Text version

ATTACHMENT 1 FOR SOLICITATION HC101320QB254

TELECOMM PROVIDER MUST PROVIDE TOTAL FIBER MILES AND ROUND TRIP

DELAY (RTD) FROM THE CUSTOMER "A" LOCATION TO THE CUSTOMER "Z"

LOCATION. 10. BLANK 11. VENDOR MUST PROVIDE LIGHT LEVEL READINGS (DB

LOSS) ON L. PURPOSE STATEMENT CONTINUED: EXTENSION FROM COMMERCIAL

POP TO GOVERNMENT SERVICE DELIVERY POINT (SDP) AT THE "Z" LOCATION

PRIOR TO CIRCUIT TURN UP TO THE GOVERNMENT ENSURING LEVELS ARE

WITHIN SPECS. LIGHT LEVELS MUST BE ADJUSTED TO -3 TO -9. 12. VENDOR MUST

CONDUCT WALK-THROUGH SITE SURVEY PRIOR TO INSTALLATION AT THE "Z"

LOCATION ONLY. 13. VENDOR MUST CONTACT DISA GOC IP BACKBONE

ENGINEERING AND IMPLEMENTATION GROUP UPON RECEIPT OF A VALID TSO TO

ESTABLISH THE COORDINATION AND ACTIVATION PROCESS. D312-418-9935/9913,

C618-418-9935/9913. 14. PROVIDER MUST CONDUCT A SATISFACTORY 24-HOUR

TEST FROM THE DROP SIDE OF THEIR OR LOCAL EXCHANGE CARRIERS FDP

INSTALLED IN THEIR EQUIPMENT SUITE AT THE "A" LOCATION TO THE

GOVERNMENT'S SDP AT THE "Z" LOCATION AND MUST INCLUDE THE EXTENSION

BETWEEN THE COMMERCIAL DEMARC AND THE GOVERNMENT'S SDP AT THE "Z"

LOCATION. VENDOR MUST ENSURE A TEST SET IS PLACED AT THE DROP SIDE OF

TELECOMM PROVIDER'S OR LOCAL ACCESS PROVIDERS FDP AS APPLICABLE AT

THE "A" LOCATION AND A SECOND TEST SET AT THE END OF THE FIBER JUMPERS

TO BE USED FOR TERMINATION TO THE GOVERNMENT'S SDP AT THE "Z"

LOCATION. TESTING MUST BE SATISFACTORY PRIOR TO TURN OVER TO THE

GOVERNMENT FOR ACCEPTANCE TESTING. TESTING CRITERIA: VENDOR MUST

TEST THE CIRCUIT FOR 24 HOURS IAW ITU-T.Y.1564 BENCH MARKING

CONFIGURATION AND PERFORMANCE OF ETHERNET SERVICE. NOTE-ETHERNET

FRAME SIZE DESIGNATOR 'H' (MTU) IS EQUAL TO 9100 BYTES.

CIRCUIT REQUIRES THE FOLLOWING PARAMETERS: (A) FIBER TERMINATION:

FRAME FORMAT: 10GB ETHERNET (OPTICAL HANDOFF-10GB ETHERNET-LAN-

PHY-SINGLE MODE FIBER), 802.3AE, 1310NM. "SC" CONNECTORS. (B) COMMITTED

INFORMATION RATE (CIR) - 10GB. (C) 10GB ETHERNET - LAN-PHY INTERFACE

REQUIRED AT COMMERCIAL DEMARC AT THE A AND Z LOCATIONS. (D)

ETHERNET FRAME SIZE WILL BE CONFIGURED TO SUPPORT MAXIMUM

TRANSMISSION UNIT (MTU) OF 9100 OCTETS (BYTES). (E) NO NETWORK

INTERFACE UNIT, DEDICATED PATH (F) GFE CLOCKING: VENDOR ESFU (OR

EQUIVALENT) NOT TO BE ENGINEERED INTO CIRCUIT. (G) TESTING CRITERIA:

VENDOR MUST TEST THE CIRCUIT FOR 24 HOURS IAW ITU-T.Y.1564 BENCH

MARKING CONFIGURATION AND PERFORMANCE OF ETHERNET SERVICE. NOTE-

ETHERNET FRAME SIZE DESIGNATOR 'H' (MTU) IS EQUAL TO 9100 BYTES. (H) LINE

MUST REMAIN FULLY OPERATIONAL AND AVAILABLE TO USERS 24 HOURS A

DAY, SEVEN DAYS PER WEEK, AT LEAST 99.5% OR BETTER. (I) 1 HOUR RESPONSE

TIME TO RESPOND TO CUSTOMER UPON RECIEPT OF TROUBLE. (J) VENDOR

REQUIRED TO HAVE CIRCUIT VISIBILITY TO ASSIST IN ANY CIRCUIT OUTAGES. N.

