ATTACHMENT 3 - DRAWINGS.pdf

PDF 7 MB Posted

Attached to
Electrical Addition - Warmwater Aquiculture Research Center - Stoneville, MS
Solicitation number
1232SA26Q0694
Issued by

About this file

This document is a set of electrical construction drawings for the Hatchery Complex Electrical Distribution Addition project at the Warmwater Aquiculture Research Unit in Stoneville, Mississippi, prepared by the U.S. Department of Agriculture Agricultural Research Service. The project is identified under A/E Contract No. 12405B21D0003 and A/E Task Order No. 12405B24F0123, with a project number of 2024-E and work area K-MAGEE.

The drawings comprise eight sheets including a title sheet, legend and abbreviations, site plan, power plan, details, existing single line diagram, single line diagram for new work, and panel schedules. Key work includes installation of new pole-mounted transformers providing power to underground service feeders; a new 50 kW generator; new electrical panels (P.84.N replacement with 400A capacity and new P.84.S 100A standby panel); new hanging quad and single receptacles; and associated electrical infrastructure including conduit, conductors, grounding systems, and equipment pads. The project involves disconnecting and removing existing conductors and transformers, demolishing existing devices, and installing new three-phase 480Y/277V distribution equipment. The drawings specify copper conductors, RMC conduit, equipment grounding requirements with ground rods and bonding jumpers, and contain detailed schematics for neutral and grounding systems, trench details, receptacle installations, and panel schedules for multiple buildings (46, 47, 47A, 47B, 47C, 48, 54, 58, 59, and 84) within the facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M I S S I S S I P P I

GRENADA

WINONA

HATTIESBURG

NO SCALE

GREENVILLE

VICKSBURG

HOLLANDALE1

JACKSON

ROSEDALE

GREENWOOD

VICINITY MAP

MEMPHIS

GULFPORT

STARKVILLE

COLUMBUS12

ALT

45PROJECT

LOCATION

TUPELO

N

WARMWATER AQUICULTURE RESEARCH UNIT

AGRICULTURAL RESEARCH SERVICE

U.S. DEPARTMENT OF AGRICULTURE

INDEX OF DRAWINGS

SHEET NO. TITLE

LOCATION MAP NO SCALE

N

T1 E1 E2 E3 E4 E5 E6 E7

TITLE SHEET

LEGEND AND ABBREVIATIONS

SITE PLAN

POWER PLAN

DETAILS

EXISTING SINGLE LINE

SINGLE LINE

PANEL SCHEDULES

STONEVILLE, MISSISSIPPI

HATCHERY COMPLEX ELECTRICAL DISTRIBUTION ADDITION

N

W

S

E

X

X

X X

X X

X

XX

X X

X

X

X

X

X

X

X

X

XX

X

X

X

X

X

X

X

X

XXX

X

X X

X X

X

X X X

X X

XX

XX

XX XXXXXX

X X X X X X X X X

X X

X

X X X X XX X XX X X X X X X

X

X X

X X X X X X X X X X X X X X X X X X X

BLDG. #46

BLDG. #58

BLDG. #59BLDG. #47

BLDG. #84

SH

OP

B

LD

G.

#4

#4 7A

#5

ENTRANCE

U. S. DEPARTMENT OF AGRICULTURE

AGRICULTURAL RESEARCH SERVICE

CATFISH GENETICS UNIT

LOCATION MAP

STONEVILLE, MISSISSIPPI

XXXXXXXXXX

X

XXX

XX

X

X X X X X X X X X X X X X X X X X X X X X

X X

X

X

X

USDA

SPRAY

DISPOSAL

AREA

WELL

MAIN.SWBD

BLDG. #84 SHED

NEW GREENHOUSE

EXIST GREENHOUSE

A/E CONTRACT NO. 12405B21D0003

A/E TASK ORDER NO. 12405B24F0123

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

JAMIE WHITTEN DELTA STATES RESEARCH CENTER

HATCHERY COMPLEX ELECTRICAL ADDITON

STONEVILLE, MS

TITLE SHEET

T1 1 808/16/2024

BSN

TMT

DRL

MID SOUTH AREA

STONEVILLE, MS

2024-E

K-MAGEEWORK AREA

A OR AMP AMPERE(S)

ACC AIR COOLED CHILLER

AC ALTERNATING CURRENT

AC AIR COMPRESSOR / AIR

CURTAIN

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING

CAPACITY

AL ALUMINUM

AM AMMETER

ASYM ASYMMETRICAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER

SWITCH

AUTO AUTOMATIC

AWG AMERICAN WIRE GAUGE

B BOILER

BC BRANCH CONTROLLER

BCW BARE COPPER WIRE

BFF BELOW FINISHED FLOOR

BFG BELOW FINISHED GRADE

BLDG BUILDING

C CONDUIT

CAT CATEGORY

CB CIRCUIT BREAKER

CCT CORRELATED COLOR

TEMPERATURE

CCTV CLOSED CIRCUIT

TELEVISION

CFCI CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CH CHILLER

CHWCP CHILLED WATER

CIRCULATING PUMP IN A

PRIMARY-SECONDARY

SYSTEM

CHWP CHILLED WATER PUMP

CHWSP CHILLED WATER SUPPLY

PUMP IN A PRIMARY-

SECONDARY SYSTEM

CKT CIRCUIT

CMH COMMUNICATIONS

MANHOLE

CP CONDENSATE PUMP

CPT CONTROL POWER

TRANSFORMER

CRAC COMPUTER ROOM AC UNIT

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CT COOLING TOWER

CU COPPER OR CONDENSING

UNIT

CWP CONDENSER WATER PUMP

D DEPTH

DC DIRECT CURRENT

DF DESTRATIFICATION FAN

DH or DUH DUCT HEATERS

DHWCP DOMESTIC HOT WATER

CIRCULATING PUMP

DISC DISCONNECT SWITCH

DOAS DEDICATED OUTSIDE AIR

SYSTEM (UNIT)

DPST DOUBLE POLE SINGLE

THROW

DPDT DOUBLE POLE DOUBLE

THROW

DSCU DUCTLESS SPLIT

CONDENSING UNIT

(POWERS THE DSS INDOOR

UNIT)

DSHP DUCTLESS SPLIT HEAT

PUMP (POWERS THE DSS

INDOOR UNIT)

DSS DUCTLESS SPLIT SYSTEM

(INDOOR UNIT)

DWBP DOMESTIC WATER

BOOSTER PUMP

DX DIRECT EXPANSION (DX)

COOLING COIL

EC EMPTY CONDUIT

EF EXHAUST FAN

ELEC ELECTRICAL

EMH ELECTRICAL MANHOLE

EMT ELECTRICAL METALLIC

TUBING

E or EMER EMERGENCY

EPA EFFECTIVE PROJECTED

AREA

EQUIP EQUIPMENT

ERV ENERGY RECOVERY

VENTILATOR

ERU ENERGY RECOVERY UNIT

ETR EXISTING TO REMAIN

NOTE: ABBREVIATIONS ABOVE

ARE FOR ELECTRICAL SHEETS

ONLY. NOT ALL ABBREVIATIONS

SHOWN WILL BE USED ON THIS

PROJECT.

