Attachment 3 Drawings.pdf

PDF 14 MB Posted

Attached to
Upgrade Phase III Chiller - Athens, GA Federal contract opportunity
Solicitation number
1232SA25R0014
Issued by
Department of Agriculture Agricultural Research Service

About this file

These engineering design drawings detail a Phase 3 Chiller Upgrade project for the USDA Agricultural Research Service at the Richard B. Russell Agricultural Research Center located at 950 College Station Road in Athens, Georgia. The comprehensive set of 17 architectural and engineering drawings includes mechanical, electrical, and demolition plans for replacing an existing 500-ton chiller (CH-1) with a new water-cooled centrifugal chiller. The drawings specify technical requirements for removing existing equipment, installing new chiller and pump systems, modifying electrical infrastructure, and upgrading plant controls, with specific details on piping, electrical connections, equipment schedules, and system integration.

Key technical specifications include installing a new 900-ton water-cooled centrifugal chiller (CH-1), a new chilled water pump (CHWP-1), 12-inch condenser water piping, 10-inch chilled water piping, and updating the electrical system with a new tap box and power connections. The design incorporates variable primary flow configuration, direct digital controls, and includes provisions for chiller staging, pump control, and integrated monitoring systems. The project involves precise demolition of existing infrastructure, new equipment installation, and comprehensive mechanical and electrical system upgrades to improve the facility's cooling capabilities.

View the file

Other files for this federal contract opportunity

Other files attached to Upgrade Phase III Chiller - Athens, GA, newest first.
File Type Posted
Attachment 1 Specifications.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COR

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\T

-1

.d w g A pr

5,

- 9 :2

2a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

T-101

TITLE SHEET

INDEX OF DRAWINGS

SHEET NO. DRAWING NO. TITLE

T-101 1 OF 17 TITLE SHEET

AD101 2 OF 17 DEMOLITION FLOOR PLAN

A-101 3 OF 17 FLOOR PLAN

A-102 4 OF 17 DETAILS

M-001 5 OF 17 MECHANICAL LEGEND

MD101 6 OF 17 MECHANICAL DEMOLITION PLAN

MD501 7 OF 17 MECHANICAL DEMOLITION DETAILS

MD502 8 OF 17 MECHANICAL DEMOLITION DETAILS

M-101 9 OF 17 MECHANICAL PLAN

M-501 10 OF 17 MECHANICAL DETAILS

M-502 11 OF 17 MECHANICAL DETAILS

M-601 12 OF 17 MECHANICAL EQUIPMENT SCHEDULES

M-701 13 OF 17 CHILLER PLANT CONTROLS

E-001 14 OF 17 ELECTRICAL LEGEND

ED101 15 OF 17 ELECTRICAL DEMOLITION

E-101 16 OF 17 ELECTRICAL FLOOR PLAN

E-501 17 OF 17 ELECTRICAL DETAILS AND SCHEDULES

USDA

LOCATION MAPVICINITY MAP

U.S. DEPARTMENT OF AGRICULTURE

AGRICULTURAL RESEARCH SERVICE

UPGRADE CHILLER - PHASE 3, ATHENS GA

DESIGN CONTRACT NO: 12405B21D0003

DESIGN ORDER NO: 12405B24F0343

RICHARD B. RUSSELL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD

ATHENS, GA 30605

GENERAL NOTE:

THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO PERFORMING WORK, FABRICATION OR PURCHASE OF ANY EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DISCREPANCIES SHALL BE BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.

DOWNTIME DURING INSTALLATION MUST BE MINIMIZED. INSTALLATION MUST BE COORDINATED WITH THE SITE OPERATION

SCHEDULE. BELTSVILLE AGRICULTURAL RESEARCH CENTER

10300 BALTIMORE AVENUE

BELTSVILLE, MD 20705

PROJECT LOCATION

CO

LLEG

E STATIO

N RO

AD

ATLANTA

PROJECT LOCATION

AUGUSTA

MACON

DALTON

JND

X9 X10 X11 X12

XA

XB

XC

XE

EXISTING DOOR TO REMAIN

EXISTING DOOR TO REMAIN

AREA OF WORK

EXISTING DOOR TRACK TO REMAIN.

JAMB CHANNEL TO REMAIN.

8'- 6"

EXISTING DOOR

PANEL TO REMAIN. EXISTING POST BRACE. REMOVE AFTER

HEADER ANGLES AND JAMB CHANNEL

ARE INSTALLED AND MADE SECURE.

CUT POST FLUSH WITH BOTTOM OF

EXISTING STEEL PLATE AND GRIND

SMOOTH. REMOVE BASE PLATE

ANCHORS TO BELOW FINISHED FLOOR.

GROUT HOLES WITH 4000PSI

NON-SHRINK EPOXY GROUT. STRIKE

SMOOTH WITH FLOOR.

EXISTING DOOR

PANEL TO REMAIN.

SAW CUT CMU EDGES SMOOTH

STEEL PLATE TO REMAIN. SEE DETAIL 1/A-102

COR

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\A rc h\

Fi na l\A D

1.

dw g

A pr

5,

- 9

:1 9a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

AD101

DEMOLITION FLOOR PLAN

SCALE:

DEMOLITION FLOOR PLAN

1/8" = 1'-0"

AD-101

NORTH

SCALE:

DEMOLITION ELEVATION

1/2" = 1'-0"

AD-101

MM

AD101

GRAPHIC SCALE

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

4'

SCALE: 1/2"=1'-0"

0 1' 2' 8'

X9 X10 X11 X12

XB

XC

XE

2'-

7"

EXISTING

SLIDING DOOR

EXISTING

SLIDING DOOR

8'- 6"

'-7

NEW 12"X3" CHANNEL

EXISTING 12"X3" CHANNEL. GRIND ALL

WELDS, EXISTING AND NEW, SOOTH,

PREP AND PAINT AS SPECIFIED

NEW 4" x 3" x 3/16" STEEL ANGLE

EACH SIDE OF OPENING

A-101

SCALE:

FLOOR PLAN

1/8" = 1'-0"

A-101

GRAPHIC SCALE

NORTH

COR

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\A rc h\

Fi na l\A -1

.d w g

A pr

5,

- 9

:1 9a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

SCALE:

ELEVATION

1/2" = 1'-0"

A-101

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

MM

A-102

A-101

A-102

2'-5"

FLOOR PLANCOR

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\A rc h\

Fi na l\A -1

.d w g

A pr

5,

- 9

:1 9a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

T:

\20

P ro jec ts\

-M

U

SD

A Ph as e 3

C hil ler U pg ra de s -

A the ns G

A\

W or kin g F old er

\A rch

\F ina l\A -1

.dw g A pr

, 2

5 - 9:

am

4'

SCALE: 1/2"=1'-0"

0 1' 2' 8'

HEAD

EXISTING 12"X8"X16"

CMU BLOCK

CHANNEL AT JAMB BEYOND

4"X3"X316" STEEL ANGLE

TYP.

REMOVE STEEL POST COMPLETE.

GRIND SMOOTH AT STEEL PLATE

EXISTING STEEL PLATE

3/16

CONT.

EXISTING CHANNEL

SECTION AT BASE SECTION AT BASE

1" 2"

EXISTING CONCRETE

FLOOR

58" DIA X 4" EXPANSION ANCHOR

12"X3"" CHANNEL

1" 2"

12"X3" CHANNEL

58" DIA X 4" EXPANSION ANCHOR

EXISTING CMU BLOCK

3/16

CONT.

3/16

CONT.

SEALANT TYP. AT BLOCK CONNECTION

EXISTING 12"X8"X16"

CMU BLOCK

12"X3" CHANNEL

58" DIA X 4" EXPANSION

ANCHOR BELOW

58" DIA X 4" EXPANSION

ANCHOR BELOW

12"X3" CHANNEL

EXISTING 12"X3" CHANNEL.

STRAIGHTEN CHANNEL AND GRIND

EXISTING WELDS SMOOTH

JAMB SECTION AT LARGE DOOR OPENING JAMB SECTION AT CMU

3/16

CONT.

3/16

CONT.

PROVIDE GROUT REPAIRS

AT DAMAGED CMU (TYP.

BOTH SIDES OF WALLS)

A-102

DETAILS

GRAPHIC SCALE

COR

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\T

LO

VE

L~

1.

