Job Name SAFB Training Center

AHUMark for

Unit Parameters

39L Size: 6

Insulation: 1" 1.5# Tuf-Skin II Single Wall

Hand: Right

No Export Crate

Controls: No Product Integrated Controls

FLT Flat Filter Section

2in Pleated MERV8 Filters - kit

(2) 20in. x 20in.

User Specified Base Rail Split (Shipped Attached)

LA Horizontal Cooling (LFA) Coil/Fan Section

Belt Drive RPM: 1137

Belt Drive Factory Installed

Motor HP: 2

Voltage: 208/230/460 3 Phase 60Hz

Efficiency: Premium

Enclosure: ODP

RPM: 1800

Manufacturer - Generic

Frame Size - 145T

Motor Shaft Diameter (in.) - 0.875

Full Load Amps - 6.1/5.6/2.8

MCA - 7.7/6.9/3.5

MOCP - 10/10/6

Efficiency - 86.5%

Discharge: UpBlast Rear

CW 5.9 sq.ft. 6 Rows 8 FPI Half Circuit

0.016 in. Tube Wall Thickness

Starter 208-230 3 Phase 60Hz

Weights and Dimensions

(LxWxH in ft in) 4' 9" x 3' 10" x 2' 4" **

Dry 501 LB ** Wet 540 LB ** Weights and Dimensions are approximate. Weights include base unit weight, coils (wet & dry), fans and fan motors, and other components, but does not include filters, drives and skids. Approximate dimensions are provided primarily for shipping purposes. Shipping skids are not included.

All filter media efficiency ratings are for the filter media only.

AHUBuilder v6.69n 7/27/2022

SUBJECT TO CHANGE WITHOUT NOTICE

AHUBuilder v6.69n 07-27-2022

Cooling Application's Balance Criteria: Fluid Flow Coil Model Carrier 28NA Number of Coils 1 Row / FPI / Circ 6 / 8 / HF Fin Thickness .0060 in Fin Type Sine Wave Face Area Type Large Coil Face Area 5.90 sqft Face Velocity 508.0 fpm Fin-Casing Material Al-Galv.

Tube Diameter 0.5 in Tube spacing: Stf x Str 1.25 x 0.781 in Tube Wall Thickness 0.016 in Actual Airflow 3000 CFM Site Altitude 0 ft Standard Airflow (adj. to std. dry atmosphere) 2893 SCFM Total Cooling Capacity 110.55 MBH Sensible Cooling Capacity 78.25 MBH Fluid Flow Rate 22.0 gpm Fluid Pressure Drop 10.5 ft wg Fluid Velocity 3.8 ft/s Entering Fluid Temperature 44.00 F Leaving Fluid Temperature 54.01 F Fluid Temperature Rise 10.0 F Entering Air Dry Bulb 80.00 F Entering Air Wet Bulb 67.00 F Entering Air Enthalpy 31.50 BTU/lb Leaving Air Dry Bulb 55.40 F Leaving Air Wet Bulb 54.58 F Leaving Air Enthalpy 23.0 BTU/lb Air Friction 0.75 in wg Brine FW Brine Concentration 0 % Fouling Factor 0.0 (hr-sqft-F)/BTU

NOTE: Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory (www.ahridirectory.org).

LEGEND:

Stf -- Tube spacing across coil face Str -- Tube spacing in direction of airflow

SAFB Training Center

AHU

Project:

Tag:

Chilled Water Coil Performance Summary

Unit Acoustics Sound Power Level:

Discharge Inlet Casing

63 Hz 88 77 82 125 Hz 89 68 77 250 Hz 85 63 68 500 Hz 84 61 64 1000 Hz 82 62 66 2000 Hz 76 62 63 4000 Hz 72 56 59 8000 Hz 67 48 57

Unit Acoustics A-weighted Sound Power Level:

Discharge Inlet Casing

63 Hz 62 51 56 125 Hz 73 52 61 250 Hz 76 54 59 500 Hz 80 57 60 1000 Hz 82 62 66 2000 Hz 77 63 64 4000 Hz 73 57 60 8000 Hz 66 47 56

SAFB Training Center

AHU

Project:

Unit Acoustics Summary

Fan Model 39LA06 Unit Size 06 Fan Type LA (For LFA Clg. Coils) Inlet Guide Vanes No Actual Airflow, CFM 3000 Site Altitude, ft 0 Upstream Ext. Static, in wg 0.00 Downstream Ext. Static, in wg 0.50 Cooling Coil Static, in wg 0.75 Heating Coil Static, in wg 0.00 Total Accessory Static, in wg 0.20 Total Static Pressure, in wg 1.45 Fan RPM 1085 Fan BHP 1.7 Fan Electrical Power, kW 1.6

Certified by the AHRI Central Station Air-Handling Unit (AHU) Certification Program, which is based on AHRI Standard 430/431.

