Attachment 2 - Salient Characteristics.pdf

PDF 91 KB Posted

Attached to
B5576 Chiller Federal contract opportunity
Solicitation number
FA460824QC101
Issued by
Department of the Air Force Global Strike Command

About this file

This document is an Attachment 2 - Salient Characteristics for a federal contract opportunity solicitation. The solicitation is for the procurement of one (1) TRANE 160-Ton 200V Air-Cooled Scroll Chiller (ACSA) for Barksdale Air Force Base in Louisiana. This is a brand name requirement, as detailed in Attachment 3. The key details of the salient characteristics include the model number digit descriptions, compressor information, and various configurable options for the chiller unit. The associated federal contract opportunity is a commercial items solicitation, number FA460824QC101, issued by the Department of the Air Force Global Strike Command. Quotes are requested by 2:00 PM CDT on June 24, 2024, and the solicitation is a 100% small business set-aside with a NAICS code of 333415 and a size standard of 1,250 employees.

View the file

Other files for this federal contract opportunity

Other files attached to B5576 Chiller, newest first.
File Type Posted
Attachment 1 - Provisions and Clauses .pdf PDF
Combined Synopsis Solicitation.pdf PDF
Attachment 3 Brand Name Class Justification and Approval.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AC-SVX002C-E N 7

Attachment 2, Salient Characteristics

FA460824QC101

• TRANE"

Model Number Descriptions

Unit Model Number

Digit 1, 2, 3, 4 - Unit Model

ACSA = Air-Cooled Scroll Chiller

Digit 5, 6, 7 - Nominal Tonnage

140 = 140 Tons

180 = 180 Tons

200 = 200 Tons

215 = 215 Tons

230 = 230 Tons

Digit 8 - Compressor Type

2 = Scroll with Variable Volume Ratio

Digit 9- Unit Voltage

A= 200/60/3

B = 230/60/3

E = 460/60/3

F = 575/60/3

Digit 10- Manufacturing Location

U = Trane Commercial Systems, Pueblo, CO

USA

Digits 11, 12 - Design Sequence

**=Factory assigned

Digit 13 - Unit Sound Package

X = Standard Unit

L = Superior

R = Standard with Noise Reduction Request

Q = Superior with Noise Reduction Request

Digit 14 - Agency Listing

U =UljcUL Listing

C = No Agency Listing

Digit 15 - Pressure Vessel Code

X = Not Applicable

Digit 16 - Factory Charge

A= Refrigerant Charge R-410A

B = Nitrogen Charge

Digit 17 -Auxiliary Items

X = No Auxiliary Items

Digit 18 - Evaporator Application

N = Standard Cooling (above 40°F)

P = Low Temp Process Cooling (below 40°F)

C = Ice Making

Digit 19, 20 - Evaporator Type

B2 = Brazed Plate Heat Exchanger (Standard)

Digit 21 - Water Connection

X = Grooved Pipe

A= Grooved Pipe+ Flange Adapter

Digit 22 - Flow Switch Set Point

C = Flow Switch Setpoint 15

F = Flow Switch Setpoint 35

H = Flow Switch Setpoint 45

L = Flow Switch Setpoint 60

Digit 23 - Insulation

A= Factory Insulation -All Cold Parts 0. 75 inch

B = Evaporator-Only Insulation for High Humidity/Low Evap Temp 1.25 inch

Digit 24 - Unit Application

X = Standard Ambient (32 to 115°F)

L = Low Ambient (-20 to 115°F)

H = High Ambient (32 to 130°F)

W = Wide Ambient (-20 to 130°F)

Digit 25 - Condenser Length

S = Standard

Digit 26 - Condenser Fin Options

M = Aluminum Microchannel

C = CompleteCoat™ Microchannel

Digit 27 - Fan Type

E = EC Condenser Fan Motors

Digit 28 - Compressor Starter

X = Across-the-Line Starter

Digit 29 - Incoming Unit Power Line

Connection 1 = Single Point Unit Power Connection

Digit 30 - Power Line Connection

Type

T = Terminal Block

H = Circuit Breaker with High Fault Rated Control Panel

Digit 31 - Short Circuit Current Rating

A = Default Short Circuit Rating

B = High Short Circuit Rating

Digit 32 - Electrical Accessories

X= None

U = Under/Over Voltage Protection

C = 15A - 115V Convenience Outlet

B = Convenience Outlet and Under/Over Voltage Protection

Digit 33 - Remote Communications Options

X= None

B =BACnet® Interface

M = Modbus™ Interface

L = LonTalk® Interface

Digit 34 -Hard Wire Communication

A= Hard Wired Bundle -All

D=Unit Status Programmable Relay

Digit 35 - Smart Flow Control

T = Variable Primary Flow (Constant Delta T)

Digit 36 - Structural Options

A = Standard Unit Structure

Digit 37 - Appearance Options

X = No Appearance Options

Digit 38 - Unit Isolation

1 = Elastomeric Isolators

= 160 Tons

8 AC-SVX002C-EN

Attachment 2, Salient Characteristics

FA460824QC101

O = None

• TRANE

Model Number Descriptions

Digit 39 - Shipping Package

X = No Shipping Package

T = Tarp Covering Full Unit

Digit 40 - Pump Package

X = No Pump Option

2 = Single Pump, High Pressure, Single VFD

4 = Dual Pump, High Pressure, Dual VFD

Digit 41- Not Used

Digit 42- Not Used

Digit 43 - Special Requirement

S = Special Requirement F = Ship to Final Finisher

Compressor Information

Model Number

Digit 1, 2, 3 - Compressor Type

DSH = Danfoss

Digit 4, s, 6 - Capacity

381 = 30tons

485 = 40tons

Digit 7 - Agency Approval

A=UL

Digit 8 - Voltage

3 = 200-230V/60Hz/3ph

4 = 460V/60Hz/3ph

7 = 57SV/60Hz/3ph

Digit 9, 10 - Custom

AT = Trane Pueblo

AT = Trane Epinal

File details come from the government source that posted it. Updated .