ATTACHMENT 1
SPECIFICATIONS
400A POWER DISTRIBUTION CENTER
VTI PORTABLE POWER DISTRIDUTJON CENTER (PPDC) MODEL# BCK-441P179S2122
POWER INPUT:
| • | The PPDC is designed to operate on 3 phase, 3 wire, 480 Volt, 60 Hz power up to 600 Amps. |
| • | Three (3) Duraline E1 023-160 I molded rubber receptacles rated for 690 Amps continuous provide connections for incoming power. |
ENCLOSURE:
| • | Weatherproof NEMA 3R enclosure constructed of mild steel and powder coated. |
| • | Dimensions: 82" L x 48" H x 36" D |
| • | The enclosure incorporates a hinged cover to prevent accidental contact with the breaker operators. Over-extension is prevented with chains on either side which arc covered in heat shrink tubing to eliminate pinch |
hazards.
| • | Receptacle guards are provided on each side of the enclosure to prevent damage to the components on the front and rear of the PPDC. |
| • | Aluminum C-channel feet on the bottom of the legs prevents corrosion from seawater. |
| • | The PPDC is provided with forklift tunnels and lifting eyes. |
CONSTRUCTION NOTES:
• All receptacles will be mounted to front or back receptacle mounting plates. These will be attached to the main enclosure with machine screws and an internal tooth lock washer, flat washer, hex nut, and Loctite 242 thread locking compound.
• All receptacles with soft rubber flanges will be mounted with flat metal washers on the front of the receptacle to prevent distortion of the rubber flange. On the inside of the enclosure they will be secured with hex bolts, internal tooth washers, flat washers, hex nuts, and Loctite 242 thread locking compound.
• All receptacles will be equipped with weatherproof covers. The covers will be attached to steel cables. The cables will be secured to the enclosure using machine screws and internal tooth washers, flat washers, hex nuts, and Loctite 242 thread locking compound.
• All electrical connections to the 120/20& Volt receptacles will use ring terminals and oriented to prevent the insulation from contacting adjacent connections.
• All electrical connections to the 480 Volt receptacles will use 45° lugs and oriented to lift the cable up and away from adjacent connections. In addition, the threaded studs on the back of the receptacles will be fitted with insulating rubber caps to prevent any accidental contact.
• Connections to the PPOC transformer will be secured with hex bolts, Belleville washers, internal tooth washers, flat washers, hex nuts, and Loctite 242 thread locking compound.
• All other components that are secured to the enclosure with threaded fasteners will be secured with an internal tooth washer, flat washer, hex nut and Loctite 242 thread locking compound.
QUALITY CONTROL NOTES:
| • | Prior to shipping the unit will be thoroughly cleaned and inspected for any extraneous debris. |
| • | Prior to shipping the device will be inspected for loose, stripped or |
missing fasteners.
• Prior to shipping the device will be inspected to determine free movement of all breaker operators and appropriate clearance around the operators.
480 V AC POWER DISTRIBUTION
MAIN BREAKER:
• 3 Pole, 600 Amp, 480 Volt, 35 KAIC Siemens MCCB
· Part# 3VA54605EC3 10AA0
PANELBOARD:
| • | A 600 Amp, 3 Phase, 3 Wire, 480 Volt Siemens Main Breaker Panelboard provides 480 Volt power distribution to the receptacles. |
| o | Part# P5F90VJ600ETS |
| • | The panelboard is fitted with a dead front trim panel that lays flat against the body of the breakers but provides adequate clearance around the |
operator to provide unimpeded operation.
