This document is an Attachment 1- Drawings (81-00001-3J) related to a Request for Proposal (RFP) issued by the Department of the Army Materiel Command Army Contracting Command. The RFP (Solicitation Number: W90VN924R0093) is for the Repair Deteriorated Bldg. No. S-1330 at the Busan Storage Facility. The RFP is limited to existing Area IV General Construction Multiple Award Indefinite Delivery Indefinite Quantity (MAIDIQ) Contractors with specific contract numbers. A site visit has been scheduled for May 23, 2024 at 10:30 a.m. The attachment contains drawings related to the repair work required under this contract opportunity.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFP-W90VN924R0093.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
R-11SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
APPROVED BY
PROJECT NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
O & M
HOUSING DIV.
REVIEWED BY
UNITED STATES ARMY GARRISON DAEGU
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
DIRECTORATE OF PUBLIC WORK
HGFEDCBA
D - 24 - 22
CHON, HYON TAE
DESIGN REVIEW SIGNATURE
ORGANIZATION
USING AGENCY
36TH SIGNAL
MASTER PLN.
ENVIRONMENTAL
NAME SIGNATURE
O&M DIV.
FIRE DEPT.
SAFETY OFFICE
DPTMS(AT/FP)
188TH MP COM.
IND. HYGENIST
UNIT #15746, APO AP 96218-5746
DRAWING NO.
CHIEF,
DESIGN & TECH. REVIEW Br.
AS SHOWN
1 1 OF 1R - 1
T I T L E S H E E T
TITLE SHEET
USING AGENCY
DATE:25 APR 24
81-00001-3J
CIVIL
3 OF 46AD101
9 8 OF 46
10 9 OF 46
AE101
AE201
AE301
AE302
11 10 OF 46AE303
12 11 OF 46M - 1
13 12 OF 46M - 2
14 13 OF 46M - 3
19 18 OF 46
20 19 OF 46
M - 4
M - 5
M - 6
M - 7
M - 8
M - 9
21 20 OF 46M - 10
22 21 OF 46M - 11
23 22 OF 46M - 12
24 23 OF 46M - 13
29 28 OF 46
M - 14
M - 16
M - 17
M - 18
39 38 OF 46
40 39 OF 46
E - 6
E - 7
E - 8
E - 9
E - 10
E - 11
41 40 OF 46E - 12
42 41 OF 46E - 13
43 42 OF 46E - 14
E - 15
E - 16
E - 17
E - 18
PANEL SCHEDULE "A", "B", "C", "2PD" AND "D2"
BLDG. NO. S-1330
REPAIR DETERIORATED
PROJECT NO. 81-00001-3J, BSF
BLDG. NO. S-1330
REPAIR DETERIORATED
BSF
34 33 OF 46
E - 1
E - 2
E - 3
E - 4
E - 5
ELECTRICAL
ARCHITECTURAL
MECHANICAL
A001
A002
AD102
AD103
M - 15
SCOPE OF WORK
LEGEND AND ABBREVIATIONS
GENERAL NOTES
GENERAL NOTES AND SCOPE OF WORK
EQUIPMENT SCHEDULE
NEW REFRIGERATION PLAN (ZONE - 1)
NEW REFRIGERATION PLAN (ZONE - 2)
DETAIL DRAWINGS - 1
DETAIL DRAWINGS - 2
DETAIL DRAWINGS - 3
LEGEND, NOTES AND SCOPE OF WORKS
POWER PLAN - RECEPTACLE
POWER PLAN - FREEZER AND CHILLING SYSTEM
POWER PLAN- ROOF TOP AND MECH. RM
EXISTING/ REMOVAL POWER SINGLE LINE DIAGRAM
NEW POWER SINGLE LINE DIAGRAM
PANEL SCHEDULE "4PA", "4PC", "4PD" AND "M"
PANEL SCHEDULE "2PB", "2PC" AND "M"
FIRE ALARM PLAN - 1ST FLOOR
FIRE ALARM SINGLE LINE DIAGRAM
GENERAL NOTES, SPECIFIC NOTES, MATERIAL NOTES
CAM-LOCK TYPE PIR INSULATION PANEL SYSTEM (TYP), PHOTO VIEW
DOOR SCHEDULE, DOOR TYPES, NOTE
INTERIOR & EXTERIOR FINISH SCHEDULE, MATERIAL COLOR SCHEDULE, ABBREVIATION, NOTE, GENERAL NOTES
CEILING DETAILS (TYP)
EXISTING / REMOVAL REFRIGERATION PLAN (ZONE - 1)
EXISTING / REMOVAL REFRIGERATION PLAN (ZONE - 2)
REMOVAL / NEW HVAC PARTIAL PLAN - MECH. ROOM
EXISTING / REMOVAL DRAIN PIPING PLAN (ZONE - 1)
EXISTING / NEW DRAIN PIPING PLAN (ZONE - 1)
EXISTING / REMOVAL FIRE PROTECTION PIPING PLAN (ZONE - 1)
EXISTING / REMOVAL FIRE PROTECTION PIPING PLAN (ZONE - 2 & VALVE ROOM)
NEW FIRE PROTECTION PIPING PLAN (ZONE - 1)
NEW FIRE PROTECTION PIPING PLAN (ZONE - 2 & VALVE ROOM)
LIGHTING PLAN - 1ST FLOOR AND 2ND FLOOR
LIGHTING FIXTURE SCHEDULE, LIGHTING FIXTURE DETAILS AND EXTERIOR LTG. CONTROL DIAGRAM
POWER PLAN - SLIDING DOORS AND AIR CURTAINS
PANEL SCHEDULE "2PA", "2PE", "2PM" AND DETAIL OF ARC FLASH LABELS
FIRE ALARM PLAN - 2ND FLOOR AND ATTIC AREA
FIRE ALARM NOTIFICATION AND MASS NOTIFICATION SYSTEM PLAN - 1ST AND 2ND FLOOR
FIRE ALARM REMOTE AND CONTROL WIRING PLAN
EXST / REMOVAL PLAN
CEILING REMOVAL PLAN
NEW FLOOR PLAN
ASBESTOS REMOVAL PLAN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
1.
