ATTACHMENT 2 - 100 Bid Document Drawings.pdf

PDF 18 MB Posted

Attached to
Y1DA--PROJECT 675-23-105, Bid-Build (BB) Renovate Various Spaces at Lake Nona
Solicitation number
36C24826Q0105
Issued by

About this file

This document is a comprehensive set of construction documents for a renovation project at the Lake Nona VA Medical Center in Orlando, Florida, with project number 675-23-105. The project involves renovating various spaces across multiple areas including a pharmacy, computer tomography room, medical media area, Office of Information and Technology (OIT), tool crib, and warehouse spaces across the 1st and 4th floors of Building 1.

The renovation scope includes architectural, structural, mechanical, plumbing, and electrical work, with a focus on maintaining the facility's operational status during construction. Key design specifications include using Construction Type IB, fully sprinklering the building, and adhering to multiple building codes including the 2018 International Building Code. The project requires strict infection control measures, including maintaining negative air pressure, constructing critical barriers, and implementing comprehensive cleaning protocols. The design team includes AESUS Design Group as the primary architectural and engineering firm, with Simply Structural providing structural engineering services. The total renovation area is approximately 8,272 square feet, with work concentrated on modernizing and upgrading various medical and administrative spaces within the VA Medical Center.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DX

A3-301

X

XX

X

DETAIL FLAG NUMBER

DOOR NUMBER

AE-501

BUILDING SECTION CUT

OTHER SECTION CUT

SHEET WHERE APPEARS (TYPICAL)

AE-301

AA

SHEET WHERE APPEARS

ELEVATION NUMBER

SHEET WHERE APPEARS

x x x x

EXISTING COLUMN CENTER LINEA

X

WINDOW TAG

AE-301

AA

AE-301

AA

ELEVATION NUMBER

AE-710

4 2

DASHED LINE

AROUND

AREA DETAILED

PLAN OR DETAIL NUMBERX

NOTE: IN ADDITION TO THE FOLLOWING INFECTION CONTROL MEASURES OF ICRA

CLASS & PERMIT LEVEL IV, THE CONTRACTOR SHALL REVIEW THE VA SAFETY-QUALITY

CONTROL-INFECTION CONTROL DOCUMENTS IN THE SPECIFICATIONS. THE AE WILL

PROVIDE A FORM FOR THE CONTRACTOR TO FILL OUT

DURING CONSTRUCTION:

A. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

B. COMPLETE ALL CRITICAL BARRIERS I.E. SHEET ROCK, PLYWOOD, PLASTIC,

TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE

METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO

WORK SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE

CONSTRUCTION BEGINS.

C. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA

EQUIPPED AIR FILTRATION UNITS. PROVIDE NEGATIVE AIR PRESSURE

MONITOR.

D. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.

E. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH

THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER

BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER

COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE.

F. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT

IS INSPECTED BY A SAFETY OFFICER AND INFECTION CONTROL

COORDINATOR AND THOROUGHLY CLEANED BY THE ENVIRONMENTAL

MANAGEMENT SERVICES.

UPON COMPLETION OF PROJECT:

A. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT

AND DEBRIS ASSOCIATED WITH CONSTRUCTION.

B. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY

COVERED CONTAINERS.

C. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS

SOLID LID.

D. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.

E. WET MOP AREA WITH DISINFECTANT.

F. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING

PERFORMED.

Approved: Associate Director

Approved: Chief Facilities

Management

Approved: Manager / Engineer

Approved: Director

Approved: Union representative

Approved: Safety Officer

EQ-X

CPT1

W-X

E

EA EACH

E EAST

EWC ELECTRIC WATER COOLER

ELEC ELECTRIC (AL)

EL ELEVATION

ELEV ELEVATOR

EMER EMERGENCY

ENGR ENGINEER

EQ EQUAL

EQUIP EQUIPMENT

EXIST EXISTING

ETR EXISTING TO REMAIN

EXP EXPANSION

EXP BT EXPANSION BOLT

EJ EXPANSION JOINT

EXP EXPOSED

EXT EXTERIOR

EIFS EXTERIOR INSULATION AND

FINISH SYSTEM

F

FWC FABRIC WALL COVERING

FT FEET, FOOT

FGL FIBERGLASS

FIN FINISH

FIN GR FINISH GRADE

FDV FIRE DEPARTMENT VALVE

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER

CABINET

FHC FIRE HOSE CABINET

FP FIREPROOF

FIXT FIXTURE

FLASH FLASHING

FLEX FLEXIBLE

FLR FLOOR

FD FLOOR DRAIN

FLUOR FLUORESCENT

FTG FOOTING

FDTN FOUNDATION

FRMG FRAMING

FURN FURNACE, FURNITURE

G

GA GAGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GL GLASS

GL BLK GLASS BLOCK

GB GRAB BAR

GR GRADE

GRAN GRANITE

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GUT GUTTER

GYP BD GYPSUM BOARD

H

HNDRL HANDRAIL

HDW HARDWARE

HDWD HARDWOOD

HD HEAD

HVAC HEATING, VENTILATING, AIR CONDITIONING

HT HEIGHT

HPT HIGH POINT

HC HOLLOW CORE

HM HOLLOW METAL

HORIZ HORIZONTAL

HB HOSE BIBB

HOSP HOSPITAL

HR HOUR

I

IN INCH

INFO INFORMATION

ID INSIDE DIAMETER

INSUL INSULATED,INSULATION

INT INTERIOR

J

JAN JANITOR

JT JOINT

K

KPL KICKPLATE

KIT KITCHEN

KB KNEE BRACE

L

LAB LABORATORY

LAM LAMINATE

LC LAUNDRY CHUTE

LV LAVATORY

LT LIGHT

LD LINEAR DIFFUSER

L CL LINEN CLOSET

LL LIVE LOAD

LLV LONG LEG VERTICAL

LPT LOW POINT

M

MACH MACHINE

MH MANHOLE

MFD MANUFACTURED

MFR MANUFACTURER

MRB MARBLE BASE

MRF MARBLE FLOOR

MKR BD MARKER BOARD

MO MASONRY OPENING

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MED MEDICAL

MC MEDICINE CABINET

MEMB MEMBRANE

MTL METAL

MIN MINIMUM, MINUTE

MISC MISCELLANEOUS

MOD MODIFIED

MLDG MOLDING

N

NAT FIN NATURAL FINISH

NOM NOMINAL

N NORTH

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NO NUMBER

O

OFF OFFICE

OC ON CENTER

OPNG OPENING

OPP OPPOSITE

OPH OPPOSITE HAND

ORCH ORCHESTRA

ORN ORNAMENTAL

OD OUTSIDE DIAMETER

OH OVERHANG, OVERHEAD

OF/CI OWNER FURNISHED/

CONTRACTOR INSTALLED

O OXYGEN

P

P PAINT

PR PAIR

PNL PANEL

PTD PAPER TOWEL DISPENSER

PTN PARTITION

PERF PERFORATED

PC PIECE

PLAM PLASTIC LAMINATE

PLAS PLASTIC, PLASTER

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PCC PRECAST CONCRETE

PREFAB PREFABRICATE

PREFIN PREFINISH

PROD PRODUCTION

Q

QTY QUANTITY

QT QUARRY TILE

A

AFF ABOVE FINISHED FLOOR

ACST ACOUSTIC (AL)

ACT ACOUSTICAL CEILING TILE

APC ACOUSTICAL PANEL CEILING

AWP ACOUSTICAL WALL PANEL

AWT ACOUSTICAL WALL

ADJ ADJUSTABLE

A/C AIR CONDITIONING

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

AB ANCHOR BOLT

AL ANGLE

APPROX APPROXIMATE

ARCH ARCHITECT (URAL)

ASPH ASPHALT

ASSY ASSEMBLY

AUTO AUTOMATIC

AWN AWNING

B

BALC BALCONY

BSMT BASEMENT

BM BEAM, BENCHMARK

BR BEDROOM

BLKG BLOCKING

BD BOARD

BOT BOTTOM

BRKT BRACKET

BRK BRICK

B CL BROOM CLOSET

BLDG BUILDING

BLT IN BUILT-IN

BUR BUILT-UP ROOFING

C

CAB CABINET

CPT CARPET

CSMT CASEMENT

CI CAST IRON

CB CATCH BASIN

CLG CEILING

CEM CEMENT

CL CENTER LINE

CER CERAMIC

CT CERAMIC TILE

CO CLEANOUT, CASED OPENING

CLR CLEAR, COLOR

CLO CLOSET

COL COLUMN

CMPST COMPOSITE

CONC CONCRETE

CMU CONCRETE MASONRY UNIT

CONSTR CONSTRUCTION

CONT CONTINUOUS

CONTR CONTRACTOR

COTR CONTRACTING OFFICER

CJ CONTROL JOINT

COP COPING

CU COPPER

CG CORNER GUARD

CORR CORRIDOR

CNTR COUNTER

CSK COUNTER SUNK

D

DMPF DAMPPROOFING

DL DEAD LOAD

DEMO DEMOLITION

DET DETAIL

DIA DIAMETER

DIFF DIFFUSER

DIM DIMENSION

DR DOOR, DRAIN

DH DOUBLE HUNG

DN DOWN

DS DOWNSPOUT

DWR DRAWER

DWG DRAWING

DF DRINKING FOUNTAIN

DUPL DUPLICATE

R

R RADIUS, RISER

RWD REDWOOD

REF REFERENCE, REFRIGERATOR

REINF REINFORCE

REQD REQUIRED

RB RESILIENT BASE

RF RESILIENT FLOORING

RA RETURN AIR

REV REVISION

RD ROOF DRAIN

RM ROOM

RO ROUGH OPENING

RS ROUGH SAWN

S

SCHED SCHEDULE

SECT SECTION

SHTHG SHEATHING

SHT SHEET

SHV SHELVING

SIM SIMILAR

S SOUTH

SP FIN SPECIAL FINISH

SPEC SPECIFICATION

SQ SQUARE

SF SQUARE FEET

SST STAINLESS STEEL

STD STANDARD

STL STEEL

STL JST STEEL JOIST

STOR STORAGE

STRUCT STRUCTURAL

S4S SURFACED FOUR SIDES

SUSP SUSPEND

SW SWITCH

SYMM SYMMETRICAL

T

TK BD TACKBOARD

TEL TELEPHONE

TV TELEVISION

TMPD TEMPERED

TEMP TEMPORARY

TER TERRAZZO

THK THICKNESS

TPD TOILET PAPER DISPENSER

T&G TONGUE AND GROOVE

TOS TOP OF SLAB, STEEL

T TREAD

TYP TYPICAL

U

UC UNDERCUT

UNFIN UNFINISH

UNO UNLESS NOTED OTHERWISE

V

VAC VACUUM

VR VAPOR RETARDER

VNR VENEER

VP VENEER PLASTER

VIF VERIFY IN FIELD

VERT VERTICAL

VEST VESTIBULE

VCT VINYL COMPOSITION TILE

VWC VINYL WALL COVERING

W

W CAB WALL CABINETS

WC WALL COVERING, WATER CLOSET

WP WATERPROOFING, WEATHER

PROOF, WORKING POINT

WT WEIGHT

WWF WELDED WIRE FABRIC

W WEST

WF WIDE FLANGE

WDW WINDOW

W/ WITH

W/O WITHOUT

WD WOOD

WDP WOOD PANELING

13800 Veterans Way

Florida Department of Veterans Affairs

KEYED NOTE

WALL TYPE

X

X WINDOW TREATMENT TYPE

EQUIPMENT

INTERIOR FINISH TYPE

FURNITURE, FIXTURE, EQUIPMENT

CONTRACT LIMIT LINE

COLUMN CENTER LINE

NEW WALL

DEMOLITION

EXISTING WALL

NORTH

APPROVED FOR CONSTRUCTION

Project No: 675-23-105

Orlando, FL 32827

DESIGN TEAM

ABBREVIATIONS

OWNER

CODE REFERENCES

BUILDING CODE:

