This file is an attachment to a federal solicitation for wastewater treatment plant improvements. The solicitation number is 140P2023R0125 and is seeking proposals for work on the MORU 272051 Wastewater Treatment Plant issued by the Department of the Interior National Park Service National Office. Offerors should review Attachment 2 for the general civil requirements related to the solicitation. Proposals are due by the date specified in the solicitation document for improvements to the wastewater treatment plant located on National Park Service property.
View the file
Other files
Show 40 more
Latest 50 of 58 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OLD
BALDY
MOUNTAIN
TO 385
MOUNT RUSHMORE
SCULPTURES
VISITOR AREA
LEGEND
AMPHITHEATER
WATER RESERVOIR
CONCESSION
BUILDING
ENERGY
CENTER
DORMITORY
INTERPRETIVE
CENTER
MAINTENANCE BUILDING
SCULPTOR'S STUDIO
& RESIDENCE
WASTE WATER
TREATMENT PLANT
WATER PUMPING
& STORAGE AREA
SWITCHBACK
(INACTIVE)
HOUSING
AREA
TO 36
16A
KEYSTONE
TO 16
TO
HAYWARD
THIS PROJECT
MOUNT RUSHMORE NATIONAL MEMORIAL
SCALE OF FEET
400' 0' 800'
100 0 100 200
400'
SCALE OF METERS
WASTEWATER TREATMENT PLANT EXPANSION
MAP LEGEND
PARK BOUNDARY
PAVED ROAD
UNPAVED ROAD
TRAIL
VISITOR CENTER
PARK HEADQUARTERS
PARKING
RESTROOMS
HQ.
V.C.
297 16
16A
16A 36
89 101
DEERFIELD
RESERVOIR
HILL
CITY
JEWEL
CAVE
N.M. CUSTER
PRINGLE
ARGYLE
CUSTER
STATE
PARK
WIND CAVE
NATIONAL
PARK
HERMOSA
HAYWARD
KEYSTONE
SHERIDAN
LAKE MOUNT RUSHMORE
NATIONAL MEMORIAL
PACTOLA
RESERVOIR
NEMO
BLACK
HAWK RAPID
CITY
SOUTHWESTERN
SOUTH DAKOTA
05 10
MILES
KILOMETERS
5 10
OR
OR
Development (Title I)
Prepared in Accordance with Design by Design Development (Title I)
Construction Drawing Not Preceded
Approved by Superintendent on
Variance from Design Development (Title I)
Project Manager
Drawing No.
Date
Date
QUALITY DESIGN CERTIFICATION
PMIS/PKG NO.
DRAWING NO.
SHEET
OF
DEPARTMENT OF THE INTERIOR
UNITED STATES
NATIONAL PARK SERVICE
DENVER SERVICE CENTER STATEREGION COUNTY
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF PROJECT
C R e v it L o c a l\
-0
S e ri e s
G e n e ra l_ R ic W e b e r.
rv t
/1
/2
:4 :2
A
M
MOUNT RUSHMORE NATIONAL MONUMENT
272051
PLANT EXPANSION 323
1 235REGION PENNINGTON SOUTH DAKOTA
186787
FINAL CONSTRUCTION
DOCUMENTS
WASTEWATER TREATMENT
A/E FIRM
PRIME/ARCH: OTHER ENGINEERS:
A/E CONTRACT #
HDR INC.
OMAHA, NE
KENNETH HAHN ARCHITECTS
OMAHA, NE
VOLUME 1
Mark Sheet REVISION Date Initial
R
E
G
I S
T E
R
E
D
P
R
O
F
E
SS
I O
N
A
L
A
R
C H
I T
E
C
T
S
O
U
T
H
D A
K
O
T
A
14417
STEPHEN R. SMITH
R
E
G . N
O
6/13/2023
06/13/23
Stephen R. Smith, PA Christopher Lee Robinson, PE
Svein Magnussen, PE Shaun Nienhueser, PE
Kyle L. Ganskop, PE Kaitlyn E. Roholff, PE
SHEET NUMBERING SYSTEM
DISCIPLINE DESIGNATION
G - GENERAL
X - DEMOLITION
C - CIVIL
S - STRUCTURAL
A - ARCHITECTURAL
D - PROCESS
M - MECHANICAL (HVAC)
P - PLUMBING
E - ELECTRICAL
Y - PROCESS, INSTRUMENTATION AND CONTROLS (P&ID)
04-A101
AREA DESIGNATION (SEE LIST BELOW)
DISCIPLINE DESIGNATION (SEE LIST BELOW)
SHEET TYPE DESIGNATION (SEE LIST BELOW)
SHEET NUMBER
AREA DESIGNATION
00 - GENERAL
01 - SITE
02 - NORTH BUILDING
03 - SOUTH BUILDING
04 - WEST AERATION BASIN (1A/2A)
05 - EAST AERATION BASIN (1B/2B)
06 - WEST CLARIFIER (#1)
07 - EAST CLARIFIER (#2)
08 - WINTER BIOSOLIDS BUILDING
09 - PROCESS & INSTRUMENTATION DIAGRAMS
SHEET TYPE DESIGNATION
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - LARGE SCALE VIEWS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - NETWORK
8 - PROFILES
9 - ISOMETRICS
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
C R e v it L o c a l\ -0
S e ri e s
G e n e ra l_ R ic W e b e r.
rv t
/1
/2
:0 :1
A
M
G001
MOUNT RUSHMORE NATIONAL MONUMENT
272051
SCHEDULE OF ALL SHEETS /
ALL VOLUMES
KHA
CLZ / TWM / HHD
06/13/23
RDW
18678700-
FINAL CONSTRUCTION DOCUMENTS
SCHEDULE OF DRAWINGS
SHEET SUB-SHEET SHEET NAME
1 00-G000 COVER SHEET
2 00-G001 SCHEDULE OF ALL SHEETS / ALL VOLUMES
3 00-G002 SYMBOLS, ABBREVIATIONS, GENERAL NOTES
4 00-G003 ACCESSIBILITY REQUIREMENTS
5 00-S001 STRUCTURAL GENERAL NOTES
6 00-S501 GENERAL STRUCTURAL DETAILS
7 00-S502 GENERAL STRUCTURAL DETAILS
8 00-S503 GENERAL STRUCTURAL MASONRY DETAILS
9 00-S504 GENERAL STRUCTURAL DETAILS
10 00-S505 GENERAL STRUCTURAL DETAILS
11 00-D001 PROCESS LEGEND
12 00-D002 PROCESS FLOW DIAGRAMS
13 00-D003 PROCESS FLOW DIAGRAMS
14 00-D004 PROCESS FLOW DIAGRAMS
15 00-D005 PROCESS FLOW DIAGRAMS
16 00-D006 HYDRAULIC PROFILE
17 00-D501 GENERAL PROCESS DETAILS
18 00-M001 MECHANICAL LEGEND
19 00-M501 MECHANICAL DETAILS
20 00-M601 MECHANICAL SCHEDULES
21 00-P501 PLUMBING DETAILS
22 00-P601 PLUMBING SCHEDULES
23 00-E001 ELECTRICAL LEGEND
24 00-E002 ELECTRICAL LEGEND 2
25 00-E501 ELECTRICAL DETAILS
26 00-E502 ELECTRICAL DETAILS
27 00-E601 CONTROL BLOCK DIAGRAM 1
28 00-E602 CONTROL BLOCK DIAGRAM 2
29 00-E605 LUMINAIRE SCHEDULE
30 00-E606 LIGHTING CONTROL STRATEGY
31 00-E607 HAZARDOUS CLASSIFICATION AND ELECTRICAL EQUIPMENT INSTALLATION
SCHEDULE OF DRAWINGS
SHEET SUB-SHEET SHEET NAME
101 02-D501 NORTH BUILDING PROCESS DETAILS
102 02-D901 NORTH BUILDING PROCESS ISOMETRIC VIEW
103 02-D902 NORTH BUILDING PROCESS ISOMETRIC VIEW
104 02-D903 NORTH BUILDING MICRO-C ISOMETRIC
105 02-M101 NORTH BUILDING LOWER LEVEL MECHANICAL PLAN
106 02-M102 NORTH BUILDING UPPER LEVEL MECHANICAL PLAN
107 02-P101 NORTH BUILDING LOWER LEVEL PLUMBING PLAN
108 02-P102 NORTH BUILDING UPPER LEVEL PLUMBING PLAN
109 02-P103 NORTH BUILDING PLUMBING RISER DIAGRAMS
110 02-E101 NORTH BUILDING LOWER LEVEL POWER PLAN
111 02-E102 NORTH BUILDING UPPER LEVEL POWER PLAN
112 02-E103 NORTH BUILDING LOWER LEVEL LIGHTING PLAN
113 02-E104 NORTH BUILDING UPPER LEVEL LIGHTING PLAN
114 02-E105 NORTH BUILDING LIGHTNING PROTECTION / GROUNDING PLAN
115 02-E601 NORTH BUILDING MCC1 ONE-LINE
116 02-E602 NORTH BUILDING 02-SWBD-1 ONE-LINE AND ELEVATION
117 02-E603 NORTH BUILDING 02-MCC-1 AND ELEVATION
118 02-E604 NORTH BUILDING 02-MCC-2 ONE-LINE AND ELEVATION
119 02-E605 NORTH BUILDING MOTOR CONTROL DIAGRAM 1
120 02-E606 NORTH BUILDING MOTOR CONTROL DIAGRAM 2
121 02-E607 NORTH BUILDING SCHEDULES
122 03-VOL3 COVER SHEET VOLUME 3
123 03-G001 SOUTH BUILDING CODE ANALYSIS
124 03-X101 SOUTH BUILDING ARCHITECTURAL DEMOLITION PLANS
125 03-X102 SOUTH BUILDING LOWER LEVEL PROCESS DEMOLITION PLAN
126 03-X103 SOUTH BUILDING UPPER LEVEL PROCESS DEMOLITION PLAN
127 03-X104 SOUTH BUILDING MECHANICAL DEMOLITION PLANS
128 03-X105 SOUTH BUILDING LOWER LEVEL ELECTRICAL DEMOLITION PLAN
129 03-X106 SOUTH BUILDING UPPER LEVEL ELECTRICAL DEMOLITION PLAN
130 03-X601 SOUTH BUILDING ELECTRICAL MCC-2 ONE-LINE - DEMO
131 03-X602 SOUTH BUILDING MISC ONE-LINE - DEMO
132 03-X603 SOUTH BUILDING MISC ONE-LINE - DEMO
133 03-S101 SOUTH BUILDING FOUNDATION PLAN
134 03-S102 SOUTH BUILDING UPPER LEVEL FLOOR PLAN