JM

C \A pp D at a\

Lo ca l\T em p\ Ac

Pu bl is h_

0\ A-

2.

dw g

A pr

5,

- 9

:2 0a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

SCALE: 3"=1'-0"

3"0 6" 1'

MM

SCALE:

DOOR SILL DETAILS

3" = 1'-0"

A-102

SCALE:

JAMB DETAILS

3" = 1'-0"

A-102

SCALE:

HEAD DETAIL AT OPENING

3" = 1'-0"

A-102

C:

\U se rs\

TL

OV

EL

~1

.JM

C\

Ap pD ata \Lo ca l\T em p\A cP ub lis h_

0\A -1

.dw g A pr

, 2

5 - 9:

am

GENERAL NOTES:

1. ALL EXISTING AND NEW STEEL MUST BE

CLEANED, PRIMED, AND PAINTED

2. PAINT CMU AROUND DOOR OPENINGS.

MUST BE PAINTED TO MATCH EXISTING

CMU WALLS

A-102

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\M ec h\

M -0

.d w g

A pr

5,

- 7

:4 4a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

M-001

MECHANICAL LEGEND

1. THIS PROJECT IS A RENOVATION OF AN EXISTING FACILITY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS MUST BE BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY

CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.

2. INSTALLATION OF HVAC WORK MUST BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS DONE. PIPING SHOWN ON PLANS IS SCHEMATIC. PROVIDE ALL TRANSITIONS, ELBOWS, REDUCERS, ETC. REQUIRED TO AVOID

CONFLICTS.

3. WRITTEN DIMENSIONS ON DRAWINGS MUST HAVE PRECEDENCE OVER SCALED DIMENSIONS. VERIFY DIMENSIONS ON SITE.

4. EQUIPMENT MUST BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE, USDA ARS 242.1, AND

INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.

5. INSTALLATION OF EQUIPMENT MUST PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT

NECESSITATING REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.

6. CONTRACTOR MUST COORDINATE WALL, FLOOR, AND ROOF PENETRATIONS.

7. CAULK WITH SILICONE ALL GAPS BETWEEN WALL, CEILING, AND FLOOR OPENINGS AND PIPING PENETRATIONS. PATCH LARGE GAPS BEFORE CAULKING IS APPLIED. PROVIDE FIRESTOPPING FOR ALL FIRE/SMOKE RATED WALLS, FLOORS, AND

CEILINGS.

8. EXACT LOCATIONS OF CONTROL DEVICES MUST BE COORDINATED WITH THE CONTROLS CONTRACTOR.

9. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.

10. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.

11. ALL EQUIPMENT INSTALLED IN THIS PROJECT MUST COMPLY WITH THE "BUY AMERICAN ACT". BASIS OF DESIGN

SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM ANOTHER MANUFACTURER IS ACCEPTABLE. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY. REFER TO SPECIFICATIONS FOR COMPLETE

REQUIREMENTS.

12. CONTROLS CONTRACTOR MUST PROVIDE ALL LOW VOLTAGE DEVICES, CONDUCTORS, AND PATHWAYS IN ACCORDANCE WITH THE REQUIREMENTS OF 26 20 00. INSTALL CONTROL WIRING IN CONDUIT. SEE DIVISION 26 SPECIFICATIONS FOR

REQUIREMENTS.

HVAC GENERAL NOTES:

1. THE DEMOLITION PLANS AND EXISTING CONDITIONS SHOWN ARE APPROXIMATE AND ARE TO BE FIELD VERIFIED. ITEMS TO

BE REMOVED ARE DENOTED BY HATCHING.

2. DEMOLITION MUST INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS IDENTIFIED. THE CONTRACTOR MUST COORDINATE ALL REQUIRED RENOVATION AND NEW CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL EXTENT OF THE

DEMOLITION WORK REQUIRED.

3. THE CONTRACTOR IS RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF ALL EXISTING BUILDING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES AS REQUIRED TO BUILD, ERECT, INSTALL, OR ACCOMMODATE ALL NEW

CONSTRUCTION.

4. IN THE EVENT THE CONTRACTOR ENCOUNTERS MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR MUST

IMMEDIATELY REPORT THE CONDITION TO THE CONTRACTING OFFICER IN WRITING.

5. THE CONTRACTOR IS RESPONSIBLE FOR THE ERECTION, MAINTENANCE, AND REMOVAL OF ALL CONSTRUCTION

ASSISTANCE DEVICES SUCH AS SCAFFOLDING AND BARRIERS.

6. THE BUILDING ENVELOPE MUST REMAIN WATERTIGHT THROUGHOUT THE CONSTRUCTION PROCESS.

7. IF IT BECOMES NECESSARY DURING DEMOLITION TO TEMPORARILY REMOVE ANY EXISTING WORK NOT SPECIFICALLY NOTED TO BE REMOVED OR RELOCATED (THEREBY IMPLYING THAT THEY ARE TO BE LEFT FOR FUTURE USE), THE CONTRACTOR MUST REINSTALL SAID WORK TO FULLY OPERABLE CONDITION IN THEIR ORIGINAL LOCATIONS

8. CONTRACTOR MUST DEMOLISH ALL EQUIPMENT, PIPING, INSULATION, SUPPORTS, CONTROLS THERMOSTATS, WIRING

AND ALL APPURTENANCES WITH THE HVAC SYSTEM TO BE DEMOLISHED.

HVAC GENERAL DEMOLITION NOTES:

ABBREVIATIONS:

AFF ABOVE FINISHED FLOOR

ARCH ARCHITECTURAL

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING,

AND AIR CONDITIONING ENGINEERS

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS

APD AIR PRESSURE DROP

BLDG BUILDING

BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR

CHW CHILLED WATER

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CONN CONNECT, CONNECTING, CONNECTION

CONT CONTINUED

COR CONTRACTING OFFICER'S (OWNER'S)

REPRESENTATIVE

CW CONDENSER WATER

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

DDC DIRECT DIGITAL CONTROLS

DEG F (°F) DEGREES FAHRENHEIT

DIA, Ø DIAMETER

DIV DIVISION

DN DOWN

DP DIFFERENTIAL PRESSURE

DWG DRAWING

DX DIRECT EXPANSION

(E) EXISTING (USED WITH EQUIPMENT MARKS)

EA EXHAUST AIR

EAG EXHAUST AIR GRILLE

EFF EFFICIENCY

ELEC ELECTRICAL

EMCS ENERGY MONITORING AND CONTROLS SYSTEM

EWT ENTERING WATER TEMPERATURE

EXT EXTERIOR

EXH EXHAUST

FFE FINISHED FLOOR ELEVATION

FLA FULL LOAD AMPS

FPD FLUID PRESSURE DROP

FSD FIRE SMOKE DAMPER

FT FOOT, FEET

FT H20 FEET OF WATER

GA GAUGE

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

HP HORSEPOWER

HR HOUR

HTG HEATING

HVAC HEATING, VENTILATING, AND AIR CONDITIONING

HZ HERTZ

IMC INTERNATIONAL MECHANICAL CODE

IN, IN. INCH, INCHES

IN WG INCHES WATER GAUGE

LB POUNDS

LRA LOCKED ROTOR AMPS

LWT LEAVING WATER TEMPERATURE

MBH 1000 BRITISH THERMAL UNITS

MCA MINIMUM CIRCUIT AMPACITY

MECH MECHANICAL

MIN MINIMUM

MOCP MAXIMUM OVER CURRENT PROTECTION

PH PHASE

PRV PRESSURE RELIEF VALVE

PSI POUNDS PER SQUARE INCH

QTY QUANTITY

RLA RUNNING LOAD AMPS

RPM REVOLUTIONS PER MINUTE

TEMP TEMPERATURE

TYP TYPICAL

UL UNDERWRITER'S LABORATORY

UMCS UTILITY MONITORING AND CONTROL SYSTEM

V VOLTAGE, VOLTS

VFD VARIABLE FREQUENCY DRIVE

NORTH ARROW

PLAN

NORTH

HATCHING INDICATES ITEMS TO

BE DISMANTLED AND REMOVED.

DEMOLITION LEGEND:

EXISTING EQUIPMENT

CH-1 (E) (E) AFTER AN EQUIPMENT

MARK INDICATES EXISTING

TRUE NORTH

X9 X10 X11 X12X8

XB

XC

XE

X7X6

M V

MV

MV

M V

VF

D

VF

D

VF

D

VF

D

CHWP-2 (E)

CWP-2 (E)

CWP-1 (E)

CH-2 (E)

CH-1 (E)

CHWP-1 (E)

CT-2 (E)

CT-2 (E)

EXISTING 10" CHILLED WATER

SUPPLY AND RETURN

EXISTING 12" CONDENSER

WATER SUPPLY AND RETURN

COR

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\T

LO

VE

L~

1.

