Attachment 1 Salient Characteristics.pdf

PDF 150 KB Posted

Attached to
Portable Fire Pump
Solicitation number
W912PB25QA051
Issued by

About this file

This document details the salient characteristics for a Portable Fire Pump (PFPN 10-2000) for USAG Bavaria's DES Fire Department in Grafenwoehr. The portable fire pump must meet stringent technical specifications, including a flow rate of at least 2,000 l/min at 10 bar and 2,250 l/min at 4 bar, with a maximum weight of 175 kg when operationally ready. Key features include a 3-cylinder 4-stroke in-line engine with electronic injection (max 55 kW output), a fully automatic priming system, side-mounted control panel with color display, two rotatable pressure outlets, a 19-liter fuel tank, and a BEOS charging socket for the starter battery.

The procurement requires delivery to USAG Bavaria's Fire Department, with the vendor also providing practical on-site operating training and a parts manual. The pump must conform to EN 14466 standards, with specific requirements for the carrying frame, control panel functionality, and operational characteristics such as engine RPM control via potentiometer and integrated pressure governor with thermal overheat protection and cavitation warning lamp.

View the file

Other files

File Type Posted
W912PB25QA051.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics - Portable Fire Pump PFPN 10-2000 o The portable fire pump must meet the following minimum specifications:

o Flow rate of at least 2.000 l/min at 10 bar and at least 2.250 l/min at 4 bar at 3m suction height according to EN 14466.

o Weight maximum 175 kg when operationally ready according to EN 14466 as PFPN 10-

2000. Simple operation with control panel inclusive color display. Control Panel side-mounted.

Buttons to control the main functions engine start and engine stop and suction system.

The engine rpm should be controlled with a potentiometer.

o Pressure governor with intake pressure controller, thermal overheat protection and cavitation warning lamp must be integrated in the control panel.

o The pump must have a fully automatic priming system, which works without any additional operating step at free discharge operation.

o The pump must have 2 rotatable pressure outlets.

o The engine must be a 3-cylinder 4-stroke in-line engine with electronic injection and max. 55 kW output.

o BEOS charging socket for starter battery.

o The fuel tank must have a capacity of at least 19 liters.

o Carrying frame according to DIN EN 14466, annex A

**The unit must be delivered to USAG Bavaria, DES Fire Department Grafenwoehr including practical operating training on-site & parts manual.