This statement of work outlines requirements for inspection, testing, and monitoring of fire alarm systems at the Weber Basin Job Corps Center in Ogden, Utah. The contractor will be responsible for scheduled testing of fire alarm and mass notification systems in 32 buildings according to the tasks in Appendix A, including control panels, initiating devices, and notification appliances. The contractor must also provide continuous remote monitoring of fire alarm systems, notifying emergency services and the center of all alarm and trouble events. Inspections will be conducted annually and reports submitted to the center and contracting officer within 14 days. The contractor must utilize existing government utilities and sanitary facilities, and comply with all applicable safety, licensing, and conduct requirements while on site.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK
FOR
INSPECTION, TESTING AND
MONTIORING OF FIRE ALARM SYSTEMS
Weber Basin Job Corps Job Corps National Office
October 2023
TABLE OF CONTENTS
1. BACKGROUND 3
1.1. DESCRIPTION OF SERVICES 3
2. GOVERNMENT FURNISHED PROPERTY AND SERVICES 4
2.1. UTILITIES 4
2.2. SECURITY, FIRE AND MEDICAL SERVICES 4
3. GENERAL INFORMATION 4
3.1. DAMAGES TO GOVERNMENT BUILDINGS, EQUIPMENT OR VEGETATION 4
3.2. PERMITS, LICENSES AND CERTIFICATIONS (RESERVED) 4
3.3. HOURS OF OPERATION 4
3.4. RECOGNIZED HOLIDAYS 5
3.5. TRAFFIC LAWS 5
3.6. WEAPONS, FIREARMS, AND AMMUNITION 5
3.7. GOVERNMENT INTERFACE 5
3.8. SAFETY 5
3.9. WORKMANSHIP 6
3.10. TOOLS 6
3.11. TEST EQUIPMENT 6
3.12. SANITARY FACILITIES 6
3.13. PERSONNEL 6
4. LIST OF APPENDICES: 6
APPENDIX A - FIRE DETECTION AND ALARM SYSTEM IT TASKS 7
APPENDIX B - BUILDINGS REQUIRING FIRE ALARM SERVICE 8
APPENDIX C- LIST OF FIRE ALARM SYSTEM COMPONENTS______________________________9
STATEMENT OF WORK
1. BACKGROUND
Job Corps Centers is a residential program that serve students, and thus require life safety systems to be operational at all times to ensure safety of building occupants in the event of an emergency. This effort will provide all personnel, labor, equipment, tools, materials, instruments, meters, gauges, test equipment, transportation, supervision, and other items and services necessary to perform inspection and testing (IT) for the Fire Alarm Systems (FA) for the Weber Basin Job Corps located in Ogden, Utah. A table showing buildings requiring FA services is included in the attached sheet titled Appendix B.
1.1. DESCRIPTION OF SERVICES
1.1.1. LOCATION OF SERVICES
This project is located at the Weber Basin Job Corps campus located at 7400 S Cornia Drive, Ogden, UT.
1.1.2. TASK 1: SCHEDULED FIRE ALARM AND MASS NOTIFICATION SYSTEM TESTING
Buildings shown below have fire alarm systems that are in service. Drawings are attached that show the general building floorplans. The Contractor shall inspect each system and test it in accordance with the attached inspection schedule in Appendix A for Fire Alarm. Guidance on the tasks in Appendix A can be found in NFPA 70B, latest edition (Recommended Practice for Electrical Equipment Maintenance). Fire alarm system descriptions and locations are as follows:
Building # Building Name Panel Brand Model
1 Administration ADT Focus 200 2 Medical Services ADT Unimode 5 3 Custer Dorm ESL 1500 4 Bridger Dorm ESL 1500 5 Donner Dorm ADT Unimode 5 6 Male Laundry ESL 1500 7 Apache Dorm ADT Unimode 5 9 Female Laundry ADT Unimode 5 10 SSB Firelite Unimode SUD 11 Dining Hall/ Multi Purpose Potter PFC-6075 12 Gym ADT Unimode 5 13 Maintenance and Rec Firelite Unimode 10 15 Warehouse ESL 1500 16 Placement Firelite Unimode 5 UD 18 Paint Booth ADT Unimode 5 20 Trades ADT Unimode 5, ESL 1500 22 Paint Storage ADT Unimode 5 23 Maintenance Storage WHSE ADT Unimode 4519 30 Welding firelite MS-5UD 31 Education ADT Unimode 4-16 32 Culinary Arts ADT Unimode 5
1.1.3. TASK 2: FIRE MONITORING SERVICES
The Contractor shall provide continuous remote monitoring, 24 hours a day, 365 a year, of fire alarm system. Remote monitoring includes notification of emergency services for all alarm events, and notification to center via phone call to designated employee for all alarm and trouble event. Remote monitoring also includes monthly testing of system via remote signal command. The fire system has three reporting panels (main panel in administrative, student services panel and kitchen panel). The panels in administrative and student services building have two existing identified hard wired telephone lines, primary and secondary. The kitchen panel reports via cellular communication.