JM

C \A pp D at a\

Lo ca l\T em p\ Ac

Pu bl is h_

6\ M

D

1.

dw g A pr

5,

- 7 :4

4a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

MD101

MECHANICAL DEMOLITION PLAN

KEYED NOTES

1. DISMANTLE AND REMOVE EXISTING 500 TON CHILLER, CH-1,

AND ALL APPURTENANCES.

2. DISMANTLE AND REMOVE EXISTING CHILLED WATER PUMP,

CHWP-1, AND ALL APPURTENANCES.

3. DISMANTLE AND REMOVE EXISTING CONDENSER WATER

SUPPLY AND RETURN PIPING, HANGERS AND ALL

APPURTENANCES.

4. DISMANTLE AND REMOVE EXISTING CHILLED WATER SUPPLY

AND RETURN PIPING, INSULATION, HANGERS AND ALL

APPURTENANCES..

5. EXISTING EQUIPMENT/PIPING TO REMAIN.

08' 8'

1'-0"

4'

SCALE: 1/8" =

GRAPHIC SCALE

NORTH

MECHANICAL DEMOLITION PLAN1

SCALE: 1/8" = 1'-0"MD101

JND

MD501

MD501

MD502

MD502

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\T

LO

VE

L~

1.

JM

C \A pp D at a\

Lo ca l\T em p\ Ac

Pu bl is h_

6\ M

D

1.

dw g A pr

5,

- 7 :4

4a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

MD501

MECHANICAL DEMOLITION DETAILS

MECHANICAL DEMOLITION DETAIL1

SCALE: NONEMD501

EXISTING 12" CONDENSER

WATER PIPING TO REMIAN

CLOSE CONDENSER WATER

SUPPLY VALVE

DISMANTLE AND REMOVE EXISTING

CONDENSER WATER PIPING FROM

EXISTING VICTAULIC CLAMP TO CH-1

MECHANICAL DEMOLITION DETAIL2

SCALE: NONEMD501

TIE IN TO POINT FOR 12" CONDENSER

WATER PIPING TO CH-1

CLOSE CONDENSER WATER

RETURN VALVE

EXISTING 12" CONDENSER

WATER TO REMAIN

DISMANTLE AND REMOVE EXISTING

CONDENSER WATER PIPING FROM

CH-1 TO VALVE AS SHOWN

TIE IN TO POINT FOR 12" CONDENSER

WATER PIPING FROM CH-1

CWP-2 (E)

CWP-1 (E)

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\M ec h\

M D

2.

dw g

A pr

5,

- 7

:4 4a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

MD502

MECHANICAL DEMOLITION DETAILS

MECHANICAL DEMOLITION DETAIL1

SCALE: NONEMD502

DISMANTLE AND REMOVE EXISTING

CHILLED WATER PUMP, CHWP-1

DISMANTLE AND REMOVE EXISTING

8" CHILLED WATER PIPING

DISMANTLE AND REMOVE

EXISTING CHILLER, CH-1

CHILLED WATER TIE IN POINT. CLOSE

CHILLED WATER VALVE. VALVE IS

NOT VISIBLE IN THIS PICTURE.

MECHANICAL DEMOLITION DETAIL2

SCALE: NONEMD502

DISMANTLE AND REMOVE EXISTING

CHILLED WATER PUMP, CHWP-1

CHILLED WATER TIE IN POINT.

CLOSE CHILLED WATER VALVE.

DISMANTLE AND REMOVE EXISTING

8" CHILLED WATER PIPING

XB

XC

XE

X7X6

M V

MV

MV

M V

VF

D

VF

D

VF

D

VF

D

CHWP-2 (E)

CWP-2 (E)

CWP-1 (E)

CH-2 (E)

CH-1

CHWP-1

CT-2 (E)

CT-1 (E)

EXISTING 10" CHILLED WATER

SUPPLY AND RETURN

EXISTING 12" CONDENSER

WATER SUPPLY AND RETURN

COR

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\M ec h\

M -1

.d w g

A pr

5,

- 7

:4 4a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

M-101

MECHANICAL PLAN

KEYED NOTES

1. PROVIDE WATER COOLED CENTRIFUGAL CHILLER AND

HOUSEKEEPING PAD. INSTALL CHILLER ON MANUFACTURER

PROVIDED VIBRATION ISOLATORS.

2. PROVIDE CHILLED WATER PUMP AND CONCRETE INERTIA

BASE WITH VIBRATION ISOLATORS.

3. PROVIDE 12" CONDENSER WATER SUPPLY FROM TIE IN POINT

TO CHILLER AS SHOWN.

4. PROVIDE 12" CONDENSER WATER RETURN FROM CHILLER TO

TIE IN POINT AS SHOWN.

5. PROVIDE 10" CHILLED WATER RETURN FROM CHWP-1 TO CH-1

AS SHOWN. PROVIDE INSULATION PER SPECIFICATIONS.

6. PROVIDE 10" CHILLED WATER SUPPLY FROM CH-1 TO TIE IN

POINT AS SHOWN. PROVIDE INSULATION PER

SPECIFICATIONS.

7. PROVIDE REFRIGERANT RELIEF DISCHARGE PIPING AS

SHOWN. TERMINATE AS HIGH ON WALL AS POSSIBLE.

TERMINATE PIPE INSIDE A WALL-CAP WITH BIRD SCREEN.

PRIME AND PAINT WALL CAP TO MATCH BUILDING EXTERIOR.

REFER TO DETAILS.

8. AREA BETWEEN CHILLERS TO REMAIN OPEN FOR TUBE

REPLACEMENT AND CLEANING.

9. NEW CHILLED WATER PUMP TO BE CONNECTED TO EXISTING

VFD. ADJUST AMPERAGE AND HORSEPOWER SETTINGS IN

VFD FOR NEW PUMP.

08' 8'

1'-0"

4'

SCALE: 1/8" =

GRAPHIC SCALE

NORTH

MECHANICAL PLAN1

SCALE: 1/8" = 1'-0"M-101

GENERAL NOTES

1. PROVIDE ALL REQUIRED PIPE HANGERS, FASTENERS AND

GASKETS. REFER TO SPECIFICATIONS.

2. PROVIDE ALL REQUIRED ANCHOR BOLTS, STRUCTURAL STEEL

MEMBERS, AND CONCRETE FOR INERTIA BASE AND

HOUSEKEEPING PAD.

JND

M-501

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\M ec h\

M -5

.d w g

A pr

5,

- 7

:4 4a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

M-501

MECHANICAL DETAILS

SEE DRAWINGS FOR CONTINUATION

14 GA GALVANIZED STEEL PLATE

SECURED TO WALL EXTENDING MIN

6-INCHES OUT FROM PIPE PENETRATION

RUPTURE DISC ASSEMBLY

PURGE DISCHARGE VENT LINE

FLEXIBLE STEEL CONNECTION

CHILLER

MIN 9"

DRIP LEG (LENGTH AS REQUIRED

FOR EASY ACCESS)

1/4" FL x 1/4" NPT DRAIN VALVE

NOTE

RELIEF PIPE SIZES AND QUANTITY

OF CONNECTIONS VARY BY CHILLER

MANUFACTURER. SIZE AND INSTALL

PIPING AS RECOMMENDED BY THE

CHILLER MANUFACTURER'S

LITERATURE.

