Attachment 3 - 550-23-104 BID Drawings.pdf

PDF 5 MB Posted

Attached to
Z1DA--550-23-104 Install Rooftop PV Multiple Buildings (CON)
Solicitation number
36C25226B0024
Issued by

About this file

These are bid documents for the installation of rooftop photovoltaic systems at the VA Illiana Health Care System (VAIHCS) located at 1900 E. Main Street, Danville, Illinois. The project, designated as 550-23-104, involves installing solar photovoltaic systems on Buildings 103 and 104, with the work fully sprinklered. The project is being managed by GUIDON Design Inc., with Heapy Engineering serving as the electrical consultant and Michael Wlos as the Contracting Officer's Representative (COR) for the VA.

The electrical scope includes installation of 450W solar panels mounted on roof-mounted racking systems across both buildings, with seven 60 kVA inverters per building to convert DC power to AC. The systems incorporate power optimizers on each panel string, DC splice boxes rated at 100A/3-phase disconnects, and conduit routing with no roof penetrations allowed—all attachments must coordinate with the existing roof manufacturer. Building 103 will have seven inverter zones with 18 panels per string across seven strings per inverter, while Building 104 will have seven inverter zones with 16 panels per string. Additional requirements include lightning protection systems, roof-mounted conduit support details, walking paths for maintenance access, single-line diagrams showing integration into existing electrical infrastructure, and coordination with existing switchboards and emergency power systems. All work must comply with current building codes, maintain facility operations, and be coordinated with the contracting officer.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

A u to d e s k D o c s

/1

.5

.1

I n s ta ll R o o ft o p P h o to v o lt a lic /1

.5

.1

A v

.r v t

/1 /2

:0

:5

A

M

GI000

COVER SHEET

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

INSTALL ROOFTOP

PHOTOVOLTAIC - MULTIPLE

BUILDINGS

1900 E. MAIN ST., DANVILLE, IL

550-23-104

B103 & B104

11/15/2023

550-23-104

INSTALL ROOFTOP PHOTOVOLTAIC -

MULTIPLE BUILDINGS

VA ILLIANA HEALTH CARE SYSTEM (VAIHCS)

1900 E. MAIN ST., DANVILLE, IL

BID DOCUMENTS

BID DOCUMENTS

FULLY SPRINKLERED

SHEET INDEX

SHEET NUMBER SHEET NAME

GENERAL

GI000 COVER SHEET

ELECTRICAL

E001 INDEX, LEGEND, AND GENERAL NOTES

E103 BUILDING 103 PLAN

E104 BUILDING 104 PLAN

E203 BUILDING 103 SINGLE LINE

E204 BUILDING 104 SINGLE LINE

E301 ROOF PATHING PLANS

Contact:Contact: Contact:

Heapy Engineering

Matt Graham

Electrical Engineer

ELECTRICAL

VA Illiana Health Care System

Michael Wlos

COR

1900 E. Main St.

Danville, IL 61832 p: 217.554.5985 e: michael.wlos@va.gov

OWNER

GUIDON DESIGN INC.

Tory McNeil

Project Manager

1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 e: tmcneil@guidondesign.com

PROJECT MANAGER

3850 Priority Way South Dr Indianapolis, IN 46240 p: 937-224-0861 e: msgraham@heapy.com

AREA MAP

VICINITY MAP

CAMPUS MAP

Revisions: Date:

B103

B104

11/15/2023

19.5002.17

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL

REFER TO PLANS FOR

QUANTITY & SIZE OF

CONDUITS

LOCKING SQUARE

WASHER & LOCKNUT

9.52mm (3/8") MIN

GALVANIZED THREADED

ROD, TYP.

UV-INHIBITED POLYCARBONATE OR

HIGH-DENSITY POLYPROPYLENE PLASTIC

BLOCK, LENGTH AS REQUIRED

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

ELECTRICAL SYMBOLS

EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.

DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE

REQUIRED.

ELECTRICAL CONNECTION.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED

OTHERWISE).

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERWISE), WITH IN-USE WEATHERPROOF EXTRA DUTY GRAY COVER, VERTICAL MOUNT.

DISCONNECT SWITCH.

ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.

GF

WP/GF

E2

B

E2

NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

DETAIL: B = DETAIL DESIGNATION

E2 = SHEET WHERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

E2 = SHEET WHERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

WIRE & CONDUIT IN WALL OR ABOVE CEILING.

WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.

EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES

CIRCUIT(S).

EXISTING WIRE & CONDUIT TO REMAIN.EX

CONDUIT TO BE REMOVED.

X - 1,2

4"

4"

4"

T2 1 ELEVATION: 1 = ELEVATION DESIGNATION

T2 = SHEET WHERE ELEVATION IS LOCATED

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE). WHEN SHOWN, RECEPTACLE TO HAVE

"CONTROLLED" MARKINGS.

ROOF RACK-MOUNT PV SOLAR PANEL.

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SWITCH

BLDG - BUILDING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTWN - BETWEEN

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CKT - CIRCUIT

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

COR - CONTRACTING OFFICER'S REPRESENTATIVE

CORR - CORRIDOR

CTR - CENTER

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DIV - DIVISION

DN - DOWN

DWG - DRAWING

EA - EACH

EC - ELECTRICAL (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EX - EXISTING

EXP - EXPANSION

EXT - EXTERIOR

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

GC - GENERAL TRADES (DIVISION 01)

GEC - GROUNDING ELECTRODE CONDUCTOR

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT

FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

GFP - GROUND FAULT PROTECTION

HC - HVAC (DIVISION 23)

HP - HORSE POWER OR HIGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

IN - INCHES

KEC - KITCHEN EQUIPMENT CONTRACTOR

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MPPT - MAXIMUM POWER POINT TRACKING (POWER OPTIMIZER)

MTD - MOUNTED

MTG - MOUNTING

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED CONTRACTOR INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

PC - PLUMBING (DIVISION 22)

PLBG - PLUMBING

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH-IN

S - SURFACE MOUNTED

SC - SECURITY (DIVISION 28)

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TC - TECHNOLOGY (DIVISION 27)

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERWISE

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W/ - WITH

W/O - WITHOUT

WP - WEATHERPROOF

ZVC - ZONE VALVE CABINET

NOTE:

1. SUPPORT SHALL BE REST ON ROOF AND NOT

PENETRATE ROOF MEMBRANE.