ABBREVIATIONS LIST

EUH ELECTRIC UNIT HEATER

EXP EXPLOSION PROOF

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

F FUSE

FACP FIRE ALARM CONTROL

PANEL

FCU FAN COIL UNIT

FLEX FLEXIBLE

FWE FURNISHED WITH

EQUIPMENT

G OR GND GROUND

GFGI GOVERNMENT FURNISHED

GOVERNMENT INSTALLED

GFI GROUND FAULT

INTERRUPTER

GRS GALVANIZED RIGID STEEL

CONDUIT

GUH GAS UNIT HEATER

GWH GAS WATER HEATER

H or HT HEIGHT

HAC HEATED AIR CURTAIN

HOA HAND-OFF AUTOMATIC

HP HORSE POWER

HP HEAT PUMP (OUTDOOR

PORTION OF SPLIT SYSTEM

HEAT PUMP, USE CU FOR

STANDARD DX OUTDOOR

UNIT)

HT HEAT TRACKING

HVU HEATING/VENTILATING UNIT

HWCP HEATING WATER

CIRCULATING PUMP IN A

PRIMARY-SECONDARY

SYSTEM

HWP HEATING WATER SUPPLY IN

A PRIMARY-ONLY SYSTEM

HWRP HOT WATER

RECIRCULATION PUMP

HWSP HEATING WATER SUPPLY

PUMP IN A PRIMARY-

SECONDARY SYSTEM

HWUH HOT WATER UNIT HEATER

HZ HERTZ

IDS INTRUSION DETECTION

SYSTEM

IMC INTERMEDIATE METAL

CONDUIT

IRH INFRARED HEATER

J OR JB JUNCTION BOX

K KILO

KAIC THOUSAND AMPERE

INTERRUPTING CAPACITY

KCM OR KCMIL THOUSAND OF CIRCULAR

MILS

KEF KITCHEN EXHAUST FAN

KH KITCHEN HOOD

KV KILOVOLT

KVA KILOVOLT-AMPERES

KW KILOWATT

KWHR KILOWATT-HOUR

L LENGTH

LA LIGHTNING ARRESTOR

LAN LOCAL AREA NETWORK

LAV LAVATORY

LM LOCKHEED MARTIN

LTG LIGHTING

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB or MB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MGB MAIN GROUND BAR

MH MANHOLE or MOUNTING

HEIGHT

MIN MINIMUM

MLO MAIN LUGS ONLY

MOD MOTOR OPERATED DAMPER

MT or MTD MOUNT or MOUNTED

MRS MOTOR RATED SWITCH

N NEUTRAL

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S

ASSOCIATION

NFPA NATIONAL FIRE

PROTECTION ASSOCIATION

NC NORMALLY CLOSED

NESC NATIONAL ELECTRICAL

SAFETY CODE

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

P POLE(S) or PUMP

PA PUBLIC ADDRESS

PDU POWER DISTRIBUTION UNIT

PF POWER FACTOR

PH PHASE

PIU VAV TERMINAL UNIT WITH

PARALLEL OR SERIES FAN

(PRIMARY INDUCTION UNIT)

PMT PAD MOUNTED

TRANSFORMER

PNL PANEL OR PANELBOARD

PTAC PACKAGED THRU-WALL AIR

CONDITIONER

PVC POLYVINYL CHLORIDE

RECEPT or RECP RECEPTACLE

RF RETURN FAN

RH RADIANT HEATERS

(ELECTRIC)

RMC RIGID METAL CONDUIT

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

RVNR REDUCED VOLTAGE NON-

REVERSING

SA SURGE ARRESTOR

SCCR SHORT CIRCUIT CURRENT

RATING

SD SMOKE DAMPER

SF SUPPLY FAN

S/N SOLID NEUTRAL

SP SUMP PUMP

SPD SURGE PROTECTIVE DEVICE

SPDT SINGLE POLE DOUBLE

THROW

SPEC SPECIFICATIONS

SPST SINGLE POLE SINGLE

THROW

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TMGB TELECOMMUNICATIONS

MAIN GROUNDING BUSBAR

TOL THERMAL OVERLOAD

TP TWISTED PAIR

TYP TYPICAL

U URINAL

UH UNIT HEATER

UG UNDERGROUND

UIO UNLESS INDICATED

OTHERWISE

UL UNDERWRITERS

LABORATORY

UTP UNSHIELDED TWISTED PAIR

V VOLTS

VA VOLT AMPERES

VAV VAV TERMINAL UNIT

VEF VEHICLE EXHAUST FAN

VM VOLTMETER

VRF VARIABLE REFRIGERANT

FLOW SYSTEM

W WATTS or WIRE or WIDTH

WC WATER CLOSET

WEF WELDING EXHAUST FAN

WH WATER HEATER

WHDM WATTHOUR DEMAND METER

WSHP WATER SOURCE HEAT

PUMP

WP WEATHERPROOF

XFMR TRANSFORMER

Z IMPEDANCE

GENERAL NOTES - ELECTRICAL:

1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF WORK. THE DRAWINGS ARE NOT

INTENDED TO INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL PERFORMANCE

AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.

2. REVIEW ALL PROJECT DOCUMENTS PRIOR TO START OF CONSTRUCTION. REPORT ANY

DISCREPANCIES TO CONTRACTING OFFICER PRIOR TO PROCEEDING WITH WORK.