2018 INTERNATIONAL BUILDING CODE

2018 EXISTING BUILDING CODE

2018 INTERNATIONAL ENERGY CONSERVATION CODE

2018 INTERNATIONAL FIRE CODE

ACCESSIBILITY CODE & GUIDELINES:

ABAAS & BFDG

MECHANICAL CODE:

2018 INTERNATIONAL MECHANICAL CODE

PLUMBING CODE:

2018 INTERNATIONAL PLUMBING CODE

ELECTRICAL CODE:

2018 INTERNATIONAL ELECTRICAL CODE

PROJECT DESCRIPTION

FACILITY MAP

SYMBOL LEGEND

BUILDING INFORMATION

DESCRIPTION OF BUILDING: EXISTING BUILDING

PROJECT INCLUDES ARCHITECTURAL, STRUCTURAL,

MECHANICAL, PLUMBING, AND ELECTRICAL.

GENERAL NOTES

VICINITY MAP

INFECTION CONTROL MEASURES

SHEET INDEX

DESCRIPTIONSYMBOL

RENOVATE VARIOUS SPACES AT LAKE NONA 675-23-105

ORLANDO VA MEDICAL CENTER

Department of Veterans Affairs

Architect

MPE Engineers

1050 E. Southern Ave. Suite 5, Tempe, Arizona 85282

AESUS Design Group

1053 10th Ave, San Diego, CA 92101

San Diego, CA 92101

Davy Architecture

Orlando Gonzales (ogonzales@aesusdesign.com)

480-454-2861

Davyarchitecture.com

619-238-3811

Structural Engineers

NORTH

PROJECT AREA

BUILDING OCCUPANCY:

INSTITUTIONAL GROUP I-2 PER IBC 308.3

CLINIC/AMBULATORY CARE - BUISINESS "B"

OFFICES & LOCKERS - BUSINESS - "B"

ACCESSORY USE = STORAGE S-1

CONSTRUCTION TYPE:

CONSTRUCTION TYPE: IB (222)

FIRE RESISTANCE IN ACCORDANCE WITH IBC TABLES 601 & 602

FULLY SPRINKLERED

BUILDING AREA:

ACTUAL ALLOWABLE (IBC 506.2)

OVERALL EXISTING 4TH FLOOR 189,500 SF

4TH FLOOR RENOVATION AREA 8,272 SF

BUILDING HEIGHT:

ACTUAL ALLOWABLE (TABLE 504.3)

4TH FLOOR HEIGHT 20 FT

EXISTING BUILDING STORIES 5

MINIMUM NUMBER OF EXITS (TABLE 1006.3.2)

OCCUPANT LOAD PER STORY MIN EXITS PER STORY

1-500 2

EXIT ACCESS TRAVEL DISTANCE (TABLE 1017.2)

I-2 OCCUPANCY WITH SPRINKLERS = 200 FEET

DEAD END CORRIDORS (IBC 1020.4)

I-2 OCCUPANCY WITH SPRINKLERS = 20 FEET

PROJECT SITE

NFPA

NFPA 101 LIFE SAFETY CODE

NFPA NATIONAL FIRE CODES

NFPA 900 (OSHA)

Orlando VA Medical Center

A.

B.

C.

D.

E.

F.

ANY CHANGES MUST BE APPROVED BY COR BEFORE DOING ANY

ADDITIONAL WORK. WORK SCHEDULE TO BE PERFORMED DURING

REGULAR DAY SHIFT HOURS (8AM-4:30PM) ANY WORK OUTSIDE OF

REGULAR SCHEDULE REQUIRES APPROVAL FROM COR.

COORDINATE STAGING AREA WITH COR, AND FIND INTERIOR

COVERED STORAGE ON SITE FOR MATERIALS THAT MUST BE

PROTECTED FROM ELEMENTS - COORDINATE WITH COR.

PERFORM WORK IN ACCORDANCE WITH VHA DIRECTIVE 2004-012

SAFETY AND HEALTH DURING CONSTRUCTION ACTIVITIES AND VHA

DIRECTIVE 7701 OCCUPATIONAL SAFETY AND HEALTH (OSH) .

WORK PERFORMED FOR THIS PROJECT MAY INTERRUPT SERVICE TO

ADJACENT AREAS AT TIMES BUT WILL NOT INTERRUPT OVERALL

FACILITY OPERATION. SEE ELECTRICAL FOR POWER INTERRUPTION

AND OUTAGE REQUIREMENTS.

CONTRACTOR TO VERIFY ALL DETAILS AGAINST EXISTING

CONDITIONS PRIOR TO PURCHASE OF EQUIPMENT AND PRIOR TO

CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR BRINGING ANY

DISCREPANCIES IN PLANS AND EXISTING SITE CONDITIONS TO

IMMEDIATE ATTENTION OF CONTRACTING OFFICER

REPRESENTATIVE.

CONTRACTOR SHALL PERFORM ALL WORK AND PROVIDE ALL

MATERIALS IN ACCORDANCE WITH VA MASTER CONSTRUCTION

SPECIFICATIONS, WHICH CAN BE FOUND AT

HTTP://WWW.CFM.VA.GOV/TIL/. WHERE DISCREPANCIES ARE FOUND

THE MORE STRINGENT SHALL APPLY.

G. NOT ALL KEYNOTES ARE ON ALL SHEETS.

730 N. 52 nd

Street, Suite 105

Phoenix, AZ 85008

Office: (602) 443-0303 Ext. 101

Simply Structural

Mike Wilda (mwilda@simplystructural.com)

GI000 COVER SHEET

ARCHITECTURAL

GI002 ADA GRAPHICS

GI003 EXISTING SITE PLAN

GI004 OVERALL PLAN - BUILDING 1 & BUILDING 9 - 1ST FLOOR

GI005 OVERALL PLAN - BUILDING 1 - 4TH FLOOR

GI001

AE101 1ST FLOOR PLANS - PHARMACY

AE102 1ST FLOOR PLANS - COMPUTER TOMOGRAPHY

AE103 4TH FLOOR PLANS - MEDICAL MEDIA

AE104 4TH FLOOR PLANS - O.I.T.

AE105 1ST FLOOR PLANS - DOMICILIARY STORAGE

AE106 WAREHOUSE FLOOR PLANS - ADD ALT 1

AE201 INTERIOR ELEVATIONS

AE501 DETAILS

AE502 DETAILS

STRUCTURAL

S101 GSN

S201 PLANS

S301 TYPICAL AND FOUNDATION DETAILS

S302 FRAMING DETAILS

GENERAL

SYMBOLS AND ABBREVIATIONS

THE SCOPE OF WORK SHALL BE DEMOLISH, REDESIGN AND RENOVATION OF

VARIOUS SPACES LOCATED AT LAKE NONA VAMC. SPACES INCLUDE: PHARMACY,

MEDICAL MEDIA, DOM STORAGE, OIT OFFICE, AND WAREHOUSE SPACES.

THIS WORK SHALL INCLUDE BUT NOT BE LIMITED TO ARCHITECTURAL, STRUCTURAL,

MECHANICAL, PLUMBING, & ELECTRICAL.

AE601

DOOR SCHEDULE, NOTES, DETAILS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

GI000

COVER SHEET

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseDESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10

RENOVATE VARIOUS SPACES AT

LAKE NONA

13800 VETERANS WAY ORLANDO, FL 32827

675-23-105

VARIOUS

08/04/2023 AESUSRevisions: Date:

321 4 5 6

90% CONSTRUCTION

DOCUMENTS

AESUS

MECHANICAL/PLUMBING

M001 MECHANICAL SYMBOLS AND ABBREVIATIONS

M101 MECHANICAL 1ST FLOOR PLANS

M102 MECHANICAL 4TH FLOOR PLANS

P001 PLUMBING SYMBOLS AND ABBREVIATIONS

P101 PLUMBING PLANS

ELECTRICAL

ED-101 ELECTRICAL DEMOLITION PLANS

ED-102 ELECTRICAL DEMOLITION PLANS - WAREHOUSE

EL-101 ELECTRICAL LIGHTING PLANS

EL-102 ELECTRICAL LIGHTING PLANS - WAREHOUSE

E-001 SYMBOLS AND ABBREVIATIONS

EP-101 ELECTRICAL POWER PLANS OVERALL PLANS - LEVEL 1 & 4

EP-102 ELECTRICAL POWER PLANS

F101 FIRE PLANS

EP-103 ELECTRICAL POWER PLANS - WAREHOUSE

EP-701 ELECTRICAL PANEL SCHEDULES

M501 MECHANICAL DETAILS & CONTROL DIAGRAMS

EP-401 ELECTRICAL DETAILS

AE503 TYPICAL CEILING DETAILS

AE504 TYPICAL CEILING DETAILS

AE505 SUSPENDED ACOUSTIC TILE CEILING DETAILS

AE506 SUSPENDED GYPSUM BOARD CEILING DETAILS

AE507 SUSPENDED GYPSUM BOARD CEILING DETAILS

design

AESUS

1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861

Architecture, Engineering, and, Sustainable Design group

FEC

DOOR IDENTIFICATION

REFER TO DOOR

SCHEDULE

WINDOW IDENTIFICATION

REFER TO WINDOW

SCHEDULE

KEYNOTE

IDENTIFICATION

WALL TYPE, REFER

TO WALL TYPES

LEGEND

FINISH IDENTIFICATION

REFER TO FINISH

SCHEDULE

REVISION

REFERENCE

DIMENSION LINE TO

CENTERLINE

LEVEL IDENTIFICATION

HIDDEN, FUTURE, OR

EXISTING TO BE REMOVED

MATCHLINE

ADA CLEARANCE

PROPERTY LINE

INTERIOR ELEVATION

REFERENCE, TYP.- --

CLR

DIM

EQUIPMENT

IDENTIFICATION

GENERAL IDENTIFICATION TAGS

ROOM IDENTIFICATION TAGS

VIEW REFERENCE SYMBOLS

SHEET NUMBER

DETAIL NUMBER

SHEET NUMBER

FLOOR PLAN

REFERENCE

LOCATION SYMBOLS

DIMENSION TO ELEVATION

GRID BUBBLE AND LINE

DIMENSIONS

LINE STYLES

LEVEL NAME

x' - x"

AREA OF WORK

DIMENSION TO FACE

OF STUD U.O.N.

