Attachment 1 - Statement of Work 2Jan24.pdf
PDF 150 KB Posted
- Attached to
- FY24 JPRA Generator Maintenance (MX) Federal contract opportunity
- Solicitation number
- FA462024QA104
About this file
This statement of work outlines the requirements for annual maintenance and biannual load testing of five generators located at a federal facility in Spokane, Washington. The contractor shall provide all labor, tools, equipment, and parts to perform preventative maintenance annually or as recommended by the manufacturer, including checking fluid levels, filters, belts, batteries, and running functional and load bank tests. Specific models and information for the five Cummins Onan generators are listed. Preventative maintenance and inspections shall be scheduled annually with the agency, while coolant shall be replaced every three years. The location of work will be on-site and hours are from 7:30 am to 4:00 pm Monday through Friday excluding federal holidays. The solicitation references this statement of work and seeks maintenance services for the generators in accordance with the requirements and specifications outlined.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 002.pdf | ||
| Amendment 001.pdf | ||
| Attachment 5 - Generator Name Plate Photos.pdf | ||
| 24QA104 COMBO.pdf | ||
| Attachment 2 - Statement of Work Appendix A.pdf | ||
| Attachment 3 - Pricing Schedule.xls | XLS spreadsheet | |
| Attachment 4 - WD 2015-5537 (Rev. 21) 25 Dec 23.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK
FOR
Annual Maintenance and Biannual Load Testing on Five (5) Generators at
JPRA White Bluff
11604 W NEWKIRK RD, SPOKANE, WA
2 January 2024
1.0 PURPOSE
The Service Contractor shall provide all tools, supplies, equipment, parts and labor necessary to perform full service maintenance and annual preventive maintenance on five Cummins Onan generators at 11604 W Newkirk Rd, Spokane, WA in accordance with manufacturer recommendations.
1.1 Generator service contractor shall provide the necessary labor, material, equipment and expertise to provide annual maintenance per manufactures recommendation for listed generators:
Product Description Product Model Serial # Cummins Onan Generator 8430GS-400KW Onan
DFED 5775894
A070008430 ST
Cummins Onan Generator 8919GS-750KW Onan
DQFAA
E110218918 ST
Cummins Onan Generator KTA50-G1 KTA-3067-G2 33110332 ST Cummins Onan Generator DMT-250 850135 ST Cummins Onan Generator DQDAB 1511339 QSL9-G7 F150841982
1.2 PREVENTIVE MAINTENANCE VISITS
Preventive maintenance shall be done in accordance with the manufacturer’s recommendation.
However, at minimum, maintenance shall be conducted annually, and scheduling will be pre-approved by the using agency. This visit shall provide a comprehensive inspection of the system to ensure that components are performing to defined technical specifications. All Generator are easily accessible can drive up to. The following list describes the service tasks that should be provided with this visit.
2.0 GENERAL REQUIREMENTS/ASSUMPTIONS
2.1 All services shall be performed on-site by qualified technicians who are certified to maintain specified generators. Pertinent Information:
Bldg 20: 750Kw Cummins 35 gallons oil Oil filter: LF14000NN 2ea Fuel filter: FF2203 1ea Coolant filter: WF2054 2ea Oil/water separator: FS1006 1ea
Bldg 15: 750Kw Cummins UNK oil capacity Oil filters: LF670 5ea Fuel filter: FF202 2ea Coolant filter: WF2071 4ea UNK coolant capacity
Bldg 12: 400Kw Cummins 23 Gallons oil Oil filter: LF9070 1ea (long life) Fuel filter: FS1040 1ea (long life) Coolant filter: WF2126 1ea (long life) UNK coolant capacity
Bldg 8: 250Kw Cummins UNK oil capacity Oil filter: LF670 1ea Fuel filter: FF105 2ea Coolant filter: WF2071 1ea UNK coolant capacity
Bldg 35 275KW QSL9-G7 Oil Capacity 6 Gal Oil filter Unk Fuel Filter Fleetguard FS19732 & FF5580 Coolant filter Unk Coolant capacity 10 Gal
GENERATOR SYSTEM MAINTENANCE GUIDELINES
SCHEDULE A
PREVENTIVE MAINTENANCE LIST
Check condition of the drive belts Check oil level Check block heater operation Check fuel level Verify the generator set breaker is closed Verify all controls are in automatic position Check air cleaner condition Take fuel sample for visual analysis Drain fuel/water separator filter (If equipped) Check anti-freeze Freeze Point and DCA concentration Check battery charging system Drain exhaust system and condensate trap Check starting batteries (Load test & Specific Gravity) Check radiator, block heater & fuel hose condition Replace if necessary Check generator room for adequate cooling and combustion air inlet Replace coolant in all units in 2024, then every 3 years thereafter
Functional Tests Operate the generator set to verify frequency, voltage & engine operation Test protective alarm operation as control system allows Change crankcase oil and filter yearly Contractor will be responsible for disposal of old oil or coolant per industry standard.
Change coolant/water filter (if applicable.
Change fuel filters yearly.
Perform County/State Confidence Test (Yearly copy required) o This test info is compiled through our annual Spokane Regional Clean Air Agency certifications; the contractor would present us with any data collected. JPRA will provide the technicians with our GENERATOR OPERATIONS LOG, AFCESA 487 to be used to log the testing information.
Full Resistive Load Bank Test - Recommend 2 Hours (Biannually); 2 times a year, IAW
UFC 3-540-01.
3.0 SCOPE OF RESPONSIBILITY
The items stated here are responsibilities of both the vendor and the customer.
3.1 Vendor Responsibilities
3.1.1 Meet the customer’s service schedule date.
3.1.2 Perform all the maintenance service tasks.
3.1.3 Submit service reports to the customer.
3.1.4 Inform and provide recommendations to the customer about any action items not included in the SOW (statement of work).
3.2 Customer Responsibilities
3.2.1 Provide dates and times when the scheduled work can be performed.
3.2.2 Facilitate site access for service personnel.
3.2.3 Notify vendor of any safety training and safety equipment requirements.
3.2.4 Provide an on-site point of contact.
3.2.5 Maintain the generators in an environment that adheres to manufacturer specifications.
4.0 LOCATION
The location of this project will be on-site at 11604 W Newkirk Rd, Spokane, WA.
5.0 CONTRACT PERFORMANCE PERIOD
5.1 Schedule: Preventive maintenance dates will be discussed and approved between vendor and the customer. Period of performance: One (1) Base Year, plus 4 optional one-year periods.
6.0 WORK SCHEDULE:
Working hours shall be between the hours of 7:30 am and 4:00 pm, Monday-Friday (excluding federal holidays). The contractor shall provide the Government a schedule of actual work days to resolve conflicts with JPRA’s training schedule. Any time changes will need to be coordinated with the Government. It will be necessary to work closely with JPRA staff to create the least amount of operational interruptions.
7.0 ACCESS TO WHITE BLUFF:
The government will provide access through the controlled entry gate. The contractor will be required to check in with the control entry receptionist in Building 2. The contractor will be required to provide a list of names, to include place of birth, address, and Social Security Number two weeks prior to gaining access to White Bluff. If contractor currently possesses a Fairchild AFB base pass copies can be provided to the Government and if valid, the other information will not be required. If deliveries are anticipated, the contractor will need to notify JPRA personnel at least 1 day in advance.