Attachment 1 - Isolation Room Air Balancing - Room List - 2023.xlsx
XLSX spreadsheet 21 KB Posted
- Attached to
- ISOLATION ROOM AIR BALANCING MAINTENANCE Federal contract opportunity
- Solicitation number
- RFQ-23-009308
About this file
This document is an Excel spreadsheet listing isolation rooms at the National Institutes of Health Clinical Center that require air balancing maintenance. The spreadsheet includes 85 rooms across multiple buildings, identifying each by number, building, use, pressure relationship to adjacent areas, and applicable ASHRAE standard. Room uses include patient rooms, operating rooms, laboratories, imaging rooms, and more. Pressure designations include negative, positive, and neutral. The related federal contract opportunity is solicitation number RFQ-23-009308 for isolation room air balancing maintenance services at the NIH Clinical Center issued by the Department of Health and Human Services. The solicitation seeks maintenance of air pressure differentials in isolation rooms to standards specified in ASHRAE 170-2017 Table 7.1.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Isolation Room Air Balancing -Pricing Matrix.xlsx | XLSX spreadsheet | |
| Isolation Room Air Balancing - SOW.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Room Survey List
| Isolation Room Report - Room Survey List | |||||||||
| Monthly Survey | Bi-Annual Survey | ||||||||
| Room # | Bldg. | Space Use Function/Description | Design Pressure | Standard/Parameter Basis | Room # | Bldg. | Space Use Function | Design Pressure | Standard/Parameter Basis |
| 1-1642 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | B2-2426 | CRC | Kitchen - Clean Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 1-1660 | CRC | Anteroom - Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | B2-2434 | CRC | Metabolic Kitchen - Clean Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 1-1662 | CRC | Protective Environment Airborne Isolation Room (PE/AII) | Positive | ASHRAE 170-2017 Table 7.1 | B2-3576 | CRC | ROB - Soiled/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 1-5477 | CRC | Clean Work Room | Positive | ASHRAE 170-2017 Table 7.1 | 1-1664 | CRC | HEPA Transplant Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 3-1406 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 1-1665 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 3-1662 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 1-1672 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 3-3650 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 1-1676 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 3-3684 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 1-1684 | CRC | HEPA Transplant Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 3-5650 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 1-2637 | CRC | Therapy Tub Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 3-5684 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 1-2664 | CRC | HEPA Transplant Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-1402 | CRC | Entry Vestibule | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 1-2672 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-1662 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 1-2676 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| Corr. 5-2400 | CRC | SCSU Corridor | Positive | ASHRAE 170-2017 Table 7.1 | 1-2684 | CRC | HEPA Transplant Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-2403 | CRC | Entry Vestibule | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 1-5632 | CRC | Nuc. Med Scan Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 5-2404 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 1-5676 | CRC | Nuc. Med Scan Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 5-2412 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 3-1412 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-2416 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 3-1416 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-2421 | CRC | Nurse Station | Positive | ASHRAE 170-2017 Table 7.1 | 3-1424 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-2422 | CRC | Anteroom, Inpatient Isolation/Seclusion | Negative | ASHRAE 170-2017 Table 7.1 | 3-1425/2425* | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 5-2422.1 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 3-1428 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-2424 | CRC | Supply Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 3-1436 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-2445 | CRC | Patient Care Room | Negative | ASHRAE 170-2017 Table 7.1 | 3-1440 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-2466 | CRC | Patient Care Room | Negative | ASHRAE 170-2017 Table 7.1 | 3-1448 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-3438 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 3-1452 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-3458 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 3-1460 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-3662 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 3-1464 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-5436 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 3-1472 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 5-5458 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 3-1665/2665* | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 7-3662 | CRC | Patient Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 3-2404 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 1C433 | ACRF | Nuc. Med ScanRoom | Positive | ASHRAE 170-2017 Table 7.1 | 3-2412 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 1C435 | ACRF | PET/CT Control Room | Negative | ASHRAE 170-2017 Table 7.1 | 3-2416 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 1C560 | ACRF | CT Scanning Room | Negative | ASHRAE 170-2017 Table 7.1 | 3-2424 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C325 | ACRF | Mycology Laboratory | Negative | ASHRAE 170-2017 Table 7.1 | 3-2428 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C325A | ACRF | Anteroom | Positive | ASHRAE 170-2017 Table 7.1 | 3-2436 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C325B | ACRF | Clinical Laboratory Spaces | Negative | ASHRAE 170-2017 Table 7.1 | 3-2440 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C500 | ACRF | Anteroom | Positive | ASHRAE 170-2017 Table 7.1 | 3-2448 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C500A | ACRF | BSL3 Infectious Disease Suite | Negative | ASHRAE 170-2017 Table 7.1 | 3-2452 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C500B | ACRF | AutoClave Room | Negative | ASHRAE 170-2017 Table 7.1 | 3-2460 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C560 | ACRF | General Operating Room (OR #4) | Positive | ASHRAE 170-2017 Table 7.1 | 3-2464 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C560A | ACRF | Clean Storage Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 3-2472 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C564 | ACRF | General Operating Room (OR #5) | Positive | ASHRAE 170-2017 Table 7.1 | 3-2637 | CRC | Therapy Tub Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C566 | ACRF | General Operating Room (OR #6) | Positive | ASHRAE 170-2017 Table 7.1 | 3-3433 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C566A | ACRF | Clean Storage Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 3-3457 | CRC | Clean/Med Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C572 | ACRF | General Operating Room (OR #7) | Positive | ASHRAE 170-2017 Table 7.1 | 3-3613 (Within Room 3-3617) | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C572A | ACRF | Clean Storage Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 3-3618 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C576 | ACRF | General Operating Room (OR #8) | Positive | ASHRAE 170-2017 Table 7.1 | 3-3624 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C576A | ACRF | Clean Storage Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 3-3628 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C609 (Within Room 2C601) | ACRF | Surgical Suite, Workroom And Supply Space | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 3-3636 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C601/609B* | ACRF | General Operating Room (OR #1) | Positive | ASHRAE 170-2017 Table 7.1 | 3-3640 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C609C | ACRF | Cardiac Catherization Laboratory | Positive | ASHRAE 170-2017 Table 7.1 | 3-3655 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C610 | ACRF | General Operating Room (OR #2) | Positive | ASHRAE 170-2017 Table 7.1 | 3-3660 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C610A | ACRF | Operating Room, Sterile Storage | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 3-3664 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C611 | ACRF | Environmental Services (EVS) Room | Negative | ASHRAE 170-2017 Table 7.1 | 3-3672 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C612 | ACRF | X-Ray, Mobile C-Arm Alcove | Negative | ASHRAE 170-2017 Table 7.1 | 3-3676 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C614 | ACRF | General Operating Room (OR #3) | Positive | ASHRAE 170-2017 Table 7.1 | 3-5433 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C614A | ACRF | Clean