2.
3.
6.
OF CONSTRUCTION SHALL BE USED.
NOT SPECIFICALLY INDICATED BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS
DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE
EXISTING UTILITIES AS A RESULT OF HIS/HER WORK.
OF CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE AND SHALL PAY FOR ALL DAMAGES TO
TO UTILITIES. NOTIFY THE OWNER’S REPRESENTATIVE OF ANY UNDERGROUND UTILITIES IN THE WAY
EXTREME CAUTION AND MUST EXERCISE PROPER CARE DURING EXCAVATION TO PREVENT DAMAGE
ACCURACY OR THE EXISTENCE OF OTHER OBSTACLES WHICH MAY BE ENCOUNTERED WORK WITH
PLANS ARE FROM THE LATEST AVAILABLE RECORDS BUT ARE NOT GUARANTEED AS TO THE
THE EXISTENCE AND LOCATION OF UNDERGROUND UTILITIES AND STRUCTURES AS SHOWN ON THESE
4.
LOCATIONS AND DEPTHS PRIOR TO EXCAVATION FOR THE NEW LINES.
CONTRACTOR SHALL EXPOSE THE EXISTING LINES AT THE PROPOSED CONNECTIONS TO VERIFY THEIR
WHEREVER CONNECTIONS OF NEW UTILITIES TO EXISTING UTILITIES ARE SHOWN ON THE PLANS, THE
THE PROJECT AREA PRIOR TO EXCAVATING. THE CONTRACTOR SHALL COORDINATE ALL WORK.
THE CONTRACTOR SHALL NOTIFY ALL AGENCIES TO VERIFY THE ACTUAL LOCATION OF ALL UTILITIES IN
5.
ADDITIONAL COSTS TO THE OWNER.
SCHEDULED TO REMAIN DURING THE CONSTRUCTION PERIOD WHICH SHALL BE REPAIRED AT NO
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGES INCURRED TO EXISTING WORK
7.
PATCHING SHALL MATCH THE FINISH OF THE ADJACENT SURFACES.
THE CONTRACTOR SHALL PATCH ALL SURFACES EXPOSED FROM CUTTING, AND/OR REMOVAL WORK.
8.
ACCESSIBILITY GUIDELINES (ADAAG).
ALL STANDARDS, REQUIREMENTS AND GUIDELINES OF THE AMERICANS WITH DISABILITIES ACT
ALL GOVERNING AGENCIES. THIS WORK SHALL BE DESIGNED AND CONSTRUCTED TO CONFORM WITH
ALL WORK SHALL CONFORM TO ALL APPLICABLE LAWS, CODES, REGULATIONS, AND ORDINANCES OF
9. ALL DIMENSIONS SHOWN ON FLOOR PLAN ARE TO FACE OF FINISH, UNLESS OTHERWISE.
10.
PROVIDE DUST CONTROL MEASURES AS REQUIRED.
CLEAN AND FREE FROM ACCUMULATION OF WASTE MATERIALS AND RUBBISH. CONTRACTOR SHALL
AREA, THE OWNER’S PREMISES, INCLUDING STREETS AND OTHER AREAS USED BY THE CONTRACTOR
CONTRACTOR SHALL, AT ALL TIMES, DURING THE COURSE OF THE WORK, KEEP THE CONSTRUCTION
11.
OF OPERATIONS, INTERRUPTION OF MECHANICAL AND ELECTRICAL UTILITIES.
DELIVERY ACCESS TO AND FROM WORK, SPECIAL NOISY OPERATIONS, TIMING OF WORK, SEQUENCE
COORDINATE ALL OPERATIONS WITH THE OWNER’S REPRESENTATIVE FOR MATERIALS STORAGE,
12.