All other panels have two pair of identified hard wire telephone lines, primary and secondary. Contractor can utilize any of the existing equipment to monitor. The fire system includes 27 panels, 84 pull stations, 36 CO2 detectors, 52 heat detectors and 147 smoke detectors. See appendix C for a complete list of components.
1.1.4. SUBMITTALS/DELIVERABLES
The Contractor shall provide a separate inspection report for each system tested/inspected. Furnish reports in both hard format to the Center and electronic PDF format to the CO. Each report will include the following at a minimum:
• Job Corps Center Name
• Building Number and Name
• Item Description
• Location
• Inspection and Testing Performed in accordance with Appendices
• Indication of Pass/Fail
• Recommendations for repair in case of failed test
• Indication of System Normal, Warning or Caution Condition
• Date of Inspection
• Name of Inspector
• Signature of Inspector
Inspection reports are due within fourteen (14) days of the system inspection.
2. GOVERNMENT FURNISHED PROPERTY AND SERVICES
2.1 UTILITIES
Use of Government existing facilities will be permitted without metering and without payment of use charges, as long as facilities are cleaned and maintained in an acceptable condition. At Substantial Completion, restore these facilities to condition existing before initial use. The following are available for use by the Contractor: water, and electrical power services. The following are not available: telephone service. The Contractor is expected to provide whatever phone service he deems necessary for the duration of the project.
2.2 FIRE SERVICES
Municipal or volunteer fire protection services are not available at this site.
3. GENERAL INFORMATION
3.1 DAMAGES TO GOVERNMENT BUILDINGS, EQUIPMENT OR VEGETATION
Damages to Government buildings, equipment, or vegetation are addressed in FAR clause 52.237-2 – Protection of Government Buildings, Equipment, and Vegetation. The Contractor shall use reasonable care to avoid damaging existing buildings, equipment, and vegetation on the Government installation. If the Contractor's failure to use reasonable care causes damage to any of this property, the Contractor shall replace or repair the damage at no expense to the Government as the Contracting Officer directs. If the Contractor fails or refuses to make such repair or replacement, the Contractor shall be liable for the cost, which may be deducted from the contract price.
3.2 PERMITS, LICENSES AND CERTIFICATIONS (RESERVED)
3.3 HOURS OF OPERATION
The Contractor shall perform services during normal duty hours which are 0800-1630 Monday through Friday, excluding Federal Holidays. The Contractor may work weekends and holidays if approved in advance at his convenience. Work required outside of the standard work hours shall be coordinated with the Center.
3.4 RECOGNIZED HOLIDAYS
The Contractor is not required to provide service on federal holidays, except in emergency situations. The holidays are as follows:
New Year’s Day - 1 January Martin Luther King Day - 3rd Monday in January Washington’s Birthday - 3rd Monday in February Memorial Day - last Monday in May Juneteenth – 19 June Independence Day - 4 July Labor Day - 1st Monday in September Columbus Day - 2nd Monday in October Veteran’s Day - 11 November Thanksgiving Day - 4th Thursday in November Christmas Day - 25 December
If a holiday fall on Saturday, the preceding Friday will be the observed holiday. If the holiday falls on Sunday, the following Monday will be the observed holiday. If a holiday falls on a scheduled service day, the Contractor will be responsible for rescheduling services for the first day post the holiday observance.
3.5 TRAFFIC LAWS
The Contractor and its employees shall comply with all site traffic regulations.
3.6 WEAPONS, FIREARMS, AND AMMUNITION
Contractor employees are prohibited from possessing weapons, firearms, or ammunition, on themselves or within their Contractor-owned or privately owned vehicle while on the Center.