Storage Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 3-5461 | CRC | Clean/Med Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C642 | ACRF | Clean Storage Room | Positive | ASHRAE 170-2017 Table 7.1 | 3-5618 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C706 | ACRF | Cardiac Catheter System Component Room | Positive | ASHRAE 170-2017 Table 7.1 | 3-5624 | CRC | Intensive Care - Patient Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C710 | ACRF | Clean Storage Room | Positive | ASHRAE 170-2017 Table 7.1 | 3-5628 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C716 | ACRF | Endoscope, Sterilization and Storage Room | Negative | ASHRAE 170-2017 Table 7.1 | 3-5636 | CRC | Patient Room - Proctective Environment (PE) | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C717 | ACRF | MRI Scanning Room | Positive | ASHRAE 170-2017 Table 7.1 | 3-5640 | CRC | Intensive Care - Patient Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C718 | ACRF | Central Sterile, Receiving and Decontamination | Negative | ASHRAE 170-2017 Table 7.1 | 3-5649 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C722 | ACRF | Instrument Sterilization Room | Negative | ASHRAE 170-2017 Table 7.1 | 3-5660 | CRC | Intensive Care - Patient Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C729 | ACRF | Cardiac Catherization Laboratory | Positive | ASHRAE 170-2017 Table 7.1 | 3-5664 | CRC | Intensive Care - Patient Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C733 | ACRF | Clean Storage Room | Positive | ASHRAE 170-2017 Table 7.1 | 3-5672 | CRC | Intensive Care - Patient Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C735 | ACRF | Surgical Suite, Workroom And Supply Space | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 3-5676 | CRC | Intensive Care - Patient Room | Positive | ASHRAE 170-2017 Table 7.1 |
| 2C735A | ACRF | General Operating Room (OR #12) | Positive | ASHRAE 170-2017 Table 7.1 | 5-1665 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C741 | ACRF | Surgical Suite, Workroom And Supply Space | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 5-2428 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C741A | ACRF | General Operating Room (OR #11) | Positive | ASHRAE 170-2017 Table 7.1 | 5-2459 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C741B | ACRF | Clean Storage Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 5-2637 | CRC | Therapy Tub Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C743 | ACRF | Clean Storage Room | Positive | ASHRAE 170-2017 Table 7.1 | 5-3433 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C753 | ACRF | Clean Storage Room | Positive | ASHRAE 170-2017 Table 7.1 | 5-5433 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C756 | ACRF | Clean Storage Room | Positive | ASHRAE 170-2017 Table 7.1 | 5-5661 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C765 | ACRF | Clean Storage Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 7-3661 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C767 | ACRF | General Operating Room (OR #10) | Positive | ASHRAE 170-2017 Table 7.1 | 7-5671 | CRC | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 2C767B | ACRF | Clean Storage Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | 1N318 | Old Bldg. 10 | Lab | Negative | ASHRAE 170-2017 Table 7.1 |
| 3S261 | ACRF | Medical Autopsy Room | Negative | ASHRAE 170-2017 Table 7.1 | 1N320 | Old Bldg. 10 | Lab | Positive | ASHRAE 170-2017 Table 7.1 |
| 5C310 | ACRF | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 | B1C267 | ACRF | Endoscope, Sterilization and Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 7C426 | ACRF | Exam Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | B1C275/279* | ACRF | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 |
| 9C426 | ACRF | Exam Room, Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | B1C285A | ACRF | Soiled Instrument and Equipment Receiving and Decontamination Room, Healthcare | Negative | ASHRAE 170-2017 Table 7.1 |
| 11C424A | ACRF | Patient Room – Airborne Infection Isolation (AII) | Negative | ASHRAE 170-2017 Table 7.1 | 1C313 | ACRF | Radiography Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 |
| * These Rooms have dual room numbers | 1C315 | ACRF | Radiography Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | ||||
| Total Rooms = 85 | 1C323 | ACRF | Fluoroscopy Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | ||||