135 03-S103 SOUTH BUILDING ROOF FRAMING PLAN AND TRUSS LOADING DIAGRAMS
136 03-S301 SOUTH BUILDING SECTIONS
137 03-S302 SOUTH BUILDING SECTIONS
138 03-S303 SOUTH BUILDING SECTIONS
139 03-A101 SOUTH BUILDING LOWER LEVEL FLOOR PLAN
140 03-A102 SOUTH BUILDING UPPER LEVEL AND LOADING DOCK FLOOR PLAN
141 03-A103 SOUTH BUILDING REFLECTED CEILING AND ROOF PLANS
142 03-A201 SOUTH BUILDING EXTERIOR ELEVATIONS
143 03-A301 SOUTH BUILDING SECTIONS AND DETAILS
144 03-A302 SOUTH BUILDING WALL SECTIONS
145 03-A303 SOUTH BUILDING WALL SECTIONS
146 03-A501 SOUTH BUILDING DETAILS
147 03-A601 SOUTH BUILDING DOOR AND WINDOW SCHEDULES
148 03-A602 SOUTH BUILDING ROOM FINISH SCHEDULE
149 03-D101 SOUTH BUILDING LOWER LEVEL PROCESS PLAN
150 03-D102 SOUTH BUILDING UPPER LEVEL PROCESS PLAN
151 03-D103 SOUTH BUILDING EQ BASINS PLAN
152 03-D301 SOUTH BUILDING PROCESS SECTION
153 03-D302 SOUTH BUILDING PROCESS SECTION
154 03-D303 SOUTH BUILDING PROCESS SECTION
155 03-D304 SOUTH BUILDING PROCESS SECTION
156 03-D501 SOUTH BUILDING TANK DETAILS
157 03-D502 SOUTH BUILDING PROCESS DETAILS
158 03-D901 SOUTH BUILDING FERRIC CHLORIDE ISOMETRIC
159 03-D902 SOUTH BUILDING SODIUM HYDROXIDE ISOMETRIC
160 03-D903 SOUTH BUILDING SODIUM HYDROXIDE ISOMETRIC
161 03-M101 SOUTH BUILDING LOWER LEVEL MECHANICAL PLAN
162 03-M102 SOUTH BUILDING UPPER LEVEL MECHANICAL PLAN
163 03-P101 SOUTH BUILDING LOWER LEVEL PLUMBING PLAN
164 03-P102 SOUTH BUILDING UPPER LEVEL PLUMBING PLAN
165 03-P103 SOUTH BUILDING PLUMBING RISER DIAGRAMS
166 03-E101 SOUTH BUILDING LOWER LEVEL POWER PLAN
167 03-E102 SOUTH BUILDING UPPER LEVEL POWER PLAN
168 03-E103 SOUTH BUILDING LOWER LEVEL LIGHTING PLAN
169 03-E104 SOUTH BUILDING UPPER LEVEL LIGHTING PLAN
170 03-E105 SOUTH BUILDING LIGHTNING PROTECTION / GROUNDING PLAN
SCHEDULE OF DRAWINGS
SHEET SUB-SHEET SHEET NAME
171 03-E301 SOUTH BUILDING LIGHTING SECTIONS
172 03-E601 SOUTH BUILDING 03-MCC-1 ONE-LINE
173 03-E602 SOUTH BUILDING 03-MCC-1 ELEVATION
174 03-E603 SOUTH BUILDING MOTOR CONTROL DIAGRAM 1
175 03-E604 SOUTH BUILDING MOTOR CONTROL DIAGRAM 2
176 03-E605 SOUTH BUILDING SCHEDULES
177 04-VOL4 COVER SHEET VOLUME 4
178 04-X101 WEST AERATION BASIN (1A/2A) PROCESS DEMOLITION PLANS
179 04-X102 WEST AERATION BASIN (1A/2A) ELECTRICAL DEMOLITION PLAN
180 04-S101 WEST AERATION BASIN (1A/2A) PLAN
181 04-D101 WEST AERATION BASIN (1A/2A) PROCESS PLAN
182 04-E101 WEST AERATION BASIN (1A/2A) POWER AND LIGHTING PLANS
183 05-S101 EAST AERATION BASIN (1B/2B) FOUNDATION PLAN
184 05-S102 EAST AERATION BASIN (1B/2B) UPPER LEVEL FLOOR PLAN
185 05-S301 EAST AERATION BASIN (1B/2B) SECTIONS
186 05-D101 EAST AERATION BASIN (1B/2B) PROCESS PLAN & SECTION
187 05-E101 EAST AERATION BASIN (1B/2B) POWER AND LIGHTING PLAN
188 06-X101 WEST CLARIFIER (#1) ELECTRICAL DEMOLITION PLAN
189 06-D101 WEST CLARIFIER (#1) DEMOLITION & PROCESS PLAN
190 06-E101 WEST CLARIFIER (#1) POWER AND LIGHTING PLAN
191 07-S101 EAST CLARIFIER (#2) FOUNDATION PLAN
192 07-S102 EAST CLARIFIER (#2) UPPER LEVEL FLOOR PLAN
193 07-S301 EAST CLARIFIER (#2) SECTIONS
194 07-D101 EAST CLARIFIER (#2) PROCESS PLAN & SECTIONS
195 07-E101 EAST CLARIFIER (#2) POWER AND LIGHTING PLAN
196 08-X101 WINTER BIOSOLIDS STORAGE DEMOLITION PLAN
197 08-X102 WINTER BIOSOLIDS STORAGE ELECTRICAL PLAN - DEMO
198 08-D101 WINTER BIOSOLIDS STORAGE PROCESS PLAN & SECTIONS
199 08-D501 WINTER BIOSOLIDS STORAGE BUILDING TANK DETAILS
200 08-M101 WINTER BIOSOLIDS STORAGE MECHANICAL PLANS
201 08-E101 WINTER BIOSOLIDS STORAGE POWER AND LIGHTING PLANS
202 08-E102 WINTER BIOSOLIDS LIGHTNING PROTECTION / GROUNDING PLAN
203 08-E601 WINTER BIOSOLIDS ONE-LINE & SCHEDULE
204 08-E602 WINTER BIOSOLIDS MOTOR CONTROL DIAGRAMS
205 09-G001 INSTRUMENTATION P&ID -INSTRUMENTATION LEGEND
206 09-G002 INSTRUMENTATION P&ID -INSTRUMENTATION LEGEND
207 09-Y501 INSTRUMENTATION INSTRUMENT INSTALLATION DETAILS
208 09-Y502 INSTREMENTATION INSTRUMENT INSTALLATION DETAILS
209 09-Y601 INSTRUMENTATION P&ID HEADWORKS
210 09-Y602 INSTRUMENTATION P&ID INFLUENT EQ BASIN & AERATED SLUDGE HOLDING TANK
211 09-Y603 INSTRUMENTATION P&ID - EQUALIZATION BASIN
212 09-Y604 INSTRUMENTATION P&ID - AERATION BASIN 1A / 2A
213 09-Y605 INSTRUMENTATION P&ID - AERATION BASIN 1B / 2B
214 09-Y606 INSTRUMENTATION P&ID - AERATION BLOWERS
215 09-Y607 INSTRUMENTATION P&ID - ARP PUMPS
216 09-Y608 INSTRUMENTATION P&ID - CLARIFIER 1
217 09-Y609 INSTRUMENTATION P&ID - CLARIFIER 2
218 09-Y610 INSTRUMENTATION P&ID - RWAS PUMPS
219 09-Y611 INSTRUMENTATION P&ID - SCUM PIT
220 09-Y612 INSTRUMENTATION P&ID - SAND FILTERS AND REAERATION COLUMN
221 09-Y613 INSTRUMENTATION P&ID - UV TREATMENT AND OUTFALL
222 09-Y614 INSTRUMENTATION P&ID - MICRO-C SYSTEM SHEET 1 OF 2
223 09-Y615 INSTRUMENTATION P&ID - MICRO-C SYSTEM SHEET 2 OF 2
224 09-Y616 INSTRUMENTATION P&ID - CENTRIFUGE FEED PUMPS
225 09-Y617 INSTRUMENTATION P&ID - DEWATERING CENTRIFUGES
226 09-Y618 INSTRUMENTATION P&ID - DEWATERING POLYMER SYSTEM
227 09-Y619 INSTRUMENTATION P&ID - TRUCK LOADOUT
228 09-Y620 INSTRUMENTATION P&ID - FERRIC CHLORIDE SYSTEM
229 09-Y621 INSTRUMENTATION P&ID - SODIUM HYDROXIDE SYSTEM
230 09-Y622 INSTRUMENTATION P&ID - NORTH BUILDING SUMP
231 09-Y623 INSTRUMENTATION P&ID - WINTER SOLIDS BUILDING
232 09-Y624 INSTRUMENTATION P&ID - NORTH BUILDING ALARM SIGNALING SYSTEM
233 09-Y625 INSTRUMENTATION P&ID - SOUTH BUILDING ALARM SIGNALING SYSTEM
234 09-Y626 INSTRUMENTATION P&ID - WINTER SOLIDS BUILDING ALARM SIGNALING SYSTEM
235 09-Y701 INSTRUMENTATION PROCESS CONTROL SYSTEM COMMUNICATIONS DIAGRAM
SCHEDULE OF DRAWINGS
SHEET SUB-SHEET SHEET NAME
32 01-X101 CIVIL SITE DEMOLITION PLAN
33 01-X102 ELECTRICAL SITE DEMOLITION PLAN
34 01-C101 TOPOGRAPHIC SURVEY
35 01-C102 SITE STAGING & ACCESS
36 01-C103 GENERAL SITE
37 01-C104 EROSION CONTROL PLAN
38 01-C105 STORM SEWER PLAN
39 01-C106 PROCESS PIPING PLAN
40 01-C107 PROCESS PIPING PLAN DETAIL VIEW
41 01-C108 PROCESS PIPING PLAN DETAIL VIEW
42 01-C109 UTILITY RELOCATIONS
43 01-C110 SITE GRADING
44 01-C111 LAYOUT POINTS
45 01-C112 POINT TABLES
46 01-C113 POINT TABLES
47 01-C114 FENCING PLAN
48 01-C501 CIVIL DETAILS
49 01-C502 CIVIL DETAILS
50 01-C503 CIVIL DETAILS
51 01-C504 CIVIL DETAILS
52 01-C505 CIVIL DETAILS
53 01-C506 CIVIL DETAILS
54 01-C507 CIVIL DETAILS
55 01-C508 CIVIL DETAILS
56 01-C801 EAST DRIVE PLAN & PROFILE
57 01-C802 CENTRAL DRIVE PLAN & PROFILE
58 01-C803 SANITARY SEWER PLAN & PROFILE
59 01-C804 6IN WATER MAIN PLAN & PROFILE
60 01-C805 4IN WATER MAIN PLAN AND PROFILE
61 01-C806 FORCE MAIN PLAN & PROFILE
62 01-C807 EAST DRIVE WALL PLAN & PROFILE
63 01-C808 AERATION BASIN WALL PLAN & PROFILE
64 01-C809 EQUILIZATION BASIN WALL PLAN & PROFILE
65 01-C810 PROPANE STORAGE AREA WALL PLAN & PROFILE
66 01-C811 SOUTH PARKING AREA WALL PLAN & PROFILE
67 01-E101 SITE PLAN
68 01-E601 DUCT BANK SCHEDULES AND SECTIONS
69 02-VOL2 COVER SHEET VOLUME 2