CIRCUIT SPECIFICATIONS CONTINUED: (K) VENDOR MUST HAVE A 24X7

NETWORK OPERATIONS CENTER. (L) TELECOMM PROVIDER MUST MAINTAIN

OPERATIONS, MAINTENANCE AND ADMINISTRATION MONITORING OF

ETHERNET CIRCUIT IAW ITU-T-Y.1731. (M) THE COMMERCIAL CIRCUIT WILL BE

ACCEPTED ON BEHALF OF THE GOVERNMENT BY THE DISA GOC IP BACKBONE

ENGINEERING AND IMPLEMENTATION GROUP, SCOTT AFB, IL. (C) 618-418-8627 (D)

770-8627.

THE LONG-HAUL CIRCUIT NO. AND LEC CKT ID'S AS APPLICABLE TO THE DISA

IE161 PROGRAM OFFICE PRIOR TO TURN UP TO THE GOVERNMENT. PRIMARY:

RAY BURKE (301) 225-2550 ALTERNATE: KEN DIEF (301) 225-2416 2. VENDOR

WINNING AWARD IS RESPONSIBLE FOR INSTALLATION AND MAINTENANCE OF

10GBE SERVICE IAW THE UNIQUE INSTALLATION FACTORS. 3. INSIDE WIRING IS

AUTHORIZED IAW THE UNIQUE INSTALLATION FACTORS. 4. VENDOR MUST

COORDINATE SITE VISIT WITH POC'S 72 HOURS IN ADVANCE PRIOR TO

REQUIRING ACCESS TO FACILITIES AT BOTH USER LOCATIONS. 5. ALL

EQUIPMENT AND CIRCUIT PROBLEMS WILL BE REPORTED BY PHONE TO THE

DISA GOC IP BACKBONE ENGINEERING AND IMPLEMENTATION GROUP, SCOTT

AFB, IL. PRIMARY: (C) 618-418-9950, (D)770-9950 TOLL FREE: 855-868-9950 6. DD

FORM 1368 WILL BE SUBMITTED ON THIS TRUNK IAW DISAC-DITCO 350-135-1 BY

RNSOC, SCOTT AFB, IL. GUIDANCE ON SUBMISSION IS AVAILABLE AT

<HTTP://WWW.DITCO.DISA.MIL/ASP/PUBLICATIONS.ASP> CLICK ON "DISA-DITCO

CIRCULAR, 350-135-1, DEFENSE COMMERCIAL COMMUNICATIONS ACQUISITION

PROCEDURES."

TEST & ACCEPTANCE INSTRUCTIONS: MINIMUM TECHNICAL SPECIFICATIONS:

SPECIFIC FORMAT TO BE USED IS: LINE RATE: 10. GIGABITS/S, +- 100 PPM LINE

CODE: OPTIC ETHERNET FRAME: 9100 OCTETS (BYTES) 1. TEST AND

ACCEPTANCE: 10GB LAN PHY CIRCUITS SHALL PASS A FULLY DOCUMENTED

SATISFACTORY 72 HOUR SOAK TEST BY DISA GOC AT SCOTT AFB, IL. PRIMARY:

D312-418-9935/9913, C618-418-9935/9913. 2. TESTING PARAMETERS AND

THRESHOLDS: THE FOLLOWING TESTING PARAMETERS SHALL BE MEASURED

DURING TEST AND ACCEPTANCE TESTING. ERROR PERFORMANCE SHALL BE

MEASURED AND RECORDED OVER THE DURATION OF THE CONTIGUOUS 24 HOUR

TESTING INTERVAL AND SHALL BE MEASURED AND RECORDED PER DEFINITION

IN ITU-T-Y.1564. 3. ERROR PERFORMANCE: ERROR PERFORMANCE SHALL BE

BETTER THAN THE FOLLOWING PARAMETER THRESHOLDS TO BE ACCEPTABLE:

AVAILABILITY SHALL BE GREATER THAN 99.5% OR BETTER. FRAME LOSS SHALL

BE EQUAL TO ZERO WHEN TESTING AT 10 GIGABIT HIGHEST FRAME RATE, AND

SHALL MEET ITU-T-Y.1564 STANDARDS. JITTER SHALL BE LESS THAN 3 MSEC.

DELAY SHALL BE BETTER THAN 10 MSEC 4. MEAN TIME TO LOSS OF BIT COUNT

INTEGRITY (MTTLBCI) SHALL BE GREATER THAN 24 HOURS. 5. ROUND TRIP

DELAY (RTD): RTD SHALL BE MEASURED OVER THE 10GB WAVE CIRCUIT AND

SHALL BE LESS THAN OR EQUAL TO 10 MILLISECONDS.