SOLAR PANEL SUPPORT CONSTRUCTED PER

MANUFACTURER RECOMMENDATIONS

PROVIDE BALLAST SYSTEM ACCORDING TO MANUFACTURER

RECOMMENDATIONS PER CALCULATED WIND LOADING

NOTE: NO ROOF PENETRATIONS ARE ALLOWED FOR PANELS, RACKING,

AND CONDUIT MOUNTING. ATTACHMENT TO ROOF MEMBRANE SHALL BE

COORDINATED WITH EXISTING ROOF MANUFACTURER'S REPRESENTATIVE.

SOLAR PANEL (TYP)

SOLAR PANEL (TYP)

SOLAR PANEL SUPPORT CONSTRUCTED PER

MANUFACTURER RECOMMENDATIONS

PROVIDE BALLAST SYSTEM ACCORDING TO MANUFACTURER

RECOMMENDATIONS PER CALCULATED WIND LOADING

EXISTING ROOF

DC CONNECTOR BOX AND

POWER OPTIMIZER (MPPT)

INVERTERS TO BE MOUNTED ON BACK

OF RACKING

ROOF-MOUNT

DC WIRE AND CONDUIT

NOTE: NO ROOF PENETRATIONS ARE ALLOWED FOR PANELS, RACKING,

AND CONDUIT MOUNTING. ATTACHMENT TO ROOF MEMBRANE SHALL BE

COORDINATED WITH EXISTING ROOF MANUFACTURER'S REPRESENTATIVE.

DETAIL NOTES

1. CONDUIT CLAMP. SIZE AS REQUIRED.

2. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL.

3. LOCKING SQUARE & LOCK NUT.

4. 3/8" [9.52mm] MIN. GALVANIZED THREADED ROD.

5. STEEL EXPANSION ANCHOR.

6. MULTIPLE MEMBRANE STRIPPING PLIES FEATHERED AT FIELD OF ROOF BY

ROOFING CONTRACTOR. PRIME FLANGE BEFORE STRIPPING.

7. PREFABRICATED FORMED 0.06" [1.52mm] THICK ALUMINUM FLASHING ROUND

COLLAR WITH MINIMUM 3" [76mm] WIDE FLANGE. ATTACHED TO ROOF PER

MANUFACTURER'S INSTRUCTIONS.

8. BATT INSULATION.

9. CONDUIT.

10. SEAL -OFF FITTING.

11. STAINLESS STEEL CLAMP.

12. PREFABRICATED RUBBER BOOT CAP WITH GRADUATED STEPS & WEATHER-

ROOF PRESSURE SEAL TO COLLAR.

13. SEALANT AT PENETRATION TO MEMBRANE JUNCTURE BY ROOFING

CONTRACTOR.

14. ROOF MEMBRANE.

15. CONCRETE DECKING.

16. WATER CUT-OFF MASTIC COMPATIBLE WITH ROOF MEMBRANE.

GENERAL NOTES

1. MAINTAIN A MINIMUM CLEARANCE OF 1'-0" [305mm] ON ALL SIDES OF ROOF

PENETRATION FROM WALLS, CURBS AND OTHER PROJECTION TO FACILITATE

PROPER FLASHING.

2. FLANGES OF ADJACENT FLASHING SHALL NOT BE CUT OR OVERLAPPED.

3. VERIFY ROOF AND STRUCTURAL SYSTEM WITH ARCHITECT.

4. COORDINATE FLASHING INSTALLATION WITH ROOFING MANUFACTURER TO

ENSURE PROPER METHODS AND MATERIALS ARE USED TO MAINTAIN ROOF

WARRANTY.

5. VERIFY EXISTING ROOF CONSTRUCTION MATCHES DETAIL, BRING ANY

VARIANCES TO THE ATTENTION OF THE ARCHITECT/ENGINEER PRIOR TO

COMMENCING CONSTRUCTION.

. FIELD OF VIEW

16 16

14 14

13 13

11 11

NO. 71, 1/2"x18" COPPER AIR TERMINAL

NO. 28 ALUMINUM

LIGHTNING CONDUCTOR (ON PARAPET)

(28x14 AWG)

NO. 251 COPPER LOOP CABLE CLIP

W/ STAINLESS STEEL SCREW (3'-0" O.C.)

NO. 150 BRONZE

FLAT SURFACE BASE

NO. A81 5/8" x18"

ALUMINUM AIR TERMINAL

NO. A150 ALUMINUM

FLAT SURFACE PLATE

NO. A37 ALUMINUM

LIGHTNING CONDUCTOR

NO. A251 ALUMINUM LOOP

CABLE CLIP

NO. A217 ALUMINUM

BONDING PLATE

NO. 211 BIMETAL

CONNECTOR

NO. 28 COPPER LIGHTNING

CONDUCTOR (28x14 AWG)

GENERAL NOTES

A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.

B. ALL ABANDONED EXTRANEOUS CONDUITS, WIRING, DEVICES, ETC. SHALL BE REMOVED.

C. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO

ARCHITECTURAL DRAWINGS AND GENERAL REQUIREMENTS SECTION 01 00 00.

D. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THE

DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND

SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS

COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT

ALL TIMES. THE CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS

OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS

ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST

BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES OCCUR,

CONTACT THE COR THROUGH THE CONTRACTING OFFICER FOR CLARIFICATION

BEFORE PROCEEDING.

E. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND (FOR

ALL OTHERS) TO MAINTAIN OPERATION OF THE EXISTING FACILITY.

F. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL CURRENT

GOVERNING CODES AND STANDARDS.

G. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING

INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE

CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD

VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY

DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE

CONTACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL

BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING

FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.

H. ALL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROJECTED

AND/OR FIRE-STOPPED AS REQUIRED TO MAINTAIN FIRE-RATINGS INDICATED.

COORDINATE WITH ALL TRADES TO ENSURE FIRE-RATED PENETRATION REQUIREMENTS

AND DETAILS ARE MET.

I. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT AND OTHER SIMILAR PENETRATIONS

OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS

THROUGH 0-HOUR RATED WALLS AND FLOORS SHALL BE FIRESTOPPED TO RETARD

PASSAGE OF FIRE AND SMOKE.

J. ALL CONDUITS IN FINISHED ROOMS AND CORRIDORS SHALL BE CONCEALED IN A

WALL OR ABOVE CEILING.

K. ACCESS PANELS IN NON ACCESSIBLE CEILINGS SHALL BE PROVIDED FOR ALL

ELECTRICAL ITEMS REQUIRING ACCESS.

L. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN

THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER THIS WORK TO MATCH

EXISTING.

M. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED

BY THE VA SHALL BE REMOVED FROM THE PREMISES AND DISPOSED OF PROPERLY

BY THE CONTRACTOR.

N. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL

OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE WORK IN

ADVANCE WITH ALL OTHER TRADES AND REPORT IMMEDIATELY ANY DIFFICULTIES

WHICH CAN BE ANTICIPATED.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO.

A u to d e s k D o c s /1

.5

.1

I n s ta ll R o o ft o p P h o to v o lt a lic /2

-0

-E le c tr ic a l- C e n tr a l.

rv t

/1

/2

:0

:2

P M

E001

INDEX, LEGEND AND GENERAL

NOTESGUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

INSTALL ROOFTOP

PHOTOVOLTAIC - MULTIPLE

BUILDINGS

1900 E. MAIN ST., DANVILLE, IL

550-23-104

B103 & B104

10/06/2023 JAS NES

BID DOCUMENTS

FULLY SPRINKLERED2023-05127

SCALE: NONE

ROOF CONDUIT SUPPORT DETAIL

SCALE: NONE

SOLAR PV ROOF ISOMETRIC

SCALE: NONE

SOLAR PV ROOF RACK

ELECTRICAL SHEET LIST

SHEET NUMBER SHEET NAME

E001 INDEX, LEGEND AND GENERAL NOTES

E103 BUILDING 103 PLAN

E104 BUILDING 104 PLAN

E203 BUILDING 103 SINGLE LINE

E204 BUILDING 104 SINGLE LINE

E301 ROOF PATHING PLANS

SCALE: NONE

CONDUIT ROOF PENETRATIONS

SCALE: NONE

LIGHTNING PROTECTION DETAILS

SCALE: NONE

LIGHTNING PROTECTION DETAILS

Revisions: Date:

103/SOLAR

10'-0" SETBACK

(LOCATION IN ELEC/MECH

ROOM BELOW)

450W SOLAR PANEL ON

ROOF MOUNT PER DETAIL (TYP)

450W SOLAR PANEL ON

ROOF MOUNT PER DETAIL (TYP)

450W SOLAR PANEL ON

ROOF MOUNT PER DETAIL (TYP)

INVERTER #1 ZONE

INVERTER #3 ZONE

INVERTER #6 ZONE

INVERTER #4 ZONE

INVERTER #7 ZONE

60KVA INVERTER

60KVA INVERTER

60KVA INVERTER

60KVA INVERTER

60KVA INVERTER

CORRIDOR

OPEN TO GRADE OPEN TO GRADE

10'-0" SETBACK

10'-0" SETBACK

UTILITY METERING

PIPING

RTU

LADDER ACCESS TO ROOF

EXTERIOR DOORS INTO SERVICE

ROOM 127-E

E103

E103

INVERTER #5 ZONEINVERTER #2 ZONE

60KVA INVERTER

60KVA INVERTER

60KVA INVERTER

E103

103/SOLAR

AVAILABLE

SPACE

1-5/8" UNISTRUT

CHANNEL

90 DEG. FITTING P1026,

TYPICAL OF BOTH ENDS

OF HORIZONTAL RUN

POST BASE P1887

PANELBOARD

FRONT VIEWSIDE VIEW

MECH ROOM

127-E

103/MSBD

(EXIST)

103/MCC

(EXIST)

103/EMCC

(EXIST)

METERING

(NEW)

103-1

(EXIST)

103/SOLAR

(NEW)

PROVIDE STRUCTURAL SUPPORT

E103

SOLAR METERING

(NEW)

UTILITY METERING

(EXIST)

EXTERIOR DOORS

E103

NEW FEED INTO 103/MSBD

UTILIZE AVAILABLE SPACE4

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO.

A u to d e s k D o c s /1

.5

.1

I n s ta ll R o o ft o p P h o to v o lt a lic /2

-0

-E le c tr ic a l- C e n tr a l.

rv t

/1

/2

:0

:3

P M

E103

BUILDING 103 PLAN

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

INSTALL ROOFTOP

PHOTOVOLTAIC - MULTIPLE

BUILDINGS

1900 E. MAIN ST., DANVILLE, IL

550-23-104

B103 & B104

10/06/2023 JAS NES

BID DOCUMENTS

FULLY SPRINKLERED2023-05127

SCALE: 1/16" = 1'-0"

BUILDING 103 ROOF PLAN

1N

NOTE: LAYOUT SHOWN FOR PRICING AND GENERAL INFORMATION ONLY. CONTRACTOR

SHALL PROVIDE LAYOUT PLAN BASED ON APPROVED MANUFACTURER'S EXACT PANEL

DIMENSIONS AND DC STRING RECOMMENDATIONS. PLAN SHALL SHOW PANEL

LOCATIONS, DC CONDUIT PATHING, AND MPPT MOUNTING LOCATIONS. LAYOUT SHALL

ALLOW MAINTENANCE ACCESS AND CLEARANCE TO ALL ROOF EQUIPMENT. EXISTING

LIGHTNING PROTECTION SYSTEM SHALL BE MODIFIED AS REQUIRED TO INSTALL THE

SOLAR POWER SYSTEM.

