This document is a Salient Characteristics specification for Combo Fire/CO Detectors for the 319 Civil Engineering Squadron (CES) at Grand Forks Air Force Base. The specification details requirements for 80 FCO-951 Series Advanced Multi-Criteria Fire/CO Detectors with System Sensor Firmware, which must be compatible with the existing Notifier fire panel.
The detectors must have specific technical features including the ability to detect four major fire elements, separate CO detection, high nuisance alarm immunity, automatic drift compensation, and a 10-year CO cell with end-of-life warning. Technical specifications include an operating temperature range of 32°F to 100°F, operating humidity range of 15% to 90%, operating voltage of 15 to 32 VDC, and various current and LED communication specifications. The detectors must be UL and CSA listed, and when used with a B200S series base, provide separate audible signals for fire and CO alarms.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics
319 CES
Combo Fire/CO Detectors
319 RW
09 July 2025
1. General:
The contractor shall provide Combo Fire/CO Detectors for the 319 CES, delivered to Grand Forks AFB, ND 58205. All capabilities shall be met as listed below or equivalent.
2. FCO-951 Series Advanced Multi-Criteria Fire/CO Detector (or equal) with System
Sensor Firmware required for compatibility with the currently installed Notifier fire panel
If you are supplying an equal product please notify us/state what product you are providing
Features Unique ability to detect all four major elements of a fire Separate CO detection signal Highest nuisance alarm immunity Automatic drift compensation for smoke and CO sensors Uses only one address on the SLC RealTest® CO testing capability UL 268 7th edition, UL 521, and UL 2075 listed; CAN/ULC S529, CAN/ULC S530 and CSA 6.19-01 listed Separate audible signal for fire or CO alarm when used with a B200S series base (B200SCOA series in Canada) 10-year CO cell with end-of-life warning
Specifications Operating Humidity Range: 15% to 90% Relative Humidity, Noncondensing Operating Temperature Range: 32°F to 100°F (0°C to 38°C) Air Velocity: 0 to 4000 ft./min. (0 to 1219.2 m/min.)
Operating Voltage Range: 15 to 32 VDC Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication) Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on) Maximum Current: 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on) Isolator Load Rating: 0.0063