sewer department shall be invited to witness all pipe flushing (above and below ground).
m. Underground pipe work will be performed by a State of Washington Level
U Certificate of Competency underground contractor IAW WAC 212-80-093.
n. All drain valves require plugs or caps downstream of the drain valve.
o. Sprinkler systems are required to have a dedicated water supply feed pipe from the water main. Tapping into the fire suppression system water main to supply the building with domestic water is not acceptable. Supplying the fire sprinkler system from the domestic water feed is not acceptable.
p. All as-built drawings, test certificates, maintenance and repair
SECTION 21 13 17 Page 2 manuals, and related system documentation shall be provided to JBLM
DPW.
q. Heat tape, heat cable, and heat tracing are not allowed for any application. All wet pipe systems including standpipes shall be in the interior of buildings and/or within heated enclosures.
r. Use only like materials on a sprinkler system, do not mix materials.
s. All metal pipe shall be a minimum of Schedule 40 regardless of CRR. Any pipe less than schedule 40 is not acceptable on JBLM.
t. All fire sprinkler system materials shall be domestically manufactured.
u. For dry pipe systems, install electric bell as secondary notification device.
v. The only color allowed for fire suppression pipe and related equipment is red.
w. For dry systems use belt-less and oil-less air compressors.
x. All fire sprinkler systems shall have line pressure gauges at riser for each system.
y. In new construction facilities, locate fire sprinkler risers in a separate riser room or mechanical room both having direct access from the exterior of the building, and located so it is accessible to DPW without entering secured areas. In renovation projects, locating a sprinkler riser inside a riser room is preferred, if the sprinkler riser is located in the open area of the building it must be enclosed inside a lockable cage to protect it from damage and tampering.
Bollards may also be necessary in warehouse facilities.
SECTION 21 13 17 Page 3
SECTION 21 13 17.00 10
DRY PIPE SPRINKLER SYSTEM, FIRE PROTECTION
05/19
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only. Unless a specific document version or date is indicated, use criteria from the most current reference as of the date of solicitation or if amended, date of solicitation amendment.
AMERICAN SOCIETY OF CIVIL ENGINEERS
ASCE 7 Minimum Design Loads for Buildings and Other
Structures
AMERICAN SOCIETY OF SANITARY ENGINEERING (ASSE)
ASSE 1015 Performance Requirements for Double Check
Backflow Prevention Assemblies and Double
Check Fire Protection Backflow Prevention
Assemblies
AMERICAN WATER WORKS ASSOCIATION (AWWA)
AWWA 10084 Standard Methods for the Examination of Water and Wastewater
AWWA B300 Hypochlorites
AWWA B301 Liquid Chlorine
AWWA C104/A21.4 Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for Water
AWWA C110/A21.10 Ductile-Iron and Gray-Iron Fittings for Water
AWWA C111/A21.11 Rubber-Gasket Joints for Ductile-Iron
Pressure Pipe and Fittings
AWWA C151/A21.51 Ductile-Iron Pipe, Centrifugally Cast, for
Water
AWWA C203 Coal-Tar Protective Coatings and Linings for
Steel Water Pipelines - Enamel and Tape -
Hot-Applied
AWWA C500 Metal-Seated Gate Valves for Water Supply
Service
AWWA C606 Grooved and Shouldered Joints
SECTION 21 13 17 Page 4
AWWA C651 Disinfecting Water Mains
AWWA C652 Disinfection of Water-Storage Facilities
ASME INTERNATIONAL (ASME)
ASME B16.1 Gray Iron Pipe Flanges and Flanges Fittings:
Classes 25, 125, and 250
ASME B16.11 Forged Fittings, Socket-Welding and Threaded
ASME B16.21 Nonmetallic Flat Gaskets for Pipe Flanges
ASME B16.39 Malleable Iron Threaded Pipe Unions: Classes
150, 250, and 300
ASME B16.4 Gray Iron Threaded Fittings: Classes 125 and
ASME B16.5 Pipe Flanges and Flanged Fittings: NPS 1/2
Through NPS 2
ASME B16.9 Factory-Made Wrought Steel Buttwelding
Fittings
ASME B18.2.2 Nuts for General Applications: machine Screw
Nuts, Hex, Square, Hex Flange, and Coupling
Nuts (Inch Series)
ASTM INTERNATIONAL (ASTM)
ASTM A 135/A 135M Standard Specification for Electric-
Resistance-Welded Steel Pipe
ASTM A 183 Standard Specification for Carbon Steel Track
Bolts and Nuts
ASTM A 193/A 193M Standard Specification for Alloy-Steel and
Stainless Steel Bolting for High Temperature or High Pressure Service and Other Special
Purpose Applications
ASTM A 449 Standard Specifications for Hex Cap Screws, Bolts, and Studs, Steel, Heat Treated, 120/105/90 ksi Minimum Tensile Strength, General Use
ASTM A 47/A 47M Standard Specification for Ferritic Malleable
Iron Castings
ASTM A 53/A 53M Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and
Seamless
ASTM A 536 Standard Specification for Ductile Iron
Castings
SECTION 21 13 17 Page 5
ASTM A 795/A 795M Standard Specification for Black and Hot-
Dipped Zinc-Coated (Galvanized) Welded and
Seamless Steel Pipe for Fire Protection Use
ASTM F 436 Standard Specification for Hardened Steel
Washers
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-301-01 Structural Engineering
UFC 3-310-04 Seismic Design of Buildings
UFC 3-600-01 Fire Protection Engineering for Facilities
UFC 3-601-02 Operations and Maintenance: Inspection, Testing, and Maintenance of Fire Protection
Systems
Joint Base Lewis - McChord
JBLM Design Standards http://www.lewis-Mcchord.army.mil/ designstandards/index1.htm
FM GLOBAL (FM)
FM P7825a Factory Mutual Research Approval Guide - Fire
Protection
FM P7825b Factory Mutual Research Approval Guide -
Electrical Equipment
FM APP GUIDE Approval Guide http://www.approvalguide.com/
MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
MSS SP-58 Pipe Hangers and Supports - Materials, Design, Manufacture, Selection, Application, and Installation.