INDICATES CLEAR

DIMENSION REQUIRED

W

H D

CASEWORK TAG

CASEWORK IDENTIFICATION

CASEWORK DEPTH

(INCHES)

CASEWORK HEIGHT

(INCHES)

CASEWORK WIDTH

(INCHES)

COMMENT

NORTH ARROW

EXISTING GRID BUBBLE

AND LINE

SIM

DIM

TOTAL

OCCUPANT LOAD

ROOM

OCCUPANT LOAD

FACTOR

ROOM AREA

ROOM NUMBER

ROOM NAME

OCCUPANCY TYPE

WALL SECTION

NUMBER

SHEET NUMBER

INDICATES SIMILAR

CONDITION

SIM

BUILDING SECTION

NUMBER

SHEET NUMBER

INDICATES SIMILAR

CONDITION

BUILDING

ELEVATION NUMBER

SHEET NUMBER

ROOM AREA

ROOM NUMBER

ROOM NAME

100 SF

ROOM

ARCHITECTURAL PLAN LEGEND

EXISTING WALL TO REMAIN

PARTIAL HEIGHT WALL

NON RATED PARTITION

1 HOUR FIRE RATED WALL

2 HOUR FIRE RATED WALL

SMOKE WALL

DOOR AND FRAME ASSEMBLY,

REFERENCE DOOR SCHEDULE -/--

WINDOW AND FRAME ASSEMBLY,

REFERENCE DOOR SCHEDULE -/--

ARCHITECTURAL CEILING PLAN LEGEND

2 X 4 SUSPENDED ACOUSTICAL

CEILING SYSTEM

2 X 2 SUPPLY AIR REGISTER

2 X 2 RETURN AIR REGISTER

2 X 2 EXHAUST AIR REGISTER

LINEAR DIFFUSER

30" x 42" ACCESSIBLE

CLEAR SPACE

5' - 0" ACCESSIBLE CLEAR

TURNING SPACE

GYPSUM CEILING

PLASTER CEILING

PENDANT LIGHT FIXTURE,

PER SCHEDULE

RECESSED CAN LIGHT FIXTURE,

PER SCHEDULE

24" X 24" LIGHT FIXTURE,

PER SCHEDULE

24" X 48" LIGHT FIXTURE,

PER SCHEDULE

12" X 48" LIGHT FIXTURE,

PER SCHEDULE

SURFACE MOUNTED LIGHT

FIXTURE, PER SCHEDULE

ILLUMINATED EXIT SIGN, REFERENCE

ELECTRICAL DRAWINGS

S

SMOKE DETECTOR, REFERENCE

ELECTRICAL DRAWINGS

OS

OCCUPANCY SENSOR, REFERENCE

ELECTRICAL DRAWINGS

SYMBOL LEGEND

AP

SECURITY CAMARA, REFERENCE

ELECTRICAL DRAWINGS

ACCESS POINT, REFERENCE

ELECTRICAL DRAWINGS

SMOKE DETECTOR, REFERENCE

FIRE PROTECTION DRAWINGS

S

SPEAKER, REFERENCE

ELECTRICAL DRAWINGS

FIRE EXTINGUISHER CABINET

PER DETAIL:

2 X 2 SUSPENDED ACOUSTICAL

CEILING SYSTEM

CARD READER

CMU WALL

CR

DEMOLITION NOTES

A. REFER TO SHEET G-001 FOR ARCH DWG REFERENCE AND MATERIAL SYMBOLS AS WELL AS ABBREVIATIONS USED ON THIS SET OF

DRAWINGS.

B. THIS AREA OF WORK CONTAINS BUILDING INFRASTRUCTURE, WHICH IS CRITICAL TO THE ONGOING OPERATIONS OF THE HOSPITAL. ALL UTILITY WORK SHALL HAVE A PRE-CONSTRUCTION MEETING AND SCHEDULED PRIOR TO ANY DEMOLITION OR SHUT-DOWNS.

C. DEMOLITION OPERATIONS ARE TO PROCEED WITH NECESSARY PREPARATIONS AND PRECAUTIONS TAKEN TO PROTECT ITEMS AND FINISHES TO REMAIN. THE CONTRACTOR SHALL COORDINATE DEMOLITION OPERATIONS WITH THE VA AND REACH SPECIFIC

DEPARTMENTS PRIOR TO ANY DEMO WORK.

D. REMOVE AND DISPOSE ALL DEMOLISHED MATERIALS OFF SITE WHICH ARE NOT SCHEDULED TO REMAIN, BE RELOCATED, OR BECOME THE

PROPERTY OF THE OWNER.

E. ANY PIPE REMAINING AFTER DEMOLITION MUST BE IDENTIFIED AT ITS TERMINATION WITH A LABEL BY THE CONTRACTOR.

F. DO NOT PENETRATE THE FLOOR FLAB WITHOUT COORDINATING WITH STRUCTURAL REQUIREMENTS.

G. UNLESS SPECIFICALLY NOTED OTHERWISE, EXISTING FLOOR AND CEILING MATERIALS SHALL REMAIN IN PLACE. PROTECT FLOORS AND

CEILINGS FROM DAMAGE DURING DEMOLITION AND RENOVATION WORK.

H. EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND VISUAL FIELD SURVEYS. THE CONTRACTOR SHALL VERIFY

ACTUAL EXISTING CONDITIONS AND NOTIFY THE VA OF ANY DISCREPANCIES.

I. DEMO WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE UNNECESSARY INCONVENIENCE OR DANGER TO USERS OF THE PREMISES AND ADJACENT AREAS AND NOT INTERFERE WITH ITS OPERATION. ANY DEMO WORK TO BE PERFORMED MUST BE PLANNED IN

ADVANCE AND APPROVED BY THE OWNER.

J. ANY EQUIPMENT, MATERIALS AND SUPPLIES TEMPORARILY REMOVED FOR THE PURPOSE OF PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS AND CONDITIONS. ANY MATERIAL DAMAGED SHALL BE REPLACED WITH NEW MATERIALS OF LIKE AND QUANTITY.

K. REFER TO AND COORDINATE WITH MECHANICAL AND ELECTRICAL DWGS. FOR ADDITIONAL DEMOLITION INFORMATION.

L. ALL MATERIALS INDICATED TO BE REMOVED SHALL BE DISPOSED OF AND REMOVED FROM THE SITE. COORDINATE WITH THE COR, THE REMOVAL AND FINAL DISPOSAL LOCATION/DESTINATION(S) OF DEMOLITION. THE GC SHALL PROVIDE MONTHLY NEMA TRACKING

REPORTS.

M. ALL REMOVED MATERIALS AND EQUIPMENT WHICH IS SALVAGEABLE SHALL REMAIN THE PROPERTY OF THE OWNER. DELIVER SUCH SALVAGED MATERIALS AND EQUIPMENT ON THE PREMISES AS DIRECTED BY THE COR AND NEATLY STORE THEM AND PROTECT FROM DAMAGE. ALL OTHER MATERIAL AND EQUIPMENT SHALL BE REMOVED FROM THE PROJECT SITE AT THE CONTRACTOR'S EXPENSE, SEE

SPECIFICATIONS.

N. THE GOVERNMENT SHALL REMOVE THE FOLLOWING EXISTING ITEMS PRIOR TO ANY DEMO WORK. THE CONTRACTOR SHALL NOTIFY THE OWNER 72 HOURS IN ADVANCE OF ANY SCHEDULED DEMO WORK IN THE AREA OF THE ITEM TO ALLOW REMOVAL BY THE OWNER:

FURNITURE, MEDICAL AND OTHER EQUIP., STORAGE ITEMS AND PERSONAL BELONGINGS.

O. PATCH/REPAIR ALL ELEMENTS THAT ARE TO REMAIN AND ARE DAMAGED FROM THE DEMO WORK, BACK WITH CONSTRUCTION TO MATCH

EXISTING CONDITIONS.

P. IN WALLS TO BE REMOVED, STRIP ALL EXISTING ELECTRICAL WIRING TO NEAREST ACTIVE J-BOX & CONDUIT.

Q. INTERIM LIFE SAFETY MEASURES MAY APPLY. COORDINATE WITH HOSPITAL'S SAFETY OFFICER AND COR.

R. MATERIALS AND EQUIPMENT ACCRUING FROM WORK REMOVED AND FROM DEMOLITION OF BUILDING OR STRUCTURES, OR PARTS

THEREOF, SHALL BE DISPOSED PER SPECIFICATION SECTION 01 74 19.

S. REMOVE ALL EXISTING ABANDONED CONDUITS, WIRES, AND PIPES ASSOCIATES WITH THIS CONTRACT.

T. DIMENSIONS ON DEMO PLANS TO BE VERIFIED WITH CONDITIONS ON SITE BY G.C.

GENERAL NOTES

A. DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS SHALL HAVE PRECEDENCE. LARGER SCALE DRAWINGS SHALL HAVE PRECEDENCE OVER SMALLER SCALE DRAWINGS. THE GC SHALL NOTIFY THE VA OF ANY DISCREPANCIES OR CONFLICTS BEFORE PROCEEDING WITH

THAT PORTION OF THE WORK.

B. THE CONTRACTORS SHALL COORDINATE EQUIPMENT AND MATERIAL TRAFFIC AND STORAGE WITH COR.

C. ALL UTILITY WORK SHALL BE COORDINATED WITH MECHANICAL, PLUMBING, ELECTRICAL, AND FIRE PROTECTION.

D. ALL ASPECTS OF CONTRACTOR STAGING AND CONSTRUCTION PHASING SHALL BE APPROVED BY COR.

E. REFER AND ADHERE TO THE INFECTION PREVENTION MEASURE REQUIREMENTS IN SPECIFICATION SECTION 01 00 00 GENERAL REQUIREMENTS. TEMPORARY ICRA BARRIER SHALL BE PROVIDED AT ALL PATIENT RELATED AREAS AND COMPLETED PRIOR TO THE

START OF ANY WORK.