70 02-G001 NORTH BUILDING CODE ANALYSIS
71 02-X101 NORTH BUILDING ARCHITECTURAL DEMOLITION PLANS
72 02-X102 NORTH BUILDING LOWER LEVEL PROCESS DEMOLITION PLAN
73 02-X103 NORTH BUILDING MECHANICAL DEMOLITION PLANS
74 02-X104 NORTH BUILDING LOWER LEVEL PLUMBING DEMOLITION
75 02-X105 NORTH BUILDING UPPER LEVEL PLUMBING DEMOLITION PLAN
76 02-X106 NORTH BUILDING LOWER LEVEL ELECTRICAL DEMOLITION PLAN
77 02-X107 NORTH BUILDING UPPER LEVEL ELECTRICAL DEMOLITION PLAN
78 02-X301 NORTH BUILDING PROCESS DEMOLITION SECTIONS
79 02-X601 NORTH BUILDING ELECTRICAL MCC - 1 ONE-LINE - DEMO
80 02-X602 NORTH BUILDING MISC ONE-LINE - DEMO
81 02-S101 NORTH BUILDING FOUNDATION PLAN
82 02-S102 NORTH BUILDING UPPER LEVEL FLOOR PLAN
83 02-S103 NORTH BUILDING ROOF FRAMING PLAN AND TRUSS LOADING DIAGRAMS
84 02-S301 NORTH BUILDING SECTIONS
85 02-S501 NORTH BUILDING STRUCTURAL DETAILS
86 02-A101 NORTH BUILDING LOWER LEVEL FLOOR PLAN
87 02-A102 NORTH BUILDING UPPER LEVEL FLOOR PLAN
88 02-A103 NORTH BUILDING REFLECTED CEILING AND ROOF PLANS
89 02-A201 NORTH BUILDING EXTERIOR ELEVATIONS
90 02-A301 NORTH BUILDING SECTIONS AND DETAILS
91 02-A302 NORTH BUILDING WALL SECTIONS
92 02-A501 NORTH BUILDING DETAILS
93 02-A601 NORTH BUILDING DOOR AND WINDOW SCHEDULES
94 02-A602 NORTH BUILDING CASEWORK & INTERIOR ELEVATIONS & SECTIONS
95 02-A603 NORTH BUILDING ROOM FINISH SCHEDULE
96 02-D101 NORTH BUILDING LOWER LEVEL PROCESS PLAN
97 02-D102 NORTH BUILDING UPPER LEVEL PROCESS PLAN
98 02-D301 NORTH BUILDING PROCESS SECTIONS
99 02-D302 NORTH BUILDING PROCESS SECTIONS
100 02-D401 NORTH BUILDING ENLARGED PROCESS PLAN
V O
LU
M
E
V O
LU
M
E
V O
LU
M
E
V O
LU
M
E
V O
LU
M
E
V O
LU
M
V O
LU
M
SYMBOLS
∠ ANGLE
° DEGREE
⌀ DIAMETER
± PLUS / MINUS
A - L
A.F.F. ABOVE FINISH FLOOR
ALT ALTERNATE
ARCH ARCHITECTURAL OR ARCHITECT
ATC ACOUSTICAL TILE CEILING
B.O. BOTTOM OF
C.F.C.I. CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
C.F.O.I. CONTRACTOR FURNISHED, OWNER
INSTALLED
CJ CONTROL JOINT
CL CENTER LINE
CMU CONCRETE MASONRY UNITS
CONT CONTINUOUS
d PENNY (as in nail - 10d)
DBL DOUBLE
DEG DEGREE
DEPT DEPARTMENT
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
E EAST
(E) EXISTING
EA. EACH
EIFS EXTERIOR INSULATION & FINISH
SYSTEM
ELEV. ELEVATION
EQ. EQUAL
EXT. EXTERIOR
F.V. FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GWB GYPSUM WALLBOARD
GYP GYPSUM
HM HOLLOW METAL
INSUL. INSULATION
INT. INTERIOR
M - Z
MATL MATERIAL
MAX. MAXIMUM
MDF MEDIUM DENSITY FIBERBOARD
MECH MECHANICAL
MFG MANUFACTURING
MFR MANUFACTURER
N NORTH
NEC NATIONAL ELECTRICAL CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO. NUMBER
O.C. ON CENTER
O.F.C.I. OWNER FURNISHED, CONTRACTOR
INSTALLED
O.F.O.I. OWNER FURNISHED, OWNER
INSTALLED
OH OVERHEAD
OPP OPPOSITE
(PR) PAIR
P.T. PRESSURE TREATED
PVC POLYVINYL-CHLORIDE
R RADIUS
REQD REQUIRED
REV REVISION
S SOUTH
SCH SCHEDULE
SF SQUARE FOOTAGE
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
STD STANDARD
SUSP SUSPENDED
SYM SYMMETRICAL
TBD TO BE DETERMINED
T.O. TOP OF
TOS TOP OF STEEL
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
VERT VERTICAL
W WEST
W/ WITH
W/O WITHOUT
ARCHITECTURAL ABBREVIATIONS
EARTH
CONCRETE
CRUSHED ROCK
GRAVEL
CONCRETE MASONRY UNITS (PLAN)
AS INDICATED
AS INDICATED
BRICK
WOOD (ROUGH)
WOOD (FINISH)
PLYWOOD
METAL
GYPSUM WALLBOARD AS INDICATED
PLASTER AS INDICATED
RIGID INSULATION
BATT/BLANKET/LOOSE FILL INSULATION
GLASS (ELEVATION)
GLASS (LARGE SCALE SECTION)
WOOD STUD PARTITION
METAL STUD PARTITION
CONCRETE MASONRY UNITS
(SECTION)
MATERIAL LEGEND
1A
A201
ROOM NAME / NUMBER
DOOR NUMBER
WINDOW TYPE
WALL TYPE
(OPT. WALL HEIGHT)
REVISION NUMBER
SECTION NUMBER
SHEET NUMBER OF DRAWING
WHERE SECTION IS SHOWN
A4.01
DIRECTION OF SIGHT
OF ELEVATION ON PLAN
SHEET NUMBER OF DRAWING
WHERE ELEVATION IS SHOWN
DIRECTION OF SIGHT
OF ELEVATION ON PLAN
SHEET NUMBER OF DRAWING
WHERE ELEVATION IS SHOWN
X
XX KEY NOTE
SECTION IDENTIFICATION
ELEVATION IDENTIFICATION
REFERENCE SYMBOLS
A501
ROOM NAME
888.B
F01
A1
Height
TRUE NORTH ARROW
1. IN THE EVENT OF DISCREPANCIES WITHIN THE DRAWINGS OR SPECIFICATIONS, THE GREATER QUALITY AND QUANTITY OF THE ITEMS IN QUESTION SHALL BE UTILIZED AT ALL LOCATIONS WHERE SUCH
DISCREPANCIES OCCUR. CONFER WITH ARCHITECT AS NEEDED.
2. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND SHALL BE RESPONSIBLE FOR THE SAME.
COORDINATE ALL WORK AND SHOP DRAWINGS WITH OTHER TRADES.
3. ALL NEW CONSTRUCTION DIMENSIONS ARE TO EDGE OF STUD OR FACE OF CMU OR CONCRETE. ALL DIMENSIONS FROM EXISTING CONSTRUCTION WILL BE FROM FINISH FACE. DIMENSIONS TO COLUMNS
WILL BE TO CENTERLINE OR GRID.
4. ALL ANGLES ON PLANS ARE 45-OR 90 DEGREES, UNLESS NOTED OTHERWISE.
5. ALL DIMENSIONS LOCATING BUILDING AND SITE IMPROVEMENTS ARE TO FACE OF BUILDING OR EDGE
OF WALK, AND RUN PARALLEL OR PERPENDICULAR TO PROPERTY LINE.
6. ALL ELEVATIONS INDICATED ON THE DRAWINGS ARE BASED ON A LOWER LEVEL FINISH FLOOR DATUM
OF 100'-0". ACTUAL ELEVATION WILL BE SHOWN ON CIVIL PLANS.
7. WHERE ITEMS ARE LABELED "A.F.F." (ABOVE FINISHED FLOOR), CONTRACTOR SHALL SET THE ITEM AS
MEASURED FROM THE LOCAL FINISH FLOOR ELEVATION. COORDINATE ANY DISCREPANCIES
REGARDING THIS SITUATION TO ASSURE THAT ALL BUILDING COMPONENTS ARE PROPERLY SET TO FUNCTION AS INTENDED. CONTRACTOR SHALL ERECT ALL PARTITIONS IN A VERTICAL PLANE, NOT
NECESSARILY PERPENDICULAR TO THE FLOOR.
8. THE LOCATION OF ALL UNDERGROUND UTILITIES MAY NOT BE INDICATED ON THESE PLANS, AND SOME
LOCATIONS MAY BE INACCURATE. NO EXCAVATION WILL BE PERMITTED IN THE AREA OF
UNDERGROUND UTILITIES UNTIL SUCH UTILITIES HAVE BEEN LOCATED AND IDENTIFIED TO THE SATISFACTION OF ALL PARTIES, AND THEN ONLY WITH EXTREME CAUTION TO AVOID ANY POSSIBILITY OF DAMAGE TO THE UTILITY OR PERSONAL INJURY. HAND-DIGGING MAY BE REQUIRED WHEN THE EXCAVATION AND UTILITIES ARE EXTREMELY CLOSE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
ALL REPAIR AND REPLACEMENT COST OF ANY UNDERGROUND UTILITY DAMAGE.
9. THE CONTRACTOR SHALL COORDINATE ALL TESTING AND INSPECTIONS AS SPECIFIED, OR AS
NECESSARY TO DEMONSTRATE A COMPLETE AND SATISFACTORY INSTALLATION.
10. ALL WORK SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS, AND ORDINANCES. THE GENERAL
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION MEANS AND METHODS.
11. ALL MATERIALS AND EQUIPMENT OF THE SAME TYPE SHALL BE SUPPLIED BY THE SAME
MANUFACTURER, AND SHALL BE NEW, OF THE BEST QUALITY AND DESIGN, AND FREE FROM DEFECTS.
12. ALL ITEMS ARE NEW UNLESS SPECIFICALLY IDENTIFIED AS EXISTING.
13. "PROVIDE" MEANS TO FURNISH AND INSTALL.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL WORK. CONTRACTOR SHALL ANTICIPATE AREAS WHERE THE INSTALLATION OF MECHANICAL, ELECTRICAL, AND PROCESS WORK WILL BE RESTRICTED, CONGESTED, OR DIFFICULT TO INSTALL, AND SHALL COORDINATE INSTALLATION
BETWEEN THE TRADES.