1. AC FEEDER, ROUTE FEEDER BETWEEN INVERTER AND DISTRIBUTION PANEL 103/SOLAR. PROVIDE

ROOF BLOCKING SUPPORTS ALONG ROUTING EVERY 6'.

2. PROVIDE CROSS OVER BRIDGING WHERE AC FEEDERS CROSS WALKING PATH.

3. AC FEEDER DOWN TO PANEL 103/SOLAR. COORDINATE CONDUIT ROOF PENETRATION WITH

ROOFING CONTRACTOR FOR WARRANTY COMPLIANCE. REFER TO ROOF PENETRATION DETAIL ON

SHEET E001.

4. PROVIDE NEW BREAKER TO SERVE PANEL 103/SOLAR. REFER TO SINGLE LINE DIAGRAM.

5. PROVIDE METERING TO BE MONITORED BY BAS AND CLIENT eDART SYSTEM. PROVIDE ALL

REQUIRED ACCESSORIES AND PROGRAMMING. ALL WORK REQUIRING SHUT-DOWN OF ELECTRICAL

SERVICES ARE TO BE PERFORMED ON A WEEKEND DAY COORDINATED WITH COR.

6. UTILITY METERING. COORDINATE ROUGH-IN REQUIREMENTS WITH UTILITY PROVIDER.

NOTES:

SCALE: NONE

BUILDING 103 MAIN ELEC RM 127-E

A. OPEN BOXED AREAS SHOWN INDICATE ROOF MOUNTED OBSTRUCTIONS. THE DASHED OUTLINE

REPRESENTS A 4' OFFSET FROM THE EDGE OF THE OBSTRUCTION. CONTRACTOR SHALL FEILD

MEASURE AND COORDINATE PANEL LAYOUT WITH THE ROOF MOUNTED EQUIPMENT. PROVIDE

OPEN WALKWAYS TO THIS EQUIPMENT TO FACILATE MAINTENANCE OF THIS EQUIPMENT. ALSO

PROVIDE WALKING SPACE BETWEEN ROWS FOR PANEL CLEANING OR MAINTENANCE.

B. SOLAR PANEL SYSTEM LAYOUT SHOWN IS ONLY A REPRESENTATION OF WHERE PANELS SHALL BE PLACED. CONTRACTOR SHALL PROVIDE FINAL SOLAR PANEL ARRAY LAYOUT ALONG WITH SIGNED

AND SEALED STRUCTURAL WIND LOADING CALCULATIONS FOR THE BALLASTED DESIGN.

C. CONTRACTOR SHALL LOCATE THE SOLAR PANEL SYSTEM INVERTERS TO BE READILY ACCESSIBLE

TO A WALKWAY.

D. MAINTAIN EXISTING LIGHTING PROTECTION ON ROOF AND ROOF PARAPET. CONNECT SOLAR

PANEL RACKING EXISTING LIGHTNING PROTECTION CROSS MEMBER CABLING PER MANUFACTURER REQURIEMENTS. COORDINATE LOCATION AND NUMBER OF NEW/REPLACEMENT AIR TERMINALS FOR

A COMPLETE UL 1703 LIGHTING PROTECTION SYSTEM.

E. REFERENCE SHEET E301 FOR WALKING PATH INFORMATION.

GENERAL NOTES:

SCALE: NONE

BUILDING 103 NORTH VIEW

SCALE: NONE

BUILDING 103 SOUTH VIEW

Revisions: Date:

SCALE: NONE

FREE STANDING PANEL

SCALE: 1/8" = 1'-0"

FIRST FLOOR - SERVICE RM 127-E

104/SOLAR

450W SOLAR PANEL ON

ROOF MOUNT PER DETAIL (TYP)

PANEL IN ELECTRICAL

ADJACENT TO 104/MSB

INVERTER #1 ZONE

INVERTER #2 ZONE INVERTER #3 ZONE

INVERTER #4 ZONE

INVERTER #5 ZONE

INVERTER #7 ZONE

INVERTER #6 ZONE

60KVA INVERTER

60KVA INVERTER

60KVA INVERTER

60KVA INVERTER

60KVA INVERTER

60KVA INVERTER

10'-0" SETBACK

COOLING

TOWER

GENERATOR EXHAUST

STACK

MECH

ALCOVE

RTU

RTU

UTILITY METERING

LADDER ACCESS TO ROOF

FROM COOLING TOWER ALCOVE

EXTERIOR STAIR

ROOF ACCESS

60KVA INVERTER

E104

E104

E104

AVAILABLE SPARE

BREAKER TO BE UTILIZED

TRANS. ROOM

100A

104/MSBD

(EXIST)

METERING

(NEW)

104/SOLAR (NEW)

E104

SOLAR

METERING

(NEW)

UTILITY

METERING

(EXIST)

NEW FEED INTO 104/MSBD

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO.

A u to d e s k D o c s /1

.5

.1

I n s ta ll R o o ft o p P h o to v o lt a lic /2

-0

-E le c tr ic a l- C e n tr a l.

rv t

/1

/2

:0

:4

P M

E104

BUILDING 104 PLAN

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

INSTALL ROOFTOP

PHOTOVOLTAIC - MULTIPLE

BUILDINGS

1900 E. MAIN ST., DANVILLE, IL

550-23-104

B103 & B104

10/06/2023 JAS NES

BID DOCUMENTS

FULLY SPRINKLERED2023-05127

SCALE: 1/16" = 1'-0"

BUILDING 104 ROOF PLAN

1N

NOTE: LAYOUT SHOWN FOR PRICING AND GENERAL INFORMATION ONLY. CONTRACTOR

SHALL PROVIDE LAYOUT PLAN BASED ON APPROVED MANUFACTURER'S EXACT PANEL

DIMENSIONS AND DC STRING RECOMMENDATIONS. PLAN SHALL SHOW PANEL

LOCATIONS, DC CONDUIT PATHING, AND MPPT MOUNTING LOCATIONS. LAYOUT SHALL

ALLOW MAINTENANCE ACCESS AND CLEARANCE TO ALL ROOF EQUIPMENT. EXISTING

LIGHTNING PROTECTION SYSTEM SHALL BE MODIFIED AS REQUIRED TO INSTALL THE

SOLAR POWER SYSTEM.