F. THE CONTRACTOR TO REFER TO THE VA COR AND ASBESTOS REMEDIATION STUDY FOR ACTIONS CONCERNING THE POSSIBLE PRESENCE OF ASBESTOS. IF ASBESTOS CONTAINING MATERIALS ARE SUSPECTED, STOP WORK IN THE AREA AND CONTACT COR.

G. THE GC IS RESPONSIBLE FOR REMOVING, STORING AND RELOCATING ALL MOVEABLE EQUIPMENT, FURNITURE, SHELVING AND RELATED

ACCESSORIES. COORDINATE W/ COR.

H. PRIOR TO THE START OF ANY WORK. IT IS RECOMMENDED THAT THE CONTRACTOR VISIT THE SITE TO FAMILIARIZE THEMSELVES WITH THE EXTENT AND NATURE OF WORK TO BE PERFORMED. EXISTING CONDITIONS MAY SLIGHTLY VARY FROM THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS, DIMENSIONS AND MATERIALS IN THE FIELD AND REPORT ANY

DISCREPANCIES TO THE COR.

I. THE CONTRACTOR SHALL VERIFY ALL ITEMS AND OR MATERIALS TO BE SALVAGED BY THE VA PRIOR TO THE START OF DEMOLITION

WORK.

J. ALL DIMENSIONS ARE TAKEN FROM EXISTING FACE OF WALLS.

K. ANY REMOVED SIGNAGE SHALL BE STORED FOR FUTURE USE. COORDINATE WITH COR.

L. ALL HOSPITAL ACCESS POINTS, AND ALL BUILDING EXITS, MUST REMAIN ACCESSIBLE, CLEAR AND UNOBSTRUCTED THROUGHOUT ALL PHASES OF DEMOLITION AND CONSTRUCTION. SHORT-TERM CLOSURE MAY BE ACCEPTABLE AS COORDINATED WITH COR.

M. THE CONTRACTOR SHALL PATCH AND REPAIR ALL FIREPROOFING DAMAGED DURING CONSTRUCTION PRIOR TO PROJECT CLOSEOUT. ALL

WORK SHALL MEET CODE AND SPECIFICATION REQUIREMENTS.

N. ALL COPPER MATERIALS REMOVED FROM THE BUILDING SHALL BE STORED AND TURNED OVER TO VA.

O. ALL EXISTING PENETRATIONS, WITHIN LIMIT OF WORK AND NEW CONSTRUCTION, ARE TO BE SEALED TO MATCH EXISTING CONSTRUCTION

AND RATING. ALL WORK SHALL MEET CODE AND SPECIFICATION REQUIREMENTS.

P. PROTECT ALL EXISTING CONDITIONS & EQUIPMENT DURING CONSTRUCTION.

Q. ALL EXPOSED CONCRETE FLOORS & WALLS SHALL BE SEALED. SEE SPECIFICATIONS.

R. THE CONTRACTOR SHALL COORDINATE ALL ROOF TOP WORK WITH COR. THE EXISTING ROOF WARRANTIES WITH BAKER AND SONS

ROOFING INC. SHALL BE MAINTAINED.

S. THE CONTRACTOR SHALL SCAN (GPR - GROUND PENETRATING RADAR) THE EXISTING CONCRETE SLAB PRIOR TO SAW CUTTING ANY NEW

OPENING.

A

ABV ABOVE

ACOUS ACOUSTICAL

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADJ ADJUSTABLE

AFF ABOVE FINISH FLOOR

ALT ALTERNATE

ALUM ALUMINUM

APPROX APPROXIMATE

ARCH ARCHITECT

B

B.O. BOTTOM OF

BALC BALCONY

BD BOARD

BET BETWEEN

BLDG BUILDNG

BLKG BLOCKING

BLW BELOW

BM BEAM

BOT BOTTOM

BRKT BRACKET

BULKHD BULKHEAD

BUR BUILT UP ROOF

C

C.G. CORNER GUARD

CAB CABINET

CALK CAULKING

CEM CEMENT

CER CERAMIC

CJ CONTROL JOINT

CLG CEILING

CLOS CLOSET

CLR CLEAR

CO CASED OPENING

COL COLUMN

CONC CONCRETE

CONT CONTINUOUS

CPT CARPET

CR CARD READER

CT CERAMIC TILE

CTR CENTER

D

DBL DOUBLE

DET DETAIL

DIA DIAMETER

DIM DIMENSION

DN DOWN

DR DOOR

DS DOWN SPOUT

DW DISHWASHER

DWG DRAWING

E

E EAST

EA EACH

EIFS EXTERIOR INSULATION &

FINISH SYSTEM

ELEC ELECTRIC

ELEV ELEVATION

EMER EMERGENCY

ENCL ENCLOSURE

EOS EDGE OF SLAB

EQ EQUAL

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EW EACH WAY

EXP. JT. EXPANSION JOINT

EXST EXISTING

F

F.O. FACE OF

FA FIRE ALARM

FAP FIRE ANNUNCIATOR

PANEL

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER

PANEL

FG FINISH GROUP

FH FIRE HYDRANT

FHC FIRE HOSE CABINET

FIN FINISH

FLR FLOOR

FLUOR FLOURESCENT

FT FOOT OR FEET

FUR FURRING

G

GAL GALLON

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACTOR

GL GLASS

GND GROUND

GWB GYPSUM BOARD

GYP GYPSUM

H

H.W.H. HOT WATER HEATER

HDWD HARDWOOD

HDWR HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HOUR

HT HEIGHT

I

ID INNER DIAMETER

INCAN INCANDESCENT

INSUL INSULATION

INT INTERIOR

J

JAN JANITOR

JST JOIST

JT JOINT

L

LAM LAMINATE

LAV LAVATORY

LB(S) POUNDS

LDG LANDING

LT LIGHT

M

MAX MAXIMUM

MECH MECHANICAL

MEMB MEMBRANE

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MTD MOUNTED

MTL METAL

N

N NORTH

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

O.P. OVERFLOW PIPE

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OFF OFFICE

OH OPPOSITE HAND

OPG OPENING

OPP OPPOSITE

P

PART PARTITION

PERM PERIMETER

PG PAINT GRADE

PIV PERSONAL IDENTITY

VERIFICATION

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLYWD PLYWOOD

PR PAIR

PT PAINT

PTD PAINTED

R

R RISER

RAD RADIUS

RCP REFLECTED CEILING

PLAN

RD ROOF DRAIN

RE REFER

REF REFRIGERATOR

REINF REINFORCED

REQD REQUIRED

RESIL RESILIENT

RM ROOM

S

RO ROUGH OPENING

RTU ROOF TOP UNIT (MECH)

S SOUTH

SAFB SOUND ATTENUATION

FIBER BATT

SC SCUPPER

SCHED SCHEDULE

SEAL SEALANT

SECT SECTION

SF SQUARE FOOT

SHT SHEET

SIM SIMILAR

SPEC SPECIFICATION

SQ SQURE

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STOR STORAGE

STRUCT STRUCTURAL

SUSP SUPSPENDED

SYM SYMMMETRICAL

T

T TREAD

T&G TONGUE & GROOVE

TEL TELEPHONE

TER TERRAZZO

THK THICK

THR THRESHOLD

TO TOP OF

TYP TYPICAL

U

UC UNDERCUT

UNFIN UNFINISHED

UNO ULNESS NOTED

OTHERWISE

UON UNLESS OTHERWISE

NOTED

UTIL UTILITY

V

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VIF VERIFY IN FIELD

VTR VENT TERMINATION PIPE

VWC VINYL WALL COVERING

W

W WEST

W/ WITH

W/O WITHOUT

WC WATERCLOSET

WD WOOD

WIN WINDOW

WP WATERPROOF

WS WETSTACK

WSCT WAINSCOT

WT WEIGHT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

GENERAL NOTESSYMBOL LEGEND CONT.SYMBOL LEGENDABBREVIATIONS

C

U s e rs \h h o rt o n

\D o c u m e n ts

\A R

C H

-V

A L N

V

S H h o rt o n

H S

M .r v t

/2 /2

:1

:5

P

M

GI001

SYMBOLS AND ABBREVIATIONS RENOVATE VARIOUS SPACES AT

LAKE NONA

13800 Veterans Way, Orlando FL 32827

675-23-105

STANDARD APPROVING TEAM

09/28/2023 MR HH

100% CONSTRUCTION

DOCUMENTS

Revisions: Date:

design

AESUS

1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861

Architecture, Engineering, ADA RAMP SECTION VIEW

RAIN-LIP SLAB DEPRESSION

TAP-CONS OR APPROPRIATE

FASTENERS FOR EXISTING

MATERIAL

METAL RAMP 1/12"

MAX. SLOPE

ACCESSIBILITY SIGN - MUST BE

VISIBLY PLACED OUTSIDE THE UNIT

DOOR HARDWARE

11B-404.2.7

(A) HINGED DOOR

(B) SLIDING DOOR(C) FOLDING DOOR

GENERAL NOTES:

1. DETAILS INCLUDED ON THIS SHEET ARE NOT PROJECT SPECIFIC. DETAILS ARE

GENERAL AND MAY NOT APPLY TO THIS DRAWING PACKAGE. THESE DETAILS ARE

SUPPLEMENTAL TO WORK INDICATED ON PLAN AND DRAWINGS.

2. PROVIDE BACKING PLATE PER DETAILS. FOR ALL HANDRAIL BRACKETS, GRAB BARS,

BENCHES, AND ALL OTHER WALL MOUNTED ITEMS WHERE DETAILED OR CALLED

FOR.

3. DOORS SHALL PROVIDE A CLEAR WIDTH OF 32" MINIMUM. CLEAR OPENINGS OF

DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF

THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES (11B-404.2.3).

4. HARDWARE: OPERABLE FROM INSIDE WITHOUT USE OF KEY OR SPECIAL

KNOWLEDGE OR EFFORT. OPERABLE BY SINGLE EFFORT LEVER-TYPE DEVICE (NOT

REQUIRING GRASPING). MOUNTED 34" TO 44" ABOVE FINISH FLOOR.

5. THRESHOLDS, IF ANY, SHALL BE 1/2" HIGH MAXIMUM BEVELED. (11B-404.2.5).

6. DOOR HARDWARE CAN BE OPERATED WITH A CLOSED FIST OR A LOOSE GRIP TO

ACCOMMODATE GREAT RANGE OF USERS.

7. DOORS SURFACE WITHIN 10" FROM FINISH FLOOR OR GROUND VERTICALLY

MEASURED SHALL HAVE A SMOOTH SURFACE ON THE PUSH SIDE EXTENDING THE

FULL WIDTH OF THE DOOR. PARTS CREATING HORIZONTAL OR VERTICAL JOINTS IN

THESE SURFACES SHALL BE WITHIN 1/16" OF THE SAME PLANE AS THE OTHER.

CAVITIES CREATED BY ADDED KICK PLATE SHALL BE CAPPED (11B-404.2.10).

8. MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED THE FOLLOWING PER

THE REQUIREMENTS OF THE CALIFORNIA BUILDING CODE, TITLE 24, 1008.1.3 AND

11B-404.2.9.

A. INTERIOR DOORS - 5 POUNDS

B. EXTERIOR DOORS - 5 POUNDS

C. FIRE DOORS - 15 POUNDS

OPENING WIDTH

32" MIN

M

IN

D

O O

R H

E

IG

H T

F

IN

IS

H

F L O

O R

A B

O V

E

F

IN

IS

H

F L O

O R

A B

O V

E

U P

T O

-1

/2

11B-404.2.2. AT LEAST ONE OF THE ACTIVE LEAVES OF DOORWAYS WITH

TWO LEAVES SHALL COMPLY WITH 11B-404.2.3. CLEAR WIDTH AND

11B-404.2.4. MANEUVERING CLEARANCES.

11B-404.2.3. CLEAR WIDTH. DOOR OPENINGS SHALL PROVIDE A CLEAR

WIDTH OF 32" (813 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH

SWINGING DOOR SHALL BE MEASURED BETWEEN THE FACE OF THE

DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. OPENING

MORE THAN 24" (610 MM) DEEP SHALL PROVIDE A CLEAR OPENING OF 36"

(914 MM) MINIMUM. THERE SHALL BE NO PROJECTIONS INTO REQUIRED

CLEAR OPENING WIDTH LOWER THAN 34" (864 MM) ABOVE THE FINISH

FLOOR OR GROUND. PROJECTIONS INTO CLEAR OPENING WIDTH

BETWEEN 34" (864 MM) AND 80" (2032 MM) ABOVE THE FINISH FLOOR OR

GROUND SHALL NOT EXCEED 4" (102 MM).

32" MIN

32" MIN

32" MIN

PUSH SIDE

PULL SIDE

DOOR

18" MIN AT INTERIOR

DOOR

24" MIN AT EXTERIOR

A CLOSER & LATCH

12" MIN IF DOOR HAS BOTH

FOF

FOF

30"x48" CLR

M

IN

M

IN

56" MIN WALL-MOUNTED

59" MIN FLOOR-MOUNTED

48" MIN

FINISH

FLOOR EVEN

COMPRESSED

CARPET 1/4" MAX

BELOW THRESHOLD

/4

/4

/4

M A

X

/4

M A

X

WALKING PERPENDICULAR TO WALL

OVERHEAD OBSTRUCTION

CANE RANGE

LOBBY

ANY AMOUNT

M

IN

O R

B E

L O

W

W H

E N

M

IN

4" MAX

W H

E N

O R

B E

L O

W

SUB-SURFACE IMAGE

CENTERED ON SIGN

WOMEN'S MEN'S

1/4" THICK, 12" ∅ CIRCLE 1/4" THICK

12" EQUILATERAL TRIANGLE

BACKGROUND COLOR

SHALL CONTRAST W/

DOOR COLOR

SUB-SURFACE IMAGE

CENTERED ON SIGN

BACKGROUND COLOR

SHALL CONTRAST W/

DOOR COLOR

NOTES:

1. SYMBOLS ARE TO BE

CENTERED ON THE DOOR

AND ARE TO BE DISTINCTLY

DIFFERENT FROM THE

DOOR IN COLOR AND IN 70%

MIN CONTRAST.

2. ATTACH SIGNS USING

ADHESIVE AND THREE (3)

FLATHEAD CHROME,

TAMPER-RESISTANT WOOD

SCREWS, COUNTERSUNK.UNISEX

1/4" THICK, EQUILATERAL

TRIANGLE ON 1/4" THICK,

12" ∅ CIRCLE

T

O F

F

T O

F F

NOTES:

1. PROVIDE ACCESSIBLE ENTRY SIGNAGE AT ALL EXTERIOR ENTRY DOORS

2. PROVIDE ACCESSIBLE ROOM SIGNAGE AT ALL ACCESSIBLE ROOMS.

3. BRAILLE SHALL BE FLUSH LEFT OR CENTERED - PER APPLICABLE CODES

ROOM 101

INTERNATIONAL SYMBOL

OF ACCESSIBILITY, WHITE

SEE CBC FIG. 11B-703.7.2.3

BLUE BACKGROUND

PICTOGRAM ADJACENT

TO ROOM SIGN AT

MAIN ENTRY DOORS ONLY

ROOM NAME

AND NUMBER

+/- 5" - 9" +/- 13" - 10"

L E

T T

E R

IN

G

/8

H E

IG

H

T O

F1 3/4"1 3/4" EQ EQ

BRAILLE

CHARACTERS

/2

M

IN

M

IN

B

O T

O F

B R

A

IL

L E

M

IN

B

O T

O F

T O

P T

E X

T L

IN

E

CARD READER ON

FREE STANDING PEDESTAL

WHEN D = 10" OR LESS, H = 54"MAX

WHEN D = 11", H = 53.5" MAX

WHEN D = 11", H = 53.0" MAX

WHEN D = 11", H = 52.5" MAX

WHEN D = 11", H = 51.5" MAX

WHEN D = 11", H = 51.0" MAX

WHEN D = 11", H = 50.5" MAX

WHEN D = 11", H = 50.0" MAX

WHEN D = 11", H = 49.5" MAX

WHEN D = 11", H = 49.0" MAX

WHEN D = 11", H = 48.5" MAX

WHEN D = 11", H = 47.5" MAX

WHEN D = 11", H = 47.0" MAX

WHEN D = 11", H = 46.5" MAX

WHEN D = 11", H = 46.0" MAX

CORRESPONDING REACH

HEIGHTS FOR GIVEN DEPTHS

HIGH AND LOW

SIDE REACH LIMITS

MAXIMUM SIDE REACH

OVER OBSTRUCTION

HIGH FORWARD

REACH LIMIT

(D) ARM REACH RANGE LIMITS

SIDE ELEVATIONFRONT ELEVATION

X SHALL BE LESS THAN OR EQUAL

TO 25 INCHES. Z SHALL BE

GREATER THAN OR EQUAL TO X.

WHEN X IS LESS THAN 20 INCHES,

THEN Y SHALL BE 48 INCHES MAX

WHEN X IS 20 TO 25 INCHES, THEN Y

SHALL BE 44 INCHES MAXIMUM.

1. PROVIDE MOUNTING OF

ACCESSIBLE CONTROLS AND

OPERATING MECHANISMS PER CBC

1117B.6

2. INSTALL ACCESSIBLE ELECTRICAL

SWITCHES AND RECEPTACLE

OUTLETS PER CBC 1117B.6 ITEM 5

M A

X

LEVEL

ACCESSIBLE

AREA

LOCATED ON FREE-

STANDING PEDESTALS

REACH

DEPTH

10" MAX

M A

X

M A

X

30" MIN

MAX

10"

M

IN

"4

M A

X

MAX

10" 30" MIN

M A

X

M

IN

48" MIN

48" MIN

Y

Z

X

MAXIMUM FORWARD REACH

OVER AN OBSTRUCTION

M

IN

M A

X

ACCESSIBLE CONTROLS

AND OPERATING SYSTEMS

X

Z

M

IN

FRONT APPROACH

SIDE APPROACH

M

IN

10" MAX

M A

XR

E

A C

H H

E

IG

H T

H

M A

X

D

REACH

24" MAX

M A

X

M A

X

30" MIN

MAX

>10"- 24"

(D) CLEAR FLOOR SPACEMANEUVERING CLEARANCE FOR ALCOVES

(C) SPACE REQUIRED FOR WHEELCHAIR SEATING

PERPENDICULAR APPROACHPARALLEL APPROACH

NOTE : IF X > 24 INCHES, THEN

AN ADDITIONAL MANEUVERING

CLEARANCE OF 6 INCHES SHALL

BE PROVIDED AS SHOWN.

NOTE : IF X > 15 INCHES, THAN

AN ADDITIONAL MANEUVERING

CLEARANCE OF 12 INCHES

SHALL BE PROVIDED AS SHOWN.

REAR ACCESS

FRONT ACCESS

S

ID

E A

C C

E S

S A

IS

L E

M

IN

33" MIN

M

IN

33" MIN

30" 6"

X

M O

R E

O

R

X

48" 12"

48" MIN

M

IN

10"

30" MIN

M

IN

48" MIN

M

IN

36" MIN 60" MIN

33" MIN 33" MIN

TWO SPACES

36" MIN

SINGLE SPACE

M

IN

FRONT ACCESS

REAR ACCESS

D O

O R

F R

A M

E W

H E

N D

IM

A

B V

D O

O R

H E

A D

I S

ALIGN TOP OF

PLATE OR DEVICE

HIGHEST OPERABLE PARTS OF:

SWITCHES, CONTROLS

THERMOSTATS, INTERCOM &

FIRE ALARM MANUAL STATION

(B) BULLETIN

BOARD

(A) COAT

HOOK

(C) EMERGENCY

SIGNAGE

(D) BROCHURE

HOLDER

(F) AUDIBLE AND

VISUAL FIRE

ALARM

(E) CLOCK OR

CLOCK

OUTLET

(G) FIRE

EXTINGUISHER

CABINET

(J) AUTO DOOR

OPENER

(H) CARD

READER

(K) OPERATING

SYSTEMS/SWITCHES

EMERGENCY SIGN,

LIVE LOAD SIGN OR

OCCUPANT LOAD SIGN

(S)

COAT HOOK

DOOR MOUNT

(R)

ELECTRICAL

PANEL BOARD

(U)

EXIT SIGNAGE

WALL MOUNT

S

ID

E W

H E

N D

IM

A

B V

D O

O R

H E

A D

EXIT

EXIT

(A) MIRROR (B) RECESSED

WASTER

DISPENSER

(C) TOILET

SEAT COVER

DISPENSER

(D) SOAP

DISPENSER

(E) TOILET

PAPER

DISPENSER

(F) GRAB BARS & WATER

CLOSET

(G) URINAL

FF

NOTES: 1. FLUSH

VALVE TO BE LOCATED

TO THE WIDE SIDE OF

COMPARTMENT

M A

X

M

IN

M

IN

M A

X

6" MAX

25" MAX

8" MIN

11" MIN

M

IN

DASHED LINE

INDICATES CLEAR

SPACE

M A

X

M A

X

12" MAX 42" MIN

54" MIN

24" MIN

T O

O U

T L E

T

M

IN

7" - 9" 36" MAX

17" - 18"

6" MAX 36" MIN

12" MIN

24" MIN

M

IN

R E

C O

M M

E N

D E

D

R E

C O

M M

E N

D E

D

FF

F R

O N

T R

E A

C H

S

ID

E R

E A

C H

H A

N D

L E

T

.O

M

A X

M

IN

FF

A T

H A

N D

L E

EQ EQ

A L

IG

N

W

IT

H T

O P

O F

A D

J F

R A

M E

O N

S T

R

IK

E

L O

C A

T E

A B

V

HEIGHT OF

LETTERING TO BE 5/8"

MIN TO 2" MAX

LETTERS RAISED 1/32"

NOTES:

1. LETTERS, BRAILLE CHARACTERS & PICTOGRAM SYMBOL

TO BE RAISED .025" to .037" ABOVE THEIR BACKGROUND.