15. CONTRACTOR SHALL COORDINATE LOCATIONS FOR ALL MECHANICAL, ELECTRICAL, AND PROCESS ITEMS WITH THE GENERAL CONSTRUCTION AND SHALL NOTIFY ARCHITECT OR ENGINEER OF ANY
DISCREPANCIES PRIOR TO INSTALLATION AND/OR FABRICATION.
16. THE CONTRACTOR SHALL COORDINATE ON-SITE STORAGE OF BUILDING MATERIALS, EQUIPMENT, AND
TRASH CONTAINERS WITH PARK.
17. IT IS THE INTENT OF THIS CONTRACT THAT ALL AREAS AFFECTED BY CONSTRUCTION BE A FINISHED
AND COMPLETE PROJECT. CONTRACTOR SHALL PATCH, REPAIR, AND ADJUST AS REQUIRED TO
ACHIEVE THIS FINISHED PROJECT.
18. INSTALL 16-GA. SHEET METAL PLATES WITHIN PARTITIONS AS REQUIRED FOR INSTALLATION OF WALL-
MOUNTED CABINETS, TOILET ACCESSORIES, WALL STOPS, AND MISCELLANEOUS ITEMS.
19. ALL CHANGES IN FLOOR MATERIALS OCCUR AT THE CENTERLINE OF THE DOORS IN THE CLOSED
POSITION, UNLESS SHOWN OTHERWISE.
20. WHERE STUDS EXTEND TO BOTTOM OF STRUCTURE ABOVE, PROVIDE SLIP TRACK TO ALLOW FOR 3/4"
MINIMUM DEFLECTION OF THE STRUCTURE OR AS SPECIFIED BY STRUCTURAL, WHICHEVER IS
GREATER.
21. SEE FIRE PROTECTION AND EGRESS PLANS FOR LOCATIONS OF RATED PARTITIONS AND FIRE
EXTINGUISHERS.
22. IN SOME INSTANCES, THERMAL AND SOUND INSULATION HAS BEEN OMITTED FROM DETAILS FOR CLARITY. SEE SPECIFICATIONS, WALL TYPES, AND WALL SECTIONS FOR LOCATIONS REQUIRING
INSULATION.
23. WALL AND PARTITION TYPES ARE INDICATED AT LARGE-SCALE PLAN DETAILS. IN SOME INSTANCES, NOT ALL FRAMING OR FURRING IS SHOWN FOR CLARITY. CONTRACTOR SHALL CONSTRUCT USING TYPICAL MEANS AND METHODS AND SHALL COMPLY WITH SPECIFICATION REQUIREMENTS. CONFER
WITH ARCHITECT AS NEEDED.
GENERAL NOTES
1. THESE LEGENDS ARE COMPOSED OF STANDARD
SYMBOLS AND ARE PERTINENT TO THE CONDITIONS
IN THIS SET OF DRAWINGS TO THE EXTENT
APPLICABLE.
2. ADDITIONAL LEGENDS AND/OR ANOTHER LEGEND
SHEET MAY APPEAR IN THIS SET OF DRAWINGS TO
INDICATE SPECIFIC CONDITIONS IN LIEU OF SYMBOLS
SHOWN ON THIS SHEET.
LEGEND NOTES:
OPTION ITEM: SPECIFIC OPTION
NUMBER LISTED BY KEYNOTE AND
DETAILED IN SPECIFICATIONS
OPTIONS LEGEND
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
C R e v it L o c a l\ -0
S e ri e s
G e n e ra l_ R ic W e b e r.
rv t
/1
/2
:4 :2
A
M
G002
MOUNT RUSHMORE NATIONAL MONUMENT
272051
SYMBOLS, ABBREVIATIONS,
GENERAL NOTES
RDW
CLZ / TWM / HHD
06/13/23
RDW
18678700-
FINAL CONSTRUCTION DOCUMENTS
36"INT.
15"-16"
36"INT.
18"
10"
15"-16"
/2
ADA / ABA TRANSFER STYLE SHOWER
36"
18"
1/
2" M
A X
BACK WALL CONTROL WALL PLAN VIEW
MEN
B A
S E
LI
N
E O
F T
O P
L
IN
E
"M
IN
M A
X . T
O
CLEAR FLOOR SPACE AT
TACTILE SIGNS AT DOORS
HEIGHT OF TACTILE CHARACTERS ABOVE FINISH FLOOR OR GROUND
PICTOGRAM FIELD
DARK-ON-LIGHT
MIN.
18"
M
IN
℄ OF SIGN
MEN
8"MAX
6" M
IN
NOT IN
PICTOGRAM
FIELD
GENERAL SIGNAGE
**** 48" MIN IF
CLOSER IS
PROVIDED
***54" MIN IF CLOSER
IS PROVIDED
* IF BOTH
CLOSER AND
LATCH PROVIDED
** 48" MIN IF
BOTH CLOSER &
LATCH PROVIDED
"M
IN
18"MIN
12"MIN*
"M
IN
MIN
36"60 "M
IN
MIN
42"54 "M
IN
MIN
22"
MIN
24"
"M
IN
MIN
24"
"M
IN
FRONT APPROACH
PULL SIDE
FRONT APPROACH
PUSH SIDE
HINGE APPROACH
PULL SIDE
HINGE APPROACH
PULL SIDE
HINGE APPROACH
PUSH SIDE
LATCH APPROACH
PULL SIDE
LATCH APPROACH
PUSH SIDE
"M
IN
DOOR CLEARANCES
12" MAX. 42" MIN.
54" MIN.
M
IN
36" MIN. 6"MAX.
S
E A
T
M
A X
M A
X
B O
T T
O M
E D
G E
O F
R E
F
LE
C T
IV
E
S U
R F
A C
E
17" - 25"
MIRROR
BUMPER PADDING REQ'D TO
MEET ADA & ANSI STANDARDS
(TYP. AT ALL EXPOSED PIPING)
TOILET PAPER
DISPENSER
GRAB
BAR
GRAB BAR
URINAL
16"-18"
M
IN
GRAB
BARS,
EACH SIDE
17" - 19"
AMBULATORY TOILET STALL
REQUIREMENT
DIFFERENCES
59" MIN. (FLOOR MOUNTED W.C.)
56" MIN. (WALL HUNG W.C.)
M A
X
60" MIN. 36"WIDTH
24" MIN.
12" MIN.
T O
O P
E R
A B
LE
P
A R
T
M A
X
SOAP
TOWEL
DISPENSER
HAND
DRYER
ROBE
HOOK
M
IN
9"
MIN.
11"
MIN.
8"
M
IN
15" MIN.5"
M A
X
39" - 41"
6"
1- 1/
2" M
IN
ACCESSIBLE WATER FOUNTAIN
(ADD 6" FOR WALL W/O MIN. 9"
TOE CLEARANCE)
60" MIN. DEPTH STALL
WALL MOUNTED ACCESSORIES
M
A X
13 1/2" MIN.TO WALL
15" MIN.24" MIN.
42" MAX.
(ADD 6" FOR WALL W/O MIN. 9"
TOE CLEARANCE)
CLEARANCE
LINES
M
IN
9"
MIN.
11"
MIN.
8"
"M
IN
BABY CHANGING
STATION
ADA/ABA AND ICC/ANSI A117.1 MOUNTING HEIGHT AND CLEARANCE REQUIREMENTS
TO WALL
15"MIN.
6' -2
"M
IN
MIN
1 1/2"STRUCTURAL STRENGTH:
(1)(2)(3) BENDING STRESS (SHEAR STRESS, SHEAR
FORCE) IN A GRAB BAR OR SEAT INDUCED BY THE
MAX. BENDING MOMENT FROM THE APPLICATION OF
250 LBF SHALL BE LESS THAN THE ALLOWABLE
STRESS FOR THE MATERIAL OF THE GRAB BAR OR
SEAT.
4) TENSILE FORCE INDUCED IN A FASTENER BY A
DIRECT TENSION FORCE OF 250 LBF PLUS THE MAX.
MOMENT FROM THE APPLICATION OF 250 LBF SHALL
BE LESS THAN THE ALLOWABLE WITHDRAWAL LOAD
BETWEEN THE FASTENER AND THE SUPPORTING
STRUCTURE.
HANDRAILS
1 1/4" - 1 1/2"
M
IN
1/
2"
CIRCULAR TURNING SPACE T-SHAPED OPTION 1
67" 68"
16" 36" 16"
ICC A117.1 - 2017 TURNING SPACE
8"
8"
T-SHAPED OPTION 2 T-SHAPED OPTION 3
64"
" 38
11" 42" 11"
64"
" 40
12" 40" 12"
• THE CLEAR FLOOR SPACE SHALL BE 52 INCHES MINIMUM IN
LENGTH AND 30 INCHES MINIMUM IN WIDTH.
• THE CLEAR FLOOR SPACE SHALL BE POSITIONED FOR EITHER
A FORWARD OR PARALLEL APPROACH TO AN ELEMENT.
• ONE FULL, UNOBSTRUCTED SIDE OF THE CLEAR FLOOR SPACE
SHALL ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE OR ADJOIN
ANOTHER CLEAR FLOOR SPACE.
• FLOOR SURFACES OF A CLEAR FLOOR SPACE SHALL HAVE A
SLOPE NOT STEEPER THAN 1:48.
• IF A CLEAR FLOOR SPACE IS LOCATED IN AN ALCOVE OR
OTHERWISE CONFINED ON ALL OR PART OF THREE SIDES,
ADDITIONAL MANEUVERING CLEARANCES ARE REQUIRED.
30"
ICC A117.1 - 2017 CLEAR FLOOR SPACE
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
C R e v it L o c a l\ -0
S e ri e s
G e n e ra l_ R ic W e b e r.
rv t
/1
/2
:4 :2
A
M
G003
MOUNT RUSHMORE NATIONAL MONUMENT
272051
ACCESSIBILITY
REQUIREMENTS
RDW
CLZ / TWM / HHD
06/13/23
RDW
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OFA
u to d e s k D o c s /1
M
O R
U W a s te w a te r R e h a b a n d E x p a n s io n
/1
-0
-G
.r v t
-J u n -2
S001
MOUNT RUSHMORE NATIONAL MEMORIAL
272051
STRUCTURAL GENERAL
NOTES
GS
SKM
06/13/23
TJH
18678700-
FINAL CONSTRUCTION DOCUMENTS
STRUCTURAL NOTES
APPLICABLE CODES AND STANDARDS:
1. INTERNATIONAL BUILDING CODE 2021.
2. MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES ASCE7-16.
3. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE ACI-318-19.
4. CODE REQUIREMENTS FOR ENVIRONMENTAL ENGINEERING CONCRETE
STRUCTURES AND COMMENTARY ACI-350-20.