SEAL AROUND PIPE

PENETRATION AIR-TIGHT

CHILLER REFRIGERANT

RELIEF VENT

COMPLETELY FILL IN ANNULAR

SPACE AROUND PIPE WITH

NON-SHRINK GROUT FOR AN

AIR-TIGHT INSTALLATION

INTERIOR OF WALL EXTERIOR OF WALL

GALVANIZED STEEL WALL

CAP WITH BIRD SCREEN,

PRIMED AND PAINTED TO

MATCH BUILDING EXTERIOR

4.5" LIQUID-FILLED

PRESSURE GAUGE WITH

304 STAINLESS STEEL

CASE (RANGE 0-60 PSI)

9" RED LIQUID-IN-GLASS

THERMOMETER WITH CAST

ALUMINUM CASE AND

ADJUSTABLE ANGLE STEM

SNUBBER

FULL-PORT BALL VALVE WITH

EXTENDED VALVE STEM AND

STAND-OFF FOR

INSTALLATION OF INSULATION

WELD-ON THREADOLET (TYP)

CHILLED OR CONDENSER

WATER PIPE

PRESSURE GAUGE P/T PORT

PRESSURE AND

TEMPERATURE

PLUG WITH CAP

(DESIGN BASIS:

PETE'S PLUG II)

AUTOMATIC AIR VENT

FULL-PORT BALL VALVE

WITH EXTENDED VALVE

STEM AND STAND-OFF

FOR INSTALLATION OF

INSULATION

REDUCERS AS

REQUIRED (TYP)

WELL LENGTH SHALL REACH

APPROXIMATELY HALFWAY INTO PIPE

AUTOMATIC AIR VENT THERMOMETER

NOTES

1. ALL CHILLED WATER PIPE IS INSULATED AND JACKETED. INSULATION IS NOT SHOWN FOR CLARITY. PROVIDE EXTENDED NECK VALVE STEMS AND

EXTENDED FITTINGS FOR INSULATED PIPES.

2. ALL GAUGES SHALL BE MOUNTED IN THE VERTICAL POSITION. PROVIDE ELBOWS FOR PRESSURE GAUGES LOCATED IN VERTICAL PIPES AND

ROTATE THERMOMETER STEMS AS REQUIRED SO THAT ALL GAUGES AND THERMOMETERS ARE INSTALLED VERTICALLY REGARDLESS OF THE

ORIENTATION OF THE CHILLED WATER PIPE.

3. PROVIDE ULTRAVIOLET PROTECTIVE PLASTIC WINDOW AND WEATHERPROOF CASE FOR ACCESSORIES IN EXTERIOR LOCATIONS.

DUAL TEMPERATURE SCALE

CHW: (0-100 DEG F / -18-38 DEG C)

CW: (30-130 DEG F / 0-55 DEG C)

COUPLING NUT AND

304 SS STEM

THERMOWELL - LAGGING

EXTENSION TYPE FOR

INSULATED PIPES

PAINT TOP OF NEW PAD TO MATCH

EXISTING GRAY CONCRETE EPOXY

COATING AND SHEEN

#5 BARS, 16" O.C.

EACH WAY

PREP AND REPAINT TOP OF

EXISTING PAD CHW OR CW OUT

6-INCH TALL CONCRETE

HOUSEKEEPING PAD EXTENSION

WITH CHAMFERED EDGE - PAINT

FACE OF EDGE SAFETY YELLOW

5" LONG #5 BARS, 12" O.C. WITH 2.5"

EMBED - SECURE BARS IN EXISTING

CONCRETE PAD WITH EPOXY

CHW OR CW IN

MANUAL BUTTERFLY VALVE

PRESSURE GAUGE (TYP)

TEMPERATURE SENSOR (TYP)

5" LONG #5 BARS, 12" O.C. EACH WAY

WITH 2.5" EMBED - SECURE BARS IN

CONCRETE FLOOR WITH EPOXY

CLEAN AND ROUGHEN THE SURFACE AND

PROVIDE CONCRETE BONDING AGENT PRIOR

TO POURING THE CONCRETE PAD

CONCRETE NOTES

1. INSTALL #5 EPOXY COATED METAL DOWEL BARS, PLACED AT THE MID SLAB DEPTH AND SPACED ON 12" CENTERS. EPOXY-COATED JOINT DOWEL BARS SHALL

CONFORM TO ASTM A 615, GRADE 60, PLAIN-STEEL BARS, ASTM A 775 EPOXY COATED.

2. ALL CONCRETE SHALL HAVE A MINIMUM OF 3,000 PSI COMPRESSIVE STRENGTH AT 28 DAYS.

3. ALL CONCRETE SHALL HAVE A SLUMP OF 4" PLUS OR MINUS 1", AND HAVE 2%-4% AIR ENTRAINMENT, AND A MAXIMUM WATER/CEMENT RATIO OF 0.58.

4. CONCRETE MIX SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ACI 301 CHAPTER 3, METHOD 1 OR METHOD 2. SUBMIT BACK-UP DATA AS REQUIRED BY

CHAPTER 5 SECTION 5.3. OF THE LATEST EDITION OF ACI 318.

5. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC DEFORMED BILLET STEEL CONFORMING TO ASTM A-615 GRADE 60.

6. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH "THE BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" ACI 318 LATEST EDITION, AND

"SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS," ACI 301.

7. ALL REINFORCING DETAILS SHALL CONFORM TO "MANUAL OR STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES" ACI 315 LATEST EDITION.

8. CONTRACTOR SHALL PROVIDE SPACERS, CHAIRS, BOLSTERS, ETC., NECESSARY TO SUPPORT REINFORCING STEEL. SUPPORT ITEMS WHICH BEAR ON EXPOSED

CONCRETE SURFACES SHALL HAVE ENDS WHICH ARE PLASTIC TIPPED OR STAINLESS STEEL.

WATER BOX DRAIN VALVE PIPE SUPPORT (TYP)

NOTES

1. INSULATION IS NOT SHOWN ON THE DETAIL FOR CLARITY, PROVIDE INSULATION AND JACKET ON ALL

CHILLED WATER PIPING AND EQUIPMENT.

2. ALL INSTRUMENT PIPE SHALL BE INSULATED 1/4" DIA HARD DRAWN COPPER PIPE

NEOPRENE PAD DRAIN BALL VALVE WITH THREADED

HOSE END CONNECTION AND CAP

FINISHED FLOOR

SPHERICAL FLEXIBLE

CONNECTOR (TYP)

TMANUAL VENT

EVAPORATOR

OR CONDENSER

TUBE BARREL

T

PRESSURE/TEMPERATURE

TAP (TYP)

DIFFERENTIAL PRESSURE

TRANSMITTER (TYP)

CHW OR CW FLOW SWITCH

MANUAL BUTTERFLY

VALVE

THERMOMETER (TYP)

CHILLER HOUSEKEEPING PAD EXTENSION DETAIL1

SCALE: NONEM-501

TYPICAL CHILLER WATER BOX CONNECTIONS2

SCALE: NONEM-501

TYPICAL PIPE ACCESSORY INSTALLATIONS3

SCALE: NONEM-501

CHILLER REFRIGERANT RELIEF CONNECTION4

SCALE: NONEM-501

REFRIGERANT RELIEF VENT TERMINATION5

SCALE: NONEM-501

JND

PROVIDE PIPE HANGERS PER SPECIFICATIONS

EXISTING CMU WALL

SAW CUT OR CORE OPENING

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\M ec h\

M -5

.d w g

A pr

5,

- 7

:4 4a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

M-502

CONCRETE INERTIA BASE1

SCALE: NONEM-501

END-SUCTION PUMP DETAIL2

SCALE: NONEM-501

PIPE HANGER DETAIL3

SCALE: NONEM-501

ADJUSTABLE PUMP

ATTACHMENTS FILL BASE WITH CONCRETE ONCE

FINAL LOCATION HAS BEEN

ESTABLISHED AND THE FRAME HAS

BEEN SECURED TO THE FLOOR

REINFORCING STEEL

SPRING ISOLATOR (TYP)

BUTTERFLY ISOLATION VALVE - LOCATE

ACTUATOR FOR EASE OF SERVICE (TYP 2)

HANGER ROD

SUPPORT NUT

GLOBE STYLE SILENT CHECK VALVE

NEW RUBBER EXPANSION FITTING (TYP 2)

SPLIT-COUPLED END

SUCTION PUMP PACKAGE

PUMP INERTIA PAD SECURED

TO HOUSEKEEPING PAD -

PAINT ALL CONCRETE TO

MATCH FLOOR FINISH

CLEVIS HANGER

HOUSEKEEPING PAD

FLOOR

NOTES

1. CHILLED WATER PUMPS: INSULATE AND JACKET PIPING, APPURTENANCES, AND PUMP HEAD.

NEW SUCTION DIFFUSER

WITH STRAINER

NEW 3/4-INCH BALL VALVE WITH HOSE END

CONNECTION AND CAP CONNECTED TO

SUCTION DIFFUSER BLOWDOWN PORT

PRESSURE GAUGE WITH 1/4-INCH ISOLATION

VALVES AND HARD-DRAWN TUBING

LOCKING NUT

PIPE

HEAVY DUTY

CLEVIS HANGER

JND

MECHANICAL DETAILS

NOTE: PAINT ALL STEEL

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\M ec h\

M -6

.d w g

A pr

5,

- 7

:4 4a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

M-601

MECHANICAL EQUIPMENT SCHEDULES

WATER COOLED CENTRIFUGAL CHILLER SCHEDULE

MARK

BASIS OF DESIGN GENERAL DATA EVAPORATOR DATA CONDENSER DATA ELECTRICAL DATA

OPERATING

WEIGHT

(LB)MANUFACTURER MODEL NO.