2. UPPER CASE CHARACTERS TO BE SANS SERIF, 5/8" MIN

TO 2" MAX HEIGHT.

3. WIDTH OF UPPER CASE "O" IS 60% MIN AND 110% MAX

OF THE HEIGHT OF THE UPPERCASE "I".

4. STROKE WIDTH TO HEIGHT RATIO TO BE BETWEEN 15%

OF CHARACTER HEIGHT.

5. CHARACTERS & SYMBOLS SHALL CONTRAST WITH

6. PICTOGRAM ACCOMPANIED BY EQUIVALENT VERBAL

DESCRIPTION DIRECTLY BELOW.

7. PICTOGRAM IDENTIFICATION SIGN TO MATCH DOOR

SIGN.

8. SIGN TO BE A MINIMUM OF 6" x 6".

9. SIGNS CONTAINING TACTILE CHARACTERS SHALL BE

LOCATED SO THAT A CLEAR FLOOR SPACE OF 18" X 18",

CENTERED ON THE TACTILE CHARACTERS, IS PROVIDED

BEYOND THE ARC OF ANY DOOR SWING.

10. BRAILLE CHARACTERS TO BE CONTRACTED GRADE II,

3/8" TO 1/2" MAXIMUM BELOW TACTILE.

11. TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED

48" MINIMUM ABOVE THE FINISH FLOOR GROUND

SURFACE, MEASURED FROM THE BASELINE OF THE

LOWEST BRAILLE CELLS AND 60 INCHES MAXIMUM

ABOVE THE FINISH FLOOR OR GROUND SURFACE

MEASURED FROM THE BASELINE OF THE HIGHEST LINE

OF RAISED CHARACTERS.

DOOR SIGN

PER DETAIL:

MAX

24"

SPACE

CLEAR FLOOR

4" - 12"

EQ EQ EQ EQ

A

F F

DOOR SIGN

PER DETAIL:

FF

EQUIPMENT, PANEL

BOARD, CABINET OR

SIMILAR FEATURECORNER

GUARD

TYP

CHAIR RAIL

UON

OUTLET OR

SIMILAR

OPEN

CEILING PER

PLAN

CORNER GUARD AT

END WALL

OPEN

BARN DOORS FULLY

OPEN. MAINTAIN

GUARD RAIL GAP

FROM DOOR OF 1" TYP

U O

N

PROVIDE RESILIENT CORNER GUARDS AT

CORRIDORS AND ADMINISTRATIVE AREAS.

PROVIDE STAINLESS STEEL CORNER

GUARDS IN ALL CLINICAL AREAS

1" TYP

H A

N D

R A

IL

T

O

C H

A

IR

R A

IL

T

O

1" TYP

FF

M A

X

BABY

CHANGING

STATION

M

IN

INSULATE ENTIRE

HOT WATER AND

DRAIN PIPE

1/2" = 1'-0"

DOOR REQUIREMENTS

1/2" = 1'-0"

DOOR CLEARANCE

1/2" = 1'-0"

ACCESSIBLE RESTROOM

6" = 1'-0"

ALLOWABLE THRESHOLD

1/4" = 1'-0"

PROTRUDING OBJECTS

1 1/2" = 1'-0"

RESTROOM SIGNAGE

3" = 1'-0"

DOOR SIGNAGE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

C U s e rs \h h o rt o n

\D o c u m e n ts

\A R

C H

-V

A L N

V

S H h o rt o n

H S

M .r v t

/2 /2

:1

:5

P

M

GI002

ACCESSIBILITY DETAILS RENOVATE VARIOUS SPACES AT

LAKE NONA

13800 Veterans Way, Orlando FL 32827

675-23-105

STANDARD APPROVING TEAM

09/28/2023 MR HH

100% CONSTRUCTION

DOCUMENTS

1/4" = 1'-0"

SPACE AND REACH RANGE

1/4" = 1'-0"

WHEELCHAIR CLEARANCE

1/4" = 1'-0"

STANDARD MOUNTING HEIGHTS

Revisions: Date:

ADMIN. REVIEW 12/07/2019

design

AESUS

1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861

Architecture, Engineering, "Q

R O

A D

LAUREATE BLVD.

E

E

107326.A01

+0

+0

+0

+0

+8 5.

10+

11+

12+

13+00

14+00

15+00

16+

+0

+0

+0

+0

+0

40+ 32.12

31+

32+00

33+00

34+00

35+00

36+

37+

38+00

39+00

40+

10+

11+

12+

+0

27+ 38.

+0

+0

23+

24+

25+

26+

27+

11+00

12+00

PC

: 12+

21.00

PCC: 13+19.16

PCC: 14+79.56

PT

+6 4.

PC

+1 7.

P T:

.9

P C 2+ 2.

PRC

: 23

+56 .66

P T:

.9

P C 6+ 7.

PC

C : 31+

06.96

PT:

+1 4 .2

PC:

+1 5.9

PT: 39+

68.86

L1

L2

L3

L4

L5

L6

L7

PC

12+

63.17

PCC: 16+09.14 PT

+5 8.

PC: 18+70.73

PRC: 20+72.27

PT:

+13 .23

L8

L9

L1

PI : 10+50.00

L1

L1

C7

C

C1

C

C

C4

C

C

C

C10

C11

C12

C13

TC

4.

.2

RO

PE

C

OU

RS

E RO

PE

C

OU

RS

E

25'

UTIL

ITIES

, TR

AIL,

AND

LA

NDS

CAP

E E

ASE

MEN

T

25' UTILITIES, TRAIL,

AND LANDSCAPE EASEMENT

U

TI

LI

TI

E S

AN

D

LA

N D S C

AP

E

EA

S E M E N T

PEDESTRIAN

TR

AIL

EASEM

EN

T

25' PEDESTRIAN

TRAIL EASEMENT

LAU

REA

TE

BLV

D.

A8

NAVE

SECR ETAR Y

BL ES SED

SACR AMEN T

CH

AP EL

SAC RIS

T Y

TOI LE T

TOI LET

CO M M

EL E C

COR RI DO R

CH APLA I N

DR INK IN

G

FOU NT A I N

N O

P A R K

IN

G

N O

P A R K

IN

G

N O

P A R K

IN

G

N O

P A R K

IN

G

MERGE

ONLY

ONLY

ONLY

ONLY ONLY

ONLY

ONLY

ONLY

ONLY

3.

A1

1 AS0

1a

S

TA

IR

S

TA

IR

ADMIN

IST RA TIO

N

P A

TIE

N T

A C

T

IV

IT

Y A

R E A

O U T D O

O R R

E

CR

E

ATIO

N A

R

EA

M

AIN

E N

TRA

N C E

M E C

H

AN

IC

A L

S P

AC

E

L O

AD

IN

G

D O

C

K AIR

IN

TAKE

SHAFT

F

IR

E

P R O

TE

C

TIO

N

R

IS

E R

1B20

M ec han ic al

1B40

H

AC

1A70

O ff ic e

1A70

O ff ic e

1A70

O ff ic e

1A70

O ff ic e

1A71

O ff ic e

1A71

O ff ic e

1A71

O ff ic e

1A71

O ff ic e

1A80

St af f

T l t

1B30

R es id en t

T l t

1A80

O ff ic e

1A80

O ff ic e

1A80

O ff ic e

1A71

O ff ic e

1AC

b

L ou ng e

1A60

O ff ic e

1A60

O ff ic e

1A60

O ff ic e

1A70

O ff ic e

1A60

O ff ic e

1A60

O ff ic e

1A60

V olu nte e r s

1A40

Pa tie nt

S to r

1A10

C on fe re nc e

1A20

Pu bl ic

T l t

1A50

St af f

T l t

1AC

a

R ec e pt io n

1A40

Q uie t

R oo m

1A C

V est ib u le

1B10

Fi tn es s

R oo m

1A10

R ec r e at io n/ M u lti

P ur po se

1B

3a

Kitc h en et te

1B10

M ul ti

P ur po se

R oo m

1B10

K itc he n

1B10

In si de

D in in g

Ar ea

1B50

M ed s

1B50

Exa m

Tre atm en t

1B20

G en era l

S to r

1B30

N ur se

1B C

W ai tin g

1B20

Soile d

Li nen

C ol le ct io n

1B20

N on

-F ood

S to r

1B20

Bu lk

F oo d

C ar ts

B1

02c

H

AC

1A40

C om m

1A40

Ele c

O utd oo r D in in g Are a

1A10

C ra ft

1B20 3A

E le ct ric a l

1A50

St af f

L ou ng e

1B40

ST

G

D

D

T ectonic Cop yright 2007

T ectonic Cop yright 2007

DN

BUIL

DIN

G

CLIN

IC

BUIL

DIN

G

HO

SPIT

AL

BUIL

DIN

G

PARKIN

G

E

AST

BUIL

DIN

G

PARKIN

G

W

EST

BUIL

DIN

G

W

AREHO

USE

BUILDING 04

CENTRAL

ENERGY PLANT

BUILDING 06

GATE HOUSE

MAIN ENTRY

BUILDING 08

GATE HOUSE

SERVICE ENTRY

BUIL

DIN

G

DO

M

IC

IL

LIA

RY

BUILDING 10

CHAPEL

BUILDING 11

COMMUNITY

LIVING CENTER

1. NO SITE WORK IS BEING PERFORMED. THIS SHEET IS FOR REFERENCE ONLY.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