5. AMERICAN INSTITUTE OF STEEL CONSTRUCTION AISC STEEL CONSTRUCTION
MANUAL, 15TH ED.
6. AISI SPECIFICATION FOR DESIGN OF COLD FORMED STEEL STRUCTURAL MEMBERS.
7. AMERICAN WELDING SOCIETY (AWS) D1.1, D1.3, D1.4.
8. ASTM MATERIAL STANDARDS AS NOTED.
9. BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY STRUCTURES
TMS 402-16 AND 602-16.
10. NATIONAL DESIGN SPECIFICATION (NDS) FOR WOOD CONSTRUCTION 2018 EDITION.
EXISTING CONDITIONS:
1. NOTIFY CONTRACTING OFFICER IMMEDIATELY IF EXISTING CONDITIONS DO NOT
MATCH, OR SEEM IN CONFLICT, WITH INFORMATION SHOWN ON THE DRAWINGS.
GENERAL NOTES:
1. THE DRAWINGS REPRESENT THE FINISHED STRUCTURE, NOT THE METHOD OF
CONSTRUCTION. SAFETY AND STRUCTURAL STABILITY DURING CONSTRUCTION ARE
THE SOLE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL
PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING
CONSTRUCTION, INCLUDING BUT NOT LIMITED TO, BRACING, SHORING, FOR
CONSTRUCTION LOADS AND EQUIPMENT, ETC.
2. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE
ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR
LOCATION AND SIZE OF OPENINGS, BLOCK OUTS, FLOOR DEPRESSIONS, CURBS,
DIMENSIONS, ETC. NOT INDICATED ON THE STRUCTURAL DRAWINGS. THE LOCATION
AND SIZE OF MECHANICAL AND ELECTRICAL OPENINGS IN SLABS, WALLS AND DECKS
SHALL BE COORDINATED BY THE CONTRACTOR. PROVIDE ALL ADDITIONAL FRAMING
OR REINFORCING TO ACCOMMODATE OPENINGS AS REQUIRED BY THE APPLICABLE
STANDARD DETAILS, SECTIONS, AND NOTES AS SHOWN ON THE STRUCTURAL
DRAWINGS.
3. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS OF
EXISTING CONSTRUCTION AS REQUIRED TO COORDINATE NEW CONSTRUCTION.
SUBMIT REQUIRED CHANGES FOR APPROVAL.
4. CONTRACTOR IS TO ESTABLISH AND VERIFY EMBEDS AND INSERTS FOR ITEMS TO
BE INSTALLED BY OTHER TRADES PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND
CONSTRUCTION.
5. CONSTRUCTION MATERIAL AND EQUIPMENT PLACED ON FRAMED CONSTRUCTION
SHALL BE SUCH THAT THE LOAD DOES NOT EXCEED THE DESIGN LIVE LOAD OF THE
CONSTRUCTIONS. PROVIDE SHORING OF CONSTRUCTIONS WHERE NECESSARY FOR
THE LOADS.
6. DETAILS AND SECTIONS THAT ARE NOTED AS “TYP” ON DETAIL TITLES ARE TO BE
APPLIED TO THE PROJECT CONSTRUCTION AS GENERAL CONSTRUCTION METHODS
UNLESS NOTED OTHERWISE. THESE DETAILS ARE NOT CUT AT ALL LOCATIONS THEY
OCCUR AND MAY BE NOT CUT AT ALL.
7. CONTRACTOR TO SUBMIT FOR REVIEW ALL EQUIPMENT SIZES, OPERATING
WEIGHTS, VIBRATIONAL FORCES, SUPPORTED LOCATIONS, ALONG WITH ANY FLOOR
OPENINGS, NOTCHES, AND RECESSED REQUIRED BY SUCH EQUIPMENT. CONCRETE
SUPPORT PADS AND / OR FRAMING REQUIRED TO SUPPORT SAID EQUIPMENT SHALL
NOT BE FABRICATED AND PLACED UNTIL THE CONCRETE SUPPORT PADS AND / OR
FRAMING IS APPROVED TO SUPPORT THE EQUIPMENT.
BUILDING OCCUPANCY CATEGORY – RISK FACTOR:
1. RISK FACTOR: III
SNOW LOAD:
1. SOUTH BUILDING AND NORTH BUILDING
A. SNOW LOADS IN ACCORDANCE WITH THE BUILDING CODE LISTED ABOVE.
a. EXPOSURE FACTOR, CE: 1.2
b. SNOW LOAD IMPORTANCE FACTOR, IS: 1.1
c. THERMAL FACTOR, CT: 1.0
d. GROUND SNOW LOAD, PG: 50 PSF
e. RAIN-ON-SNOW: 0 PSF
f. FLAT ROOF SNOW LOAD, PF: 47 PSF
g. ADDITIONAL DRIFT LOAD: SEE PLANS FOR MAGNITUDES AND LOCATIONS.
2. AERATION BASIN AND CLARIFIER
A. SNOW LOADS IN ACCORDANCE WITH THE BUILDING CODE LISTED ABOVE.
a. EXPOSURE FACTOR, CE: 1.2
b. SNOW LOAD IMPORTANCE FACTOR, IS: 1.1
c. THERMAL FACTOR, CT: 1.2
d. GROUND SNOW LOAD, PG: 50 PSF
e. RAIN-ON-SNOW: 0 PSF
f. FLAT ROOF SNOW LOAD, PF: 52 PSF
g. ADDITIONAL DRIFT LOAD: SEE PLANS FOR MAGNITUDES AND LOCATIONS.
LIVE LOAD:
1. ELEVATED WALKWAYS: 60 PSF
2. MECHANICAL: 125 PSF
3. ELECTRICAL: 125 PSF
4. MAINTENANCE GARAGE: 250 PSF
5. STORAGE: 125 PSF
6. ROOF: 20 PSF (NON REDUCIBLE)
WIND LOAD:
1. WIND LOADS IN ACCORDANCE WITH THE BUILDING CODE LISTED ABOVE.
2. BASIC WIND SPEED- (3 SECOND GUST)- ULTIMATE: 120 MPH
3. EXPOSURE CATEGORY: C
4. IMPORTANCE FACTOR, IW: 1.00
SEISMIC LOAD:
1. SEISMIC LOADS IN ACCORDANCE WITH THE BUILDING CODE LISTED ABOVE
2. RISK CATEGORY: III
3. IMPORTANCE FACTOR, IE: 1.25
4. SEISMIC DESIGN CATEGORY: A
5. SITE CLASS: C
6. SPECTRAL RESPONSE ACCELERATIONS, SS: 0.163G
7. SPECTRAL RESPONSE ACCELERATIONS, S1: 0.045G
8. SPECTRAL RESPONSE COEFFICIENTS, SDS: 0.174
9. SPECTRAL RESPONSE COEFFICIENTS, SD1: 0.072
10. SEISMIC RESPONSE COEFFICIENT, CS: 0.054
11. RESPONSE MODIFICATION FACTOR, R:
A. SOUTH BUILDING AND NORTH BUILDING 4
B. AERATION BASIN AND CLARIFIER 4
12. ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
SOILS INVESTIGATION:
1. SOILS INVESTIGATION WAS MADE BY: AMERICAN ENGINEERING TESTING
2. PROJECT NO. P-0014492 DATED: AUGUST 17, 2022
3. BEARING PRESSURE: 2000 PSF ( DL + LL)
4. EQUIVALENT ACTIVE FLUID PRESSURE: 55 PCF
5. EQUIVALENT AT REST FLUID PRESSURE: 75 PCF
6. EQUIVALENT AT PASSIVE FLUID PRESSURE: 275 PCF
7. COEFFICIENT OF FRICTION: 0.45
CONCRETE NOTES:
1. CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 117, ACI 301, ACI 318, AND ACI 350.
2. PROVIDE A 2X4 FORMED CONSTRUCTION JOINT KEYWAY AT ALL HORIZONTAL AND VERTICAL
POURED EDGES.
3. REINFORCING STEEL SHALL BE ASTM A615, GRADE 60.
4. CONCRETE COVER REQUIREMENTS FOR REINFORCEMENT UNLESS NOTED OTHERWISE ON
THE DETAILS OR SECTIONS:
CONCRETE CAST AND PERMANENTLY EXPOSED TO EARTH: 3”
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 BARS AND LARGER 2”
#5 BARS AND SMALLER 1-1/2”
CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
SLABS 1”
WALLS 2”
COLUMNS 1-1/2"
5. REINFORCING BAR SPLICES SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF ACI
318 AND THE REINFORCING SPLICE LENGTHS SCHEDULE ON THE DRAWINGS.
6. CAST-IN-PLACE CONCRETE EXPOSURE CATEGORY C1 F2 S2:
LOCATION 28-DAY F’C AIR MAX W/C MAX SLUMP
WATER BEARING CONCRETE 4500 6% +/-1% 0.42 4”
FOOTING AND FOUNDATION WALLS 4000 6% +/-1% 0.5 4”
SLABS AND TOPPINGS W/ FLOOR COVERING 4000 -- 0.4 4”
EXTERIOR CONCRETE 4500 6% +/-1% 0.45 4”
7. ALL REINFORCEMENT FOR CAST-IN-PLACE CONCRETE SHALL BE ACCURATELY PLACED,
SUPPORTED, TIED, AND SECURED INTO PLACE PRIOR TO PLACING CONCRETE. ALL REBAR
DOWELS SHALL BE TIED IN PLACE PRIOR TO CONCRETE PLACEMENT. REBAR DOWELS
SHALL NOT BE EMBEDDED AFTER CONCRETE PLACEMENT UNLESS INDICATED ON THE
DRAWINGS.
8. REFER TO OTHER DISCIPLINE DRAWINGS PRIOR TO CONSTRUCTION FOR EMBEDDED ITEMS
AND PENETRATIONS NOT SHOWN ON THE STRUCTURAL DRAWINGS AS REQUIRED TO
ACCOMMODATE ALL WORK SHOWN OR SPECIFIED IN THE CONTRACT DOCUMENTS AND
OTHERWISE REQUIRED FOR THE FURNISHING OF A FUNCTIONALLY COMPLETE PROJECT.
REINFORCE AROUND OPENINGS PER STANDARD STRUCTURAL DETAILS UNLESS
OTHERWISE SHOWN.
9. PROVIDE ¾” CHAMFERS AT ALL EXPOSED EDGES. NOT ALL CHAMFERS MAY BE SHOWN.
10. ANCHOR BOLTS NOT SPECIFIED BY THE CONTRACT DRAWINGS SHALL BE DESIGNED AND
CERTIFIED BY A REGISTERED PROFESSIONAL ENGINEER, RETAINED BY THE CONTRACTOR
IN ACCORDANCE WITH THE APPLICABLE PROJECT AND CODE REQUIREMENTS. SUBMIT AS A
SHOP DRAWING FOR REVIEW AND APPROVAL BY THE CONTRACTING OFFICER. COORDINATE
LOCATION, SIZE, AND EMBEDMENT PRIOR TO CASTING CONCRETE.