MSS SP-71 Gray Iron Swing Check Valves, Flanged and
Threaded Ends
MSS SP-80 Bronze Gate, Globe, Angle and Check Valves
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 13 Installation of Sprinkler Systems
NFPA 13R Installation of Sprinkler Systems in
Residential Occupancies Up to and Including
Four Stories in Height
NFPA 24 Standard for the Installation of Private Fire
Service Mains and Their Appurtenances
SECTION 21 13 17 Page 6
NFPA 101 Life Safety Code
NFPA 291 Recommended Practice for Fire Flow Testing and Marking of Hydrants
NFPA 1963 Standard for Fire Hose Connections
NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES
(NICET)
NICET 1014-7 Program Detail Manual for Certification in the Field of Fire Protection Engineering
Technology (Field Code 003) Subfield of
Automatic Sprinkler System Layout
UNDERWRITERS LABORATORIES (UL)
UL 262 Gate Valves for Fire-Protection Service
UL 668 Hose Valves for Fire Protection Service
UL Directory A Building Materials Directory
UL Directory B Fire Protection Equipment Directory
INTERNATIONAL BUILDING CODES
IBC International Building Code
1.2 GENERAL REQUIREMENTS
a. Dry pipe sprinkler system shall be provided in areas indicated on the drawings or contained in the project's "Scope of Work" or "Statement of
Work". The sprinkler system shall provide fire sprinkler protection for the entire area. Except as modified herein, the system shall be designed and installed in accordance with UFC 3-600-01, JBLM Design Standards, NFPA 13, and NFPA 13R. Pipe sizes which are not indicated on the drawings shall be determined by hydraulic calculation. Gridded systems shall not be used. The Contractor shall design any portion of the sprinkler system that are not indicated on the drawings including locating sprinklers, piping, and equipment, and size piping and equipment when this information is not indicated on the drawings or is not specified herein.
The design of the sprinkler system shall be based on hydraulic calculations, and the other provisions specified herein.
b. Fire sprinkler system shall be a designated seismic system in accordance with ICC, IBC, and ASCE 7. Importance factor Ip shall be equal to 1.5.
Provide seismic protection for equipment in accordance with Section 26 05
48.00 10, UFC 3-600-01, JBLM Design Standards, N.F.P.A. #13, and IBC
2015. Provide special inspections in accordance with Section 01 45 35
CODE REQUIRED SPECIAL INSPECTIONS, STRUCTURAL OBSERVATIONS, TESTS AND
PROCEDURES. Provide designated seismic system certification for the Fire sprinkler system components listed in this section in accordance with
ASCE 7. Comply with all applicable Special Inspector of Record requirements of UFC 3-301-01.
SECTION 21 13 17 Page 7
c. All water discharged from the inspector's test valves and drains in addition to water discharged during hydrant flow testing and full forward flow testing of the backflow preventer are subject to compliance with
JBLM EPA issued Municipal Separate Storm Sewer (MS4) Permit and JBLM 200-
3 for requirements for dechlorinization.
1.2.1 Multistory Buildings
Provide floor control valve assemblies for each respective floor of the building. Each sprinkler system floor control valve assembly shall consist of a control valve, dry pipe valve, air maintenance device, Nitrogen
Generation System, check valve, pressure gauges, and a main drain valve.
1.2.2 Hydraulic Design
The system shall be hydraulically designed to discharge a minimum density over the hydraulically most demanding area indicated on the drawings. If design criteria is not provided on the drawings, the sprinkler system design shall be in accordance with UFC 3-600-01, NFPA 13, or NFPA 13R, whichever is more stringent. Hydraulic calculations shall be in accordance with the
Area/Density Method of NFPA 13. Water velocity in the piping shall not exceed 20 ft/s.
1.2.2.1 Hose Demand
An allowance for exterior hose streams shall be as indicated on the drawings. If hose stream demands are not provided on the drawings, the hose stream demands shall be in accordance with UFC 3-600-01 or NFPA 13, whichever is more stringent. Hose stream demands for Residential occupancy shall be 250 gpm. Hose stream demands shall be added to the sprinkler system demand at the fire hydrant shown on the drawings closest to the point where the water service enters the building or at the point of connection to the existing system, whichever is applicable. An allowance for interior hose stations shall be as indicated on the drawings and shall also be added to the sprinkler system demand.
1.2.2.2 Basis of Calculations
The design of the system shall be based upon a water supply with a static pressure and flow at the residual pressure indicated on the drawings or contained in the hydrant flow test report provided by the Fire Protection
Specialist. Water supply shall be presumed available at the point of connection to the existing system. Hydraulic calculations shall be based upon the Hazen-Williams formula with a "C" value of 120 for steel piping, 150 for copper tubing, 140 for new cement-lined ductile-iron piping, and 100 for existing underground piping. Additionally, hydraulic calculations shall be based on operation of the fire pump(s) provided in Section 21 30 00 FIRE
PUMPS.