1. AC FEEDER, ROUTE FEEDER BETWEEN INVERTER AND DISTRIBUTION PANEL 104/SOLAR. PROVIDE

ROOF BLOCKING SUPPORTS ALONG ROUTING EVERY 6'.

2. PROVIDE CROSS OVER BRIDGING WHERE AC FEEDERS CROSS WALKING PATH.

3. AC FEEDER DOWN TO PANEL 104/SOLAR. COORDINATE CONDUIT ROOF PENETRATION WITH

ROOFING CONTRACTOR FOR WARRANTY COMPLIANCE. REFER TO ROOF PENETRATION DETAIL ON

SHEET E001.

4. UTILIZE SPARE BREAKER TO SERVE PANEL 104/SOLAR. REFER TO SINGLE LINE DIAGRAM.

5. PROVIDE METERING TO BE MONITORED BY BAS AND CLIENT eDART SYSTEM. PROVIDE ALL

REQUIRED ACCESSORIES AND PROGRAMMING. ALL WORK REQUIRING SHUT-DOWN OF ELECTRICAL

SERVICES ARE TO BE PERFORMED ON A WEEKEND DAY COORDINATED WITH COR.

6. UTILITY METERING. COORDINATE ROUGH-IN REQUIREMENTS WITH UTILITY PROVIDER.

NOTES:

SCALE: NONE

BUILDING 104 MAIN ELEC ROOM RM 100A

A. OPEN BOXED AREAS SHOWN INDICATE ROOF MOUNTED OBSTRUCTIONS. THE DASHED OUTLINE

REPRESENTS A 4' OFFSET FROM THE EDGE OF THE OBSTRUCTION. CONTRACTOR SHALL FEILD

MEASURE AND COORDINATE PANEL LAYOUT WITH THE ROOF MOUNTED EQUIPMENT. PROVIDE

OPEN WALKWAYS TO THIS EQUIPMENT TO FACILATE MAINTENANCE OF THIS EQUIPMENT. ALSO

PROVIDE WALKING SPACE BETWEEN ROWS FOR PANEL CLEANING OR MAINTENANCE.

B. SOLAR PANEL SYSTEM LAYOUT SHOWN IS ONLY A REPRESENTATION OF WHERE PANELS SHALL BE PLACED. CONTRACTOR SHALL PROVIDE FINAL SOLAR PANEL ARRAY LAYOUT ALONG WITH SIGNED

AND SEALED STRUCTURAL WIND LOADING CALCULATIONS FOR THE BALLASTED DESIGN.

C. CONTRACTOR SHALL LOCATE THE SOLAR PANEL SYSTEM INVERTERS TO BE READILY ACCESSIBLE

TO A WALKWAY.

D. MAINTAIN EXISTING LIGHTING PROTECTION ON ROOF AND ROOF PARAPET. CONNECT SOLAR

PANEL RACKING EXISTING LIGHTNING PROTECTION CROSS MEMBER CABLING PER MANUFACTURER REQURIEMENTS. COORDINATE LOCATION AND NUMBER OF NEW/REPLACEMENT AIR TERMINALS FOR

A COMPLETE UL 1703 LIGHTING PROTECTION SYSTEM.

E. REFERENCE SHEET E301 FOR WALKING PATH INFORMATION.

GENERAL NOTES:

SCALE: NONE

BUILDING 104 NORTH VIEW

SCALE: NONE

BUILDING 104 SOUTH VIEW

Revisions: Date:

SCALE: 1/8" = 1'-0"

FIRST FLOOR - TRANSFORMER RM 100A

480Y/277V-3PH-4W

CIRCUIT AMPS

AVAILABLE SHORT

DESCRIPTION

REF.

POINT

FAULT CURRENT

1 EX. 103/MSB 19,550 ISCA

MAIN DIST. "103/MAIN SWITCHBOARD"

103/SOLAR

INVERT

#1

60KW

POWER OPTIMIZER

(TYP)

STRING PV-S-1

450W SOLAR PANEL (TYP)

POWER OPTIMIZER

(TYP)

STRING PV-S-2

450W SOLAR PANEL (TYP)

POWER OPTIMIZER

(TYP)

STRING PV-S-3

450W SOLAR PANEL (TYP)

POWER OPTIMIZER

(TYP)

STRING PV-S-4

450W SOLAR PANEL (TYP)

A1

A1

A1

A2 3

A1

A3

A3

A3

A3

POWER OPTIMIZER

(TYP)

STRING PV-S-5

450W SOLAR PANEL (TYP)

A1

A3

POWER OPTIMIZER

(TYP)

STRING PV-S-6

450W SOLAR PANEL (TYP)

A1

A3

POWER OPTIMIZER

(TYP)

STRING PV-S-7

450W SOLAR PANEL (TYP)

A1

A3

DC

SPLICE

BOX

100A/3P

DISC.

103/SOLAR 17,772 ISCA

TO BUILDING

GROUND

TYP. OF 7 INVERTERS

18 PV

PANELS

18 PV

PANELS

18 PV

PANELS

18 PV

PANELS

18 PV

PANELS

18 PV

PANELS

18 PV

PANELS

MANHOLE

NO. 33A

200A

T/103

M

G F P

SWBD

600AF

480AT

BUSSBAR

ABANDONED

IN SWBD

600AF

300AT

600AF

480AT

METERING

1600AF

1600AT 600AF

300AT

SPACE

100A 3P

EMERG

FROM

BLDG 104

300A

3P 800AF

800AT

SPACE

TRANSFER SWITCH CHILLEREMERGENCY POWER SECTIONNORMAL POWER SECTION

M

200A 200A

L

N E

SPACE SPACE

100A 3P

100A 3P

100A 3P

SPACESPACE

103/PE

103/PF

103/MCC

103/EG

103/EF

103/EE

103/EMCC

300A 3P

103/MDP1(CHILLER)

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO.