11. ALL CAST-IN-PLACE AND POST-INSTALLED ANCHORS INDICATED IN THE STRUCTURAL
DOCUMENTS SHALL COMPLY WITH CHAPTER 17 OF ACI 318 AND CHAPTER 19 OF THE IBC.
ALL EXPANSION AND ADHESIVE ANCHORS SHALL HAVE AN ICC REPORT SHOWING
EQUIVALENT LOAD CAPACITY. SUBMIT AND INSTALL PER THE ICC EVALUATION REPORT.
12. PRIOR TO INSTALLING POST INSTALLED ANCHORS INTO CONCRETE, THE CONTRACTOR
SHALL LOCATE REINFORCING. DO NOT DAMAGE CONCRETE REINFORCING.
13. ABSOLUTELY NO WELDING OF REINFORCING BARS OR TORCHING TO BEND REINFORCING
BARS SHALL BE ALLOWED WITHOUT SPECIFIC APPROVAL FROM THE CONTRACTING
OFFICER.
MASONRY:
1. MASONRY WORK SHALL BE IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS OF
TMS 402-16 AND SPECIFICATIONS 602-16.
2. THE COMPRESSIVE STRENGTH OF THE MASONRY UNITS SHALL BE 1900 PSI ON THE NET
AREA, PROVIDING A MINIMUM 28-DAY DESIGN COMPRESSIVE STRENGTH (F’M) OF 1500 PSI BY
THE UNIT STRENGTH METHOD.
3. THE MINIMUM 28-DAY COMPRESSIVE STRENGTH (F’C) OF MASONRY GROUT SHALL BE 2000
PSI.
4. SEE TYPICAL BOND BEAM INTERSECTION DETAIL FOR MASONRY BOND BEAM DETAILS AND
NOTES. LINTEL BLOCKS SHALL NOT BE USED AS BOND BEAM BLOCKS EXCEPT AT OPENINGS
WHERE BOND BEAMS AND LINTELS COINCIDE.
5. IF BOND BEAMS AT INTERSECTING WALLS ARE SHOWN ON THE DRAWINGS TO MEET AT
DIFFERENT ELEVATIONS, EXTEND BOND BEAM REINFORCING OF BOTH BOND BEAMS
AROUND INTERSECTING CORNER NOT LESS THAN 4 FEET IN EACH DIRECTION.
6. PROVIDE STANDARD 90-DEGREE HOOKS IN THE TOP BOND BEAM AT ALL VERTICAL WALL
REINFORCING.
7. SPLICE LENGTHS FOR MASONRY REINFORCEMENT SHALL BE 72 BAR DIAMETERS UNLESS
SHOWN OTHERWISE.
7.1 WHEN REQUIRED SPLICE LENGTH EXCEEDS 4'-0", USE HIGH LIFT GROUTING WITH NO
SPLICES OR USE MECHANICAL TENSION SPLICES WITH LOW LIFT GROUTING.
8. IN CASES WHERE REINFORCING BARS CANNOT BE EXTENDED AS FAR AS REQUIRED, THE
BARS SHALL EXTEND AS FAR AS POSSIBLE AND END WITH STANDARD HOOK.
9. MASONRY CONTRACTOR SHALL COORDINATE WITH MECHANICAL, ELECTRICAL, AND OTHER
CONTRACTORS AND BUILD IN OPENINGS FOR THE UTILITIES AND DUCTWORK THAT EXCEED
16 INCHES IN WIDTH. PROVIDE ADDITIONAL REINFORCEMENT AT OPENINGS AS INDICATED.
DO NOT CUT REINFORCEMENT. OPENINGS SHALL BE COORDINATED BEFORE
CONSTRUCTING WALLS.
10. AT NON-LOAD BEARING WALLS, PROVIDE 8” DEEP BOND BEAM FOR OPENINGS 4’-8” AND LESS
AND 16” DEEP BOND BEAM FOR OPENINGS GREATER THAN 4’-8” AND LESS THAN 6’-0”.
CONTACT CONTRACTING OFFICER FOR LARGER OPENINGS.
11. ALL STEEL LINTELS 16 INCHES AND DEEPER, WITH 3 5/8” SOLID MASONRY UNITS ON SIDES, PROVIDE ADJUSTABLE MASONRY ANCHORS AT 8 INCHES ON CENTER VERTICALLY AND 24
INCHES ON CENTER HORIZONTALLY.
STRUCTURAL STEEL:
1. STRUCTURAL STEEL DESIGN PROPERTIES:
WIDE FLANGE AND TEE SHAPES – ASTM A992 FY = 50 KSI
ANGLES, CHANNELS AND PLATES – ASTM A 36 FY = 36 KSI
COLD-FORMED HOLLOW STRUCTURAL SECTIONS, ASTM A 500, GRADE B FY = 46 KSI
COLD-FORMED HOLLOW STRUCTURAL PIPE, ASTM A500, GRADE B FY = 42 KSI
STAINLESS STEEL FY = 33 KSI
BOLTS – ASTM A325N
ANCHOR RODS – ASTM F1554 FY = 36 KSI
LIGHT GAGE STEEL STUDS/JOIST 12 TO 16 GAGE FY = 50 KSI
18 + GAGE FY = 33 KSI
2. ALL WELDS AND WELDING PROCEDURES SHALL BE PERFORMED IN ACCORDANCE WITH
APPLICABLE PROVISIONS OF AISC AND AWS WELDING PROCEDURES AND CODES OUTLINED
IN THE SPECIFICATION. ALL WELDS SHALL BE MADE WITH E-70XX ELECTRODES AND IN
ACCORDANCE WITH AWS FOR METAL ALLOY BEING WELDED UNLESS NOTED OTHERWISE.
3. WHEN FILLET WELDS SIZES ARE NOT INDICATED, PROVIDE MINIMUM WELD SIZE IN
ACCORDANCE WITH AISC SPECIFICATIONS, TABLE J2.4. OR 3/16”, WHICHEVER IS GREATER.
4. ALL GROOVE WELDS INDICATED ON THE PLANS AND SECTIONS SHALL BE COMPLETE JOINT
PENETRATION WELDS (CJP) UNLESS SPECIFICALLY INDICATED TO BE PARTIAL PENETRATION
WELDS.
5. DIMENSIONS TO CENTERLINE OF COLUMNS AND BEAMS, TOP SURFACES OF BEAMS AND
TUBES AND BACKS OF CHANNELS AND ANGLES UNLESS NOTED OTHERWISE.
6. ALL FIELD BOLTED CONNECTIONS SHALL BE MADE WITH 3/4" DIAMETER A325N BOLTS,
UNLESS NOTED OTHERWISE. ALL FIELD BOLTED CONNECTIONS SHALL BE SNUG TIGHTENED
UNLESS INDICATED AS PRETENSIONED OR SLIP CRITICAL. PRETENSIONED CONNECTIONS
SHALL BE TIGHTENED USING DIRECT TENSION INDICATORS. INSTALL HIGH STRENGTH
BOLTS ACCORDING TO RCSC’S “SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A
325 OR A 490 BOLTS” FOR THE TYPE OF JOINT SPECIFIED.
POST INSTALLED ANCHORS
1. POST INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONTRACT
DRAWINGS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE CONTRACTING
OFFICER BEFORE INSTALLING POST INSTALLED ANCHORS FOR MISSING OR MISPLACED
CAST-IN-PLACE ANCHORS.
2. CARE SHALL BE TAKEN IN PLACING POST– INSTALLED ANCHORS TO AVOID CONFLICTS WITH
THE EXISTING REBAR. HOLES SHALL BE DRILLED AND CLEANED IN ACCORDANCE WITH THE
MANUFACTURER’S WRITTEN INSTRUCTIONS.
3. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE SPECIFIED BELOW, SHALL
BE SUBMITTED BY THE CONTRACTOR TO THE CONTRACTING OFFICER ALONG WITH
CALCULATIONS THAT ARE PREPARED AND SEALED BY A REGISTERED PROFESSIONAL
ENGINEER. THE CALCULATIONS SHALL DEMONSTRATE THAT THE SUBSTITUTED PRODUCT IS
CAPABLE OF ACHIEVING THE PERTINENT EQUIVALENT DESIGN PERFORMANCE VALUES
(MINIMUM) OF THE SPECIFIED PRODUCT USING THE APPROPRIATE DESIGN PROCEDURE
AND/ OR STANDARDS(S). AS REQUIRED BY THE BUILDING CODE. PRODUCT ICC-ES REPORTS
SHALL BE INCLUDED WITH THE SUBMITTAL PACKAGE.
4. UNLESS NOTED OTHERWISE ON PLANS, ACCEPTABLE CONCRETE ANCHORS PRODUCTS
SHALL BE:
A. MECHANICAL ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL
HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND
ICC-ES AC193. PRE-APPROVED MECHANICAL ANCHORS INCLUDE:
1. KWIK BOLT 3 (ICC-ES ESR-2302) AND KWIK BOLT TZ (ICC-ES ESR 1917) BY HILTI,
INC.
2. TRUBOLT+ (ICC-ES ESR-2427) BY ITW RAMSET/REDHEAD.
3. STRONG BOLT (ICC-ES ESR-1771) AND STRONG BOLT 2 (ICC-ES ESR-3037) BY
SIMPSON STRONG TIE ANCHOR SYSTEMS.
B. ADHESIVE ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE
BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 308. PRE-
APPROVED ADHESIVE ANCHORS INCLUDE:
1. HIT-RE-500 SD (ICC-ES ESR 2322) SYSTEM ADHESIVE ANCHORS BY HILTI, INC.
2. EPCON G5 (ICC-ES ESR-1137) ADHESIVE ANCHORING SYSTEM BY ITW
RAMSET/REDHEAD.
3. SET-XP (ICC-ES ESR-2508) ADHESIVE ANCHORING SYSTEMS BY SIMPSON STRONG
TIE ANCHOR SYSTEMS.
C. CONCRETE SCREW ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE
SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2
AND ICC-ES AC193. PRE-APPROVED SCREW ANCHORS INCLUDE:
1. KWIK HUS-EZ (ICC-ES ESR-3027) BY HILTI, INC.
2. TITAN HD (ICC-ES ESR-2713) BY SIMPSON STRONG TIE ANCHOR SYSTEMS.
WOOD ROOF TRUSSES:
1. THE CONTRACTOR SHALL SUBMIT A COMPLETE SET OF CALCULATIONS AND SHOP
DRAWINGS OF THE ROOF SYSTEM TO THE CONTRACTING OFFICER AND ENGINEER FOR
REVIEW PRIOR TO FABRICATIONS. THE CALCULATIONS SHALL INCLUDE THE FOLLOWING:
TRUSS LAYOUT DRAWING, INDIVIDUAL TRUSS DESIGNS, TEMPORARY BRACING AND
PERMANENT BRACING. SHOP DRAWINGS SHALL INDICATE THE TRUSS LAYOUT, TEMPORARY,
AND PERMANENT BRACING LOCATIONS. THE CALCULATIONS SHALL INCLUDE THE BRACING
MEMBER SIZE, LOCATIONS AND THE POSITIONING OF THE CONNECTOR PLATES. ALL
CALCULATIONS AND SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY THE
CONTRACTORS LICENSED ENGINEER.