1.2.3 Sprinkler Coverage
Sprinklers shall be uniformly spaced on branch lines. In buildings protected by automatic sprinklers, sprinklers shall provide coverage throughout 100 percent of the building. This includes, but is not limited to, telephone rooms, electrical equipment rooms, boiler rooms, switchgear rooms, elevator machine/mechanical rooms, transformer rooms, and other electrical and
SECTION 21 13 17 Page 8 mechanical spaces. Coverage per sprinkler shall be in accordance with NFPA
13, but shall not exceed 100 square feet for Extra Hazard or Storage occupancies, 130 square feet for Ordinary Hazard occupancies, and 225 square feet for Light Hazard occupancies. Exceptions are as follows:
1) Sprinklers may be omitted from small rooms which are exempted for specific occupancies in accordance with NFPA 101 and UFC 3-600-01.
1.2.4 System Volume Limitations
Where the volume of any individual system piping volume exceeds 500 gallons the dry pipe valve shall be provided with a quick-opening device. The maximum system capacity controlled by one dry pipe valve shall not exceed
750 gallons. The calculated volume of each system shall be indicated on the
Sprinkler System Shop Drawings adjacent to the riser detail.
1.3 COORDINATION OF TRADES
Piping offsets, fittings, and any other accessories required shall be furnished as required to provide a complete installation and to eliminate interference with other construction. Sprinklers shall be installed over and under ducts, piping and platforms when such equipment exceeding 48 inches in width. These obstructions can negatively affect or disrupt the sprinkler discharge pattern and coverage.
1.4 DELIVERY AND STORAGE
All equipment delivered and placed in storage shall be housed in a manner to preclude any damage from the weather, sunlight, humidity and temperature variations, dirt and dust, or other contaminants. Additionally, all pipes shall either be capped or plugged until installed.
1.5 FIELD MEASUREMENTS
The Contractor shall become familiar with all details of the work, verify all dimensions in the field, and shall advise the Contracting Officer of any discrepancy before performing the work.
1.6 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval information only. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
Shop drawings, manufacturer's catalog data, sway brace calculations, hydraulic calculations, preliminary system test procedures, final system test procedures, and contractor certifications, must be reviewed, approved, stamped, and signed by the Fire Protection Specialist prior to submitting for government approval per UFC 3-600-01.
SD-02 Shop Drawings
Shop Drawings; G
Submit two hard copies and one electronic (.pdf) version of the
Sprinkler System Shop Drawings, no later than 21 days prior to the
SECTION 21 13 17 Page 9 start of the Sprinkler System installation.
As-Built Drawings; G
As-built shop drawings, at least 14 days after completion of the
Final Tests. The Sprinkler System Drawings shall be updated to reflect as-built conditions after all related work is completed.
Provide electronic drawings in AutoCAD format on a CD.
SD-03 Product Data
Sway Brace Details and Calculations; G
Details and load calculations shall be provided for sizing of sway bracing.
Materials and Equipment; G
The data shall be highlighted to show model, size, options, etc., that are intended for consideration. Data shall be adequate to demonstrate compliance with all contract requirements. In addition, a complete table of contents that includes equipment description and model number shall be provided. Catalog data sheets shall also indicate U.L. Listing / FM approval and the country of manufacture.
Hydraulic Calculations; G
Hydraulic calculations, including a drawing showing hydraulic reference points and pipe segments.
Graphic Map; G
Graphic maps, include representation of the graphic map to be providing locations of all drains and valves.
Spare Parts; G
A stock of spare sprinklers and head wrenches in accordance with the quantities defined in NFPA 13 shall be provided in a spare sprinkler cabinet that resides at the sprinkler riser.
Preliminary Tests Procedures; G
Proposed procedures for Preliminary Tests shall be approved by the government at least 14 days prior to the proposed start of the tests. Proposed date and time to begin Preliminary Tests, shall be submitted with the Preliminary Tests Procedures. Contractor to coordinate all tests with Public Works, Fire Department, and
Contracting Officer.
Final Acceptance Test Procedures; G
Proposed procedures for Final Acceptance Test shall be approved by the government, no later than 14 days prior to the proposed start of the tests. Proposed date and time to begin Final Acceptance
Test, shall be submitted with the Final Acceptance Test Procedures.
Contractor to coordinate all tests with Public Works, Fire
SECTION 21 13 17 Page 10
Department, and Contracting Officer.
On-site Training; G
After final system acceptance testing has been approved by the government, propose an On-site Training schedule along with proposed date and time at least 14 days prior to the proposed start of On-site Training.
Fire Protection Specialist; G
The name and documentation of certification of the proposed Fire
Protection Specialists, no later than 14 days after the Notice to
Proceed and prior to the submittal of the sprinkler system drawings and hydraulic calculations.
Qualifications of Installer; G
The name and documentation of certification of the proposed
Sprinkler System Installer, concurrent with submittal of the Fire
Protection Specialist Qualifications.
SD-06 Test Reports
Preliminary Test Report; G
Electronic copies (.pdf) of the completed Preliminary Test Report, no later than 14 days after the completion of the Preliminary
Tests.
Final Acceptance Test Report; G
Electronic copies (.pdf) of the completed Final Acceptance Tests
Reports, no later than 14 days after the completion of the Final
Acceptance Tests.
SD-07 Certificates
Fire Protection Specialist Certifications; G
Certification Letter by Fire Protection Specialist; G
Qualifications of Welders; G
Qualifications of Installer; G
Certificates of qualifications, as specified; G
Seismic Certification of Dedicated Seismic Systems; G
State of Washington Certificate of Competency; G
Provide a State of Washington Certificate of Competency for any individual, business, or firm engaged in the inspecting, designing, testing, maintaining or servicing of fire and life safety systems.
