Attachment 1 - Salient Characteristics.pdf
PDF 155 KB Posted
- Attached to
- 820 RHS HVAC Units
- Solicitation number
- F3GHBA4200AW01
About this file
This document is an Attachment 1 containing the salient characteristics for a Request for Quotation (RFQ) for HVAC units under Solicitation Number F3GHBA4200AW01.
The RFQ is seeking three HVAC units for Nellis Air Force Base: a 25-ton dedicated outdoor air system, a 15-ton dedicated outdoor air system, and a 3-ton split system. The key requirements include horizontal discharge, 460V 3-phase power, BACnet compatibility, specific features such as modulating gas heat, VFD, and ERV. The solicitation is set aside for small businesses under NAICS code 333415. Quotes are due by September 18, 2024, and the contract type will be Firm Fixed Price. The government will award to the lowest-priced, technically acceptable offer.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| F3GHBA4200AW01 - BNJ.pdf | ||
| IFS - Nellis Mechanical and Plumbing.pdf | ||
| F3GHBA4200AW01 - Combo.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F3GHBA4200AW01 - 820 RHS HVAC Units
Attachment 1 - Salient Characteristics
Brand Name ONLY: Trane
CLIN 0001:
The first unit must be a 25-ton dedicated outdoor air system with horizontal discharge curb, 460 volts, 3phase, 60 hertz, BACnet compatible.
- Horizontal Discharge/ Vertical Return Dedicated exhaust
- DX 6-Row
- 460-3-60
- Fin and Tube Modulating HGRH
- Digital Scroll-1st circuit only
- Air Cooled Fin and Tube
- Indirect Fired Natural Gas – Standard efficiency (80%)
- 250 MBH, (10:1 Turndown Natural Gas)
- Direct Drive with Variable frequency Drive (VFD)
- Supply and Exhaust Fan Piezo Rings/Taps
- Multi-Zone VAV – UC600
- BACnet compatible
- MERV-8 Filters
- ERV- Composite Construction with Frost Protection with VFD
- ERC-5262C
- 100% OA 2-Position Damper with Return Air 2-Position Damper
- Barometric relief dampers
- Non-Fused disconnect
- Active VFD head pressure low ambient control
- Hailguards
- Reliatel
- Supply discharge air sensor
- 2-inch Double wall construction
- Stainless steel drip pan
- Horizontal discharge curb
CLIN 0002:
The second unit must be a 15-ton dedicated outdoor air system with horizontal discharge curb, 460 volts, 3 phase, 60 hertz, and BACnet compatible.
- Horizontal Discharge/ Vertical Return Dedicated exhaust
- DX 6-Row
- 460-3-60
- Fin and Tube Modulating HGRH
- Digital Scroll-1st circuit only
- Air Cooled Fin and Tube
- Indirect Fired Natural Gas – Standard efficiency (80%)
- 150 MBH, (10:1 Turndown Natural Gas)
- Direct Drive with Variable frequency Drive (VFD)
- Supply and Exhaust Fan Piezo Rings/Taps
- Multi-Zone VAV – UC600
- BACnet compatible
- MERV-8 Filters
- ERV- Composite Construction with Frost Protection with VFD
- ERC-4136C
- 100% OA 2-Position Damper with Return Air 2-Position Damper
- Barometric relief dampers
- Non-Fused disconnect
- Active VFD head pressure low ambient control
- Hailguards
- Reliatel
- Supply discharge air sensor
- 2-inch Double wall construction
- Stainless steel drip pan
- Horizontal discharge curb
CLIN 0003:
The third unit must be a 3-ton split type system and 120/208 powered for mechanical room cooling requirement. (Nothing else is required)
**Installation is not required
File details come from the government source that posted it. Updated .