Attachment 1 - Salient Characteristics.pdf

PDF 210 KB Posted

Attached to
Spangdahlem AB - Partial Cabinet Replacement - Amendment 1
Solicitation number
FA560625Q2007
Issued by

About this file

Attachment 1 - Salient Characteristics is a detailed specification document for a cabinet replacement project at Spangdahlem Air Base in Germany. The 52 Fighter Wing requires six 19-inch, 42U rack cabinets with specific technical requirements, including ventilated doors, cable management systems, and fiber optic connectivity. Each cabinet must include two 230-volt, 32-amp Power Distribution Units (PDUs), vertical cable managers, bonding busbars, and Closet Connector Housing (CCH) with fiber optic patch panels and pigtail cassettes.

The procurement involves comprehensive equipment specifications with precise technical standards, including telecommunications-style rails, single-mode fiber interconnects, and grounding conductor kits. The solicitation (FA560625Q2007) is issued by the Department of the Air Force United States Air Forces in Europe - Air Forces Africa, with key response dates of 13 March 2025 for questions (1200 CEST) and 21 March 2025 for proposals (1200 CEST). The project requires precise equipment configuration to meet DISN Implementation Standards and EIA/ECA-310 standards for rack and telecommunications infrastructure.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 1 - Salient Characteristics Partial Cabinet Replacement, Bldg 24

The six (6) new rack cabinets shall be 19-inch, 42U, 800mm (W) x 1200mm (D), 4-post, adjustable-depth, floor-mounted, lockable rack cabinets IAW the current version of the EIA/ECA- 310 standard. Each new rack cabinet shall include ventilated doors, top cover plates with fan module and cable entry brush, M6 screw & cage nut set, vertical potential equalization bonding busbar (vertical rack bonding busbar), rack bonding conductors, cable support rails, non-metallic vertical finger duct cable managers with covers, rear vertical PDU/accessory bars, blank panels, and all other associated accessories. All rack cabinet rails shall be telecommunications-style rails that are unpainted and have drilled and tapped mounting holes IAW DISN Implementation Standards, Chapters 2.7.20 to 2.7.26. Each equipment cabinet should also include a one (1) RU Closet Connector Housing (CCH) with two (2) 24 F, LC UPC duplex, Single-mode (OS2), single-fiber (250 µm) Pigtailed Splice Cassettes, providing interconnect or cross-connect capabilities.

Each equipment cabinet must have two (2) Power Distribution Units (PDU). The PDUs will be 3-contact, 230 Volt, 32 Amp with C13 and C19 power connectors. The PDU will have an IEC 60309 1P+N+PE input plug to connect to European style connectors.

See List of Materials below:

No. Item Mfg U/I Qty 1 Equipment Cabinets N/A EA 6 2 Power Distribution Units (PDU), ZeroU, 32Amp, 230V N/A EA 12 3 Vertical, non-metallic duct cable managers N/A EA 12 4 Rear Vertical PDU/Accessory Bar N/A EA 12 5 Vertical Potential Equaqlization Bus Bar N/A EA 6 6 6AWG Rack Bonding Conductor Kit, including lugs N/A EA 6 7 6AWG Ground Bonding Conductor Kit, inlcuding grounding clamps N/A EA 6 8 Misc Supplies and Hardware N/A EA X 9 Closet Connector Housing (CCH) Pigtail Cassette, 24F LC UPC SM N/A EA 12

10 Closet Connector Housing (CCH) FO Patch Panel, 1U N/A EA 6 11 Closet Connector Housing (CCH) External Relief Kit (1U-3U) N/A EA 6