SD-09 Field Reports
SECTION 21 13 17 Page 11
Inspection by Fire Protection Specialist; G
SD-10 Operation and Maintenance Data
Operation and Maintenance Instructions; G
Submit two hard copies and one electronic (.pdf) version of manuals listing step-by-step procedures required for system startup, operation, shutdown, and routine maintenance, at least 14 days prior to field training.
SD-11 Closeout Submittals
As-Built Drawings
Warranty Letter
Spare Parts
Operation and Maintenance (O&M) Instructions; G
Instruction of Government Employees
1.6.1 Combined Submittals
The Shop Drawings, Materials and Equipment, Sway Bracing and Hydraulic
Calculations shall be submitted in the same package so they can be reviewed at the same time.
1.7 HYDRAULIC CALCULATIONS
Hydraulic calculation procedures shall be as outlined in NFPA 13 except that calculations shall be performed by computer using software intended specifically for fire protection system design using the design criteria shown on the drawings or if design criteria is not provided on the drawings, the design criteria provided in UFC 3-600-01 and NFPA 13, whichever is more stringent. Calculations that uses typical k-factors for typical branch lines, sprigs (stub-ups), or drops is not acceptable. Calculations shall be based on the water supply data provided by the Fire Protection Specialist.
Calculations shall substantiate that the design area used in the calculations is the most demanding hydraulically. Water supply curves and system requirements shall be plotted on semi-logarithmic graph paper so as to present a summary of the complete hydraulic calculation. A summary sheet indicating sprinklers in the design area and their respective hydraulic reference points, elevations, actual discharge pressures and actual flows shall be provided. Elevations of hydraulic reference points (nodes) shall be indicated. Documentation shall identify each pipe individually and the nodes connected thereto. The diameter, length, flow, velocity, friction loss, number and type fittings, total friction loss in the pipe, equivalent pipe length and Hazen-Williams coefficient shall be indicated for each pipe. If the submittal shop drawings cannot clearly identify hydraulic reference points (nodes) and remote areas, a drawing showing hydraulic reference points and pipe designations used in the calculations shall be included that is independent of shop drawings.
SECTION 21 13 17 Page 12
1.8 FIRE PROTECTION SPECIALIST (QUALIFIED FIRE PROTECTION ENGINEER)
Work specified in this section shall be performed under the supervision of and certified by the Fire Protection Specialist (Qualified Fire Protection
Engineer). The Fire Protection Specialist shall be an individual who is a registered professional engineer in the State of Washington and has NCEES licensing. The Fire Protection Specialist shall be regularly engaged in the design and installation of the type and complexity of system specified in the Contract documents, and shall have served in a similar capacity for at least three systems that have performed in the manner intended for a period of not less than 6 months. Any individual, business, or firm engaged in the inspecting, testing, maintaining, designing, or servicing of fire and life safety systems and equipment shall be certified to perform these activities in accordance with the State of Washington. The Fire Protection Specialist shall not be a part of the specialty subcontractor design team and shall have no business relationships (owner, partner, operating officer, distributor, salesman or technical representative) with any construction subcontractors involved with the project or with any fire protection equipment device manufacturers, suppliers or installers for any such equipment provided as part of this project.
1.9 QUALIFICATIONS OF INSTALLER
The contractor performing the Sprinkler System work shall be licensed to perform this type of work in the State of Washington in accordance with UFC
3-601-02 and hold a State of Washington "Certificate of Competency".
1.10 REGULATORY REQUIREMENTS
Compliance with referenced NFPA standards is mandatory. This includes advisory provisions listed in the appendices of such standards, as though the word "shall" had been substituted for the word "should" wherever it appears. In the event of a conflict between specific provisions of this specification and applicable NFPA standards, this specification shall govern. Interpret reference to "Authority Having Jurisdiction" to mean JBLM
Public Works Life Safety Systems Manager.
1.11 SHOP DRAWINGS
The Sprinkler System Shop Drawings shall conform to the requirements established for "Working Plans" as prescribed in NFPA 13. Drawings shall include plan and elevation views demonstrating that the equipment will fit the allotted spaces with clearance for installation and maintenance. Each set of drawings shall include the following:
a. Submitted shop drawing size shall be ISO A1 (22x34).
b. Descriptive index of drawings in the submittal with drawings listed in sequence by drawing number. A legend identifying device symbols, nomenclature, and conventions used.
c. Floor plans drawn to a scale not less than 1/8" = 1'-0" which clearly show locations of sprinklers, risers, pipe hangers, seismic separation assemblies, sway bracing, inspector's test connections, drains, and other applicable details necessary to clearly describe the proposed arrangement. Each type of fitting used and the locations of reducing couplings, and welded joints shall be indicated.
SECTION 21 13 17 Page 13
d. Actual center-to-center dimensions between sprinklers on branch lines and between branch lines, from end sprinklers to adjacent walls, from walls to branch lines, from sprinkler feed mains, cross-mains and branch lines to finished floors, roofs, and ceilings. A detail shall show the dimension from the sprinkler and sprinkler deflector to the ceiling in finished areas.
e. Gridlines horizontally and vertically shall be provided as part of the backgrounds.
f. When the floor plan exceeds a single drawing, match lines shall be provided that indicate on which sheet the building continues.
g. When the floor plan exceeds a single drawing, a key plan shall also be provided that identifies which portion of the building is provided on that drawing and which drawings are used for other portions of the building.
h. Longitudinal and transverse building sections showing typical branch line and cross-main pipe routing as well as elevation of each typical sprinkler above finished floor.
i. Details of each type of riser assembly, each pipe hanger, each means of branch line restraint, restraint of underground water main at point-of-entry into the building, and electrical devices and interconnecting wiring.
j. For all trapeze hangars, provide a table indicating the size of the pipe to be supported, size and type of the trapeze member, section modulus of the trapeze member, distance from the structure to pipe being supported
(A and B dimensions), and the section modulus required.
k. Details for each sway brace configuration, orientation, angle, and structural connection along with calculations. The maximum L/R ratio shall be 200. The "total Calculated Load" divided by the "Allowable Load per Fastener" shall not exceed a maximum value of 0.90.