DIMENSIONS RELATING TO EXISTING CONSTRUCTION ARE TO BE FIELD VERIFIED. THE

CONTRACTOR SHALL IMMEDIATELY COMMUNICATE, IN WRITING TO THE CONTRACTING

OFFICER, CONCERNS WHERE THEY BELIEVE DESIGN DOCUMENTS ARE INSUFFICIENT,

INADEQUATE OR INCORRECT FOR PERFORMING THE CONSTRUCTION WORK.

3. THE ENUMERATION OF PARTICULAR ITEMS OF WORK IN ONE PORTION OF THE CONTRACT

DOCUMENTS SHALL NOT BE CONSTRUED TO EXCLUDE OTHER ITEMS NECESSARY OR

IMPLIED THEREFROM.

4. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF WORK SEQUENCING SUCH

THAT NO WORK SHALL BE LEFT IN AN UNFINISHED OR INCOMPLETE CONDITION.

5. PRODUCTS SHALL BE INSTALLED PER MORE STRINGENT REQUIREMENTS OF THE DESIGN

DOCUMENTS OR THE MANUFACTURER'S PRINTED INSTRUCTIONS FOR THE INDICATED

APPLICATION. THESE INSTRUCTIONS SHALL BE MAINTAINED ON SITE FOR THE DURATION OF

THE INSTALLATION AT A MINIMUM.

6. WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURER'S PUBLISHED

STANDARDS FOR QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL AS, THE

REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY CONFLICTING

REQUIREMENTS OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT TO THE

CONTRACTING OFFICER'S ATTENTION PRIOR TO PROCEEDING WITH THE WORK.

7. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-PLACE, AND NEW WORK.

8. WORK NOTED "N.I.C." IS NOT MEANT TO BE PART OF THE CONSTRUCTION SCOPE OF WORK

AGREEMENT.

9. THE CONTRACTOR SHALL PAY FOR AND COORDINATE THE REMOVAL AND LEGAL DISPOSAL

OF MATERIALS AND RUBBISH.

10. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY DIMENSIONS AND SHALL VERIFY NEW AND

EXISTING CONDITIONS, SHOWN ON THESE DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE

CONTRACTING OFFICER IN WRITING OF ANY DIFFERING CONDITIONS BEFORE

COMMENCEMENT OF WORK.

11. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN, LARGE SCALE DETAILS GOVERN OVER

SMALL SCALE DETAILS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IN

WRITING OF ANY DIFFERING CONDITIONS BEFORE COMMENCEMENT OF WORK.

12. THE CONTRACTOR SHALL PERFORM WORK IN ACCORDANCE WITH APPLICABLE CODES,

ORDINANCES AND REGULATORY AGENCIES AND SHALL OBTAIN NECESSARY BUILDING AND

FIRE PERMITS FROM ALL AUTHORITIES HAVING JURISDICTION.

13. PIPE DUCTS AND BUS DUCTS THAT PENETRATE FLOOR SLABS OR WALL PARTITIONS SHALL

BE INSTALLED IN A MANNER THAT WILL PRESERVE THE MOISTURE RESISTIVENESS, FIRE

RATING, AND STRUCTURAL INTEGRITY OF THE BUILDING.

14. THE CONTRACTOR SHALL PLAN HIS/HER WORK TO PROVIDE ADEQUATE PROTECTION FOR

PERSONS AND PROPERTY, AND EXECUTE THE WORK IN SUCH A MANNER TO AVOID ANY

HAZARD TO PERSONS AND PROPERTY AS NECESSARY.

15. THE CONTRACTOR SHALL COORDINATE THE PHASING OF THE WORK TO BE PERFORMED IN

OR ABOUT EXISTING FACILITIES, IF APPLICABLE, WITH THE OWNER'S REPRESENTATIVE

PRIOR TO START OF SUCH WORK.

16. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT

RACEWAY FILL RATIO TO LESS THAN 40% FULL.

17. THE ELECTRICAL CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER

TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR

SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE AND CORRECT

ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.

18. FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND

CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH

DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS.

PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE

BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR. SINGLE

GROUND CONDUCTOR IN ONE RACEWAY MUST BE SIZED FOR THE LARGEST OVERCURRENT

DEVICE.

19. REFER TO ONE-LINE DIAGRAM, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND

CONDUIT SIZES NOT SHOWN ON PLANS.

20. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE

ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL,

MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS

APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED

WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

21. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE

ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT

EQUIPMENT FROM CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN

ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF

DISPOSAL IS ENTIRELY THE CONTRACTOR'S RESPONSIBILITY.

22. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.

23. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS

BEFORE PROCUREMENT OF ANY MATERIALS AND DEVELOPMENT OF ANY SHOP DRAWINGS

OR SUBMITTALS.

24. THE CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS OF ALL OF THE NEW UTILITIES AND

SERVICE.

25. PROVIDE LABELS ON NEW RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY

SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT SHALL

BE BLACK, 1/4 ” IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT

PERMITTED.

26. NEW EQUIPMENT AND DEVICES ARE TO BE SURFACE MOUNTED UNLESS OTHERWISE NOTED.

27. DEVICES NOTED AS "GFI" SHALL BE GROUND FAULT CIRCUIT INTERRUPTING DEVICES.

28. DEVICES NOTED AS "WP" SHALL BE WEATHERPROOF WHILE-IN-USE

APPLICABLE CODES AND STANDARDS:

ABBREVIATIONS TITLE EDITION

NFPA 101 LSC LIFE SAFETY CODE (LSC) 2021

NFPA 70 NEC NATIONAL ELECTRICAL CODE (NEC) 2023

P&P 242.1M-ARS ARS FACILITIES DESIGN STANDARDS 2022

IESLL IES LIGHTING LIBRARY STANDARDS COLLECTION 2023

SYMBOL / KEY

REVISION TAG DESIGNATION

DESCRIPTION

TOP DESIGNATION IS SECTION DESIGNATION

KEY NOTE DESIGNATION

BOTTOM DESIGNATION IS SECTION SHEET LOCATION (STANDARD SYMBOL SCALED DOWN FOR LEGEND)

NOTE: ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES A 2 WIRE #10AWG CIRCUIT WITH A #10AWG

GND. A GREATER NUMBER OF WIRES IS INDICATED AS FOLLOWS:

4 WIRE, 2 CIRCUITS & GROUND (LONGER SLASH INDICATES NEUTRAL)

6 WIRE, 3 CIRCUITS & GROUND, ETC.(WIRING LARGER THAN #10AWG SHALL BE AS NOTED)

INDICATES #10 GROUND CONDUCTOR UOI (DOUBLE TICK/SLASH INDICATES ISOLATED GROUND)

PANELBOARD AND CIRCUIT DESIGNATION

RACEWAY CONCEALED IN WALL OR CEILING OR EXPOSED ON STRUCTURE AS REQUIRED

HOMERUN TO PANELBOARD - LETTERS INDICATE PANEL, NUMBERS INDICATE CIRCUIT

RACEWAY CONCEALED UNDER FLOOR OR BELOW GRADE. UNDER SLAB APPLICATIONS: RUN BELOW GRAVEL

(NOT ALL SYMBOLS MAY APPLY, TYP.)