A u to d e s k D o c s /1

.5

.1

I n s ta ll R o o ft o p P h o to v o lt a lic /2

-0

-E le c tr ic a l- C e n tr a l.

rv t

/1

/2

:0

:4

P M

E203

BUILDING 103 SINGLE LINE

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

INSTALL ROOFTOP

PHOTOVOLTAIC - MULTIPLE

BUILDINGS

1900 E. MAIN ST., DANVILLE, IL

550-23-104

B103 & B104

10/06/2023 JAS NES

BID DOCUMENTS

FULLY SPRINKLERED2023-05127

DESIGN NOTES:

A SYSTEM DESIGNED AROUND MULTIPLE 50KW INVERTER UNITS, EACH SERVED BY MULTIPLE

STRINGS OF SOLAR PANELS. FINAL LAYOUT, NUMBER OF STRINGS, AND PANELS PER STRING

TO BE COORDINATED WITH THE SOLAR EQUIPMENT SUPPLIER.

396.9 kVA 396.9 kVA (477 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 477 A

Total Conn.: 477 A

Total Est. Demand: 396.9 kVA

Total Conn. Load: 396.9 kVA

Spare 396900 VA 100.00% 396900 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 132.30 kVA 132.30 kVA 132.30 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 -- -- -- 18.9 0.0 -- -- -- 24

21 -- -- -- 18.9 0.0 -- -- -- 22

19 103/INV7 90 A 3 18.9 0.0 3 90 A Spare 20

17 -- -- -- 18.9 18.9 -- -- -- 18

15 -- -- -- 18.9 18.9 -- -- -- 16

13 103/INV5 90 A 3 18.9 18.9 3 90 A 103/INV6 14

11 -- -- -- 18.9 18.9 -- -- -- 12

9 -- -- -- 18.9 18.9 -- -- -- 10

7 103/INV3 90 A 3 18.9 18.9 3 90 A 103/INV4 8

5 -- -- -- 18.9 18.9 -- -- -- 6

3 -- -- -- 18.9 18.9 -- -- -- 4

1 103/INV1 90 A 3 18.9 18.9 3 90 A 103/INV2 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 600 A

Supply From: Enclosure: Type 1 Mains Type: M.L.O.

Location: Mounting: Surface A.I.C. Rating: 22,000

Panel: 103/SOLAR

NOTES

1 NEW 600A/3P BREAKER IN EXISTING MAIN SWITCHBOARD "103/SWBD". MATCH

EXISTING BREAKERS MANUFACTURER AND TYPE. RUN 2 SETS 4-350KCMIL, 1-#1

GRD. IN 4" C.

2 PROVIDE METERING TO BE MONITORED BY BAS AND CLIENT eDART SYSTEM.

PROVIDE ALL REQUIRED ACCESSORIES AND PROGRAMMING. ALL WORK

REQUIRING SHUT-DOWN OF ELECTRICAL SERVICES ARE TO BE PERFORMED ON

A WEEKEND DAY COORDINATED WITH COR. METERING SHALL BE SIMILAR TO

SCHNIEDER ELECTRIC 3500 SERIES WITH RS-485/MODBUS COMMUNICATIONS.

COORDINATE INTERGRATION WITH SITE BAS MAINTENANCE VENDOR (CONSERV).

3 4-#3, 1-#8 GRD. IN 1.25" C.

4 UTILITY METERING. COORDINATE ROUGH-IN REQUIREMENTS WITH UTILITY

PROVIDER.

A1 DC STRING CONDUCTOR SIZING PER MANUFACTURER RECOMMENDATIONS.

A2 NUMBER OF CONSOLIDATED DC STRING RETURNS TO INVERTER PER

MANUFACTURER RECOMMENDATIONS.

A3 GEC PER MANUFACTURER RECOMMENDATIONS.

SCALE: NONE

SINGLE LINE DIAGRAM

MAIN ELEC. ROOM

103/MSBD

Incoming Power

Revisions: Date:

104/SOLAR

INVERT

#1

60KW

POWER OPTIMIZER

(TYP)

STRING PV-S-1

450W SOLAR PANEL (TYP)

POWER OPTIMIZER

(TYP)

STRING PV-S-2

450W SOLAR PANEL (TYP)

POWER OPTIMIZER

(TYP)

STRING PV-S-3

450W SOLAR PANEL (TYP)

POWER OPTIMIZER

(TYP)

STRING PV-S-4

450W SOLAR PANEL (TYP)

A1

A1

A1

A2 3

A1

A3

A3

A3

A3

POWER OPTIMIZER

(TYP)

STRING PV-S-5

450W SOLAR PANEL (TYP)

A1

A3

POWER OPTIMIZER

(TYP)

STRING PV-S-6

450W SOLAR PANEL (TYP)

A1

A3

POWER OPTIMIZER

(TYP)

STRING PV-S-7

450W SOLAR PANEL (TYP)

A1

A3

DC

SPLICE

BOX

M

100A/3P

DISC.

TO BUILDING

GROUND

TYP. OF 7 INVERTERS

SPARE

16 PV

PANELS

16 PV

PANELS

16 PV

PANELS

16 PV

PANELS

16 PV

PANELS

16 PV

PANELS

16 PV

PANELS

M

CIRCUIT AMPS

AVAILABLE SHORT

DESCRIPTION

REF.

