Attachment 1- Salient Characteristics.pdf
PDF 189 KB Posted
- Attached to
- Combo Fire/CO Detectors
- Solicitation number
- FA465925QZ031
About this file
The document is a Salient Characteristics specification for Combo Fire/CO Detectors for the 319 CES at Grand Forks AFB, ND. The procurement requires FCO-951 Series Advanced Multi-Criteria Fire/CO Detectors with specific technical requirements, including the ability to detect four major fire elements, separate CO detection signal, and compatibility with Notifier fire panels. Key specifications include an operating temperature range of 32°F to 100°F, operating voltage range of 15 to 32 VDC, and a 10-year CO cell with end-of-life warning.
The detectors must meet multiple safety certifications, including UL 268 7th edition, UL 521, UL 2075, CAN/ULC S529, CAN/ULC S530, and CSA 6.19-01. The document emphasizes the detector's advanced features such as automatic drift compensation, highest nuisance alarm immunity, and the ability to use only one address on the SLC. Vendors are instructed to notify the contracting agency if they plan to provide an equivalent product, with the delivery location specified as Grand Forks AFB in North Dakota.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sources Sought - Combo Detector.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics
319 CES
Combo Fire/CO Detectors
319 RW
09 July 2025
1. General:
The contractor shall provide Combo Fire/CO Detectors for the 319 CES, delivered to Grand Forks AFB, ND 58201. All capabilities shall be met as listed below or equivalent.
2. FCO-951 Series Advanced Multi-Criteria Fire/CO Detector with System Sensor
Firmware and compatible with Notifier fire panel (or equal) If you are supplying an equal product please notify us/state what product you are providing
Features Unique ability to detect all four major elements of a fire Separate CO detection signal Highest nuisance alarm immunity Automatic drift compensation for smoke and CO sensors Uses only one address on the SLC RealTest® CO testing capability UL 268 7th edition, UL 521, and UL 2075 listed; CAN/ULC S529, CAN/ULC S530 and CSA 6.19-01 listed Separate audible signal for fire or CO alarm when used with a B200S series base (B200SCOA series in Canada) 10-year CO cell with end-of-life warning New modern profile Expanded color options
Specifications Operating Humidity Range: 15% to 90% Relative Humidity, Noncondensing Operating Temperature Range: 32°F to 100°F (0°C to 38°C) Air Velocity: 0 to 4000 ft./min. (0 to 1219.2 m/min.)
Operating Voltage Range: 15 to 32 VDC Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication) Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on) Maximum Current: 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on) Isolator Load Rating: 0.0063