NEW WORK LINE WEIGHT

EXISTING WORK LINEWEIGHT

TOP DESIGNATION IS PLAN / ENLARGED PLAN / DETAIL NUMBER

BOTTOM DESIGNATION IS SHEET LOCATION (STANDARD SYMBOL SCALED DOWN FOR LEGEND)

LA1:13

LA1:13

EP101

A

EP101

GENERAL SYMBOLS LEGEND

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

JAMIE WHITTEN DELTA STATES RESEARCH CENTER

HATCHERY COMPLEX ELECTRICAL ADDITION

STONEVILLE, MS

LEGEND AND ABBREVIATIONS

E1 2 808/16/2024

BSN

TMT

DRL

K-MAGEE

T

T

T

X X

X

X

X

X X X X X X X X X X X

X X X X X X

X

X

X

X X

XX

XXXXXXXXXX

X X

X X

X X

X

X X X X X X X X X X X X

X

X X

X X

X X

XXXX

X X

X X

TANK

E

E

E

LP

OEP

O

EP

OEP

OEP

O

EP

O

EP

PP

PP

PP PP

PP

PP

PP

O

EP

O

EP

O

EP

OEP OEP OEP

OEP OEP OEP OEP OEP OEP OEP OEP OEP OEP OEP OEP OEP

PP

PP

PP

SI

G

N

SIGN

SIGN

BLDG

# 47

BLDG

# 59 BL

DG

# 4

7A

BLDG

# 58

BLDG

# 48

OEP

OEP

UE

UE

PP

SHED

X X

X

GATE

BLDG

# 84

BLDG

# 54

MAIN.SWGR

WATER

COOLANT

AREA

GRATE

ELEV.:

120.1

W W

W W

NEW

GREENHOUSE

P.84. SHED

T T

OEP OEP

OEP

O

EP

O

EP

PP

UE

UE

O

EP

O

EP

O

EP

UEUE

UE

UE

E

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

REFER TOE3 FOR WORK IN THIS AREA

EXISTING

GREENHOUSES

SCALE:1"=20'-0"

0 20'20' 10'

SCALE:

SITE PLAN

1" = 20'-0"

E2

KEYED NOTES

GENERAL NOTES

1. PANEL MAIN.SWBD. EXISTING POINT OF SERVICE FOR

84.N and 84.E FEEDERS.

2. BLDG 84 POINT OF CONNECTION FOR 84.N AND 84.E

FEEDERS.

3. DISCONNECT POWER AND REMOVE CONDUCTORS.

ABANDON CONDUIT IN PLACE. CUT CONDUIT FLUSH

WITH GRADE AND CAP.

4. DEMO SWITCH.

5. DEMOLISH THE EXISTING TRANSFORMER.

6. NEW GREENHOUSE PANELS. REFER TO 2/E4.9. PROVIDE

NEW PANELS. REFER TO E6 AND 2/E4 FOR WORK IN

THIS AREA. PROVISION PANELS AS SCHEDULED,

BRANCH CIRCUITS TO BE INSTALLED BY OTHERS.

7. INSTALL NEW POWER POLE WITH NEW POLE MOUNTED

TRANSFORMERS PROVIDING POWER TO NEW

UNDERGROUND SERVICE FEEDERS. REFER TO 1/E4.

8. INSTALL NEW 50KW GENERATOR PROVIDING POWER TO

NEW UNDERGROUND SERVICE FEEDERS.

9. MINIMUM CLEARANCE OF ELECTRICAL CROSSING IS TO

MATCH CLEARANCE OF EXISTING ELECTRICAL

CROSSINGS

1. REVIEW ALL PROJECT DOCUMENTS PRIOR TO START

OF CONSTRUCTION. REPORT ANY DISCREPANCIES TO

CONTRACTING OFFICER PRIOR TO PROCEEDING WITH

WORK. DIMENSIONS RELATING TO EXISTING

CONSTRUCTION ARE TO BE FIELD VERIFIED. THE

CONTRACTOR SHALL IMMEDIATELY COMMUNICATE, IN

WRITING TO THE CONTRACTING OFFICER, CONCERNS

WHERE THEY BELIEVE DESIGN DOCUMENTS ARE

INSUFFICIENT, INADEQUATE OR INCORRECT FOR

PERFORMING THE CONSTRUCTION WORK.

2. EXISTING UNDERGROUND INSTALLATIONS, SUCH AS

WATER MAINS, GAS MAINS, SEWER, TELEPHONE LINES,

FIBER OPTICS, POWER LINES, AND BURIED

STRUCTURES IN THE VICINITY OF THE WORK AREA ARE

INDICATED ON THE DRAWINGS ONLY TO THE EXTENT

SUCH INFORMATION HAS BEEN MADE AVAILABLE TO OR

DISCOVERED BY THE SURVEYOR IN PREPARING THE

DRAWINGS. THERE IS NO GUARANTEE AS TO THE

ACCURACY OR COMPLETENESS THEREOF AND IS

EXPRESSLY DISCLAIMED. THE CONTRACTOR SHALL BE

SOLELY RESPONSIBLE FOR LOCATING ALL EXISTING

UNDERGROUND INSTALLATIONS, INCLUDING SERVICE

CONNECTIONS, IN ADVANCE OF EXCAVATING OR

TRENCHING.

3. OVERHEAD ELECTRICAL LINES MAY ALSO SUPPORT

OTHER OVERHEAD UTILITIES.

