Attachment 3 -NPC L Power Cart Specs.docx
DOCX document 23 KB Posted
- Attached to
- NPC L Power Cart
- Solicitation number
- FA445226Q0029
About this file
This is a technical specifications document for a 20-kVA power cart designed to support a Negative Pressure Conex Light (NPC L) unit at the University of Nebraska Medical Center. The Air Force Air Mobility Command/Surgeon General's Medical Readiness Logistics Division requires one unit for this application.
The power cart must meet specific electrical requirements including 208-240 VAC, 3-phase, 50/60 Hz input power conversion to 115-volt line-to-neutral and 200-208 volt line-to-line 3-phase 4-wire output at 400 Hz frequency. Safety features must include an AC output contactor with an aircraft safety interlock system for connect/disconnect operations. The cart requires an input cable minimum 50 feet in length with single-jacket 3-conductor configuration plus ground, and an output cable minimum 20 feet long with multiple banded conductors terminated with a standard aircraft plug connector.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ_NPC L Power Cart.pdf | ||
| Attachment 1 -RFQ Information Sheet.xlsx | XLSX spreadsheet | |
| Attachment 2 -Clauses and Provisions.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NPC L Power Cart Specs General System Requirements:
· Capacity: 20-kVA rating
Input Power Specifications:
· Voltage/Frequency: 208 to 240 VAC, 3 phase, 50/60 Hz
Output Power Specifications:
· Voltage/Frequency: 115 volts (line-to-neutral)/200-208 volts (line-to-line), 3 phase, 4-wire, 400 Hz
· Protection/Safety: must include an AC output contactor connect/disconnect device equipped with an aircraft safety interlock system
Cables and Connectors:
· Input Cable: minimum 50 feet long, single-jacket 3-conductor with ground
· Output Cable: minimum 20 feet long, banded with multiple conductors
· Aircraft Connector: output cable must be terminated with a standard aircraft plug