1.12 QUALITY ASSURANCE
1.12.1 Qualifications of Welders
Submit certificates of each welder's qualifications prior to site welding;
certifications shall not be more than one year old.
1.13 FIRE RISER AREA
If a fire suppression sprinkler riser is located within a facility and is not in a mechanical room or dedicated fire protection room, the riser shall be installed in a fenced enclosure adjacent to an exterior man door with access gate and means of locking (padlock) to prevent access by building occupants to valves and controls. DPW will provide padlock. Do not locate valves and controls in stairwells.
1.14 DRY PIPE SYSTEM RESETTING INSTRUCTIONS
Provide instructions that are printed on white bond paper, laminated, and
SECTION 21 13 17 Page 14 securely mounted to each dry system riser using an approved method for permanent mounting. The instructions shall indicate step-by-step procedures for resetting of the dry pipe riser including step-by=step procedures for resetting of any installed accelerators, air maintenance device, and
Nitrogen Generation System for use by DPW personnel in an emergency situation.
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
Materials and equipment shall be domestically made and standard products of a manufacturer regularly engaged in the manufacture of such products and shall essentially duplicate items that have been in satisfactory use for at least 2 years prior to bid opening.
2.2 NAMEPLATES
All equipment shall have a nameplate that identifies the manufacturer's name, address, type or style, model or serial number, and catalog number.
2.3 REQUIREMENTS FOR FIRE PROTECTION SERVICE
Materials and Equipment shall have been tested by Underwriters Laboratories, Inc. and listed in UL Fire Prot Dir or approved by Factory Mutual and listed in FM P7825a and FM P7825b. Where the terms "listed" or "approved" appear in this specification, such shall mean listed in UL Fire Prot Dir or FM P7825a and FM P7825b. Submit manufacturer's catalog data included with the
Sprinkler System Drawings for all items specified herein. The data shall be highlighted to show model, size, options, etc., that are intended for consideration. Data shall be adequate to demonstrate compliance with all contract requirements. Manufacturer's catalog data shall be current and shall not indicate products that have been superseded or products that no longer are manufactured.
2.4 UNDERGROUND PIPING COMPONENTS
2.4.1 Pipe
Provide outside-coated, cement mortar-lined, Class 52 ductile-iron pipe
(with a rated working pressure of 175 psi) conforming to NFPA 24 for piping under the building and less than 5 feet outside of the building walls.
Minimum pipe size for UFC 3-600-01 and NFPA 13 systems shall be 6 inches.
Minimum pipe size for NFPA 13D and NFPA 13R systems shall be 4 inches.
Piping more than 5 feet outside of the building walls shall be outside coated, AWWA C104/A21.4 cement mortar-lined, AWWA C151/A21.51 ductile-iron pipe, and AWWA C110/A21.10 fittings conforming to NFPA 24 or provided under
Section 33 11 00 WATER DISTRIBUTION.
2.4.2 Fittings and Gaskets
Flanged elbows or bends (straight sizes), tees, crosses, concentric reducers, base elbows (except reducing size) and bottom base tees shall be ductile iron conforming to AWWA C110/A21.10. Gaskets shall be suitable in design and size for the pipe with which such gaskets are to be used. Gaskets for ductile iron pipe joints shall conform to AWWA C111/A21.11.
SECTION 21 13 17 Page 15
2.4.3 Valves and Valve Boxes
Valves shall be gate valves conforming to AWWA C500 or UL 262. Valves shall have cast-iron body and bronze trim. Valve shall open by counterclockwise rotation. Except for post indicator valves, all underground valves shall be provided with an adjustable cast-iron or ductile iron valve box of a size suitable for the valve on which the box is to be used, but not less than
5.25 inches in diameter. The box shall be coated with bituminous coating. A cast-iron or ductile-iron cover with the word "WATER" cast on the cover shall be provided for each box.
2.4.4 Gate Valve and Indicator Posts
Gate valves for underground installation shall be of the inside screw type with counter-clockwise rotation to open. Where indicating type valves are shown or required, indicating valves shall be gate valves with an approved indicator post of a length to permit the top of the post to be located 3 feet above finished grade. Gate valves for use with indicator post shall conform to UL 262. Indictor post shall conform to UL 789. Provide each indicator post with one coat of primer and two coats of red enamel paint.
2.4.5 Buried Utility Warning and Identification Tape
Detectable aluminum foil plastic-backed tape or detectable magnetic plastic tape manufactured specifically for warning and identification of buried piping shall be provided for all buried piping. Tape shall be detectable by an electronic detection instrument. Tape shall be provided in rolls, 3 inches minimum width, color-coded for the utility involved and imprinted in bold black letters continuously and repeatedly over the entire tape length.
Warning and identification shall be "CAUTION BURIED WATER PIPING BELOW" or similar wording. Code and lettering shall be permanent and unaffected by moisture and other substances contained in the trench backfill material.
Tape shall be buried at a depth of 12 inches below the top surface of earth or the top surface of the subgrade under pavement.