4. VERIFY EXISTING CONDITIONS, WHEN SPECIFIC

INFORMATION IS INCORRECT, MISSING OR IS IN

CONFLICT, BRING THE CONFLICT TO THE ATTENTION OF

THE CONTRACTING OFFICER PRIOR TO BEGINNING

WORK RELATED TO THAT ITEM.

5. THE CONTRACTOR SHALL PROVIDE AS-BUILT

DRAWINGS OF ALL OF THE NEW UTILITIES AND

SERVICE.

SITE LEGEND

EXISTING

LPLP

PP

E

W

GENERATOR

TRANSFORMER

LIGHT POLE

POWER POLE

OVERHEAD POWER

GRAVEL

CONCRETE

ASPHALT

UNDERGROUND POWER

DEMOLITION

WATER

FENCE

OEP

T

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

UE

UE

OEP

UEUE

NEW

PP

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

JAMIE WHITTEN DELTA STATES RESEARCH CENTER

HATCHERY COMPLEX ELECTRICAL ADDITION

STONEVILLE, MS

SITE PLAN

E2 3 808/16/2024

BSN

TMT

DRL

X

ETR

KEYED NOTES

GENERAL NOTES

LEGEND

EXISTING PANEL

EXISTING HANGING

DUPLEX RECEPTACLE

EXISTING HANGING

QUAD RECEPTACLE

EXISTING WALL MOUNTED

RECEPTACLE

NEW HANGING QUAD

RECEPTACLE. DETAIL 6/E4.

NEW HANGING SINGLE

RECPTACLE. DETAIL 6/E4.

NEW PANEL

1. REPLACE EXISTING 225A PANEL WITH WITH A 400A PANEL

"P.84.N".

2. INSTALL A 100A STANDBY PANEL "P.84.S".

3. INSTALL 3 NEW HANGING QUAD RECEPTACLES AND 3 NEW

HANGING SINGLE RECEPTACLES.

4. DEMOLISH DEVICE. DEMOLISH CONDUCTORS AND CONDUIT

BACK TO SOURCE. CUT FLASH AND PLUG.

5. PROTECT/PRESSURE BRANCH AND FEEDER CIRCUITS FROM

THIS DEVICE FOR REUSE.

6. NEW ATS.

7. EXISTING DEVICES TO REMAIN. REWORK BRANCH CIRCUIT FEED

FROM PANEL P.84.S.

8. EXISTING BLOWER TO REMAIN.REWORK BRANCH CIRCUIT FROM

PANEL P.84.S:2,4.

9. RECONNECT EXISTING BANK CIRCUIT.

1. VERIFY EXISTING CONDITIONS, WHEN SPECIFIC

INFORMATION IS INCORRECT, MISSING OR IS IN

CONFLICT, BRING THE CONFLICT TO THE ATTENTION

OF THE CONTRACTING OFFICER PRIOR TO THE

BEGINNING WORK RELATED TO THAT ITEM.

2. THE CONTRACTOR SHOULD PROVIDE AS-BUILT

DRAWINGS OF ALL OF THE NEW UTILITIES AND

SERVICE.

3. EXISTING LIGHT FIXTURES, BRANCH CIRCUITRY, AND

CONTROLS TO REMAIN. REROUTE CIRCUIT FROM

EXISTING PANEL TO P.84.S:1.

4. ALL CIRCUITS NOT LISTED TO REMAIN ON P.84.N.

SCALE:

B.84. DEMOLITION

3/16" = 1'-0"

E3

SCALE:

B.84. NEW WORK

3/16" = 1'-0"

E3

0 4' 8' 16'

SCALE: 3/16"= 1'-0"

2'

ETR

ETR

ETR

ETR

P.84.N

TRANSFORMER

T. P.84.N

DISCONNECT

84.E

DISCONNECT

84.N

TRANSFORMER

P.84.S:12

P.84.S:7

P.84.S:9

P.84.S:11

P.84.S:3 P.84.S:10P.84.S:6

P.84.S:8

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

JAMIE WHITTEN DELTA STATES RESEARCH CENTER

HATCHERY COMPLEX ELECTRICAL ADDITION

STONEVILLE, MS

POWER PLAN

E3 4 808/16/2024

BSN

TMT

DRL

ETR

ETR

P.84.S

P.84.N

ETR

ATS. P.84. 6

SPD

P.84.S:26,28,30

SPD

P.84.N:19,21,23

GENERAL NOTES

1. VERIFY EXISTING CONDITIONS, WHEN SPECIFIC

INFORMATION IS INCORRECT, MISSING OR IS IN

CONFLICT, BRING THE CONFLICT TO THE ATTENTION OF

THE CONTRACTING OFFICER PRIOR TO BEGINNING

WORK RELATED TO THAT ITEM.

2. THE CONTRACTOR SHALL PROVIDE AS-BUILT

DRAWINGS OF ALL OF THE NEW UTILITIES AND

SERVICE.

120v

B

208v

208v

120v 120v

N

C

A

120.0000°

30.0000°

SCALE:

POWER POLE DETAIL

N.T.S.

E4

SCALE:

GREENHOUSE ELECTRICAL EQUIPMENT

MOUNTING DETAIL

N.T.S.

E4

SCALE:

TRENCH DETAIL

N.T.S.

E4

KEYED NOTES:

NEW PVC COATED GALVANIZED RIGID

STEEL CONDUIT. SIZE AS REQUIRED FOR

CONDUCTORS.

NEW NEMA 4XSS ELECTRICAL PANEL

"P.GH.N".

NEW NEMA STANDBY PANEL P.GH.S

NEW C6X8.2 GALVANIZED STEEL CONTROL

PANEL SUPPORT. HOT DIP GALVANIZE

AFTER FABRICATION.

NEW P1001 UNISTRUT

NEW UNDERGROUND POWER SUPPLY.

NEW 24" DIA.x30" DEEP CONCRETE

FOOTINGS FOR NEW CONTROL PANEL

SUPPORT.

PROVIDE GROUNDING BUS BAR

NEW UTILITY PRIMARY

NEW UTILITY POLE

NEW SURGE ARRESTOR

NEW SURGE ARRESTOR AND NEUTRAL GROUND

NEW EQUIPMENT SUPPORT

FUSED CUTOUT

NEW TRANSFORMER

WEATHERHEAD RMC 2"Ø.

BARE COPPER GROUND

RMC 2"Ø.