AHRI certified units are subject to rigorous and continuous testing, have performance ratings independently measured and are third-party verified. Certified units may be found in the AHRI Directory at www.ahridirectory.org

Accessories:

(1) Flat pleated 2 inch MERV 8 [0.20]

SAFB Training Center

AHU

Project:

Supply Fan Performance Summary

Air Filter Submittal Project:

Unit Tag:

Carrier Part Number

Kit Description

Unit Airflow, CFM

Filter Velocity, FPM

Filter Sizes and Quantities

DFpro MERV 8 Pleated Filter

The 100% synthetic graduated density media is continuously bonded to a 30 gauge galvanized, corrosion resistant, expanded metal support grid with an effective open area of 96%. The media is resistant to a wide range of chemicals, does not absorb moisture and will not support microbial growth.

The controlled pleat spacing maximizes surface area and dust holding capacity and is bonded to the enclosure frame to prevent dust bypass. The enclosure frame is constructed of high wet strength moisture resistant beverage board. The diagonal support members of the frame are bonded to the entering and exiting apexes of each pleat to prevent pleat collapse and filter bowing.

0.1

0.2

0.3

0.4

200 250 300 350 400 450 500 550 600 650 700

In it ia l R e si st an ce in w .g

Filter Face Velocity (feet per minute)

Filter Pleated (2") MERV 8

SAFB Training Center

AHU

31KFD39LF006522

Filter Kit, 2'' FLT Pleated (MERV8), 39L006

(2) 20in. x 20in.

AHUBuilder v6.69n 7/27/2022

PART# WEIGHT

VOLUME

GALLONS

DIAMETER

DIA

LENGTH

TL

VENT

A

DRAIN

B

CENTER OF IN/

OUT DIMENSION

C D

ASME

CHILL WATER

BUFFER TANKS

Description:

Chill Water Buffer Tanks Specifications:

Built to ASME Code Section VIII National Board Registered Carbon Steel Gray Primer

150 PSI @ 400 ˚F

Other Design Pressures Available -Custom Sizes also Available

* Denotes Stock Units

OPENINGS

E

1” NPT

1.5” NPT

2” NPT / GROOVE PIPE

2.5” NPT / GROOVE PIPE

3” NPT / GROOVE PIPE

4” FLANGE / GROOVE PIPE

6” FLANGE / GROOVE PIPE

8” FLANGE / GROOVE PIPE

10” FLANGE / GROOVE PIPE

12” FLANGE / GROOVE PIPE

14” FLANGE / GROOVE PIPE

16” FLANGE / GROOVE PIPE

18” FLANGE / GROOVE PIPE

20” FLANGE / GROOVE PIPE

DIA

AIR VENT

A

F

C

B

DRAIN

D

TL

DIVIDER PLATE

INLET

E

OUTLET

E

8"

12" X 16"

MANWAY

FOR 42" DIA

& GREATER

*CWT-120

*CWT-200

*CWT-300

CWT-500

CWT-680

CWT-850

CWT-1040

300 lbs 513 lbs 617 lbs

1239 lbs 1507 lbs 1777 lbs 2358 lbs

F

E

3”NPT

3”Flange 4”Flange

Per Request Per Request Per Request Per Request

ELBI of America, Inc. • 525 McCarty Street • Houston, TX 77029 • Tel. (713) 674-2900 • Fax (713) 674-2982 www.elbi.net elbi@elbi.net

125/150 PSI WP * Please specify

Houston, TX 77032

OPTIONAL

RV:42016

3" Flange

RV:82017Elbi of AmEricA, inc. • 15882 Diplomatic Plaza, Suite 170, Houston, TX 77032 • Tel. (713) 674-2900 • Fax (713) 674-2982 www.elbi.net • elbi@elbi.net

JoeA Arrow

AHU Specs
AHU
Unit Report
Chilled Water Coil Performance Summary
Unit Acoustics Summary
Supply Fan Performance Summary
Assembly Drawing, (Side View)
Assembly Drawing, (Top View)
Fan/Coil, (Side View)
Fan/Coil, (Top View)
Coil Connection Locations, (Side View)
First Coil, (Side View)
Filter Submittal

Chilled Water Tank Specs