This document outlines the scope of work for inspection services required at the VA Medical Center in Leeds, Massachusetts. The contractor shall provide field inspection services for cast-in-place concrete, masonry, structural steel, firestopping, spray fireproofing, intumescent coatings, and exterior envelopes. Inspectors must meet specified certification and experience requirements for each discipline. Inspections will include rebar placement, break and slump testing of concrete, welding and bolted connection reviews for structural steel, firestopping of all wall and floor penetrations, material thickness and location checks for fireproofing and coatings, and qualitative and quantitative testing of exterior walls. The related federal contract opportunity is solicitation number 36C24124Q0066 from the Department of Veterans Affairs for an indefinite delivery/indefinite quantity contract to provide testing and inspection services on a blanket purchase agreement.

View the file

Other files

File Type Posted
36C24124Q0066.docx DOCX document
Attachment 3_Past Performance Worksheet.xlsx XLSX spreadsheet
Attachment 2_Cost-Price Schedule.xlsx XLSX spreadsheet

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SCOPE OF WORK

VA Medical Center Leeds, MA

Independent Special Inspector, VACWM, Leeds, MA

1. GENERAL

The VA Central Western Mass requires Special Inspection services to certify work has been completed in accordance with drawings and specifications. Inspections and testing may be required on concrete, structural framing, exterior envelope, roofing, masonry, and fire-resistant materials, etc. Inspections shall take place within 2 days of task order award.

2. PROJECT SCOPE OF WORK

The contractor shall provide inspection services at the Central Western Massachusetts Edward P.

Boland campus. This includes the following tasks:

Provide field visits for the following testing and inspections below and submit testing and inspection reports to provide instances of noncompliance.

Division 3 Cast-In-Place Concrete Inspections

a) Inspector to be ACI, ICC, or NICET technician Level III certification with 1-year experience.

b) Rebar inspection per approved shop drawings

c) Break testing and/or slump testing per specifications and drawings.

d) Quantity and Duration will be updated on each order.

Division 4 Masonry Inspections

a) Inspector to be International Code Council (ICC) certified with one-year experience.

b) Break testing and/or slump testing per specifications and drawings.

c) Quantity and Duration will be updated on each order.

Division 5 Metals Inspections

a) Structural Steel Inspection - Inspector to be American Welding Society (AWS) certified with 1-year experience.

b) Welds, Bolted connection, cold form framing to be inspected per specifications and shop drawings.

Division 7 Thermal and Moisture Protection inspections

a) Firestopping Inspector to have passed the UL Firestop Exam with 1 year experience or passed the FM Firestop Exam with 1 year experience.

b) All penetrations to be inspected to the approved UL systems and confirmed labeled by

GC.

d) Spray Fireproofing and Intumescent Coatings Inspector to be ICC certified with 1 year experience or Fire inspector I certification.

e) VA to provide shop drawings with material depth requirements and locations.

f) Quantity and Duration will be updated on each order.

g) Exterior Envelop Inspector shall be Air Barrier Association of America (ABAA) certified.

h) Qualitative and Quantitative testing requirements per specifications and manufactures requirements (pull test, leakage tests)

i) Quantity and Duration will be updated on each order.