METER BASE (TYP OF 2)

3/4" X 10' COPPER GROUND ROD

PVC-RMC ADAPTER

SURGE ARRESTOR

FUSED CUTOUT

TRANSFORMER

WEATHERHEAD RMC 2"Ø.

RMC 2"Ø.

1 1

7 7

FINISHED GRADE

COMPACTED METERIAL

MARKER TAPE

CONDUIT(S)

SAND

2" 2"

SCALE:

RECPTACLE DETAIL

N.T.S.

E4

SCALE:

GEN PAD

N.T.S.

S100

(2) #5 BARS CONTINUOUS

3"

1'-4"

1/2" CHAMFER ALL

EXPOSED EDGES

(TYPICAL)

EQUIPMENT PAD

AS SPECIFIED

6"

TURNDOWN

PROVIDE APPROX 8" CLEAR

AROUND ALL EQUIPMENT SIDES

TURN-DOWN (TYP.

ALL SIDES)

UNDISTURBED OR

COMPACTED/STABLE

NATIVE SOIL

QUAD RECEPTACLE

CEILING STRAIN RELIEF

P.GH.N P.GH.S

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

JAMIE WHITTEN DELTA STATES RESEARCH CENTER

HATCHERY COMPLEX ELECTRICAL ADDITION

STONEVILLE, MS

DETAILS

E4 5 808/16/2024

BSN

TMT

DRL

SO CABLE

SINGLE RECEPTACLE

CEILING STRAIN RELIEF

SO CABLE

ATS.GH

1'-6"

SCALE:

NEUTRAL AND GROUNDING DIAGRAM

N.T.S.

E4

MBJ MAIN BONDING JUMPER

SBJ SYSTEM BONDING JUMPER

SSBJ SUPPLY SIDE BONDING JUMPER

EGC EQUIPMENT GROUNDING CONDUCTOR

GEC GROUNDING ELECTRODE CONDUCTOR

NC NEUTRAL CONDUCTOR

GE GROUNDING ELECTRODE

GES GROUNDNG ELECTRODE SYSTEM

ISBT INTERSYSTEM BONDING TERMINATION

EBJ EQUIPMENT BONDING JUMPERS

BJ GROUNDING ELECTRODE SYSTEM BONDING JUMPER

ABBREVIATIONS:

NEW P.84.N (B84)

SE RATED

N

G

N

G

NEW P.84.S (B84)

EBJ

EBJ

TRANSFORMER

MBJ

N

G

BMGB (B84)

2 31

WATER PIPE

(MAIN SERVICE)

BUILDING

STEEL

#4(G), 3/4" PVC C.

#6(G), 3/4" PVC C.

SBB (GH)

WATER PIPE

(MAIN SERVICE)

BUILDING

STEEL

#4(G), 3/4" PVC C.

#6(G), 3/4" PVC C.

3/4"X10' COPPER

CLAD DRIVEN

GROUND ROD

#3/0(G), 1" PVC C.

#3/0 AWG BARE COPPER

GROUDING CONDUCTOR

BURIED 30" BELOW GRADE.

FUTURE BY OTHERS

N

G

NEW ATS.84.S (B84)

EBJ

3/4"X10' COPPER

CLAD DRIVEN

GROUND ROD

#3/0(G), 1" PVC C.

#3/0 AWG BARE COPPER

GROUDING CONDUCTOR

BURIED 30" BELOW GRADE.

N

G

NEW GENERATOR

EBJ

3/4"X10' COPPER

CLAD DRIVEN

GROUND ROD

#3/0(G), 1" PVC C.

#3/0 AWG BARE COPPER

GROUDING CONDUCTOR

BURIED 30" BELOW GRADE.

GEN-G(GH)

GEN-N(GH)

NEW P.84.N (B84)

SE RATED

N

G

N

G

NEW P.84.S (B84)

EBJ

EBJ

MBJ

N

G

NEW ATS.84.S (B84)

EBJ

GEN-N(GH)

GEN-G(GH)

PROVIDE GROUNDING BUSBAR

MINIMUM 4" WIDE AND 1/4"

THICK.4 5 2 31

PROVIDE GROUNDING BUSBAR

MINIMUM 2" WIDE AND 1/4" THICK.

MOUNT 36" ABOVE GRADE.4 5

GROUNDING NOTES

1. PROVIDE CONNECTION TO ANY ADDITIONAL

GROUNDS IN THIS ROOM USING INSULATED #6 AWG

IN 3/4" PVC. C.

2. PROVIDE CONNECTIONS TO HVAC/CRAC UNITS IN

THE ROOM USING INSULATED #6 AWG.

3. PROVIDE CONNECTION TO BUILDING STEEL IF

ACCESSIBLE IN ROOM USING INSULATED #4 AWG.

4. BUSBAR MUST BE TIN PLATED COPPER WITH

PRE-DRILLED HOLES FOR USE WITH TWO-HOLE

COMPRESSION LIGHTS WITH 5/16" OR 7/16" BOLT

HOLES.

5. GROUND CONNECTION TO EXTERIOR GROUND MUST

BE EXOTHERMIC TYPE. ALL OTHER GROUND

CONNECTIONS MUST BE TWO HOLE BOLTED

CONNECTIONS.

SPD SPD

GEN1

100kVA

GEN2

75kVA

UTILITY TFMR

500kVA 480Y/277V

3PH/4W

MAIN

800AF

600AT

2 SETS:

4#500kCMIL

B.

P.

E

0A

F

AT

.P

.E

0A F

AT

A.

P.

ED

P

0A F

AT

.P

.H V1

0A

F

AT

.P

.E

0A F

ATW

0A

F

AT

ED

P2

.N

0A F

5A

T

ED

P1

.N

0A F

0A

T

A.

P.

HV

0A F

5A

T46

0A F

0A

T

.P

.N

0/3

BLDG

BLDG

47A

BLDG

47B

BLDG

BLDG

BLDG

WELL

WO1

BLDG

47C

B.

P.

N

0/3

WELL

WO3

WELL

WO2

WELL

WO4

.P

.N

0/3

B

0/3 47

C

0/2

175/3

RK1

B.

P.