CAPACITY

(TONS)

COMPRESSOR DATA REFRIGERATION FULL LOAD

COOLING

EFFICIENCY

(kW/TON)

FLUID

FLUID FLOW DATA

(GPM)

PRESSURE

DROP @

DESIGN

FLOW

(FT H2O)

FLUID TEMPERATURE

DATA (°F)

FLUID

FLUID FLOW DATA

(GPM)

PRESSURE

DROP @

DESIGN

FLOW

(FT H2O)

FLUID TEMPERATURE

DATA (°F) VOLTAGE

(VOLTS/PH)

MCA

(A)

MOCP

(A)

NAME-

PLATE

RLA

(A)

PRI-

MARY

RLA

(A)

LRA

(A)

TYPE QTY REFRIGERANT

TYPE CIRCUITS DESIGN MINIMUM MAXIMUM ENTERING LEAVING DESIGN MINIMUM MAXIMUM ENTERING LEAVING

CH-1 TRANE CVHF870 900 CENTRIFUGAL 1 R-514A 1 0.581 WATER 2,150 873 4,802 15.5 50 40 WATER 2,540 1,418 5,197 3.63 85 95 460 / 3 863 1,200 742 692 4,743 39,641

NOTES

1. CHILLER MANUFACTURER MUST SHIP CHILLER ASSEMBLED IN A SINGLE PIECE FROM FACTORY WITH NITROGEN HOLDING CHARGE TO AVOID COMPONENT

CONTAMINATION DURING SHIPMENT. SHIPMENT IN PIECES IS NOT ALLOWED UNDER ANY CIRCUMSTANCE. FULL DISASSEMBLY/REASSEMBLY KIT MUST BE PROVIDED ALONG WITH LOCAL FACTORY SERVICE SUPERVISION LABOR FOR WARRANTY MAINTENANCE PURPOSES.

2. MANUFACTURER TO PROVIDE FULL REFRIGERANT CHARGE SHIPPED LOOSE FOR FIELD INSTALLATION BY CHILLER INSTALLER PRIOR TO OPERATION.

3. PROVIDE DIRECT DRIVE MULTI STATE COMPRESSOR.

4. PROVIDE SHELL AND TUBE EVAPORATOR AND CONDENSER WITH ASME PRESSURE VESSEL RATING.

5. PROVIDE GROOVED PIPE CONNECTIONS.

6. PROVIDE REFRIGERANT COOLED VARIABLE FREQUENCY DRIVE.

7. PROVIDE 3/4" FACTORY INSTALLED INSULATION ON ALL COLD SURFACES EXCEPT ECONOMIZER. PROVIDE ECONOMIZER WITH 3/8" INSULATION.

8. PROVIDE FACTORY INSTALLED DISCONNECT SWITCH WITH CIRCUIT BREAKER.

9. PROVIDE FACTORY INSTALLED BACNET INTERFACE CARD COMPATIBLE WITH EXISTING CONTROL SYSTEM.

10. PROVIDE WEB CONNECTION KIT WITH MODEM AND LABOR FOR SETUP TO MATCH CH-2 FOR CONNECTION WITH FACTORY SERVICE MONITORING.

11. PROVIDE FACTORY INSTALLED CHILLED WATER AND CONDENSER WATER FLOW SENSORS.

12. PROVIDE FACTORY INSTALLED PHASE PROTECTION, REVERSAL AND IMBALANCE PROTECTION.

13. PROVIDE LOOSE SHIPPED NEOPRENE ISOLATOR PADS TO MATCH EXISTING CHILLER PADS FOR FIELD INSTALLATION.

14. PROVIDE FACTORY START-UP. FIVE YEARS COMPLETE PARTS, REFRIGERANT, LABOR AND SERVICE WARRANTY.

15. CHILLER MUST BE CERTIFIED BASED ON AHRI AND ASHRAE 90.1 STANDARDS.

16. CHILLER MUST BE SHIPPED COMPLETELY WRAPPED IN HEAVY DUTY BAG TO PROTECT FROM ROAD DAMAGE, ROAD SALT, AND CONSTRUCTION DIRT.

17. AFTER CHILLER IS INSTALLED AND PRIOR TO REFRIGERANT CHARGING, PERFORM EDDY CURRENT TESTING AS RECOMMENDED BY CHILLER MANUFACTURER. PROVIDE

BASELINE TESTING INFORMATION TO CHILLER MANUFACTURER AND TO GOVERNMENT FOR WARRANTY PURPOSES.

NOTES

1. PROVIDE 150 LB FLANGED INLET AND OUTLET CONNECTIONS.

2. PROVIDE STAINLESS STEEL IMPELLER.

3. PROVIDE INLET AND OUTLET ISOLATION VALVES.

4. PROVIDE INLET AND OUTLET FLEX CONNECTIONS.

5. PROVIDE FACTORY FURNISHED VIBRATION ISOLATORS.

6. PROVIDE CONCRETE AND STEEL INERTIA PAD. REFER TO DETAIL.

7. PUMP TO BE VARIABLE SPEED. PUMP MOTOR TO BE WIRED TO EXISTING VFD INSTALLED IN PHASE 2.

PUMP SCHEDULE

MARK

BASIS OF DESIGN PUMP DATA ELECTRICAL DATA

WEIGHT

(LB) NOTES

MANUFACTURER MODEL NO. TYPE

FLOW

(GPM)

TOTAL

HEAD

(FT H20)

RPM

INLET

SIZE

(IN.)

OUTLET

SIZE

(IN.)

IMPELLER

SIZE

(IN.)

MOTOR

POWER

(HP)

VOLTAGE

(VOLTS/PH)

CHWP-1 TACO FI18013E END SUCTION 2,150 75 1750 4 3 10.05 60 460 / 3 - ALL

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\M ec h\

M -7

.d w g

A pr

5,

- 7

:4 4a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTT

M-701

CHILLER PLANT CONTROLS

12"

COOLING OVERFLOW

12"

COOLING TOWER

EQUALIZER PIPING

MV

8"

VFD

CT-2 (E)

12" TS

8"

VFD

12"

MV

COOLING TOWER DRAIN

COOLING OVERFLOW

COOLING BYPASS

DPT

VFD

12"

8" 12"

12" MV

12"

12" 12" DPT VFD

12"

8"

12" MV CWP-1 (E)

12" 12"

COOLING BYPASS

12"

10" TS

CONDENSER

CHILLER

CONTROLLER

10" TS CH-2 (E)

900 TONS

EVAPORATOR

12" 12"

DPT

TS

TS

10" TS DPT

PS CONDENSER

CHILLER

CONTROLLER

10" DPT TS

PS

EVAPORATOR

3/4"

CHEMICAL SHOT FEEDER

10"

10" EMERGENCY CHILLED

WATER RETURN CONNECTION

10"

VFD DPT

10"

10"

10" EMERGENCY CHILLED

WATER SUPPLY CONNECTION

10"

LVL

CT-1 (E)

TS LVL

CH-1

900 TONS

12"

12" 12"

DPT

TS

TS

10"

CHILLER PLANT CONTROLS - SCHEMATIC1

SCALE: NONEM-701

CHILLER STOP CYCLE:

WHEN THE DDC SYSTEM INDEXES THE CHILLER TO STOP THE FOLLOWING SHALL OCCUR:

A. THE CHILLER CONTROL PANEL SHALL INDEX CHILLER TO STOP.

B. THE CHILLER CONTROL PANEL SHALL DISABLE THE CONDENSER WATER PUMP AFTER A TIME DELAY AND

SEND A SIGNAL TO THE DDC SYSTEM TO DISABLE THE CHILLED WATER PUMP.

C. THE DDC SYSTEM SHALL CLOSE THE CHILLER ISOLATION VALVE ON THE CONDENSER WATER SUPPLY

AND ON THE CHILLED WATER RETURN ASSOCIATED WITH THE CHILLER.