2.5 ABOVEGROUND PIPING COMPONENTS
Aboveground piping shall be steel for NFPA 13 and NFPA 13R designs.
2.5.1 Steel Piping Components
2.5.1.1 Steel Pipe
Except as modified herein, steel pipe shall be black where indicated as permitted by NFPA 13 and shall conform to applicable provisions of ASTM A
795/A 795M, ASTM A 53/A 53M, or ASTM A 135/A 135M. Pipe in which threads are cut, grooves are cut, grooves are rolled formed, or flanges are installed shall be Schedule 40, except Schedule 30 piping is allowed for sizes 8 inches and greater in diameter. Pipe shall be marked with the name of the manufacturer, kind of pipe, and ASTM designation.
2.5.1.2 Fittings for Non-Grooved Steel Pipe
Fittings shall be cast iron conforming to ASME B16.4, steel conforming to
ASME B16.9 or ASME B16.11, or malleable iron conforming to ASME B16.3. Steel press fittings shall be approved for fire protection systems. Fittings into which sprinklers, drop nipples or riser nipples (sprigs) are screwed shall
SECTION 21 13 17 Page 16 be threaded type. Plain-end fittings with mechanical couplings, fittings that use steel gripping devices to bite into the pipe and segmented welded fittings shall not be used.
2.5.1.3 Grooved Mechanical Joints and Fittings
Joints and fittings shall be designed for not less than 175 psi service and shall be the product of the same manufacturer along with the grooving tools.
Segmentally welded fittings shall not be used. Fitting and coupling houses shall be malleable iron conforming to ASTM A 47/A 47M, Grade 32510, and ductile iron conforming to ASTM A 536, Grade 65-45-12. Gasket shall be the flush type that fills the entire cavity between the fitting and the pipe.
Nuts and bolts shall be heat-treated steel conforming to ASTM A 183 and shall be cadmium plated or zinc electroplated.
2.5.1.4 Flanges
Class 150 Flanges shall conform to NFPA 13 and ASME B16.1. Gaskets shall be non-asbestos compressed material in accordance with ASME B16.21, 1/16 inch thick, and full face or self-centering flat ring type.
2.5.1.5 Gaskets
Gaskets shall be AWWA C111/A21.11, cloth inserted red rubber gaskets.
2.5.1.6 Bolts
Bolts shall be ASTM A 449, Type 1 or 2, Grade 5. Bolts shall extend no less than three full threads beyond the nut with Bolts tightened to the required torque.
2.5.1.7 Nuts
Nuts shall be ASTM A 193/A 193M or ASTM A 194/A 194M, Grade 7.
2.5.1.8 Washers
Washers shall meet the requirements of ASTM F 436. Flat circular Washers shall be provided under all bolt heads and nuts.
2.5.2 Pipe Hangers
Pipe hangers and support shall meet MSS SP-58 and MSS SP-69 requirements and shall be listed in UL Fire Prot Dir, FM P7825a, and FM P7825b for fire protection use. Pipe hanger and supports shall be adjustable and of the type suitable for the application, construction, and pipe type and sized to be supported. Finish of rods, nuts, washers, hangers, and supports shall be zinc-plated after fabrication.
2.5.3 Valves
Valves shall be UL listed UL Fire Prot Dir or FM approved FM P7825a and FM
P7825b for fire protection service. Valves shall have flange, grooved, or threaded end connections.
2.5.3.1 Control Valve and Gate Valves
SECTION 21 13 17 Page 17
Manually operated sprinkler control valve may be butterfly style with an integral tamper switch or gates valve style with an externally mounted tamper switch. Gate valve shall be outside stem and yoke (OS&Y) type and shall be listed in UL Bld Mat Dir or FM P7825a and FM P7825b.
2.5.3.2 Check Valves
Check valve 2 inches and larger shall be listed in UL Bld Mat Dir or FM
P7825a and FM P7825b. Check valves 4 inches and larger shall be of the swing type with flanged or grooved cast iron body, shall have a clear waterway and shall meet the requirements of MSS SP-71, for Type 3 or 4.
2.5.3.3 hose Valves
Valve shall comply with UL 668 and shall have a minimum rating of 300 psi.
Valve shall be non-rising stem, all bronze, 90 degree angle or straight pattern type, with 2-1/2 inch American National Standard Fire Hose Screw
Thread (NH) male outlet in accordance with NFPA 1963. Hose valves shall be equipped with 2-1/2 inch lugged cap, cap, gasket, and chain. Valve finish shall be polished brass or rough chrome plated.
2.6 DRY PIPE VALVE ASSEMBLY
The dry pipe valve shall be a latching differential type listed in UL Fire
Prot Dir or FM P7825a and FM P7825b and shall be complete with trim piping, valves, fittings, pressure gauges, priming water fill cup, velocity drip check, drip cup, and other ancillary components as required for proper operation. The assembly shall include a quick-opening device by the same manufacturer as the dry pipe valve for systems over 500 gallons in capacity.
2.7 NITROGEN GENERATION SYSTEM
Nitrogen Generation System shall be in accordance with UFC 3-600-01 and
NFPA 13. Provide a Nitrogen Generation System that is capable of delivering a minimum of 98 percent nitrogen throughout all of the system piping within
14 days from the commencement of the inerting process. The Nitrogen
Generation System must be self-contained with "drop-in" operability with a simple one step direct connection of the nitrogen gas supply line to each zone. The use of stand-alone compressed nitrogen bottle system is not permitted. A process that involves continuous venting of the piping network is not permitted. Design the Nitrogen Generation System so all equipment is installed within the confines of the riser room with the exception of the
Nitrogen Purge Valve Assembly. The Nitrogen Generation system shall be sized to pressurize the largest dry pipe sprinkler system within 30 minutes.