| 1C325 | ACRF | Fluoroscopy Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C402B | ACRF | Nuc. Med. Scan Room | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C433 | ACRF | Nuc. Med. Control Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C434 | ACRF | Nuc. Med. Scan Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C436 | ACRF | Nuc. Med. Scan Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C437 | ACRF | Lab | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C470C | ACRF | CT Scan Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C470F | ACRF | Class 1 Imaging Room | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C472 | ACRF | Nuc. Med. Hot Lab | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C474F | ACRF | PET Scan Room | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C478 | ACRF | Class 1 Imaging Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C482 | ACRF | Nuc. Med. Hot Lab | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C488A | ACRF | CT Scan Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C488F | ACRF | PET Scan Room | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C552 | ACRF | Anesthesia Work Room | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C560 | ACRF | CT Scan Room | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C562 | ACRF | CT Scan Room | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C569 | ACRF | Anesthesia Work Room | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C580A | ACRF | Class 2 Imaging Room | Positive | ASHRAE 170-2017 Table 7.1 | |||||
| 1C580C | ACRF | Angiography Room | Positive | ASHRAE 170-2017 Table 7.1 | |||||
| 1C580E | ACRF | Angiography Room | Positive | ASHRAE 170-2017 Table 7.1 | |||||
| 1C580G | ACRF | Class 2 Imaging Room | Positive | ASHRAE 170-2017 Table 7.1 | |||||
| 1C580K | ACRF | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 1C580R | ACRF | Post Procedure Area | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C580S | ACRF | Post Procedure Area | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C580T | ACRF | Post Procedure Area | Neutral / No Requirement | ASHRAE 170-2017 Table 7.1 | |||||
| 1C580EX | ACRF | Class 2 Imaging Room | Positive | ASHRAE 170-2017 Table 7.1 | |||||
| 1C580LX | ACRF | Clean Supply Room | Positive | ASHRAE 170-2017 Table 7.1 | |||||
| 2C533 | ACRF | Frozen Section Laboratory | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| 11C310 | ACRF | Soiled Utility/Storage Room | Negative | ASHRAE 170-2017 Table 7.1 | |||||
| * These Rooms have dual room numbers | |||||||||
| Total Rooms =113 |
ASHRAE 170 - Table 7.1
| Space Name | FGI Reference | Pressure Relationship to Adjacent Areas [ACH] | Minimum Outdoor Air Changes per Hour [ ACH ] | Minimum Total Air Changes per Hour [ACH] | Design Relative Humidity [ % ] | Design Temperature [ F° ] |
| Airborne Infection Isolation (AII) | 2.1-2.4.2 | Negative | 2 | 12 | max 60 | 70-75 |
| Anesthesia Workroom | 2.2-3.3.3 | Negative | N/R | 8 | N/R | N/R |
| Angiography Room | 2.2-3.4.2.1 (2) | Positive | 3 | 15 | max 60 | 70–75/21–24 |
| Clean Supply Room | 2.1-2.8.11.3 | Positive | 2 | 4 | N/R | N/R |
| Clean Workroom | 2.1-2.8.11.2 | Positive | 2 | 4 | max 60 | 72-78 |
| Computed Tomography (CT) Scan Room (NR) | 2.2-3.4.3.1 | No Requirement | 2 | 6 | max 60 | 72 - 78 |
| Computed Tomography (CT) Scan Room (NEG) | 2.2-3.4.3.1 | Negative | 2 | 12 | max 60 | 70–75/21–24 |
| Fluoroscopy Room (NR) | 2.2-3.4.4.3 | No Requirement | 2 | 6 | max 60 | 72–78/22–26 |
| Fluoroscopy Room (Positive) | 2.2-3.4.4.3 | Positive | 3 | 15 | max 60 | 70–75/21–24 |
| General Operating Room | 2.2-3.3.3 | Positive | 4 | 20 | 20-60 | 68-75 |
| Magnetic Resonance Imaging (MRI) Scan Room | 2.2-3.4.5.2 | Positive | 3 | 15 | 20-60 | 70-75 |
| Positron Emission Tomography (PET) Scan Room | 2.2-3.4.7.3 (2) | Negative | 2 | 6 | N/R | 70–75/21–24 |
| Post-Procedure Area – Phase II | 2.1-3.4.5 | No Requirement | 2 | 6 | 20–60 | 70–75/21–24 |
| Protective Environment (PE) | 2.2-2.2.4.3 | Positive | 2 | 12 | max 60 | 70-75 |
| Protective Environment Airborne Isolation Room (PE/AII) | 2.2-2.2.4.3 | Positive | 2 | 12 | max 60 | 70-75 |
| Radiography Room | 2.2-3.4.4.2 | No Requirement | 2 | 6 | max 60 | 72 - 78 |
| Single-photon emission computed tomography (SPECT) Room | 2.2-3.4.7.4 | No Requirement | 2 | 6 | max 60 | 72 - 78 |
| Soiled Workroom/Storage | 2.1-2.8.12.2 | Negative | 2 | 10 | N/R | N/R |
| Sterile Processing Clean Workroom | 2.1-5.1.2.2 (3) | Negative | N/R | 10 | N/R | N/R |
| Sterile Processing Decontamination Room | 2.1-5.1.2.2 (2) | Negative | 2 | 6 | N/R | 72-78 |
| Sterile Storage | 2.1-5.1.2.4 (1) | Positive | 2 | 4 | max 60 | 68-73 F |
| Surgery - Clean Equipment Supply Storage (NR) | 2.2-3.3.7.13 | No Requirement | 2 | 6 | N/R | N/R |
| Surgery - Clean Equipment Supply Storage (POS) | 2.2-3.3.7.13 | Positive | 2 | 4 | max 60 | 72-78 |
File details come from the government source that posted it. Updated .