CHILLER STAGING:

THE SYSTEM IS VARIABLE PRIMARY: THE CHILLERS CONTROL IS PRIMARY/STANDBY WHERE EACH CHILLER IS SIZED AT 100% OF THE REQUIRED LOAD. SOFTWARE PRIMARY/STANDBY FUNCTION SHALL ALLOW EITHER OF THE CHILLERS TO ACT AS THE PRIMARY CHILLER BY OPENING/CLOSING THE ASSOCIATED ISOLATION VALVES FOR EACH CHILLER. THE STANDBY CHILLER SHALL REMAIN OFF UNTIL RECEIVING A COMMAND TO TO ACTIVATE FROM THE DDC. THE CHILLED WATER PUMP SHALL ADJUST TO MAINTAIN THE CHILLED WATER DIFFERENTIAL PRESSURE

(FLOW RATE, AS RECOMMENDED BY THE MANUFACTURER) FOR THE CHILLERS.

DESIGNATING PRIMARY, STANDBY AND 'OUT OF SERVICE' CHILLERS:

THE CHILLER PLANT GRAPHICAL SCREEN SHALL ALLOW THE OPERATOR TO DESIGNATE WHICH CHILLER IS PRIMARY, STANDBY, AND 'OUT OF SERVICE'. THE DDC SYSTEM SHALL CHANGE THE PRIMARY/ STANDBY STATUS OF THE CHILLERS ON A WEEKLY BASIS. THE DDC SYSTEM SHALL THEN AUTOMATICALLY START/STOP CHILLERS AS

REQUIRED TO MAINTAIN EQUAL CHILLER RUN TIME.

CHILLED WATER PUMP CONTROL:

ALL CHILLED WATER PUMPS ARE SIZED FOR 100% SYSTEM CAPACITY AS VARIABLE SPEED PRIMARY CONFIGURATION. THE DDC SYSTEM SHALL START THE CHILLED WATER PUMP ASSOCIATED WITH THE ACTUVE CHILLER VIA THE VFD WHENEVER THE CHILLER CONTROL PANEL IS ENABLED AND CHILLER CONTROL PANEL IS

CALLING FOR COOLING. THE STANDBY PUMP SHALL REMAIN OFF.

THE DDC SYSTEM SHALL MODULATE OUTPUT TO THE PUMP VFD AS REQUIRED TO MAINTAIN DIFFERENTIAL

PRESSURE (DP) SETPOINT AT THE LOCATION OF THE DP TRANSMITTER.

THE DDC SYSTEM SHALL ALTERNATE THE PRIMARY/STANDBY PUMPS ON A WEEKLY BASIS WITH THEIR

ASSOCIATED CHILLER.

MINIMUM CHILLED WATER FLOW CONTROL:

DDC SYSTEM SHALL MODULATE THE CHILLED WATER PUMP SPEED CONTROL AS REQUIRED TO MAINTAIN MINIMUM FLOW THROUGH CHILLER. THE MINIMUM FLOW SHALL VERIFIED WITH THE EQUIPMENT MANUFACTURER.

ADEQUATE FLOW THROUGH EACH CHILLER SHALL BE DETERMINED BY THE CHILLER FLOW SENSOR.

CHILLER SAFETIES:

CONTRACTOR SHALL COORDINATE ALL SAFETY AND INTERLOCK REQUIREMENTS WITH CHILLER MANUFACTURER.

THE CONTROLS CONTRACTOR SHALL PROVIDE THE INSTALLATION AND WIRING OF CHILLED WATER FLOW SWITCHES AND OTHER COMPONENTS PROVIDED WITH CHILLER AS REQUIRED FOR PROPER OPERATION.

COOLING TOWER CONTROL:

WHEN THE WATER LEVEL IS AT THE “OPERATING LEVEL”, THE MAKE-UP WATER CONTROL VALVE SHALL BE CLOSED. AS THE WATER LEVEL DROPS TO “LOW LEVEL”, THE LEVEL SENSOR SHALL SEND A SIGNAL TO THE DDC

SYSTEM TO OPEN THE MAKE-UP WATER CONTROL VALVE.

TOWER START-UP:

UPON INITIAL SYSTEM START-UP THE TOWER BY-PASS VALVE AND INDIVIDUAL TOWER ISOLATION VALVES SHALL BE UTILIZED AND SEQUENCED TO WARM UP CONDENSER WATER SYSTEM FOR PROPER CHILLER OPERATION.

WHEN THE CONDENSER WATER SUPPLY TEMPERATURE IS ABOVE 55°F (ADJ.) (REFER TO CONDENSER WATER

TEMPERATURE RESET) THE DDC SYSTEM SHALL CALL FOR COOLING TOWER OPERATION.

COOLING TOWER FAN OPERATION:

ONCE CONDENSER WATER FLOW IS PROVEN, THE DDC SYSTEM SHALL START THE COOLING TOWER FAN VIA THE VFD. THE DDC SYSTEM SHALL STOP THE COOLING TOWER FAN WHEN THE VFD IS OPERATING AT MINIMUM SPEED AND CONDENSER WATER SUPPLY TEMPERATURE IS 5°F BELOW SETPOINT FOR 10 MINUTES (ADJ) OR IF

CONDENSER WATER FLOW IS NOT PROVEN.

THE PURPOSE OF THE COOLING TOWER FAN SPEED CONTROL IS TO MAINTAIN THE OPTIMAL CONDENSER WATER SUPPLY TEMPERATURE SETPOINT. THE DDC SYSTEM SHALL CONTROL THE COOLING TOWER FAN VFD USING A

4-20MA OUTPUT.

CONDENSER WATER PUMP:

THE CONDENSER WATER PUMP SHALL RUN ANYTIME THE COOLING TOWER IS CALLED TO RUN AND SHALL HAVE A USER DEFINABLE DELAY (ADJ.) ON STOP. THE CONDENSER WATER PUMP SHALL BE VARIABLE AND VARY FLOW AS

DEMAND CHANGES.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

A. CONDENSER WATER PUMP FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

B. CONDENSER WATER PUMP RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

C. CONDENSER WATER PUMP RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT

CHILLER PLANT CONTROLS - SEQUENCE OF OPERATIONS2

SCALE: NONEM-701

JND

CWP-2 (E)

CHWP-2 (E)

CHWP-1

VFD DPT

10"

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\E le c\

D R

AW

IN

G S\

E-

1.

dw g A pr

5,

- 7 :3

6a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTTNo. 032883

GEORGIA

PROFESSIONAL **

E-001

ELECTRICAL LEGEND

SYMBOL / KEY

REVISION TAG DESIGNATION

DESCRIPTION

TOP DESIGNATION IS SECTION DESIGNATION

KEY NOTE DESIGNATION

BOTTOM DESIGNATION IS SECTION SHEET LOCATION (STANDARD SYMBOL SCALED DOWN FOR LEGEND)

NOTE: ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES A 2 WIRE #12AWG CIRCUIT WITH A #12AWG

GND. A GREATER NUMBER OF WIRES IS INDICATED AS FOLLOWS:

4 WIRE, 2 CIRCUITS & GROUND (LONGER SLASH INDICATES NEUTRAL)

6 WIRE, 3 CIRCUITS & GROUND, ETC.(WIRING LARGER THAN #10AWG SHALL BE AS NOTED)

INDICATES #10 GROUND CONDUCTOR UOI (DOUBLE TICK/SLASH INDICATES ISOLATED GROUND)

PANELBOARD AND CIRCUIT DESIGNATION

RACEWAY CONCEALED IN WALL OR CEILING OR EXPOSED ON STRUCTURE AS REQUIRED

HOMERUN TO PANELBOARD - LETTERS INDICATE PANEL, NUMBERS INDICATE CIRCUIT

(NOT ALL SYMBOLS MAY APPLY, TYP.)

TAG STYLE ANNOTATION: CIRCUIT DESIGNATION, POINT TOWARD ASSOCIATED BRANCH/DIST PANEL.

TAG STYLE ANNOTATION: ELEC EQUIP DESIGNATION (PANELBOARDS, XFMRS, DIST BOARDS, ETC.)