3.7 GOVERNMENT INTERFACE
Do not unduly interfere with regularly scheduled Government operational activities in the performance of contract requirements. In the event a Government supervisor so requests, temporarily cease work in the area and report the instructions, to include name of the Government person involved, to the CO immediately by the most expedient means. Notify the CO verbally of disputes with customers or other base Contractors and follow-up in writing.
3.8 SAFETY
The Contractor shall comply with all applicable Occupational Safety and Health Administration (OSHA) standards, federal, state, and local laws, regulations, and requirements regarding worker safety while performing work at the Center. Compliance shall also include following industry standards concerning worker safety and personal protective equipment. The Contractor shall comply with all safety and health requirements necessary for the protection of personnel, facilities and equipment.
3.8.1 WRITTEN SAFETY PROGRAM
Maintain a written Safety Program, as required by OSHA and make said plan available for review by the Government upon request by the Contracting Officer.
3.9 WORKMANSHIP
All work shall be performed by qualified, experienced Contractor personnel.
3.10 TOOLS
All tools shall be furnished by the Contractor.
3.11 TEST EQUIPMENT
The Contractor shall furnish his own test equipment.
3.12 SANITARY FACILITIES
The Contractor's workmen may use existing sanitary facilities, subject to the regulations governing their use by Government personnel in the buildings in which the work is being accomplished.
3.13 PERSONNEL
Contractor personnel shall present a neat appearance. Contractor personnel shall be easily recognizable while on the installation in conjunction with this contract.
The Government is authorized to restrict the employment under the contract of any Contractor employee or prospective Contractor employee, who is identified as a potential threat to the health, safety, security, general well- being, or operational mission of the installation and its population.
4. LIST OF APPENDIXES:
• APPENDIX A – FIRE DETECTION AND ALARM SYSTEM ITEM TASKS
• APPENDIX B – BUILDINGS REQUIRING FIRE ALARM SERVICE
• APPENDIX C— LIST OF FIRE SYSTEM COMPONENTS
APPENDIX A - FIRE DETECTION AND ALARM SYSTEM INSPECTION, TESTING
AND MONITORING TASKS
Frequency Component Tasks
Daily
1. Control Panels, Annunciator and fire detection Equipment
• 24-7 remote monitoring of all fire systems. Notification to emergency services for alarm events. Notification to center of trouble events.
Monthly
1. Control Panels and Annunciator Equipment (unmonitored only)
• Reserved
Annual
1. Control Panel and Annunciator Equipment (monitored)
1. Test to verify proper receipt of alarm, supervisory, and trouble signals (inputs) and operation of notification appliances and auxiliary functions (outputs).
2. Verify that all lamps and LEDs are illuminated.
3. Load test backup batteries (when provided).
2. Initiating Devices:
a. Manual Fire Alarm
Stations
1. Verify station is accessible (visual).
b. Radiant Energy Detectors (Optical Detectors)
• Reserved
. Gas Detectors • Reserved
3. Notification Appliances and
Voice Communication (telephone, speakers, horns, and strobe lights)
1. Test to verify operability.
4. Digital Alarm Transmitters and Receivers
1. Test to verify operability.
APPENDIX B - BUILDINGS REQUIRING FIRE ALARM TESTING, INSPECTION, AND MONITORING
Building 1 - 7 9-13 15-16 18 20 22-23 30-32 Services Fire Alarm System Annual Tasks x
Fire Alarm System 2-Year Tasks
Fire Alarm System 5-Year Tasks
Fire Suppression Annual Tasks
2-Year Tasks
5-Year Tasks
APPENDIX C – FIRE ALARM SYSTEM COMPONENTS
Building # Building Name Panel Brand Model