POINT

FAULT CURRENT

1 EX. 104/MSB 29,460 ISCA

104/SOLAR 27,601 ISCA

G

1200AT

1600AF

480Y/277V-3PH-4W

DIESEL GENERATOR W/

96 HOUR TANK

COMBINATION GENERATOR

QUICK-CONNECT / LOAD BANK

CONNECT

TEMPORARY

GENERATOR

LOAD BANK

K

K

GEN-EM

15A /2P

480V-1PH

15 KVA

120/240V

-1PH-3W

45A /2P

GEN-N

480V-1PH

15 KVA

120/240V

-1PH-3W

NENENE NE NE NENE NENE

800AF

100AT

600AF

420AT

600AF

300AT

600AF

420AT

600AF

300AT

SPARE

MCC-1 PL-2 CHILLER PL-5 PL-4

600AF

300AT

600AF

300AT

400AF

200AT

300AF

300AT

600AF

420AT

400AF

200AT

600AF

300AT

400AF

200AT

480V 1600A 4W SWITCHBOARD @ 65kA

OLDER INCOMING SECTION 480V 3200A 3P-4W SWITCHBOARD @ 100kA

IQ

1600AF

1600AT

GF

RELAY

NORMAL POWER DISTRIBUTION (RM 101)EMERGENCY POWER SWITCHGEAR

350A /3P

CHILLER 1

350A /3P

CHILLER 2

40 KVAR

POWER

FACTOR

CORRECTION

CAPACITOR

40 KVAR

POWER

FACTOR

CORRECTION

CAPACITOR

104/NX

3200AF

3200AT

800AF

800AT MANHOLE

NO. 35A

(FUTURE

ALT.

SOURCE

3200AF

3200AT

300A

0\

3P

T/104

4160V - 480/277V

2000KVA

MASTER CONTROL CENTER

ATS-104/ATSS

480Y/277V-3PH-4W

400A

60AF

50AT

60AF

50AT

ATS-104/ATSC

480Y/277V-3PH-4W

400A

104/SH1A

104/EMDP-2A

400AF

250AT

104/CDH1A

ATS-101/ATSS

480Y/277V-3PH-4W

400A

60AF

50AT

60AF

50AT

ATS-101/ATSC

480Y/277V-3PH-4W

400A

101/SH1A 101/CH1A

101/MSB

ATS-103/ATSS

480Y/277V-3PH-4W

200A

60AF

50AT

60AF

50AT

ATS-103/ATSC

480Y/277V-3PH-4W

400A

103/SH1A 103/CH1A

103/MSB

ATS-102/ATSS

480Y/277V-3PH-4W

200A

60AF

50AT

60AF

50AT

ATS-102/ATSC

480Y/277V-3PH-4W

400A

102/SH1A 102/CH1A

102/MSB

480V-3PH

30 KVA

208Y/120V

-3PH-4W

50A /3P

104/

CL1A

ATS-125

208Y/120V-3PH-4W

100A

125/EM

125/MDP

480V-3PH

30 KVA

208Y/120V

-3PH-4W

100/P2

480Y/277V-3PH-4W

MAIN DIST. "104/MSWB"

800AF

600AT

104/PL-3

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO.

A u to d e s k D o c s /1

.5

.1

I n s ta ll R o o ft o p P h o to v o lt a lic /2

-0

-E le c tr ic a l- C e n tr a l.

rv t

/1

/2

:0

:4

P M

E204

BUILDING 104 SINGLE LINE

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

INSTALL ROOFTOP

PHOTOVOLTAIC - MULTIPLE

BUILDINGS

1900 E. MAIN ST., DANVILLE, IL

550-23-104

B103 & B104

10/06/2023 JAS NES

BID DOCUMENTS

FULLY SPRINKLERED2023-05127

403.2 kVA 403.2 kVA (485 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 485 A

Total Conn.: 485 A

Total Est. Demand: 403.2 kVA

Spare 201600 VA 100.00% 201600 VA Total Conn. Load: 403.2 kVA

Power 201600 VA 100.00% 201600 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 134.40 kVA 134.40 kVA 134.40 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 -- -- -- 16.8 16.8 -- -- -- 24

21 -- -- -- 16.8 16.8 -- -- -- 22

19 104/INV7 80 A 3 16.8 16.8 3 80 A Spare 20

17 -- -- -- 16.8 16.8 -- -- -- 18

15 -- -- -- 16.8 16.8 -- -- -- 16

13 104/INV5 80 A 3 16.8 16.8 3 80 A 104/INV6 14

11 -- -- -- 16.8 16.8 -- -- -- 12

9 -- -- -- 16.8 16.8 -- -- -- 10

7 104/INV3 80 A 3 16.8 16.8 3 80 A 104/INV4 8

5 -- -- -- 16.8 16.8 -- -- -- 6

3 -- -- -- 16.8 16.8 -- -- -- 4

1 104/INV1 80 A 3 16.8 16.8 3 80 A 104/INV2 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 600 A

Supply From: Enclosure: Type 1 Mains Type: M.L.O.

Location: Mounting: Surface A.I.C. Rating: 42,000

Panel: 104/SOLAR

DESIGN NOTES:

A SYSTEM DESIGNED AROUND MULTIPLE 50KW INVERTER UNITS, EACH SERVED BY MULTIPLE

STRINGS OF SOLAR PANELS. FINAL LAYOUT, NUMBER OF STRINGS, AND PANELS PER STRING

TO BE COORDINATED WITH THE SOLAR EQUIPMENT SUPPLIER.

NOTES

1 UTIILZE EXISTING SPARE 800A FRAME BREAKER IN EXISTING

SWITCHBOARD "104/MSB". RUN 2 SETS OF 4-350 KCMIL, 1-#1 GRD. IN 4" C.

2 PROVIDE METERING TO BE MONITORED BY BAS AND CLIENT eDART

SYSTEM. PROVIDE ALL REQUIRED ACCESSORIES AND PROGRAMMING. ALL

WORK REQUIRING SHUT-DOWN OF ELECTRICAL SERVICES ARE TO BE

PERFORMED ON A WEEKEND DAY COORDINATED WITH COR. METERING

SHALL BE SIMILAR TO SCHIENDER ELECTRIC 3500 SERIES WITH

RS-485/MODBUS COMMUNICATIONS. COORDINATE INTEGRATION INTO BAS

SYSTEM WITH SITE BAS SYSTEM MAINTENANCE VENDOR (CONSERV).