KEY PLAN - 1ST FLOOR

LEGEND

GENERAL NOTES

NOT TO SCALE

MAIN HOSPITAL

BUILDING 1

PARKING -

EAST

PARKING -

WEST

PHARMACY

DOMICILIARY

BUILDING 9

MAIN ENTRY

COMPUTER TOMOGRAPHY

TOOL CRIB

WAREHOUSE - BUILDING 5

SHOPS

PATIENT STORAGE

C U s e rs \h h o rt o n

\D o c u m e n ts

\A R

C H

-V

A L N

V

S H h o rt o n

H S

M .r v t

/2 /2

:1

:0

P

M

GI003

EXISTING SITE PLAN RENOVATE VARIOUS SPACES AT

LAKE NONA

13800 Veterans Way, Orlando FL 32827

675-23-105

STANDARD APPROVING TEAM

09/28/2023 MR HH

100% CONSTRUCTION

DOCUMENTS

1" = 100'-0"1

EXISTING SITE PLAN

Revisions: Date:

design

AESUS

1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861

Architecture, Engineering, UP

DN

UP

UP

DN

DN

UP

UP UP

UPUP

UP

UP

UP

DN

UP

DN DN

UP

UP

UP

UP

UPUP

1AS01a

STAIR

STAIR

ADMINISTRATION

PATIENT ACTIVITY AREA

OUTDOOR RECREATION AREA

MAIN ENTRANCE

MECHANICAL

SPACE

LOADING DOCK

AIR INTAKESHAFT

FIRE

PROTECTION

RISER

1B203

Mechanical

1B404

HAC

1A702

Office 1A704

Office 1A706

Office 1A708

Office 1A710

Office 1A712

Office 1A714

Office 1A716

Office

1A803 Staff

Tlt

1B302

Resident

Tlt

1A805

Office

1A804

Office

1A802

Office

1A711

Office

1AC01b

Lounge

1A601

Office

1A605

Office

1A606

Office

1A701

Office

1A603

Office

1A602

Office

1A604

Volunteers

1A401

Patient

Stor

1A101

Conference

1A201

Public

Tlt

1A502 Staff

Tlt

1AC02a

Reception

1A402

Quiet

Room

1AC03

Vestibule

1B101

Fitness

Room

1A105

Recreation/Multi

Purpose

1B103a

Kitchenette

1B103 Multi

Purpose

Room

1B102

Kitchen

1B105

Inside

Dining Area

1B502

Meds

1B501

Exam/

Treatment

1B206

General

Stor

1B301

Nurse

1BC03

Waiting

1B208

Soiled

Linen

Collection

1B202

Non-Food

Stor

1B204 Bulk

Food

Carts 1B102c

HAC

1A405 Comm

1A403 Elec

Outdoor Dining Area

1A103 Craft

1B203A

Electrical

1A501 Staff

Lounge

1B402

STG

D1

D2

AREA OF WORK

NOT IN SCOPE OF WORK

1. REFER TO SHEET GI001 FOR DEMOLITION GENERAL NOTES.

2. REFER TO SHEET GI001 FOR GENERAL NOTES.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

KEY PLAN - 1ST FLOOR

LEGEND

GENERAL NOTES

NOT TO SCALE

MAIN HOSPITAL

BUILDING 1

PARKING -

EAST

PARKING -

WEST

PHARMACY

DOMICILIARY

BUILDING 9

MAIN ENTRY

COMPUTER TOMOGRAPHY

TOOL CRIB

WAREHOUSE - BUILDING 5

SHOPS

PATIENT STORAGE

C U s e rs \h h o rt o n

\D o c u m e n ts

\A R

C H

-V

A L N

V

S H h o rt o n

H S

M .r v t

/2 /2

:1

:1

P

M

GI004

OVERALL PLAN - BUILDING 1 &

BUILDING 9 - 1ST FLOOR

RENOVATE VARIOUS SPACES AT

LAKE NONA

13800 Veterans Way, Orlando FL 32827

675-23-105

STANDARD APPROVING TEAM

09/28/2023 MR HH

100% CONSTRUCTION

DOCUMENTS

N

0 20' 40' 80'

1" = 40'-0"1

OVERALL PLAN - BUILDING 1 - 1ST

FLOOR

1" = 40'-0"2

OVERALL PLAN - BUILDING 9 - 1ST

FLOOR

Revisions: Date:

design

AESUS

1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861

Architecture, Engineering, DN

DN

DN

DN

UP

DN

UP

DN

DN DN

UPDNUP

UP

UP UP UP

UP

UP

DN

UP

UP

AREA OF WORK

NOT IN SCOPE OF WORK

1. REFER TO SHEET GI001 FOR DEMOLITION GENERAL NOTES.

2. REFER TO SHEET GI001 FOR GENERAL NOTES.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

LEGEND

GENERAL NOTES

NOT TO SCALE

MAIN HOSPITAL

BUILDING 1

PARKING -

EAST

PARKING -

WEST

KEY PLAN - 4TH FLOOR

OFFICE OF INFORMATION AND TECHNOLOGY (OIT)

MEDICAL MEDIA

C U s e rs \h h o rt o n

\D o c u m e n ts

\A R

C H

-V

A L N

V

S H h o rt o n

H S

M .r v t

/2 /2

:1

:3

P

M

GI005

OVERALL PLAN - BUILDING 1 - 4TH

FLOOR

RENOVATE VARIOUS SPACES AT

LAKE NONA

13800 Veterans Way, Orlando FL 32827

675-23-105

STANDARD APPROVING TEAM

09/28/2023 MR HH

100% CONSTRUCTION

DOCUMENTS

N

0 20' 40' 80'

1" = 40'-0"1

OVERALL PLAN - BUILDING 1 - 4TH

FLOOR

Revisions: Date:

design

AESUS

1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861

Architecture, Engineering, UPUPUPUP

J J

K K

K.7 K.7

K.6 K.6K.7K.6K.7K.6

REMOVE (E)

MOP SINK

REMOVE (E) FULL-

HEIGHT WALL.

REMOVE (E) FINISHES

THROUGHOUT.

REMOVE (E) FINISHES

7' - 2"

47 SF

HAC

1U501c

61 SF

HAC

1U302

REMOVE (E) WALLS

AND DOORS AND

DOOR FRAMES

REMOVE (E) ROLL-UP

GRILLE GATE

ASSEMBLY, TYP. OF (2)

REMOVE (E) GLAZING

ASSEMBLY AT

TRANSACTION COUNTER,

TYP. OF (4)

PHARMACY

1U501

PICK-UP

WINDOW

1U502

COMM

1U301

ELEC

1U303

PASSAGE

1UC03

SODA CLOSET

1V102

STAIR -

PHARMACY

1US01

O.P. SECURE

PRESCRIPTION

STORAGE

1U501b

DEMO (E) STUD WALLS

AND COUNTERTOPS,

TYP OF (6)

REMOVE (E)

WIRE SHELVING

REMOVE (E) SHELVING

AND SALVAGE FOR

OWNER USE

8' - 2"

1' - 9"

/8

CONSULT

1U501a

REMOVE (E) FLOORING

AND FINISHES AND

PREP FOR (N)

REMOVE (E) FLOORING

AND FINISHES AND

PREP FOR (N)

J J

K K

REMOVE (E) 2X2 ACT AND

GRID ASSEMBY

REMOVE (E) LIGHTING,

MECHANICAL, AND

EXHAUST FIXTURES, TYP.

PHARMACY

1U501

PICK-UP

WINDOW

1U502

COMM

1U301

ELEC

1U303

PASSAGE

1UC03

SODA CLOSET

1V102

STAIR -

PHARMACY

1US01

O.P. SECURE

PRESCRIPTION

STORAGE

1U501b

HAC

1U501c

HAC

1U302

REMOVE (E) EXHAUST

GRILLES, SEE MECHANICAL

J J

K K

K.7 K.7

K.6 K.6K.7K.6K.7K.6 ø 5' - 0"

61 SF

HAC

1U302

STAFF

RESTROOM

1U501c

INSTALL (N) FINISHES AND

FIXTURES THROUGHOUT.

INSTALL (N) 2-HR SMOKE FIRE RATED

WALL PARTITION TO MATCH EXISTING

WITH WATER RESISTANT GYP BD AND

CERAMIC TILE ON ONE SIDE. PATCH AND

REPAIR FINISHES TO MATCH EXISTING.

INSTALL (N) CLASS V

BALLISTIC WINDOW

ASSEMBLY WITH PASS-THRU

AND SPEAKER, TYP. OF (6)

INSTALL (N) TYPE X GYP BOARD

OVER 9-GAUGE EXPANDED

METAL SPOT WELDED EVERY

(6) INCHES TO EACH SIDE OF (E)

FRAMING FROM TOP OF ACT

CEILING TO BOTTOM OF

STRUCTURE, AT FULL LENGTH

OF PHARMACY, TYP

AE2011

ADA

STATION

ADA

STATION

PHARMACY

1U501

PICK-UP

WINDOW

1U502

COMM

1U301 ELEC

1U303

PASSAGE

1UC03

SODA CLOSET

1V102

STAIR -

PHARMACY

1US01

BREAK ROOM

1U501b

INSTALL (N) FLOOR DRAIN AND

SLOPE TILE FLOOR 2% MAX

/4 "1

A

B TYP

E

E

E

E

E

E

INSTALL (N) CMU WALL TO

STRUCTURE WITH GYP BOARD

BOTH SIDES, TYP. OF (6)

AE201

1U501b

1U501c

INSTALL (N) DOOR AND DOOR FRAME

INSTALL (N) PIV

CARD READER ON

PUSH SIDE OF DOOR

CONSULT

1U501a1

1' - 7"

16' - 2"

5' - 5" 12' - 4"

2' - 2" 21' - 0"

AE20116

1U501a.2

INSTALL (N) DOOR AND DOOR FRAME

AND INFILL OPENING TO MATCH

EXISTING, SEE DETAIL /4 AE501

J J

K K

INSTALL (N) HARD LID

CEILING ASSEMBLY, TYP.

INSTALL (N) LIGHTING,

MECHANICAL, AND

EXHAUST FIXTURES, TYP.

12' - 9"

2' - 11 1/4"

PHARMACY

1U501

PICK-UP

WINDOW

1U502

COMM

1U301

ELEC

1U303

PASSAGE

1UC03

SODA CLOSET

1V102

STAIR -

PHARMACY

1US01

BREAK ROOM

1U501b

STAFF

RESTROOM

1U501c

HAC

1U302INSTALL (N) 2x2

ACT AND GRID

ASSEMBLY, TYP

INSTALL (N) EXHAUST

DIFFUSERS, SEE

MECHANICAL, TYP

INSTALL (N) CEILING

MOUNTED CAMERA

1. REFER TO MECHANICAL, PLUMBING, ELECRICAL, AND STRUCTURAL DRAWINGS FOR ADDITIONAL

INFORMATION.

2. REFER TO SHEET GI001 FOR DEMOLITION GENERAL NOTES.

3. REFER TO SHEET GI001 FOR GENERAL NOTES.

4. REFER TO SHEET AE601 FOR FINISH, DOOR, AND WINDOW SCHEDULES, NOTES, AND DETAILS.

5. REFER TO SHEET GI002 FOR ACCESSIBILITY DETAILS AND MOUNTING HEIGHTS.

6. REFER TO SHEET AE501 FOR WALL TYPES.

7. REFER TO SHEETS AE503 - AE507 FOR CEILING DETAILS.

8. DIMENSIONS ARE TO FACE OF STUD UNLESS OTHERWISE NOTED.

9. LOCATE NEW DOORS FRAMES SO HINGED SIDE IS 3" INCHES FROM EDGE OF FRAME TO FACE OF

PERPENDICULAR STUD, UNLESS OTHERWISE NOTED.

