This document is a Statement of Objectives for the maintenance and service of the Enterprise Land Mobile Radio (ELMR) Uninterruptible Power Supply (UPS), Generator, and Heating, Ventilation and Air Conditioning (HVAC) systems at Moron Air Base. The key objectives are to provide triannual preventative maintenance service for these critical communication and facility systems for a base period of one year with four one-year option periods. The service requirements include inspections, cleaning, repairs, and functional testing of the UPS, generator, and HVAC equipment to ensure uninterrupted networking operations, power continuity, and temperature control. The contractor must respond within 8 hours for emergency service requests. This Statement of Objectives is related to Solicitation Number FA557524Q1004 for Enterprise Land Mobile Radio (ELMR) Preventative Maintenance Service, issued by the Department of the Air Force United States Air Forces in Europe - Air Forces Africa, with responses due by 12 June 2024 at 10:00 AM CET.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ELMR Combo Solicitation..pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF OBJECTIVES
MORÓN AB ELMR UPS, GENERATOR, AND HVAC ANNUAL SERVICE
MORÓN AIR BASE
1. Project title Morón AB ELMR UPS, and Generator preventative maintenance service
2. Introduction We are requesting triannual service and preventative maintenance of Morón AB’s Enterprise Land Mobile Radio (ELMR) Uninterruptible Power Supply (UPS), Generator, and Heating, Ventilation and Air Conditioning (HVAC) systems. Additionally, we are requesting this service for a base period of one (1) year and four (4) option periods of one (1) year each.
3. Background
According to DoD policy, Communication Flight is required to have the ELMR rack mounted UPS, generator and HVAC systems inspected and serviced. Service of the rack-mounted UPS, generator, and HVAC units are urgently required in our Communication Flight. These systems are vital for maintaining uninterrupted networking operations, shielding against power disruptions, facility temperature control, enabling remote management, including emergency operations and countermeasures. Given the mission-critical nature of our communication tasks, these units are indispensable for equipment continuity, protection against temperature and power-related issues, and operational efficiency.
4. Salient Characteristics and Requirements The contractor shall provide 3 service visits and emergency visits as needed to perform maintenance services for:
• 2 each HPW WM31MD Air Conditioners
• 2 each NXC UPS units
• 1 each generator
Response time for emergency visits shall be within eight (8) hours or less from the time an emergency service request was made.
Make repairs to listed equipment above and test for proper functionality as outlined, but not limited to checklists below:
o Thermal Management Air Filters
• Check for soiling, damage, corrosion.
Water/Glycol Circuits (if applicable)
May 2024
• Purge air from water circuit.
• Examine for any water/glycol leaks.
• Check for coil cleanliness.
• Check coil for damage and corrosion.
• Major visits only:
o Check chilled water in/out temperatures and pressures.
o Check chilled water valve proper functioning.
Fans Section
• Check for soiling, damage and corrosion.
• Check blower noise.
• Examine motor mounts for tightness.
• Check for abnormal vibrations.
• Major visit only:
o Measure the current and power consumption.
o Set, adjust and tighten all the electrical connections.
Refrigerant Cycle/Section
• Examine refrigerant lines for leaks or damage.
• Using the sight glass, check lines for moisture.
• Check superheat.
• Check sub-cooling.
• Check compressor noise vibration.
• Check compressor starting and running currents.
• Check coils cleanliness.
• Check coils for damage and corrosion.
• Check condensate drain from evaporator coil.
• Major visit only:
o Set, adjust and tighten the functional elements.
o Monitor suction, head and discharge pressure.
Controls
• Check connections for electric and mechanical functions.
• Check parameters setting and sensor calibration.
• Major visit only:
o Check safety devices for proper operation and adjust accordingly:
o Air clogged filter device.
o Fan safety device.
o Humidifier safety devices.
o Electrical heater safety devices.
o Hydraulic circuit safety devices.
o Functional tests on:
o Fans, humidifier, heaters, air damper and hydraulic circuits.
o Check operation sequence.
Electrodes Humidifier (if applicable)
• Check the canister for any deposits.
• Check the condition of all steam hoses.
• Check for leaks.
• Check operation of humidifier water pumps (if applicable).
• Major visit only:
o Check power and current absorption.
Infrared Humidifier (If Applicable)
• Check the pan drain for any type of blockage.
• Examine the humidifier lamps for proper operation.
• Check the pan for any type of mineral deposits.
• Check and clean internal drains.
• Check for leaks.
• Check operation of humidifier water pumps (if applicable).
Ultrasonic Humidifier (if Applicable)
• Check air filter.
• Check and clean the pan.
• Water presence check.
• Check for leaks.
• Check operation of humidifier water pumps (if applicable).
• Major visit only:
o Check pressure transducer cleanliness.
Electric heaters (if applicable)
• Check correct fixing.
• Major visit only:
o Check power and current absorption.
o AC Power - Three Phases Systems Environmental Checks
• Ambient Temperature
• Cleanliness
• UPS Location Visual Checks
• Insulation , Overheating, Damage
• Power capacitors for swelling or leaking oil
• Fuses
• Major visit only:
o Power Fuses
Synchronising(On VFI Mode) (with customer approval)
• Major visit only:
o Verify Inverter to Mains Synchronization o Verify transfer from Inverter to Bypass and vice-versa o Verify Voltage and Phase Lockout o Check all nuts, bolts, screws, and connectors for tightness and heat o Check/Adjust Inverter free running frequency
Discoloration Cleaning/Air Flow
• Check Fans, Door/Compartment Seals
• Replace Filters (If Required)
• Clean Grids, Fan, Power Module and PCB
• Clean inlet / outlet air flow Check/Record Voltage and Currents
• Input /Output, Rectifier Output Measurements Waveform (On VFI Mode)
• Output RMS Current (Phases and Neutral)
• Output Peak Current (Phases and Neutral) – as required
• Output Voltage Metering (check the calibration LCD vs Meter)
• DC Volts
• Input Volts/Current
• Output Voltage and Frequency Battery check (with customer approval)
• Major visit only:
o Check/Adjust Battery alarms Levels o Check/Adjust Battery End Of Discharge Level
Battery
• Visual check for cleanliness
• Visual check for cracks, leakage, and corrosion
• Discharge test (with customer approval)
• Major visit only:
o Check all connectors for tightness Software
• Download and record all the configuration data, alarm history, fault data