3 4-#3, 1-#8 GRD. IN 1.25" C.

4 UTILITY METERING. COORDINATE ROUGH-IN REQUIREMENTS WITH UTILITY

PROVIDER.

A1 DC STRING CONDUCTOR SIZING PER MANUFACTURER RECOMMENDATIONS.

A2 NUMBER OF CONSOLIDATED DC STRING RETURNS TO INVERTER PER

MANUFACTURER RECOMMENDATIONS.

A3 GEC PER MANUFACTURER RECOMMENDATIONS.

104/MSB

MAIN ELEC. ROOM

SCALE: NONE

SINGLE LINE DIAGRAM

18900 18900

18900 18900

18900 18900

132.30kVA

Incoming Power 396900VA

18900 18900

18900 18900

18900 18900

132.30kVA 132.30kVA

396900VA

396.9kVA

396.9kVA

477.6A

477.6A

396.9kVA 396.9kVA (477.6A)

Revisions: Date:

18900 18900

18900 18900

Incoming Power

J J J J

OPEN TO GRADE OPEN TO GRADE

ELEVATED ROOF AREA

10'-0" SETBACK

10'-0" SETBACK

ELEVATED ROOF AREA

EXIST. WALKING PATH

NEW WALKING PATH (TYP)

10'-0" SETBACK

10'-0" SETBACK

COOLING

TOWER

EXIST. WALKING PATH

NEW WALKING PATH (TYP)

ROOF PAD

ADHERE TO ROOF

MEMBRANE

METAL DECK

SUPPORT

ATTACHED TO

ROOF PAD

SYSTEM CONDUITS

ON ROOF SUPPORTS

3'-6" MIN.

6" MIN

CLEARANCE

ABOVE CONDUITS

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO.

A u to d e s k D o c s /1

.5

.1

I n s ta ll R o o ft o p P h o to v o lt a lic /2

-0

-E le c tr ic a l- C e n tr a l.

rv t

/1

/2

:0

:5

P M

E301

ROOF PATHING PLANS

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

INSTALL ROOFTOP

PHOTOVOLTAIC - MULTIPLE

BUILDINGS

1900 E. MAIN ST., DANVILLE, IL

550-23-104

B103 & B104

10/06/2023

BID DOCUMENTS

FULLY SPRINKLERED2023-05127

Revisions: Date:

SCALE: 3/64" = 1'-0"

BUILDING 103 WALKING PATH PLAN

SCALE: 3/64" = 1'-0"

BUILDING 104 WALKING PATH PLAN

A. MAINTAIN EXISTING WALKING PATHS AND PROVIDE NEW WALKWAYS AS NECESSARY ALONG ROOF

FOR ACCESS TO EXISTING ROOF MOUNTED EQUIPMENT. MAINTAIN A WALKING PATH CLEARANCE

WIDTH MINIMUM OF 3'-6".

B. ROUTING OF THE SOLAR ARRAY SYSTEMS CONDUITS SHALL NOT CROSS OR IMPED ACCESS TO

WALKING PATHS. WHERE THIS IS NOT POSSIBLE, PROVIDE CROSS OVER OR RAMP SYSTEM TO

MAINTAIN A CLEAR WALKING PATH ON ROOF. CROSS OVER/RAMP SHALL BE SIMILAR TO MIRO

INDUSTRIES BRIDGE CROSSOVER.

GENERAL NOTES:

ROOF MOUNTED BRIDGE

GI000 - Cover Sheet
Sheets
GI000 - COVER SHEET
Sheet - E001 - INDEX, LEGEND AND GENERAL NOTES
Sheets
E001 - INDEX, LEGEND AND GENERAL NOTES
E103 - BUILDING 103 PLAN
E104 - BUILDING 104 PLAN
E203 - BUILDING 103 SINGLE LINE
E204 - BUILDING 104 SINGLE LINE
E301 - ROOF PATHING PLANS
Sheet - E103 - BUILDING 103 PLAN
Sheets
E001 - INDEX, LEGEND AND GENERAL NOTES
E103 - BUILDING 103 PLAN
E104 - BUILDING 104 PLAN
E203 - BUILDING 103 SINGLE LINE
E204 - BUILDING 104 SINGLE LINE
E301 - ROOF PATHING PLANS
Sheet - E104 - BUILDING 104 PLAN
Sheets
E001 - INDEX, LEGEND AND GENERAL NOTES
E103 - BUILDING 103 PLAN
E104 - BUILDING 104 PLAN
E203 - BUILDING 103 SINGLE LINE
E204 - BUILDING 104 SINGLE LINE
E301 - ROOF PATHING PLANS
Sheet - E203 - BUILDING 103 SINGLE LINE
Sheets
E001 - INDEX, LEGEND AND GENERAL NOTES
E103 - BUILDING 103 PLAN
E104 - BUILDING 104 PLAN
E203 - BUILDING 103 SINGLE LINE
E204 - BUILDING 104 SINGLE LINE
E301 - ROOF PATHING PLANS
Sheet - E204 - BUILDING 104 SINGLE LINE
Sheets
E001 - INDEX, LEGEND AND GENERAL NOTES
E103 - BUILDING 103 PLAN
E104 - BUILDING 104 PLAN
E203 - BUILDING 103 SINGLE LINE
E204 - BUILDING 104 SINGLE LINE
E301 - ROOF PATHING PLANS
Sheet - E301 - ROOF PATHING PLANS
Sheets
E001 - INDEX, LEGEND AND GENERAL NOTES
E103 - BUILDING 103 PLAN
E104 - BUILDING 104 PLAN
E203 - BUILDING 103 SINGLE LINE
E204 - BUILDING 104 SINGLE LINE
E301 - ROOF PATHING PLANS

File details come from the government source that posted it. Updated .