2.7.1 Nitrogen Generation
Nitrogen Generation shall be beltless single stage oil-free type with a single point power connection. The Nitrogen Generation shall consist of a control panel that does not require software or programming with a LED display for a fully automatic system. The Nitrogen Generation system shall also consist of a safety relief valves, automatic drains, gauges, a minimum
10 gallon compressed air storage tank, a minimum 10 gallon nitrogen storage tank, shutoff valve, Form C dry contacts for trouble connection to the building Fire Alarm System, and pressure switch for automatic starting and stopping. The compressed air system shall be factory set to operate between
SECTION 21 13 17 Page 18 approximately 80 p.s.i. to approximately 100 p.s.i. The compressed nitrogen system shall be factory set to operate between approximately 60 p.s.i. to approximately 80 p.s.i.
2.7.2 Nitrogen Pressure Maintenance Device
Nitrogen Pressure Maintenance Device shall be a pressure regulator that automatically reduces supply nitrogen to provide the pressure required to be maintained in the piping system. The device shall have a cast bronze body and valve housing complete with diaphragm assembly, spring, filter, ball check to prevent backflow, 1/16 inch restriction to prevent rapid pressurization of the system, and adjustment screw. The device shall be capable of reducing an inlet pressure of up to 100 psig to a fixed outlet pressure adjustable to 10 psig.
2.7.3 Nitrogen Supply Piping System
System shall be configured so that each dry pipe system is equipped with a separate air maintenance device, shutoff valve, bypass valve, and pressure gauge. Piping shall be galvanized steel in accordance with ASTM A 795/A 795M or ASTM A 53/A 53M. Any air maintenance device used in conjunction with the nitrogen generation system must be listed or approved for use on sprinkler systems. The connection pipe from the Nitrogen Generation System shall not be less than 1/2 inch in diameter and shall enter the system above the priming water level of the dry pipe valve. A check valve shall be installed in the system supply nitrogen piping from the compressor. A shutoff valve of the renewable disc type shall be installed upstream of this check valve.
2.7.4 Nitrogen Purge Valve Assembly
Unless otherwise indicated, a Nitrogen Purge Valve Assembly shall be installed at the remote end of the dry pipe system. Nitrogen Purge Valve
Assemblies installed in the mechanical room or at the location of the
Nitrogen Generation control panel will not be allowed. The Nitrogen Purge
Valve Assembly shall be fully automatic with a 120 Volts A.C. power connection. The Nitrogen Purge Valve Assembly shall have LED displays that indicates nitrogen concentration levels and a purge timer to indicate the number of days remaining until purging is complete. The Nitrogen Purge
Valve Assembly shall have a built-in nitrogen analyzer that samples the exiting nitrogen levels. Once the nitrogen concentration level reaches 98 percent nitrogen, the Nitrogen Purge Valve Assembly shall automatically stop purging. After the system has stopped purging, periodic samples shall be taken to ensure concentration levels are being maintained. A set of Form
C dry contacts shall be provided connection to the building Fire Alarm
System.
2.8 WATERFLOW ALARM
Electrically operated, exterior-mounted, water flow alarm bell shall be provided and installed in accordance with NFPA 13. Waterflow alarm bell shall be 10 inch in diameter, rated for 24 VDC, and shall be connected to the Fire Alarm Control Panel in accordance with Section 28 31 74 INTERIOR
FIRE DETECTION AND ALARM SYSTEM or Section 28 31 76 INTERIOR FIRE ALARM AND
MASS NOTIFICATION SYSTEM.
2.9 ALARM INITIATING AND SUPERVISORY DEVICES
SECTION 21 13 17 Page 19
2.9.1 Sprinkler Pressure (Waterflow) Alarm Switch
Pressure switch shall include a metal housing with a neoprene diaphragm, SPDT snap action switches and a 1/2 inch NPT male pipe thread. The switch shall have a maximum service pressure rating of 175 psi. There shall be two
SPDT (Form C) contacts factory adjusted to operate at 4 to 8 psi. The switch shall be capable of being mounted in any position in the alarm line trim piping of the dry pipe valve.
2.9.2 Low Air Pressure Supervisory Switch
The pressure switch shall supervise the air pressure in system and shall be set to activate at 10 psi above the dry pipe valve trip point pressure. The switch shall have an adjustable range between 5 and 80 psi. The switch shall have screw terminal connection and shall be capable of being wired for normally open or normally closed circuit.
2.9.3 Valve Supervisory (Tamper) Switch
Switch shall be suitable for mounting to the type of control valve to be supervised in the normally open position or in the normally closed position.
The switch shall be tamper resistant and contain one set of SPDT (Form C) contacts arranged to transfer upon closure/opening of the valve of more than two rotations of the valve stem from its normal position.
2.10 FIRE DEPARTMENT CONNECTION
Fire department connection shall be projecting or flush type with cast brass body, matching wall escutcheon lettered "Auto Spkr" with a chromium plated or brass finish. The connection shall have two inlets with individual self-closing clappers, lugged caps, and chains. Female inlets shall have 2-1/2 inch diameter American National Fire Hose Connection Screw Threads (NH) per
NFPA 1963.
2.11 SPRINKLERS
Sprinklers with internal O-rings shall not be used. Sprinklers shall be used in accordance with their listed coverage limitations. Sprinklers in high heat areas including attic spaces or in close proximity to unit heaters shall have temperature classification in accordance with NFPA 13. Extended coverage sprinklers shall not be used.