2. WOOD TRUSSES SHALL BE DESIGNED BY THE MANUFACTURER TO RESIST THE LOADS PER
THE CODE AND AS SHOWN ON THE TRUSS LOADING DIAGRAMS WHERE SHOWN ON THE
DRAWINGS.
WOOD ROOF TRUSSES (CONT):
3. TRUSSES SHALL BE DESIGNED UNDER THE FOLLOWING FORMAT:
A. LATERAL FORCES APPLIED TO THE TRUSSES SUCH AS DRAG TRUSS LOADS,
COLLECTORS, ETC ARE INDICATED ON THE PLANS WHERE APPLICABLE.
B. ALL TRUSS-TO-TRUSS CONNECTIONS ARE THE RESPONSIBILITY OF THE
CONTRACTOR’S ENGINEER.
C. IT IS THE RESPONSIBILITY OF THE CONTRACTORS ENGINEER TO REVIEW ALL THE
DESIGN SPECIFICATIONS, ROOF TRUSS SUPPORT CONDITIONS, DRAG DETAILS AND TO
INCORPORATE THESE REQUIREMENTS INTO THE ENGINEERING DESIGN OF THE TRUSS
SYSTEM.
D. THE CONTRACTORS ENGINEER SHALL DEVELOP A TRUSS LAYOUT PLAN FOR THE
TRUSS SYSTEM THAT CLEARLY INDICATES THE TRUSS VERTICAL SUPPORT
CONDITIONS, TRUSS- TO-TRUSS CONNECTIONS, DRAG TRUSSES AND COLLECTORS,
AND ANY OTHER FIELD INSTALLED REINFORCEMENT. INCLUDING FIELD-INSTALLED TOP
CHORD REINFORCEMENT AT THE EAVES AS NECESSARY TO EXECUTE THE TRUSS
SYSTEM DESIGN. THE TRUSS ROOF FRAMING PLAN SHALL BE SEALED BY THE
CONTRACTORS ENGINEER AND SHALL BE INCLUDED WITH THE INDIVIDUAL TRUSS CUT
SHEETS. THE CONTRACTORS ENGINEER SHALL ALSO PROVIDE PROPER SUPERVISION
OF ANY TRUSS COMPANY TECHNICIANS.
E. DRAG LOADS (HORIZONTAL TRUSS TRANSFERS) CONNECTIONS BETWEEN THE TRUSS
AND THE STRUCTURE ARE INDICATED ON THE PLANS WHERE APPLICABLE.
F. ALL TRUSS-TO-STRUCTURE (WALLS OR BEAMS) CONNECTIONS ARE THE
RESPONSIBILITY OF THE ENGINEER OF RECORD.
G. TEMPORARY ERECTION BRACING AND PERMANENT WEB BRACING SHALL BE
DESIGNED BY THE CONTRACTOR’S ENGINEER.
4. THE CONTRACTORS ENGINEER SHALL DESIGN ALL APPLIED DEAD, LIVE, WIND, AND SEISMIC
LOADS PLUS THE LATERAL SUPPORT LOADS SHOWN BELOW. ADDITIONALLY, THE
CONTRACTORS ENGINEER WILL BE RESPONSIBLE FOR DESIGNING THE TEMPORARY AND
PERMANENT BRACING.
A. MINIMUM TRUSS GRAVITY FRAMING LOADS FOR THE TRUSS DESIGN SHALL BE PER
THE TRUSS LOADING DIAGRAMS. SELF-WEIGHT OF THE TRUSS OVER 3 PSF SHALL BE
ADDED TO THE DEAD LOAD.
5. COORDINATE ADDITIONAL LOADS WITH MECHANICAL AND ELECTRICAL.
A. PROVIDE DOUBLE TRUSSES UNDER ROOF TOP MECHANICAL UNITS, UNLESS NOTED
OTHERWISE.
WOOD FRAMING:
1. SEE SPECIFICATION FOR GRADE OF LUMBER TO BE USED FOR ALL WALL FRAMING,
BLOCKING, MISC FRAMING.
2. FOR CONNECTIONS NOT DETAILED, REFERENCE IBC TABLE 23.04.9.1 FOR TYPICAL WOOD
ADJACENT TO CONCRETE.
WOOD STRUCTURAL SHEATHING:
1. WALL SHEATHING SHALL BE 1 1/2" COMBINATION WALL SHEATHING, INSULATION, AIR AND
WATER-RESISTIVE BARRIER, STRUCTURAL 1, 7/16 PERFORMANCE CATEGORY WITH A
MINIMUM SPAN RATING OF 24/16, AND SHALL BE ATTACHED WITH 0.131" SHANK NAILS AS
FOLLOWS UNLESS SHOWN OTHERWISE:
4” OC @ ALL SUPPORTED PANEL EDGES
12” OC @ INTERMEDIATE SUPPORTS
PROVIDE FULL DEPTH BLOCKING AT ALL UNBLOCKED EDGES OF SHEATHING. PROVIDE
MINIMUM ONE HORIZONTAL ROW OF BLOCKING AT MID HEIGHT OF WALL STUDS.
2. ROOF SHEATHING SHALL BE APA STRUCTURAL I RATED PLYWOOD, EXTERIOR EXPOSURE
RATING, WITH A MINIMUM SPAN RATING OF 32/16, A MINIMUM THICKNESS OF 1/2” AND SHALL
BE ATTACHED WITH COMMON NAILS PER PLYWOOD CONNECTIONS SCHEDULE. PROVIDE
FULL DEPTH BLOCKING AT ALL UNBLOCKED EDGES OF SHEATHING.
SPECIAL STRUCTURAL INSPECTIONS:
1. SPECIAL INSPECTIONS AND TESTS SHALL BE BY AN INDEPENDENT TESTING AND
INSPECTION AGENCY EMPLOYED BY THE CONTRACTOR AND APPROVED BY THE
CONTRACTING OFFICER. TEST AND INSPECTION REPORTS SHALL BE SUBMITTED FOR
REVIEW TO THE CONTRACTING OFFICER.
2. SPECIAL INSPECTIONS AND TESTS SHALL BE PERFORMED DURING CONSTRUCTION IN
ACCORDANCE WITH CHAPTER 17 AND CHAPTER 1, SECTION 110 OF THE 2021
INTERNATIONAL BUILDING CODE, SCHEDULE OF SPECIAL INSPECTIONS, AND THE CONTRACT
SPECIFICATIONS. THE CONTRACTOR SHALL NOTIFY AND ACCOMMODATE THE APPLICABLE
INSPECTOR DURING APPROPRIATE PHASES OF THE WORK AS REQUIRED BY EACH TEST
AND INSPECTION.
3. SPECIAL INSPECTION, SEE SPECIFICATION SECTION 01 45 35, SPECIAL INSPECTIONS AND
THE SCHEDULE OF SPECIAL INSPECTIONS.
DEFERRED SUBMITTALS
SPECIFICATION
SECTION
ITEM
05 50 00 PRE-FABRICATED METAL STAIRS
06 10 00 PRE-FABRICATED WOOD TRUSSES
06/13/23
180 DEG STD HOOK90 DEG STD HOOK
CONCRETE JOINT
TL
3"
5"
4 1/2"
HW
4"
5"
3"
7"
8"
1'-1"
11 3/4"
8"
7"
1'-2 3/4"
1'-1 1/4" 11 1/2"
10 1/2"
6"6"
HL
8"
6"
10"
Ldh
BAR SIZE
#3
#5
#4 7"
9"
6"
1'-2"
1'-7"
1'-4"
1'-10"
2'-0"
#7
#9
#8
#10
#11
15"
17"
19"
14"
12"
#6 10"1'-0"
GRADE 60
f'c=4.0 OR 4.5 KSI
D
2 1/4"
3 3/4"
3"
5 1/4"
6"
12"
10 3/4"
9 1/2"
4 1/2"
COMPLYING WITH MINIMUM COVER REQUIREMENTS OF
ACI 318, 12.5.3. OTHERWISE Ldh MUST BE RE-CALCULATED.
LE
NG
TH
Ld h
DE
VE
LO
PM
EN
T
D T
Y P
* MIN COVER
HL=
HOOK LENGTH
M
IN
CO
VE
R
HW=
HOOK LENGTH
TL
TA
IL
L
EN
G
TH
NOTES:
1. PROVIDE MINIMUM LAP SPLICE LENGTHS
AND EMBEDMENTS PER TABLE UNLESS
NOTED OTHERWISE. EMBEDMENT LENGTH
EQUALS THE LAP SPLICE LENGTH UNLESS
OTHERWISE NOTED.
2. BAR SPACING AT LAP SPLICE IS THE
MINIMUM CLEAR DISTANCE BETWEEN
LAPPED BARS PLUS ONE BAR DIAMETER.
3. ALL SPLICES TO BE CONTACT SPLICES
AND WIRED TOGETHER UNLESS OTHERWISE
APPROVED BY THE ENGINEER.
LAP SPLICE AND EMDEDMENT LENGTHS
f'c =4.0 ksi fy = 60 ksi f'c =4.5 ksi
BAR
BARS SPACED
GREATER
THAN 4"
BARS SPACED
LESS THAN OR
EQUAL TO 4"
#3 14" 20"
#4 19" 32"
#5 29" 46"
#6 39" 62"
#7 55" 87"
#8 69" 107"
#9 76" 116"
#10 97" 140"
#11 120" 146"
RECTANGULAR OPENING DETAIL CIRCULAR OPENING DETAIL
TWO #5 X 4'-0" EACH
FACE TYP 4 LOCATIONS
ADDITIONAL REINF
SEE NOTE 1
SYMM ABOUT
OPENING
NOTES:
1. PROVIDE ADDITIONAL REINFORCING THE SAME SIZE AS DISCONTINUOUS
REINFORCEMENT AT OPENING. QUANTITY OF REINFORCING IN EACH
DIRECTION SHALL BE EQUAL TO OR ONE GREATER THAN THE NUMBER OF
DISCONTINUOUS BARS. PLACE 1/2 OF ADDITIONAL REINFORCING BARS
EACH SIDE OF OPENING, PLACE ADDITIONAL REINFORCEMENT AT 3" OC
(TYPICAL BOTH DIRECTIONS AND ALL LAYERS OF REINFORCEMENT). START
FIRST BAR 2" CLEAR TO OPENING.