10. CONTRACTOR TO REVIEW INTERIOR ELEVATIONS, AND CONFIRM WALL ASSEMBLY APPROPRIATE FOR

FINISHES AT WET AREAS, KITCHEN, RESTROOMS, AND JANITOR CLOSETS.

11. CONTRACTOR TO REVIEW ELEVATIONS FOR WINDOW VARIATIONS ON WINDOW SCHEDULE.

12. PROVIDE BACKING FOR ALL CASEWORK.

13. CASEWORK FINISHES TO BE HPDL-6 AND COUNTERTOP FINISHES TO BE SSM-7.

EXISTING WALL TO REMAIN

PARTIAL HEIGHT WALL

NON RATED PARTITION

1 HOUR FIRE RATED WALL

2 HOUR FIRE RATED WALL

SMOKE WALL

CMU WALL

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

KEY PLAN - 1ST FLOOR

LEGEND

GENERAL NOTES

NOT TO SCALE

MAIN HOSPITAL

BUILDING 1

PARKING -

EAST

PARKING -

WEST

PHARMACY

DOMICILIARY

BUILDING 9

MAIN ENTRY

COMPUTER TOMOGRAPHY

TOOL CRIB

WAREHOUSE - BUILDING 5

SHOPS

PATIENT STORAGE

C U s e rs \h h o rt o n

\D o c u m e n ts

\A R

C H

-V

A L N

V

S H h o rt o n

H S

M .r v t

/2 /2

:1

:5

P

M

AE101

1ST FLOOR PLANS - PHARMACY RENOVATE VARIOUS SPACES AT

LAKE NONA

13800 Veterans Way, Orlando FL 32827

675-23-105

STANDARD APPROVING TEAM

09/28/2023 MR HH

100% CONSTRUCTION

DOCUMENTS

N

0 4' 8' 16'

1/8" = 1'-0"1

1ST FLOOR PLAN - PHARMACY

DEMOLITION

1/8" = 1'-0"2

1ST FLOOR RCP - PHARMACY

DEMOLITION

1/8" = 1'-0"3

1ST FLOOR PLAN - PHARMACY

PROPOSED

1/8" = 1'-0"4

1ST FLOOR RCP - PHARMACY

PROPOSED

Revisions: Date:

design

AESUS

1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861

Architecture, Engineering, C

C

663 SF

C.T. (ED)

1E702

82 SF

CONTROL RM

1E602

REMOVE (E)

COUNTER AND

SUPPORTS

REMOVE (E) WALL.

PREP FOR (N) DOOR

AND FRAME ASSEMBLY

REMOVE (E) WALL.

PREP FOR (N) DOOR

AND FRAME ASSEMBLY

2' - 8"

REMOVE (E)

CASEWORK AND

COUNTERTOP

REMOVE (E) WALL

PROTECTION

CC

82 SF

CONTROL RM

1E602

663 SF

C.T. (ED)

1E702

DEMOLISH (E)

GYP BD SOFFIT

C

C

82 SF

CONTROL RM

1E602

663 SF

C.T. (ED)

1E702

INSTALL (N) SOLID

SURFACE COUNTER

AND SUPPORTS

INSTALL (N) 36X84 DOOR

AND FRAME ASSEMBLY

INSTALL (N) 72X84

DOOR AND FRAME

ASSEMBLY

4K802g

4K802f

ID OUTLETS/DATA/ETC

TO BE RELOCATED

AE201

AE2012

INSTALL (N) PLAM CASEWORK AND

SOLID SURFACE COUNTERTOP

INSTALL (N) PIV CARD READER

AUTOMATIC OPENER ON PUSH

SIDE OF DOOR

C

C

82 SF

CONTROL RM

1E602

663 SF

C.T. (ED)

1E702

INSTALL (N)

GYP BD SOFFIT

1. REFER TO MECHANICAL, PLUMBING, ELECRICAL, AND STRUCTURAL DRAWINGS FOR ADDITIONAL

INFORMATION.

2. REFER TO SHEET GI001 FOR DEMOLITION GENERAL NOTES.

3. REFER TO SHEET GI001 FOR GENERAL NOTES.

4. REFER TO SHEET AE601 FOR FINISH, DOOR, AND WINDOW SCHEDULES, NOTES, AND DETAILS.

5. REFER TO SHEET GI002 FOR ACCESSIBILITY DETAILS AND MOUNTING HEIGHTS.

6. REFER TO SHEET AE501 FOR WALL TYPES.

7. REFER TO SHEETS AE503 - AE507 FOR CEILING DETAILS.

8. DIMENSIONS ARE TO FACE OF STUD UNLESS OTHERWISE NOTED.

9. LOCATE NEW DOORS FRAMES SO HINGED SIDE IS 3" INCHES FROM EDGE OF FRAME TO FACE OF

PERPENDICULAR STUD, UNLESS OTHERWISE NOTED.

10. CONTRACTOR TO REVIEW INTERIOR ELEVATIONS, AND CONFIRM WALL ASSEMBLY APPROPRIATE FOR

FINISHES AT WET AREAS, KITCHEN, RESTROOMS, AND JANITOR CLOSETS.

11. CONTRACTOR TO REVIEW ELEVATIONS FOR WINDOW VARIATIONS ON WINDOW SCHEDULE.

12. PROVIDE BACKING FOR ALL CASEWORK.

13. CASEWORK FINISHES TO BE HPDL-6 AND COUNTERTOP FINISHES TO BE SSM-7.

EXISTING WALL TO REMAIN

PARTIAL HEIGHT WALL

NON RATED PARTITION

1 HOUR FIRE RATED WALL

2 HOUR FIRE RATED WALL

SMOKE WALL

CMU WALL

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

KEY PLAN - 1ST FLOOR

LEGEND

GENERAL NOTES

NOT TO SCALE

MAIN HOSPITAL

BUILDING 1

PARKING -

EAST

PARKING -

WEST

PHARMACY

DOMICILIARY

BUILDING 9

MAIN ENTRY

COMPUTER TOMOGRAPHY

TOOL CRIB

WAREHOUSE - BUILDING 5

SHOPS

PATIENT STORAGE

C U s e rs \h h o rt o n

\D o c u m e n ts

\A R

C H

-V

A L N

V

S H h o rt o n

H S

M .r v t

/2 /2

:1

:5

P

M

AE102

1ST FLOOR PLANS - COMPUTER

TOMOGRAPHY

RENOVATE VARIOUS SPACES AT

LAKE NONA

13800 Veterans Way, Orlando FL 32827

675-23-105

STANDARD APPROVING TEAM

09/28/2023 MR HH

100% CONSTRUCTION

DOCUMENTS

N

0 4' 8' 16'

1/8" = 1'-0"1

1ST FLOOR PLAN - COMPUTER

TOMOGRAPHY DEMOLITION

1/8" = 1'-0"2

1ST FLOOR RCP - COMPUTER

TOMOGRAPHY DEMOLITION

1/8" = 1'-0"3

1ST FLOOR PLAN - COMPUTER

TOMOGRAPHY PROPOSED

1/8" = 1'-0"4

1ST FLOOR RCP - COMPUTER

TOMOGRAPHY PROPOSED

Revisions: Date:

design

AESUS

1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861

Architecture, Engineering, D18

D18

DH

DHDH

D18

DH

AV EQUIPMENT

CHECK-OUT

4G208

REMOVE (E) BASE AND

FLOORING THROUGHOUT.

D18

D18

DH

DHDH

D18

DH

76 SF

AV EQUIPMENT

CHECK-OUT

4G208

REMOVE (E) 2X2

ACT AND GRID

ASSEMBY

REMOVE (E)

LIGHTING AND

MECHANICAL

FIXTURES, TYP.

REMOVE (E)

SUPPLY/RETURN

DIFFUSERS, SEE

MECHANICAL, TYP.

D18

D18

DH

DHDH

D18

DH

MEDICAL

MEDIAL

4G208

216 SF

MEDICAL MCS

' - 1

/8

21' - 6 1/8"

INSTALL (N) FULL-HEIGHT

WALL.

INSTALL (N) FLOOR

AND BASE AS

SCHEDULED, TYP.

INSTALL (N) 84x144 (4) PANEL

SLIDING GLASS DOOR AND

FRAME ASSEMBLY

5' - 6"

16' - 0 1/8"

G056

162"

24"

(E) ELECTRICAL

RACK TO REMAIN

C

D18

D18

DH

DHDH

D18

DH

MEDICAL MCS

MEDICAL

MEDIAL

4G208

CEILING OPEN

TO STRUCTURE

INSTALL (N) LIGHTING,

MECHANICAL, AND

FIXTURES, TYP.

INSTALL (N) 2x2 ACT

AND GRID ASSEMBLY

INSTALL (N)

SUPPLY/RETURN

DIFFUSERS, SEE

MECHANICAL, TYP.

1. REFER TO MECHANICAL, PLUMBING, ELECRICAL, AND STRUCTURAL DRAWINGS FOR ADDITIONAL

INFORMATION.

2. REFER TO SHEET GI001 FOR DEMOLITION GENERAL NOTES.

3. REFER TO SHEET GI001 FOR GENERAL NOTES.

4. REFER TO SHEET AE601 FOR FINISH, DOOR, AND WINDOW SCHEDULES, NOTES, AND DETAILS.

5. REFER TO SHEET GI002 FOR ACCESSIBILITY DETAILS AND MOUNTING HEIGHTS.

6. REFER TO SHEET AE501 FOR WALL TYPES.

7. REFER TO SHEETS AE503 - AE507 FOR CEILING DETAILS.

8. DIMENSIONS ARE TO FACE OF STUD UNLESS OTHERWISE NOTED.

9. LOCATE NEW DOORS FRAMES SO HINGED SIDE IS 3" INCHES FROM EDGE OF FRAME TO FACE OF

PERPENDICULAR STUD, UNLESS OTHERWISE NOTED.

10. CONTRACTOR TO REVIEW INTERIOR ELEVATIONS, AND CONFIRM WALL ASSEMBLY APPROPRIATE FOR

FINISHES AT WET AREAS, KITCHEN, RESTROOMS, AND JANITOR CLOSETS.

11. CONTRACTOR TO REVIEW ELEVATIONS FOR WINDOW VARIATIONS ON WINDOW SCHEDULE.

12. PROVIDE BACKING FOR ALL CASEWORK.

13. CASEWORK FINISHES TO BE HPDL-6 AND COUNTERTOP FINISHES TO BE SSM-7.

EXISTING WALL TO REMAIN

PARTIAL HEIGHT WALL

NON RATED PARTITION

1 HOUR FIRE RATED WALL

2 HOUR FIRE RATED WALL

SMOKE WALL

CMU WALL

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7…

This is the start of the file's text. The full file is on GovTribe.