E

0A

F

ATEL

0A F

AT

SP

AR

E

0/3 SP

D

0/3

MAIN.SWBD -480Y/277V, 3PH, 4WI, 1200AF, 35KAIC OUTSIDE CONSTRUCTION

E N E N E N E N N N E N E NE ENN

MAIN.SWBD.MDP - 1200A BUSMAIN.SWBD.EDP2 - 400A PANELBOARDMAIN.SWBD.EDP1 - 400A PANELBOARD

.P

.A

5/3

.P

.B

0/3

47B.P.NH 400AF

W

0/3

48.P.N 400AF

W 02 60 /3

.P

.A

/3

47B.P.NL 250AF

15kVA

EL

100/3

EL

SP

AR

E

0A F

AT

.P

.N

0/3

SP

D

/3

SP

D

/360kVA

208V 3P/4W

175/3

RK1

GE

N2

.IN

0A F

5A

T

GE

N1

.IN

0A F

5A

T

BLDG

N

E

KEYED NOTES

1. DISCONNECT E AND N FOR BUILDING 84.

1. VERIFY EXISTING CONDITIONS, WHEN SPECIFIC

INFORMATION IS INCORRECT, MISSING OR IS IN

CONFLICT, BRING THE CONFLICT TO THE ATTENTION

OF THE CONTRACTING OFFICER PRIOR TO THE

BEGINNING WORK RELATED TO THAT ITEM.

2. THE CONTRACTOR SHOULD PROVIDE AS-BUILT

DRAWINGS OF ALL OF THE NEW UTILITIES AND

SERVICE.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

JAMIE WHITTEN DELTA STATES RESEARCH CENTER

HATCHERY COMPLEX ELECTRICAL ADDITION

STONEVILLE, MS

EXISTING SINGLE LINE

E5 6 808/16/2024

BSN

TMT

DRL

GENERAL NOTES

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

JAMIE WHITTEN DELTA STATES RESEARCH CENTER

HATCHERY COMPLEX ELECTRICAL ADDITION

STONEVILLE, MS

SINGLE LINE

E6 7 808/16/2024

BSN

TMT

DRL

325/3

LSI100/330/3

SPD

TYPE #2

100A4NG

'P.84.N', NEMA 1 400AF 325AT -208Y/120V, 3PHASE, 4WIRE, 22kAIC

50A2G

BLOWER

100A4NG

ATS-84

208V,100A 3P, 22kAIC

100/3

LSI

'P.84.S', NEMA 1 100A-208Y/120V, 3PHASE, 4WIRE, 22AIC

100A4NG

SPD

TYPE #2

30A4NG

T-UTIL

UTIL

350A4

100A4NG

50KW GENERATOR

200/3

LSI 60/3

'P.GH.N', NEMA 3R 225AF 200AT -208Y/120V, 3PHASE, 4WIRE, 22kAIC 200A4

60A4NG

60A4NG

ATS-GH

208V,60A 3P, 22kAIC

60A

MCB

208V

P.GH.S

60A4NG

COPPER FEEDER SCHEDULE

KEY

QTY.

OF

RUNS

CONDUCTORS C

(IN)

200A4 1 4#3/0 2-1/2 350A4 1 4#500 3-1/2

50A2G 1 2#6,1#10G 1

30A4NG 1 3#8,1#6N,1#8G 1

60A4NG 1 3#4,1#1N,1#10G 1-1/2

100A4NG 1 3#1/0,1#250N,1#4G 2-1/2

GBJ

REFER TO GROUNDING

AND BONDING JUMPER

SCHEDULE

XFMR REFER TO XFMR

SCHEDULE

REFER TO NATIONAL ELECTRICAL CODE FOR

INSTALLATION OF CONDUIT TYPE.

ALL CONDUCTORS ARE COPPER.

50/2 30/3

M M

GENERAL NOTES

1. VERIFY EXISTING CONDITIONS, WHEN SPECIFIC

INFORMATION IS INCORRECT, MISSING OR IS IN

CONFLICT, BRING THE CONFLICT TO THE ATTENTION

OF THE CONTRACTING OFFICER PRIOR TO THE

BEGINNING WORK RELATED TO THAT ITEM.

2. THE CONTRACTOR SHOULD PROVIDE AS-BUILT

DRAWINGS OF ALL OF THE NEW UTILITIES AND

SERVICE.

3. COORDINATE METERING REQUIREMENTS WITH UTILITY.

30/3

SPD

TYPE #2

30A4NG

SPD

TYPE #2

Panel Name: P.84.N MLO or Main C.B.:MCB Panel Location: B.84. Surface or Flush:SURFACE

Voltage: 120/208V Frame Amps:225 Phase/Wire: 3PH/4W Grounding:EQUIPMENT GROUND

Minimum Interrupting Rating: 225A Sections:ONE SECTION - 30X New/Existing: Existing Nema Rating:NEMA 1

Load VA Branch Load Data Breaker Breaker Branch Load Data Load VA Ph A Ph B Ph C Trip Pole No. Ph. No. Trip Pole Ph A Ph B Ph C

THREE PHASE LOAD - LHS 125 6

1 a 2 20 1 SPACE 3 b 4 20 1 SPACE 5 c 6 20 1 SPACE 7 a 8 20 1 SPACE 9 b 10 60 2 LIGHTS11 c 12

R - N WALL 20 1 13 a 14 20 1 EMERGENCY LIGHTS R - N WALL 20 1 15 b 16 30 1 OUTSIDE BLOWER R - E WALL 20 1 17 c 18 20 1 FAN

SPD 100 3

19 a 20 20 1 E LIGHTS 21 b 22 20 1 W LIGHTS 23 c 24 20 1 SPARE

R - S WALL 20 1 25 a 26 20 1 R - SOUTH WALL GATE 20 1 27 b 28 20 1 SPARE SPACE 20 1 29 c 30 20 1 SPARE

Panel Name: P.84.N MLO or Main C.B.:MCB Panel Location: B.84. Surface or Flush:SURFACE

Voltage: 120/208V Frame Amps:325 Phase/Wire: 3PH/4W Grounding:EQUIPMENT GROUND

Minimum Interrupting Rating: 325A Sections:ONE SECTION - 42X New/Existing: New Nema Rating:NEMA 1

Load VA Branch Load Data Breaker Breaker Branch Load Data Load VA Ph A Ph B Ph C Trip Pole No. Ph. No. Trip Pole Ph A Ph B Ph C