2.11.1 Concealed Sprinkler
Concealed sprinklers shall be brass finished quick-response type and shall have a minimum nominal 1/2 inch orifice with a white escutcheon plate that is flat in profile. Escutcheon plates that are dome in profile will not be allowed.
2.11.2 Recessed Sprinkler
Recessed sprinklers shall be white finished quick-response type and shall have a minimum nominal 1/2 inch orifice.
2.11.3 Pendent Sprinkler
Pendent sprinklers shall be white finished in occupied spaces and brass
SECTION 21 13 17 Page 20 finished in exposed structure areas. Pendent sprinklers shall be quick-response type with a minimum nominal 1/2 inch orifice.
2.11.4 Upright Sprinkler
Upright sprinklers shall be brass finished quick-response type and shall have a minimum nominal 1/2 inch orifice.
2.11.5 Sidewall Sprinkler
Sidewall sprinklers shall be white finished in occupied spaces and brass finished in exposed structure areas. Sidewall sprinklers shall be quick-response type with a minimum nominal 1/2 inch orifice.
2.11.6 Intermediate Level Rack Sprinkler
Intermediate level rack sprinklers shall be brass finished upright or pendent type with a minimum nominal 1/2 inch orifice. The sprinkler shall be equipped with a deflector plate to shield the fusible element from water discharged above it.
2.11.7 Corrosion Resistant Sprinkler
Corrosion resistant sprinklers shall be the upright or pendent type installed in locations of high humidity (showers, kitchens, etc.), exterior of building, and as required by NFPA 13. Corrosion resistant coatings of
Lead or Nickel-Teflon shall be factory-applied by the sprinkler manufacturer.
2.11.8 Dry Sprinkler Assembly
Dry sprinkler assembly shall be polished chrome finished pendent, upright, sidewall, or 45-degree type with a minimum nominal 1/2 inch orifice.
Assembly shall include an integral escutcheon. Maximum length shall not exceed maximum indicated in UL Fire Prot Dir. Sprinkles shall have a polished chrome finish.
2.12 DISINFECTING MATERIALS
All portions of the fire protection sprinkler system installed on the potable side of the backflow preventer shall be disinfected.
2.12.1 Liquid Chlorine
Liquid chlorine shall conform to AWWA B301.
2.12.2 Hypochlorites
Calcium hypochlorite and sodium hypochlorite shall conform to AWWA B300.
2.13 ACCESSORIES
2.13.1 Sprinkler Cabinet
Spare sprinklers shall be provided in accordance with NFPA 13 and shall be packed in a suitable metal or plastic cabinet. Spare sprinklers shall be representative of, and in proportion to, the number of each type and
SECTION 21 13 17 Page 21 temperature rating of the sprinklers installed. At least one manufacturers wrench for each type of sprinkler installed shall be provided. Provide a list of sprinklers installed in the building in accordance with NFPA 13 in the sprinkler cabinet.
2.11.2 Recessed Sprinkler Escutcheon
Escutcheon shall be one-piece metallic type with a depth of less than 3/4 inch and suitable for installation on recessed sprinklers. The escutcheon shall have a factory finish that matches the finish of the pendent sprinkler head.
2.11.3 Oversized Ceiling Penetration Escutcheon
Oversized escutcheon shall be one-piece metallic type that has a recessed area to accommodate a standard recessed sprinkler escutcheon. The oversized escutcheon shall have a factory white finish that matches the finish of the recessed pendent sprinkler head.
2.11.4 Pipe Escutcheon
Provide one-piece or split-hinge metal Escutcheon Plates for piping penetrating floors, walls, and ceilings in exposed areas. Escutcheon Plates shall be polished chromium-plated zinc alloy, or polished chromium-plated copper alloy. Plates shall be secured in place by internal spring tension or set screw.
2.11.5 Sprinkler Guard
Guard shall be a steel wire cage designed to encase the sprinkler and protect it from mechanical damage. Guards shall be provided for sprinklers installed at an elevation less than 8'-0" above finished floor.
2.11.6 Identification Signs
2.11.6.1 Identification Signs
Valve identification sign shall be minimum 6 inches wide x 2 inches high with enamel baked finish on minimum 18 gauge steel or 0.024 inch aluminum with red letters on a white background or white letters on red background.
Wording of sign shall include, but not be limited to "control valve", "main drain", "auxiliary drain", "inspector's test", "alarm test", "alarm line", and similar wording as required by NFPA 13 to identify operational components.
2.11.6.2 Signage in Buildings
All auxiliary drains, remote inspector's test, and control valves shall be identified with signage on the access panel for items placed in access panels or at the ceiling for items installed above ceilings. Signage shall be metal or phenolic having a white background with a minimum 2 inch high red letters that is chain hung, the use of a "Sharpie" to write information will not be allowed. Locations of signage shall match locations identified on the Graphic Maps.
2.11.6.3 Equipment Signage
SECTION 21 13 17 Page 22
Equipment signage shall have a white background with a minimum 2 inch high red letters unless indicated differently below, the use of a "Sharpie" to write information will not be allowed. Exterior wall mounted signs shall be located at an elevation not exceeding 8 feet above exterior grade. Equipment signage shall be provided for the following items:
a. Fire Department Connection: Wall mounted fire department connection shall be provided with a metal weatherproof sign that shall be placed on the exterior wall of the building directly over the fire department connection. The sign shall be a minimum of 20 inches long by 15 inches tall and shall state "FIRE DEPARTMENT CONNECTION".