2. EXTEND ADDITIONAL REINFORCING BEYOND EDGE OF OPENING AS SHOWN
ABOVE. ADDITIONAL BARS MAY TERMINATE AT THE END OF THE WALL WITH
A STANDARD HOOK WHERE THE LENGTH OF THE WALL WILL NOT PERMIT
BARS TO EXTEND AS SHOWN ABOVE.
3. TYPICAL WALL OR SLAB REINFORCING NOT SHOWN FOR CLARITY. TERMINATE
TYPICAL REINFORCING 2" CLEAR TO OPENING.
4. OPENINGS 12" OR LESS IN SLABS AND WALLS, NO EXTRA REBARS ARE
REQUIRED UNLESS SHOWN OTHERWISE. TYPICAL REINFORCING SHALL BE
RESPACED (NOT CUT) TO ALLOW FOR OPENINGS TO BE MADE.
5. UNLESS SHOWN OTHERWISE ON DRAWINGS, PROVIDE EXTRA REINFORCING
AROUND OPENINGS AS SHOWN AND INDICATED ABOVE.
6. PROVIDE ADDITIONAL DOWELS PER NOTE 1 ABOVE FOR ALL OPENINGS NEAR
THE FLOOR SLAB, BASE SLAB, OR CORNERS.
TYP
L/2 +
LAP LENGTH W/2
CL
SYMM ABOUT
OPENINGCL
TYP
D/2 +
LAP LENGTH
SYMM ABOUT
OPENINGCL
TY
P
W /2
LA
P
LE
NG
TH
L/
L/
TY
P
D/
LA
P
LE
NG
TH
D
RE-ENTRANT CORNER
DISCONTINUOUS JOINT INTERSECTION
2 - #5x3'-0"
2" BELOW
SURFACE
SJ OR CLJ
2-#5x3'-0"
2" BELOW
SURFACE
SJ OR
CLJ
3"
3"
3"
3"
PLAN "A"
WALL CORNER
PLAN "B"
WALL INTERSECTION
PROVIDE STD
90° HOOK
AND EXTEND
REBAR TO
FAR FACE OF
INTERSECTING
WALL
NOTES:
1. SEE INDIVIDUAL STRUCTURES FOR EXTRA HORIZONTAL
REBARS AT CORNERS & WALL INTERSECTIONS.
2. WALL VERTICAL REBARS NOT SHOWN FOR CLARITY.
EXTEND ALL WALL INSIDE FACE
REBARS TO OUTSIDE WALL FACE
OUTSIDE
FACE PROVIDE STD 90° HOOK ON
ALL HORIZ REINF
INSIDE FACE
0"
TYP
0"
TYP
0"
TYP
KEYED CONSTRUCTION JOINT
ROUGHEN CONSTRUCTION JOINT
1 1/2" WIDE
CONT KEYWAY
WATERSTOP IF INDICATED
PLACE AT TOP OF KEYWAY
NOTE:
1. SEE SPECIFICATION FOR REQUIREMENT TO TIE WATERSTOPS IN PLACE TO
PREVENT MOVEMENT OR FOLDING OVER.
CONT REINF THRU
CONSTRUCTION JT
CONT REINF THRU
CONSTRUCTION JOINT
ROUGHEN SURFACEWATERSTOP IF INDICATED
CENTER IN THICKNESS
SOIL WHERE
APPLICABLE
EQ
EQ
EQ
LAP
F O
O T
IN
G
D E
P T
H 3'
-0
M A
X
6" 6"
WALL
WIDTH
1'-0"
FOOTING
WIDTH 1'-0"
FOUNDATION WALL
PROVIDE SLEEVE
2" (NOMINAL) LARGER
THAN PIPE O.D.
PIPE OF CONDUIT
PERPENDICULAR TO
FOUNDATION WALL
PROVIDE SLEEVE
2" (NOMINAL) LARGER
THAN PIPE O.D.
PROVIDE SLEEVE
2" (NOMINAL) LARGER
THAN PIPE O.D.
PIPE OF CONDUIT
PERPENDICULAR
TO FOOTING
AREA OK FOR
SLEEVES
FOR PIPES ON THIS AREA
LOWER BOTTOM OF FOOTING
TO ALLOW PIPE TO EXTEND
THROUGH FOOTING
FOR PIPES ON THIS AREA
LOWER ENTIRE FOOTING
TO ALLOW PIPE TO EXTEND
THROUGH FOOTING
NOTES:
1. FOR PIPES 3'-0" OR LESS BELOW FOOTING, PROVIDE SLEEVES AS SHOWN.
2. FOR PIPES AND CONDUITS MORE THAN 3'-0" BELOW FOOTING, PIPE SLEEVE
MAY BE ELIMINATED.
3. COORDINATE WITH MECH, ELECT AND OTHER AFFECTED TRADES.
NOTE:
1. AT SIM CONDITION GRADE NOT PRESENT.
SLAB REINF
SEE PLAN
ROUGHEN SURFACE
4" WATERSTOP
3/4" CHAMFER
TYP
SEE PLANS
10" MAX
TOC EL
SEE PLAN
#5@12 CENTERED IN CURB
TO CURB EL
SEE PLAN
2-#5 W/90 DEG CORNER BAR
PL
ANT SE
E
1/2" EXP JOINT FILLER
SLAB ON GRADE
1/2" WIDE x 1/2" DEEP
GROOVE W/ SEALANT
AT EXPOSED FLOOR
ISOLATION JOINT AT SLAB ON GRADE
FACE OF WALL OR
CONCRETE COLUMN
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OFA
u to d e s k D o c s /1
M
O R
U W a s te w a te r R e h a b a n d E x p a n s io n
/1
-0
-G
.r v t
-J u n -2
S501
MOUNT RUSHMORE NATIONAL MEMORIAL
272051
GENERAL STRUCTURAL
DETAILS
GS
SKM
06/13/23
TJH
18678700-
FINAL CONSTRUCTION DOCUMENTS
NO SCALE
REINFORCING HOOK SCHEDULE1
NO SCALE
CONCRETE REINFORCING LAP AND EMBEDMENT SCHEDULE2
NO SCALE
EXTRA REINFORCING AROUND OPENINGS3
NO SCALE
ADDITIONAL SLAB REINFORCING4
NO SCALE
TYPICAL WALL HORIZONTAL REINFORCING DETAILS5
NO SCALE
CONSTRUCTION JOINT (CJ)6
NO SCALE
INSTALLATION OF PIPES/CONDUITS7
NO SCALE
TYPICAL CONTAINMENT CURB DETAIL8
NO SCALE
TYPICAL ISOLATION JOINTS (IJ)9
NOTE:
1. INTERSECTION BARS TO BE SAME SIZE AND SPACING AS
FOOTING REINFORCING.
AT TRENCH FOOTINGS,
WHEN CONSTRUCTION
JOINT IS USED PROVIDE
INTERSECTION BARS
STANDARD 90 DEGREE HOOKS
OPTIONAL
CONST JT
CONCRETE FOOTING
SE
E
SC
HE
DU
LE
LA
P
SP
LI
CE
CORNER
BAR
OPTIONAL
CONST JT
NOTE:
1. CORNER BARS TO BE SAME SIZE AND SPACING AT
FOOTING REINFORCING.
CONCRETE FOOTING
STANDARD 90 DEGREE HOOKSAT TRENCH FOOTINGS, WHEN
CONSTRUCTION JOINT IS
USED PROVIDE CORNER BARS
SE
E
SC
HE
DU
LE
LA
P
SP
LI
CE
6" CONCRETE SLAB
W/ #4@16 EW CENTERED
GRANULAR FILL TYP
#4@12 EW EF
3 SIDES TYP
FOR FOUNDATION
REINFORCING-
SEE SECTIONS
#5@12 30"
30"
RIGID
INSULATION
SEE ARCH
#4 x 3'-4"@16
FULL WIDTH
OF SLAB
EXPANSION
JOINT SEE CIVIL
SEE 5/00S501
FOR WALL DOWELS
AT STOOP WALLS
SLOPE TO DRAIN
SEE CIVIL
1/2" COMPRESSIBLE
FILLER & SEALANT
WALL OPENING NOTCH AS
REQD TO CLEAR STOOP
4'-
1'-0"
4"
2"
SEE PLAN
FOR WALL &
SLAB REINF,
SEE SECTIONS &
DETAILS
#7@8 BOT
PAVING
EXPANSION
JOINT SEE CIVIL
SLOPE VARIES
SEE CIVIL
RIGID
INSULATION-
SEE ARCH
#5@12
#4@12 x 2'-0"
CENTERED ON CJ
TYP FULL LENGTH
OF APPROACH SLAB
12'-0" MAX
SEE PLAN 4"
3" C
LR
2" C
LR
#5@12 EW EF
4 SIDES TYP
#5@12 EW T&B
GRANULAR FILL-
SEE NOTE 3
1'-0"
TYP
EQUIP ANCHOR BOLT
EQUIP BASE PL
NOTES:
1. SEE PAD NOTES AT DETAIL 5 THIS SHEET.
2. INCREASE SLAB THICKNESS AS REQUIRED TO MAINTAIN MINIMUM 3" CONCRETE COVER
BELOW EQUIPMENT ANCHOR BOLTS. WEIGHING MORE THAN 5000 POUNDS AND
SUPPORTED ON GRADE UNLESS NOTED OTHERWISE ON PLANS.
3. AT CONTRACTOR'S OPTION REPLACE GRANULAR FILL WITH CONCRETE POURED WITH
PERIMETER GRADE BEAM AND TOP SLAB. PROVIDE ALL REINF SHOWN IN SECTION.
4. PROVIDE OPENINGS AS REQD FOR PENETRATIONS. REINFORCE AROUND OPENINGS PER
DETAIL 3 ON SHEET 00-S501.
GRADE-
SEE CIVIL
4'-
/1
1' -0
MIN
6"
M
AX 6"
NOTES:
1. PROVIDE ABOVE PAD UNDER ALL ELECTRICAL AND MECHANICAL EQUIPMENT
SUPPORTED ON STRUCTURAL SLABS. ALSO PROVIDE FOR EQUIPMENT WEIGHING
LESS THAN 5000 POUNDS WHICH ARE SUPPORTED ON GRADE, OR WHERE
SPECIFICALLY NOTED ON PLANS. FOR PAD HEIGHT GREATER THAN 8", SEE DETAIL 6
THIS SHEET.
2. PAD THICKNESS SHALL BE A MINIMUM OF 4". CONTRACTOR SHALL VERIFY THE PAD
DIMENSIONS.
3. PROVIDE EMBEDDED CHANNELS FOR ANCHORING ELECTRICAL EQUIPMENT WHERE
REQUIRED.
PAD NOTES:
1. EQUIPMENT PAD DETAILS ON THIS SHEET APPLY FOR SUPPORT OF ALL EQUIPMENT
UNLESS INDICATED OTHERWISE ON THE DRAWINGS.
2. BEFORE EQUIPMENT SUPPORT PADS ARE CAST,…