EXISTING LOAD 125 6

1 a 2 100 3 P.B84.S3 b 4

5 c 6 7 a 8 20 1 SPACE 9 b 10 60 2 LIGHTS11 c 12

R - N WALL 20 1 13 a 14 20 1 EMERGENCY LIGHTS R - N WALL 20 1 15 b 16 30 1 OUTSIDE BLOWER R - E WALL 20 1 17 c 18 20 1 FAN

SPD 100 3

19 a 20 20 1 E LIGHTS (1) 21 b 22 20 1 W LIGHTS (1) 23 c 24 20 1 SPARE

R - S WALL 20 1 25 a 26 20 1 R - SOUTH WALL GATE 20 1 27 b 28 20 1 SPARE SPACE 20 1 29 c 30 20 1 SPARE SPACE 20 1 31 a 32 20 1 SPARE SPACE 20 1 33 b 34 20 1 SPARE SPACE 20 1 35 c 36 20 1 SPACE SPACE 20 1 37 a 38 20 1 SPACE SPACE 20 1 39 b 40 20 1 SPACE SPACE 20 1 41 c 42 20 1 SPACE

P.84.N EXISTING PANEL SCHEDULE

P.84.N NEW PANEL SCHEDULE

P.84.S NEW PANEL SCHEDULE

GENERAL NOTES

1. VERIFY EXISTING CONDITIONS, WHEN SPECIFIC

INFORMATION IS INCORRECT, MISSING OR IS IN

CONFLICT, BRING THE CONFLICT TO THE ATTENTION

OF THE CONTRACTING OFFICER PRIOR TO THE

BEGINNING WORK RELATED TO THAT ITEM.

2. THE CONTRACTOR SHOULD PROVIDE AS-BUILT

DRAWINGS OF ALL OF THE NEW UTILITIES AND

SERVICE.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

JAMIE WHITTEN DELTA STATES RESEARCH CENTER

HATCHERY COMPLEX ELECTRICAL ADDITION

STONEVILLE, MS

PANEL SCHEDULES

E7 8 808/16/2024

BSN

TMT

DRL

Panel Name: P.GH.N MLO or Main C.B.: MCB Panel Location: GH Surface or Flush: SURFACE

Voltage: 120/208V Frame Amps: 225 Phase/Wire: 3PH/4W Grounding: EQUIPMENT GROUND

Minimum Interrupting Rating: 200A Sections: ONE SECTION - 30X New/Existing: New Nema Rating: NEMA 4X

Load VA LOAD

Co nt

No tes Branch Load Data Wire Breaker Breaker

No tes Wire Branch Load Data

Co nt

# LOAD Load VA Ph A Ph B Ph C TYPE Trip Pole No. Ph. No. Trip Pole TYPE Ph A Ph B Ph C

P.GH.S 60 3

1 a 2 20 1 SPARE 3 b 4 20 1 SPARE 5 c 6 20 1 SPARE

SPARE 20 1 7 a 8 20 1 SPARE SPARE 20 1 9 b 10 20 1 SPARE SPARE 20 1 11 c 12 20 1 SPARE SPARE 20 1 13 a 14 20 1 SPARE SPARE 20 1 15 b 16 20 1 SPARE SPARE 20 1 17 c 18 20 1 SPARE SPARE 20 1 19 a 20 20 1 SPARE SPARE 20 1 21 b 22 20 1 SPARE SPARE 20 1 23 c 24 20 1 SPARE SPARE 20 1 25 a 26

30 3 SPDSPARE 20 1 27 b 28 SPARE 20 1 29 c 30

Panel Name: P.GH.S MLO or Main C.B.: MCB Panel Location: GH Surface or Flush: SURFACE

Voltage: 120/208V Frame Amps: 60 Phase/Wire: 3PH/4W Grounding: EQUIPMENT GROUND

Minimum Interrupting Rating: 60A Sections: ONE SECTION - 18X New/Existing: New Nema Rating: NEMA 4X

Load VA LOAD

Co nt

No tes Branch Load Data Wire Breaker Breaker

No tes Wire Branch Load Data

Co nt

# LOAD Load VA Ph A Ph B Ph C TYPE Trip Pole No. Ph. No. Trip Pole TYPE Ph A Ph B Ph C

SPARE 20 1 1 a 2 20 1 SPARE SPARE 20 1 3 b 4 20 1 SPARE SPARE 20 1 5 c 6 20 1 SPARE SPARE 20 1 7 a 8 20 1 SPARE SPARE 20 1 9 b 10 20 1 SPARE SPARE 20 1 11 c 12 20 1 SPARE SPARE 20 1 13 a 14

30 3 SPDSPARE 20 1 15 b 16 SPARE 20 1 17 c 18

Panel Name: P.84.S MLO or Main C.B.:MCB Panel Location: B.84. Surface or Flush:SURFACE

Voltage: 120/208V Frame Amps:100 Phase/Wire: 3PH/4W Grounding:EQUIPMENT GROUND

Minimum Interrupting Rating: 100A Sections:ONE SECTION - 24X New/Existing: New Nema Rating:NEMA 1

Load VA Branch Load Data Breaker Breaker Branch Load Data Load VA Ph A Ph B Ph C Trip Pole No. Ph. No. Trip Pole Ph A Ph B Ph C 441 LIGHTING (1) 20 1 1 a 2 50 2 BLOWER (1) 182

1398 UV/PUMP 20 1 3 b 4 182 SPARE 20 1 5 c 6 20 1 HEATER (1) 1800

1800 HEATER 20 1 7 a 8 20 1 HEATER (1) 1800 1800 HEATER 20 1 9 b 10 20 1 UV&PUMP (1) 1398

1800 HEATER 20 1 11 c 12 20 1 UV/PUMP 699 SPARE 20 1 13 a 14 20 1 SPARE SPARE 20 1 15 b 16 20 1 SPACE SPARE 20 1 17 c 18 20 1 SPACE SPACE 20 1 19 a 20 20 1 SPACE SPACE 20 1 21 b 22 20 1 SPACE SPACE 20 1 23 c 24 20 1 SPACE SPACE 20 1 25 a 26

30 3 SPDSPACE 20 1 27 b 28 SPACE 20 1 29 c 30

P.GH.N NEW PANEL SCHEDULE

P.GH.S NEW PANEL SCHEDULE

Sheets and Views
T1
E1
E2
E3
E4
E5
E6
E7