This document appears to be a product specification sheet for an HVAC unit that is part of a federal contract opportunity. The specification sheet details the technical requirements for a 1200 CFM HVAC unit, including its cooling and heating capacities, electrical data, and physical dimensions.

The related federal contract opportunity is for the procurement of HVAC repair equipment for Joint Base Anacostia-Bolling in Washington D.C. The solicitation number is FA7060B3619, and it is being issued by the Department of the Air Force Headquarters District Washington. The contract will require the provision of HVAC units as detailed in Attachment 1 - Unit Specifications A and Attachment 2 - Unit Specifications B. No additional details are provided about the contract requirements, response dates, pricing terms, or set-asides.

View the file

Other files

File Type Posted
Attachment 2 - Unit Specifications B.pdf PDF
Sources Sought HVAC Repair.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DUC12B2CS5BBAM1 Tag:Qty: Model Code:

Code Description WeightField

DUC DU (Direct Drive-Vertical (std) or Multi-poise options, Generation: C) 0 Unit Type

12 12: 1200 CFM Basic Unit 160 Unit Size

B B: 3 Row Water (Std Capacity) 0 Primary Coil

2 2: 2R Secondary HW 0 Secondary Coil

C C: DU Minor Revision 0Minor Revision

S S: Standard Grade 0 Unit Grade

5 5: 120/1/60 - ECM-VE Motor 0 Motor Voltage/phase

B B: FAN CONTROL 24V 0 Controls Option

B B: Bottom Return (Or Horizontal Right Airflow) 0 Return Air Cabinet Option

A A: VERT ONLY D-pan, RH drain cnx, Galv, FG Insul'n 0 Drain Pan & Unit Insulation

M M: DU-Magic Aire 2-15-2024 0Tracking

Acc Acc: No Additional Optional Accessories 0 Accessories

Totals: 160

Configuration: Airflow (ACFM):4 Pipe 1315 0.250

Cool Fluid: Water Heat Fluid: Water

ESP:

Row-FPI-Tube

EDB

(F)

EWB

(F)

LDB

(F)

SLD

(Btu/Hr)

TLD

(Btu/Hr)

EWT

(F)GPM

LWB

(F)

WPD

(ft w.g.)

LWT

(F)

20240215

Tube Vel (fps)

FV

(fpm)

LDP

(F)

Watts:: 422

3-14-3/8" 80.00 67.00 36379 24194 57.9262.67 45.007.5 54.66 4.254

2-10-3/8" 55.00 51937 170.00 135.473.090.81 1.575

Cooling:

Heating:

3.553

2.487

422.5

587.7

54.86

Electrical Data Motor

Voltage

EH

Ph Freq HP Cap (kW)FLA

EH

FLA

Unit

MCA MOPD

UnitUnit

FLA

SCCR

Rating (kA)

Unit Marked

115 1 60 5.6 0 7 150.5 5.600 5 Yes

This unit is outside of the scope of AHRI Standard 430

Job Details

Prices Subject to change without notice 30 days after date on this quote.

Standard Magic Aire design and construction unless noted otherwise. Must include copy of this quote with order.2/15/2024 12:00:00 AM

200807 V.4.0.9.47 Reference Magic Aire Terms and Conditions.

4/23/24 9:59