DISTRIBUTION:
| • | One (1) 400 Amp Load Receptacle |
| o | One (1) Siemens 3 Pole, 400 Amp, 480 Volt, 35 KAIC Breaker |
| • | Part# 3VA53405EC310AA0 |
| o | Three (3) Duraline Single Pole, Male, Latching Cam, 30° Panel Mount Receptacle with Weatherproof Cap |
| • | Part #E1023-1626 |
Four (4) 200 Amp Load Receptacles
· One (1) Siemens 3 Pole, 200 Amp, 480 Volt, 35 KA1C Breaker . Part# 3VA52205EC310AA0 Three (3) Duraline Single Pole Female, Latching Cam, 90 Panel Mount Receptacle with Weather Cap Part# E1016-163 Two (2) 100 Amp Load Receptacles One (1) Siemens 3 Pole, 100 Amp, 480 Volt, 35 KA1C Breaker . Part# 3VA41104ED340AA0 One (1) Duraline 3 Pole, 4 Wire, 100 Amp, 480 Volt, 90° Panel Mount Female Receptacle with Ground Pin and Weather Cap . Part# 4FR110GP Four (4) 60 Amp Load Receptacles One (1) Siemens 3 Pole, 60 Amp, 480 Volt, 18 KAIC Breaker . Part# 3VA41604ED340AA0 One (1) Duraline 3 Pole, 4 Wire, 60 Amp, 480 Volt Panel Mount Receptacle with Weather Cap Part# 4FR60 Seven (7) 30 Amp Load Receptacles
| One (1) Siemens 3 Pole, 30 Amp, 480 Volt, 18 KAJC Breaker | |
| Part# 3V A4 I 304£D340AA0 |
One (1) Duraline 3 Pole, 4 Wire, 30 Amp, 480 Volt, Panel Mount Load Receptacle with Weather Cap Part# 4FR20 One (1) 45 Amp Power Transformer Feed
| One (1) Siemens 3 Pole, 45 Amp, 480 Volt, 18 KAIC Breaker | |
| Part# 3\1 A4 I 454ED340AA0 |
This breaker is required, because it feeds the primary winding of the 30 KV A power transformer.
208Y120 VAC POWER DISTRIBUTION
POWER TRANSFORMER
| One (1) 30 KVA Hevi-Duty Transformer | |
| Primary: 3 Phase, 480 VAC |
Secondary: 3 Phase, 208 / 120 V AC, Aluminum Windings, 150 °C rise Electrostatic Shield between Primary and Secondary Windings Six 2.5% full capacity taps, 2 above and 4 below normal Meets NEMA Standard TP-1 Energy Efficient Transformer Specification and Efficiency Standards of 2016.
MAIN BREAKER
| One (1) Siemens 3 Pole, 100 Amp, 120/240 Volt, 10 KAIC Breaker | |
| Part # 3VA52 I OSEC3 10AA0 |
PANELBOARD
| One (1) Siemens 30 Circuit, 3 Phase, 4 Wire, 100 Amp. 120/208 Panelboard | |
| Part# PI C30V A100CTST |
DISTRIBUTION
| Eighteen (18) 20 Amp, Contactor Controlled, 120 Volt Power Receptacles | |
| One (1) Siemens I Pole, 20 Amp, 120 Volt. 5 mA GFCI, 10 KAIC Breakers | |
| Part# BF120A |
One (1) Duraline 2 Pole, 3 Wire, 20 Amp, 120 V AC Panel Mount Load Receptacle with Weather Cap Part# 3R20
| Two (2) 20 Amp, 240 Volt Power Receptacles | |
| One (1) 2 Pole, 20 Amp, 240 Volt, IO KAJC Breakers | |
| Part# B220 |
One (1) Duraline 3 Pole, 4 Wire, 60 Amp, 208 Volt, Panel \fount Load Receptacle with Weather Cap Part# 30FR4X
| One (1) 20 Amp, 120 Volt Fan Power | |
| One (1) l Pole, 20 Amp, 120 Volt, IO KAIC Breaker | |
| Part# 8120 | |
| One (1) NMB Technologies Exhaust Fan | |
| Part# AK175IHB-AT | |
| One (1) 4 Pole Lighting Contactor | |
| One (1) Square D 4 N.O., 25 Amp, 600 Volt Contactor | |
| Part# 8910DPA24V02 | |
| One (1) lntermatic Photocell |
The photocell used 10 control the lighting connector will connect to the enclosure using a Myer's Hub.
Part# AT-15
INSTRUMENTATION
Voltage and Current Monitoring
| One (1) Crompton Analog AC Voltmeter, 0-600 VAC. 50/60 llz | |
| Part# 007-05GA-SJSJ-C7 | |
| One (1) Crompton Analog AC Ammeter, 0-600 A | |
| Part# 007-05FA-LSSJ-C6 | |
| Three (3) 600:5 Current Transformers | |
| One (I) Voltmeter/Ammeter Phase Selector Switch |
One (1) Tegam Phase Sequence Monitor (Part# T-471) to indicate the phase rotation of the incoming power.
One (1) Ground Detector consisting of three pilot lights and a pushbutton. When pressed the pilot lights will indicate a phase fault to ground.
WEIGHT:
Approximately 1500 Pounds Shipping Weight (Crated) Approximate Crate dimension, (94" L x 60" H x 42" D)