Attachment 1 - Salient Characteristics.pdf

PDF 638 KB Posted

Attached to
Mobile Utility Power Unit
Solicitation number
FA500025Q0042
Issued by

About this file

Attachment 1 - Salient Characteristics is a document detailing the required specifications for a Mobile Workstation Generator Unit for the Department of the Air Force Pacific Air Forces. The unit must be trailer-mounted with a pintle hitch and provide electrical output through at least four 110VAC receptacles and one 220VAC receptacle, with all receptacles capable of 10A.

The generator requires a minimum 20-gallon fuel tank (gasoline preferred, diesel acceptable) and includes an integrated water pumping system with 2-inch hoses for manhole system operations. It must also feature a built-in fresh-air blower ventilation system capable of forced manhole ventilation, providing hot air for cold month operations and drying wet splices. The solicitation (FA500025Q0042) notes that funds are not currently available, and the government reserves the right to cancel the solicitation without reimbursing offeror costs.

View the file

Other files

File Type Posted
Solicitation - FA500025Q0042.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Mobile Workstation Generator Unit Characteristics:

• Mobility: Trailer-mounted with a pintle hitch.

• Electrical Output: Capable of providing power through:

• At least four (4) 110VAC receptacles.

• At least one (1) 220VAC receptacle.

• All receptacles must be capable of at least 10A.

• Fuel System:

• Minimum 20-gallon fuel tank capacity (for prolonged use).

• Fuel Type: Gasoline preferred; diesel acceptable.

• Integrated Water Pumping System:

• Either a built-in submersible pump OR a body-attached centrifugal pump.

• Equipped with at least 2-inch hoses for both intake and discharge of water within manhole systems.

• Integrated Ventilation System:

• Built-in fresh-air blower for forced ventilation of manhole systems.

• Ventilator must also be capable of providing hot air for:

• Use during cold months.

• Drying out wet splices.

FA500025Q0042

Attachment 1 - Salient Characteristics