Attachment 2 - SOW HARB Distribution Transformers (FINAL).pdf
PDF 1 MB Posted
- Attached to
- HARB Distribution Transformer Procurement
- Solicitation number
- FA664825Q0027
About this file
This Statement of Work (SOW) details the Department of the Air Force's requirement for four pad-mounted, exterior distribution transformers for Homestead Air Reserve Base (HARB) in Florida. The specific transformers are: 1) a 45KVA transformer for MSA (13.2KV-208Y/120V), 2) a 300KVA transformer for MSA NW Fence Lighting (13.2KV-480V Delta), 3) a 45KVA transformer for MSA NE Fence Lighting (13.2KV-480V Delta), and 4) a 75KVA transformer for TACAN near the runway (13.2KV-208Y/120V).
The SOW requires the contractor to provide transformers meeting detailed technical specifications, including being pad-mounted, dead-front, oil-filled, three-phase units with specific voltage ratings, UL-listed, and compliant with ANSI, IEEE, and NEMA standards. Delivery is to Building 213 at Homestead ARB, with the contractor responsible for factory testing, packaging, and providing documentation including test reports, wiring diagrams, operations manuals, and a minimum 3-year warranty. The SOW specifies that installation is excluded, and a post-delivery inspection will be conducted by the government to ensure compliance with all specifications.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 1 - Model Contract - FA664825Q0027.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE AIR FORCE
Homestead Air Reserve Base
Homestead, Florida
STATEMENT OF WORK (SOW)
Project Title: Procurement of four pad-mounted, exterior distribution transformers
Location: Supplies and Equipment Warehouse (B213), Homestead ARB.
Date: September 25 2025
1.0 PURPOSE
This Statement of Work defines the requirements for the purchase and delivery of four (4) pad-mounted, exterior, three-phase transformers rated as indicated in section 3.0 (technical specifications) for use in Homestead Air Reserve Base (HARB) electrical distribution system.
2.0 SCOPE OF WORK
The contractor shall provide all labor, materials, equipment, factory testing, and shipping necessary to deliver fully compliant transformers to the designated facility. Installation is excluded.
3.0 TECHNICAL SPECIFICATIONS
• Type: Pad-mounted, dead-front, oil-filled
• kVA Rating: 45 kVA
• Frequency: 60 Hz
• Phase: Three-phase
• Primary Voltage: Refer to the specifications for each transformer below.
• Secondary Voltage: Refer to the specifications for each transformer below.
• Cooling Class: ONAN (Oil Natural / Air Natural)
• Impedance: Per ANSI C57.12 standards
• Primary Taps: ±2 x 2.5%
• Enclosure: Tamper-resistant, pad-mounted enclosure, ANSI 61 Gray or Munsell Green finish
• Protection/Fusing: Bay-O-Net fuses with internal isolation (ISO) links
• Bushings: Dead-front, separable load-break bushings per IEEE Std 386
• Fluid: PCB-free mineral oil or approved biodegradable alternative
• Certification: UL-listed and labeled
• Cooling Class: ONAN (Oil Natural / Air Natural)
• Winding Materials: Copper
• Coil Materials: Copper
1) MSA Transformer (B285): 45KVA, 13.2KV – 208Y/120V 4-wire wye QTY: 1 Each
2) MSA NW Fence Lighting Transformer: 300KVA, 13.2KV – 480V Delta QTY: 1 Each
3) MSA NE Fence Lighting Transformer: 45KVA, 13.2KV – 480V Delta QTY: 1 Each
4) TACAN (B844. Next to the runway) Transformer: 75KVA, 13.2KV – 208Y/120V QTY: 1 Each
Answers to Frequently Asked Questions:
1) Is FR3 Acceptable?
Answer: In order to use FR3 – the government would need the OEM approval and documentation that the particular transformer design (and components) is compatible to
ASTM D6871 for natural ester fluids, and IEC 62770/IEEE C57 references for transformer operation with natural esters.
2) Would a dry-type alternative be acceptable?
Answer: Dry type medium voltage outdoor distribution transformers are universally accepted at all Air Force bases; however, they can only be used if they come with the proper outdoor robust enclosure and insulation. Their OEM certification must meet ANSI/IEEE/NEMA specs and UL listing certification.
4.0 STANDARDS AND COMPLIANCE
Transformers shall comply with:
• ANSI C57 series (transformer construction and performance).
• IEEE Std 386 (separable connectors).
• DOE 10 CFR Part 431 efficiency requirements.
• NEMA TR 1.
• UL 1562 for liquid-filled distribution transformers.
5.0 DELIVERABLES
The contractor shall deliver:
• Four (4) pad-mounted transformers meeting specifications.
• Manufacturer-certified routine test reports and type test data.
• As-built drawings and wiring diagrams.
• Operations and maintenance manuals.
• Warranty documentation (minimum 3-year coverage).
6.0 DELIVERY AND LEAD TIME
• Lead Time: The Contractor shall provide estimated lead time with quote and confirmed lead time within 10 days of contract award.
• Delivery: Delivery shall be FOB Destination to:
Building 213 – Supply and Equipment Warehouse Homestead Air Reserve Base 29350 Westover Street Homestead ARB, FL 33039
• The delivery schedule must be coordinated with the facility POC prior to shipment.
• The contractor is responsible for packaging, crating, and protecting the equipment during transit to prevent damage.
• Early delivery is encouraged but must be coordinated with the facility POC.
7.0 QUALITY ASSURANCE AND ACCEPTANCE
• Contractor shall perform factory testing in accordance with ANSI/IEEE standards prior to shipment.
• Upon delivery, a post-delivery inspection will be conducted by the government or the owner.
• Equipment must be free of damage, meet all specifications, and be accompanied by the required documentation before it can be accepted.
8.0 WARRANTY
• Contractor shall provide a standard commercial warranty.
9.0 PHOTOS
Name Plate - MSA NE Transformer 45KVA, 13.2VA – 480V
Name Plate – MSA NW Transformer 45KVA, 13.2KV-480V – Change to 300KVA
Name Plate – MSA Transformer 45KVA, 13.2KV-208Y_120V