This document is a Specifications attachment for Solicitation # 140R8125Q0218, detailing requirements for two lithium-ion battery charging and storage cabinets for the Department of the Interior Bureau of Reclamation. The solicitation calls for two distinct cabinets - a large and a small charging cabinet - both designed for indoor use with specific safety features for storing undamaged lithium-ion batteries.

The large charging cabinet requires a minimum of four adjustable shelves with 160-pound capacity, 20 power outlets, a smoke detector with alarm, automatic fire suppression, and two self-closing, lockable doors. The cabinet must have minimum interior dimensions of 60 x 38 x 16 inches and maximum exterior dimensions of 78 x 48 x 30 inches. The small charging cabinet has similar requirements but with fewer power outlets (10 minimum), two shelves, and no mandatory smoke detector or fire suppression system. Both cabinets must meet EN 14470-1 fire protection standards, include a liquid-tight spill containment sump, be accessible underneath, have ventilation options, and come with a user manual. All units must be new, with parts and accessories available for a minimum of 5 years from government acceptance.

View the file

Other files

File Type Posted
Sol_140R8125Q0218.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation # 140R8125Q0218 Attachment 1

Specifications

TSC IIJA 8530 Battery Cabinets

Reclamation requires two (2) lithium-ion battery charging and storage cabinets of different sizes and with different features to ensure safe storage of lithium-ion batteries within two distinct areas of the laboratory. The cabinets must be designed specifically for the safe charging and storage of lithium-ion batteries. The units must be new. No discontinued models, refurbished equipment, or refurbished parts are acceptable. All parts and accessories must be available for a minimum of 5 years from the date of acceptance by the government.

Product meets or exceeds the Specifications listed below:

1. Line Item 1 – Large Charging Cabinet

a. Intended for indoor use

b. For charging and storage of undamaged lithium-ion batteries

c. Fire Protection/Fire Resistance in accordance with EN 14470-1: 90 minutes, minimum

d. Liquid-tight spill containment sump

e. Accessible underneath to facilitate ease of moving

f. Minimum Interior Dimensions (HxWxD): 60 x 38 x 16 inches

g. Maximum Exterior Dimensions (HxWxD): 78 x 48 x 30 inches

h. Doors:

i. Number of doors: two (2)

ii. Self-closing

iii. Lockable

i. Shelves:

i. Four (4) minimum

ii. Adjustable

iii. Capacity: 160 pounds, minimum, per shelf

j. Power outlets:

i. 115V

ii. 20 outlets, minimum

k. Smoke detector:

i. Yes

ii. With alarm

l. Fire suppression:

i. Automatic internal thermally activated fire suppression system

m. Ventilation: (Must include one of the following options)

i. Option 1: Pressure relief opening that remains closed during normal conditions, but opens in the event of excessive heat or pressure buildup

ii. Option 2: Includes vent hole(s) for connection to ventilation duct

n. Includes a user manual

Solicitation # 140R8125Q0218 Attachment 1

2. Line Item 2 – Small Charging Cabinet

a. Intended for indoor use

b. For charging and storage of undamaged lithium-ion batteries

c. Fire Protection/Fire Resistance in accordance with EN 14470-1: 90 minutes, minimum

d. Liquid-tight spill containment sump

e. Accessible underneath to facilitate ease of moving

f. Minimum Interior Dimensions (HxWxD): 32 x 38 x 16 inches

g. Maximum Exterior Dimensions (HxWxD): 48 x 48 x 30 inches

h. Doors:

i. Number of doors: two (2)

ii. Self-closing

iii. Lockable

i. Shelves:

i. Two (2) minimum

ii. Capacity: 160 pounds, minimum, per shelf

j. Power outlets:

i. 115V

ii. 10 outlets, minimum

k. Smoke detector:

i. None required

l. Fire suppression:

i. None required

m. Ventilation: (Must include one of the following options)

i. Option 1: Pressure relief opening that remains closed during normal conditions, but opens in the event of excessive heat or pressure buildup

ii. Option 2: Includes vent hole(s) for connection to ventilation duct

n. Includes a user manual