Panel Count
Horn Strobe Strobe Bell
Battery Count
Door Release
Duct Detector
CO
Detector
Heat Detector
Pull Station
Smoke Detector System type
1 Administration ADT Focus 200 1 4 0 0 2 0 0 0 0 2 4 Main Hub 2 Medical Services ADT Unimode 5 1 3 0 0 2 0 0 0 2 2 5 admin 3 Custer Dorm ESL 1500 1 2 0 0 5 12 2 8 0 3 15 admin 4 Bridger Dorm ESL 1500 1 2 0 0 5 12 2 8 n/a 4 13 admin 5 Donner Dorm ADT Unimode 5 1 3 0 0 5 12 2 8 0 4 16 admin 6 Male Laundry ESL 1500 1 1 0 0 2 0 0 0 1 2 1 admin 7 Apache Dorm ADT Unimode 5 1 2 0 0 5 12 2 8 0 5 14 admin 9 Female Laundry ADT Unimode 5 1 1 0 0 2 0 0 0 1 2 1 admin
10 SSB Firelite Unimode SUD 3 1 0 0 2 0 0 0 0 4 12 standalone
Dining Hall/ Multi
Purpose Potter PFC-6075 1 0 0 0 2 0 0 4 3 7 7 standalone 12 Gym ADT Unimode 5 1 2 0 0 2 0 0 0 1 4 7 admin 13 Maintenance and Rec Firelite Unimode 10 2 15 4 0 2 0 2 0 4 8 21 admin 15 Warehouse ESL 1500 1 0 0 2 2 0 0 0 5 3 7 admin 16 Placement Firelite Unimode 5 UD 1 0 0 1 2 0 0 0 1 3 7 admin 18 Paint Booth ADT Unimode 5 1 2 0 1 2 0 0 0 2 2 0 admin
20 Trades ADT Unimode 5, ESL
1500 4 4 0 0 8 0 0 0 22 11 1 admin 22 Paint Storage ADT Unimode 5 1 2 0 0 2 0 0 0 4 2 0 admin
Maintenance Storage
WHSE ADT Unimode 4519 1 0 0 1 2 0 0 0 0 2 2 admin 30 Welding firelite MS-5UD 1 1 2 0 2 0 0 0 2 4 1 admin 31 Education ADT Unimode 4-16 1 8 0 0 2 0 0 0 0 7 12 admin 32 Culinary Arts ADT Unimode 5 1 2 0 0 2 0 0 0 4 3 1 admin
TRAVEL
• All travel shall be included in the firm fixed priced CLINs. All travel shall be in accordance with Federal Travel Regulations. Current Federal Travel Regulations may be obtained from the following website:
https://www.gsa.gov. Any deemed necessary ODCs should be factored into the fully burdened FFP.
GOVERNMENT POINT OF CONTACT
• The government point of contact is Eric Todd Asper, Eric.Asper@usda.gov and Contracting Officer’s representative for this contract will be Susan Wilburn, susan.wilburn@usda.gov.
NON PERSONAL SERVICES STATEMENT
• The Contractor’s employees performing services as described shall be controlled, directed and supervised at all times by the Contractor. Contractor management will ensure that the employees properly comply with the performance work standards outlined in the Statement of Work. The work set forth may not be interpreted or implemented in any manner that results in the Contractor creating or modifying Federal Policy. The Government will control access to the facilities and will perform the inspections and acceptance of the completed work. The term Contractor as applied herein includes Sub Contractors and Tradespeople.
END OF WEBER BASIN JOB CORPS FACILITIES FIRE SAFETY INSPECTION,
TESTING, AND MONITORING STATEMENT OF WORK
mailto:Eric.Asper@usda.gov mailto:susan.wilburn@usda.gov
| 1. BACKGROUND 3 |
| 2. GOVERNMENT FURNISHED PROPERTY AND SERVICES 4 |
| 3. GENERAL INFORMATION 4 |
| 4. LIST OF APPENDICES: 6 APPENDIX A - FIRE DETECTION AND ALARM SYSTEM IT TASKS 7 APPENDIX B - BUILDINGS REQUIRING FIRE ALARM SERVICE 8 |
| APPENDIX C- LIST OF FIRE ALARM SYSTEM COMPONENTS______________________________9 |
| 1.1. DESCRIPTION OF SERVICES |
| 2.1 UTILITIES |
| Use of Government existing facilities will be permitted without metering and without payment of use charges, as long as facilities are cleaned and maintained in an acceptable condition. At Substantial Completion, restore these facilities to condition ... |
| 2.2 FIRE SERVICES |
| 3.1 DAMAGES TO GOVERNMENT BUILDINGS, EQUIPMENT OR VEGETATION |
| 3.4 RECOGNIZED HOLIDAYS |
| 3.5 TRAFFIC LAWS |
| 3.6 WEAPONS, FIREARMS, AND AMMUNITION |
| 3.7 GOVERNMENT INTERFACE |
| 3.8 SAFETY |
| 3.8.1 WRITTEN SAFETY PROGRAM |
| 3.9 WORKMANSHIP |
| 3.10 TOOLS |
| 3.11 TEST EQUIPMENT |
| 3.12 SANITARY FACILITIES |
| 3.13 PERSONNEL |