This document is a Statement of Work (SOW) for replacing a high-speed door at the Defense Distribution Center in Susquehanna, PA. The SOW requires a contractor to provide equipment, materials, and labor to install a new 10' 0" Wide x 14' 8" High RYTEC PredaDoor NXT High-Speed Rolling Door at Building 2001, Door #275, while removing and disposing of the existing high-speed door. Specific technical requirements include a 460V, 3-Phase power system, three-phase variable speed AC drive motor, NEMA 4 rated controller, loop detector sets, a long-range reader, and a break-away bottom bar. The door must have a travel speed of up to 50 inches per second and use 71oz, 2-Ply Rylon panel material. Work is to be performed Monday through Friday from 0630-1600, excluding Federal holidays, with the contractor required to notify the Facilities Maintenance Supervisor one week prior to arrival.

View the file

Other files

File Type Posted
Tab 11 - CSS SP3300-25-Q-0125.pdf PDF
Tab 11 - CSS SP3300-25-Q-0125.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEFENSE LOGISTICS AGENCY

HEADQUARTERS

8725 JOHN J. KINGMAN ROAD

FORT BELVOIR, VIRGINIA 22060-6221

REPLACE HIGH-SPEED DOOR AT DEFENSE DISTRIBUTION CENTER

SUSQUEHANNA, PA

Defense Logistics Agency 2001 Mission Drive New Cumberland, PA 17070

Provide equipment, materials and labor to install new high-speed door at Building 2001, Door #275. Remove and dispose of existing high-speed door.

Scope Of Work:

Provide and install new 10’ 0” Wide x 14’ 8” High RYTEC PredaDoor NXT High-Speed Rolling Door to fit existing opening. Provide a complete and operable system to include but not limited to the following.

• Power requirements 460V, 3-Phase (connect to existing safety switch)

• Three phase variable speed AC drive motor with dynamic braking and absolute encoder with exterior motor cover

• NEMA 4 rated controller with self-diagnostic capabilities with LCD display and programmable inputs and outputs to accommodate special control applications without additional electrical components

• Install two new loop detector sets with exterior control station and a On/Off selector switch on interior control box to turn off exterior station

• Install one Liftmaster LMSC1000 Long-Range Reader to operate with door controller

• Limit switches to be adjustable without the use of tools from floor level at control panel

• 71oz, 2-Ply Rylon panel material

• Slant Hood Cover to fit new door with additional wind rib

• Break away bottom bar to release in either direction without damaging door assemblies

• Travel speed for opening at up to 50 inches per second

The contractor will be required to remove and dispose of the existing high-speed door and all associated components and hardware.

Working hours are Monday thru Friday 0630-1600 excluding Federal holidays.

The contractor is required to notify Timothy Burke the Facilities Maintenance Supervisor at 717- 770-8150 or tim.burke@DLA.mil one week prior to arrival on the Installation.