TAG STYLE ANNOTATION: ELECTRICALLY POWERED EQUIPMENT (PROVIDED BY OTHERS)

TAG STYLE ANNOTATION: ELECTRICALLY POWERED MECHANICAL/PLUMBING EQUIPMENT (RE: MECHANICAL)

TOP DESIGNATION IS PLAN / ENLARGED PLAN / DETAIL NUMBER

BOTTOM DESIGNATION IS SHEET LOCATION (STANDARD SYMBOL SCALED DOWN FOR LEGEND)

LA1:13

LA1:13

EP101

A

EP101

GENERAL SYMBOLS LEGEND

ABBR.

AMPERE(S)

DESCRIPTION

A / AMP

ALTERNATING CURRENT : AIR COMPRESSOR

AIR CURTAIN : ABOVE COUNTER/ BACKSPLASH

AMPERE FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPT CAPACITY

ALUMINUM

AMP TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AIR COOLED CONDENSING UNITACCU

AC

AC

AF

AFF

AFG

AHU

AIC

AL

AT

ATS

AUTO

AUX

AWG

BRKR

BLDG

C

CAT

CB

CCT

CCTV

CFCI

CKT

CLG

CMH

COMM

CP

CPT

CRI

CT

CU

AUXILIARY

BREAKER

BUILDING

CONDUIT

CATEGORY

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

CLOSED CIRCUIT TELEVISION

CONTRACTOR FURNISHED/ INSTALLED

CIRCUIT

CEILING

COMMUNICATIONS MANHOLE

AMERICAN WIRE GUAGE

COMMUNICATIONS

CONTROL POWER TRANSFORMER

COLOR RENDERING INDEX

CURRENT TRANSFORMER : COOLING TOWER

COPPER : CONDENSING UNIT

CONDENSATE PUMP

HEIGHT

HORSE POWER : HEAT PUMP

INTERMEDIATE METAL CONDUIT

KILO

THOUSAND AMPERE INTERRUPT CAPACITY

THOUSANDS OF CIRCULAR MILS

KILOVOLT

KILOVOLT-AMPERES

KILOWATT

KILOWATT - HOUR

LENGTH

LOCAL AREA NETWORK

HAND-OFF AUTOMATICHOA

HP

IMC

K

KAIC

KCMIL

KV

KVA

KW

KWHR

L

LAN

LTG

MAX

MCA

MCB

MCC

MGB

MH

MIN

MLO

NEC

NEMA

NFPA

NC

NESC

NL

NO

NTS

LIGHTING

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN GROUND BAR

MANHOLE / MOUNTING HEIGHT

MINIMUM

MAIN LUGS ONLY

NATIONAL ELEC CODE

NATIONAL ELEC MANUFACTURER'S ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

MAXIMUM

NORMALLY CLOSED

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

NATIONAL ELEC SAFETY CODE

ABBR. DESCRIPTION

D

DC

DISC

DIST

DPST

DPDT

EC

EF

ELEC

EMER

EMH

EMT

EQUIP

DEPTH

DIRECT CURRENT

DISCONNECT

DISTRIBUTION

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

EMPTY CONDUIT

EXHAUST FAN

ELECTRICAL

ELECTRICAL MANHOLE

ELECTRICAL METALLIC TUBING

EQUIPMENT

EMERGENCY

PF

PH

PNL

PTAC

PVC

REC / RECPT

RMC

RTU

RVNR

SA

SCCR

SF

SPD

POWER FACTOR

PHASE

PANEL : PANELBOARD

PACKAGED THRU-WALL AIR CONDITIONER

POLYVINYL CHLORIDE

RECEPTACLE

RIGID METAL CONDUIT

ROOF TOP UNIT

REDUCED VOLTAGE NON-REVERSING

SHORT CIRCUIT CURRENT RATING

SUPPLY FAN

SURGE PROTECTIVE DEVICE

SURGE ARRESTORS

ETR

EUH

EXP

EWH / EWC

EXISTING

EXPLOSION PROOF

ELECTRIC WATER HEATER / COOLER

ELECTRIC UNIT HEATER SPEC

SPST

SWBD

SWGR

SPECIFICATIONS

SWITCHBOARD

SINGLE POLE SINGLE THROW

F

FACP

FCU

FLEX

G / GND

GFGI

GFI / GFCI

GRS

GUH

GWH

FUSE

FIRE ALARM CONTROL PANEL

FAN COIL UNIT

FLEXIBLE

GROUND

GOVERNMENT FURNISHED / INSTALLED

GROUND FAULT (CIRCUIT) INTERRUPTER

GALVANIZED RIGID STEEL

GAS UNIT HEATER

GAS WATER HEATER

TMGB

TOL

TYP

UH

UOI

UL

W

WP

Z

TELECOMMUNICATION MAIN GROUNDING BUSBAR

THERMAL OVERLOAD

TYPICAL

UNIT HEATER

UNLESS OTHERWISE INDICATED

UNDERWRITERS LABORATORY

WATTS : WIDTH

WEATHERPROOF

IMPEDANCE

P POLE(S)

SPDT SINGLE POLE DOUBLE THROW

SWITCHGEAR

H / HT

NAT NATIONAL

XFMR TRANSFORMER

ETC. ETCETERA

MTD MOUNTED

N NEUTRAL

QTY QUANTITY

ABBREVIATIONS

ABBREVIATIONS ABOVE ARE FOR ELECTRICAL

SHEETS ONLY. NOT ALL MAY BE USED.

MGC MAIN GROUNDING CONDUCTOR

EX / EXIST

EXISTING TO REMAIN

SYMBOL / KEY

FEEDER KEY

DESCRIPTION

GROUND

CURRENT XFMR

M METER

SURGE PROTECTIVE DEVICESPD

J JUNCTION BOX

CONTINUATION, UPSTREAM LABEL#

J JUNCTION BOX FLOOR MOUNTED

TAP BOXTB

PANELBOARD (PLAN VIEW)

MOTOR

ONE-LINE DIAGRAM, SCHEDULE, AND

DISTRIBUTION LEGEND

LOCAL DISCONNECT

LOCAL DISCONNECT W/ OCP

VARIABLE FREQUENCY DRIVEVFD

LOCAL MOTOR STARTER ( * = TYPE)*

LOCAL COMBINATION MOTOR STARTER

( * = TYPE) (2S: TWO SPEED) (RV: REDUCED VOLTAGE) (FVR/FVNR:FULL

VOLTAGE REVERSING/NON-REVERSING)

PNL PANELBOARD (ONE-LINE)

TRANSFER SWITCH ( * = TYPE)

(ATS : AUTOMATIC) (MTS: MANUAL)

1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF WORK. THE DRAWINGS ARE NOT

INTENDED TO INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL

PERFORMANCE AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT.

2. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL PARTS OF THE

WORK SO THAT NO WORK SHALL BE LEFT IN AN UNFINISHED OR INCOMPLETE

CONDITION. INSTALLATION OF ELECTRICAL WORK SHALL BE COORDINATED WITH OTHER

TRADES BEFORE ANY INSTALLATION IS DONE. CONDUIT AND DEVICES SHOWN ON PLANS

ARE SCHEMATIC.

3. ALL WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURER'S

PUBLISHED STANDARDS FOR QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL AS,

ALL REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY CONFLICTING

REQUIREMENTS OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT TO THE

CONTACTING OFFICER'S ATTENTION PRIOR TO PROCEEDING WITH THE WORK.

4. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-PLACE, AND NEW WORK.

5. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SHALL VERIFY

ALL NEW AND EXISTING CONDITIONS SHOWN ON THESE DRAWINGS. THE CONTRACTOR

SHALL NOTIFY THE C.O. IN WRITING OF ANY DIFFERING CONDITIONS BEFORE

COMMENCEMENT OF WORK.

6. THE CONTRACTOR SHALL PLAN WORK TO PROVIDE ADEQUATE PROTECTION FOR

PERSONS AND PROPERTY AT ALL TIMES, AND EXECUTE THE WORK IN SUCH A MANNER

TO AVOID ANY HAZARD TO PERSONS AND PROPERTY AS NECESSARY.

7. MINIMUM RACEWAY SIZE SHALL BE 3/4-IN. INCREASE RACEWAY SIZE AS REQUIRED TO

LIMIT RACEWAY FILL RATIO TO LESS THAN 40% FULL.

8. ALL CONDUCTORS SHALL BE COPPER.

9. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND

CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO

EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND

BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT.

MULTIPLE BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND

CONDUCTOR.

10. ALL SAFETY DISCONNECTS SHALL BE HEAVY DUTY 240V NEMA 3R NON-FUSED TYPE.

11. REFER TO ONE-LINE DIAGRAMS, SCHEDULES, AND TABLES FOR CONDUCTOR AND

CONDUIT SIZES NOT SHOWN ON PLANS.

12. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY

SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL AND CIRCUIT(S). TEXT

SHALL BE BLACK 1/4-IN IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS

ARE NOT PERMITTED.

13. COORDINATE WALL, FLOOR AND ROOF PENETRATIONS WITH THE CONTRACTING

OFFICER.

14. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT ELECTRICAL EQUIPMENT

FROM MAIN STRUCTURE SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR

UNLESS SPECIFICALLY NOTED OTHERWISE.

15. EXACT LOCATIONS OF PANELBOARDS, DISCONNECTS, TIMERS, AND SWITCHES SHALL BE

COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND

MECHANICAL EQUIPMENT. MOUNT DISCONNECTS AND SWITCHES MINIMUM 48" AFF.

MOUNT TIMERS MINIMUM 40" AFF.

16. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON

DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT

SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE

OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.

17. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY

AMERICAN ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A

STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM

ANOTHER MANUFACTURER IS ACCEPTABLE.

18. PROVIDE WEATHERPROOF COVERS FOR ALL SWITCHES.

19. THE CONTRACTOR SHALL COORDINATE WITH THE ARCHITECTURAL, MECHANICAL, CIVIL

DRAWINGS AND SPECIFICATIONS FOR EXACT LOCATION OF EQUIPMENT. ALL WORK

SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES TO AVOID INTERFERENCE.

REFER TO MECHANICAL DRAWINGS FOR PIPES, DUCTS, AND MECHANICAL EQUIPMENT.

GENERAL PROJECT NOTES:

CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES EXPOSED SURFACE-MOUNTED RACEWAY

(SEE SPECIFICATIONS).

WS

XB

XC

XE

X7X6

VF

D

VF

D

VF

D

VF

D

CH-1

CHWP-1

ETR MAIN SERVICE

SWITCHGEAR 'MSB'

HMPU:19,21,23

HMPU

CH-2

CHWP-2

HMPU:25,27,29

ETR

ETR

ETR CWP-1

HMPU:31,33,35

ETR CWP-2

HMPU:37,39,41

MSB

TEMPORARY

DISCONNECT

CH-1

ETR

BUSWAY

ETR LIGHTS

ETR LIGHTS

ETR

TB

COR

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\E le c\

D R

AW

IN

G S\

ED

1.

dw g A pr

5,

- 7 :3

6a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTTNo. 032883

GEORGIA

PROFESSIONAL **

ED101

ELECTRICAL DEMOLITIONSCALE:

ELECTRICAL DEMOLITION

1/8" = 1'-0"

ED-101

KEYED NOTES

1. DEMOLISH EXISTING BRANCH CIRCUIT BACK

TO PANEL.

2. DEMOLISH EXISTING CIRCUIT BACK TO

TEMPORARY DISCONNECT CH-1.

3. TEMPORARY DISCONNECT CH-1 IS ETR.

DEMOLISH "CH-1" LABEL. REPLACE LABEL

WITH LABEL THAT SAYS "TEMPORARY

DISCONNECT".

4. DEMOLISH EXISTING CONDUIT AND WIRING

BACK TO VFD.

08' 8'

1'-0"

4'

SCALE: 1/8" =

GRAPHIC SCALE

NORTH

GENERAL NOTES

1. REFER TO E-001 FOR GENERAL NOTES AND

SYMBOLS LIST.

2. ALL EXISTING RECEPTACLES AND EQUIPMENT

NOT ASSOCIATED WITH DEMOLITION SCOPE OF

WORK SHALL REMAIN ACTIVE. REWORK

EXISTING CIRCUITRY AS REQUIRED IN ORDER

TO RE-FEED AND/OR MAINTAIN CIRCUIT

CONTINUITY.

XB

XC

XE

X7X6

VF

D

VF

D

VF

D

VF

D CH-1

CH-2

CHWP-1

CHWP-2

MAIN SERVICE

SWITCHGEAR 'MSB'

HMPU:56,58,60

HMPU:25,27,29

ETR

NEW

ETR

NEW

ETR CWP-1

HMPU:31,33,35

ETR CWP-2

HMPU:37,39,41

HMPU

MSB

ETR

TEMPORARY

DISCONNECT

ETR

BUSWAY

ETR LIGHTS

ETR LIGHTS

ETR

TBTB

COR

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\E le c\

D R

AW

IN

G S\

E-

1.

dw g A pr

5,

- 7 :3

6a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTTNo. 032883

GEORGIA

PROFESSIONAL **

E-101

ELECTRICAL FLOOR PLANSCALE:

ELECTRICAL FLOOR PLAN

1/8" = 1'-0"

E-101

KEYED NOTES

1. PROVIDE POWER CONNECTION TO CH-1

USING THE NON FUSED DISCONNECT THAT

THE CHILLER COMES EQUIPPED WITH.

2. PROVIDE POWER VIA NEW 1350 A BUS WAY

TO THE TAP BOX. MINIMUM OF 1' CLEARANCE

AROUND BUS WAY. CROSS OVER EXISTING

BUS WAY, AND RAISE EXISTING LIGHTING AS

NEEDED. SEE DETAIL 2/E-501 FOR EXISTING

ELEMENTS.

3. PROVIDE NEW TAP BOX. PROVIDE POWER VIA

CONDUIT AND WIRE FROM TAP TO CH-1.

PROVIDE A 480 V 3PH/4W SYSTEM VIA 2 RUNS

OF 600 KCMIL COPPER WIRE AND 3/0 AWG

COPPER GROUND WIRE IN 3 1/2" CONDUIT.

4. PROVIDE POWER CONNECTION TO CHWP-1

VIA EXISTING VFD. PROVIDE NEW 150 A 480 V

3 PHASE BREAKER ON HMPU:56,58,60. REFER

TO PANEL SCHEDULE ON E-501. USE 3 AWG

COPPER WIRE AND 8 AWG COPPER GROUND

WIRE IN 1" CONDUIT.

5. REFER TO DETAIL 1/E-501 FOR ETR BREAKER.

08' 8'

1'-0"

4'

SCALE: 1/8" =

GRAPHIC SCALE

NORTH

GENERAL NOTES

1. REFER TO E-001 FOR GENERAL NOTES AND

SYMBOLS LIST.

2. REFER TO EQUIPMENT FEEDER SCHEDULE ON

DRAWING E-501.

3. PROVIDE CONDUIT SYSTEM FOR MECHANICAL

CONTROLS AS REQ'D COORDINATE WITH

MECHANICAL INSTALLER PRIOR TO ROUGH IN.

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

ADMIN OFFICER

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

T:

\2

Pr oj ec ts

\5

4- M

U

SD

A Ph as e

C hi lle r U pg ra de s

- A th en s G

A\

W or ki ng

F ol de r\E le c\

D R

AW

IN

G S\

E-

1.

dw g A pr

5,

- 7 :3

6a m

EPM

TEL

5624-M

R. SANDERS

C. GILMAN

E. JONES 4/25/25

Agricultural

Service Research

USDA ARS SOUTHEAST AREA

141 EXPERIMENT STATION ROAD

STONEVILLE MS 38776

PHASE 3 CHILLER UPGRADE USNPRC

RICHARD B. RUSSELL AGRICULTURAL RESEARCH CENTER (RRC)

950 COLLEGE STATION ROAD, ATHENS, GA 30605

JGM

M. SCOTTNo. 032883

GEORGIA

PROFESSIONAL **

E-501

ELECTRICAL DETAILS AND SCHEDULES

TVSS

1A

NWH2

1600 A

MAN OP

TU (A)

LSIG

1B

NWH2

800 A

MAN OP

TU (A)

LSI

1C

NWH2

800 A

MAN OP

TU (A)

LSI

1D

NWH2

800 A

MAN OP

TU (A)

LSI

2A

NWH2

1600 A

MAN OP

TU (A)

LSIG

2B

NWH2

1600 A

MAN OP

TU (A)

LSIG

2C

NWH2

800 A

MAN OP

TU (A)

LSI

2D

NWH2

800 A

MAN OP

TU (A)

LSI

3D

NWH2

1600 A

MAN OP

PREP SP

LSIG

3BC

NWH2

3200 A

MAN OP

TU (A)

LSIG

ETR

BREAKER

FOR CH-1

SCALE:

SECTION OF MSB

N.T.S.

E-501