DEBRIS, RUBBISH, AND CONSTRUCTION MATERIAL AT TIME OF FINAL ACCEPTANCE.
REMOVE BARRICADE AFTER COMPLETION OF THE PROJECT AND CLEAN THE PROJECT AREA OF ALL
PREVENT PEOPLE FROM ENTERING THE PROJECT AREA AND TO PROTECT THE ENCLOSED PROPERTY.
CONTRACTOR SHALL PROVIDE BARRICADES, AS REQUIRED, AND ACCEPTABLE TO THE OWNER TO
13.
REPRESENTATIVE.
TRADE SHALL BE USED TO RESOLVE SUCH DISCREPANCIES AND MUST BE APPROVED BY THE OWNER’S
SUBMIT SHOP DRAWINGS ON HOW THEY WILL RESOLVE SUCH DISCREPANCIES. GENERAL PRACTICE OF
SHALL BE BORNE BY THE CONTRACTOR AND IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO
QUESTIONS RAISED DURING CONSTRUCTION PHASE THAT MAY RESULT IN EXTRA COST, SAID COST
ALL DISCREPANCIES FOUND ON DRAWINGS DURING CONSTRUCTION PHASE, ANY DISCREPANCIES OR
IT SHALL BE CONTRACTOR’S RESPONSIBILITY TO NOTIFY THE OWNER’S REPRESENTATIVE FOR ANY OR
14. CONTRACTORS SHALL VERIFY ALL QUANTITIES.
STATE PROPERTY IN ACCORDANCE WITH ALL LOCAL GOVERNING LAWS AND REGULATIONS.
BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE DISPOSED OF OUTSIDE THE LIMITS OF
ALL MATERIALS REQUIRED TO BE DISPOSED OF IN THIS PROJECT UNLESS REQUIRED TO BE SALVAGED, INTENDED TO LIMIT THE WORK REQUIRED IN ANY WAY.
TITLES, CAPTIONS, HEADINGS, ETC. ARE INTENDED FOR GENERAL REFERENCE AND ARE NOT
THE ABOVE NOTES APPLY TO THE FULL SET OF CONSTRUCTION DOCUMENTS.
1.
2.
3.
4.
GENERAL NOTES
OFFICER.
ANY DISCREPANCIES SHALL BE BROUGHT IMMEDIATELY TO THE ATTENTION OF THE CONTRACTING
PRIOR TO COMMENCING ANY CONSTRUCTION.
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFYING ALL EXISTING CONDITION AND DIMENSIONS
THE CONTRACTING OFFICER.
AREAS CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AS DIRECTED BY
THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING
TRAFFIC AND OPERATIONS.
NECESSARY PRECAUTIONS FOR THE PROTECTION AND SAFETY OF THE PUBLIC AND/OR MILITARY
BARRICADES, MARKERS, CONES AND OTHER PROTECTIVE FACILITIES AND SHALL TAKE ALL
THE CONTRACTOR SHALL PROVIDE, INSTALL, AND MAINTAIN ALL NECESSARY SIGNS, LIGHTS, FLARES, CONTRACTOR.
INCURRED FOR SPILL CONTAINMENT AND CLEAN-UP SHALL BE THE RESPONSIBILITY OF THE
OFFICER SHALL OVERSEE THE CLEAN-UP EFFORT AND RENDER THE SITE CLEAN. ALL COSTS
APPROPRIATE MEASURES TO CONTAIN AND ADEQUATELY CLEAN-UP THE SPILL. THE CONTRACTING
CONSTRUCTION. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER AND UTILIZE
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY SEWAGE SPILLS CAUSED DURING
WORK.
OF THIS WORK MUST BE DONE TO INSURE ROUGH-IN WORK IS ACCOMPLISHED PRIOR TO FINISHING
REPLACEMENT OF MECHANICAL, ELECTRICAL, TELEPHONE AND FIRE ALARM SYSTEM COORDINATION
CUT, PATCH AND RESTORE WALLS, FLOORS AND CEILING TO MAKE WAY FOR THE INSTALLATION AND
INCONVENIENCE TO THE CUSTOMER’S MISSION OPERATION.
APPROVAL FROM THE GOVERNMENT AND EXECUTE WORK STAGE BY STAGE WITHOUT ANY
THE CONTRACTOR SHALL SUBMIT WORK SCHEDULE PRIOR TO COMMENCING THE WORK AND GET
CONTRACTOR.
THAT MAY OCCUR DURING THE COURSE OF HIS WORK SHALL BE RESTORED AT THE EXPENSE OF THE
THE CONTRACTOR SHALL TAKE MEASURES TO PROTECT EXISTING FACILITIES AND ANY DAMAGES
MATCHING EXISTING COLOR AND FINISH.
ANY STRUCTURAL STEEL MEMBERS EXPOSED TO INTERIOR SPACE SHALL BE RE-PAINTED WITH
CONTRACTING OFFICER AT THE LOCATION INDICATED BY CONTRACTING OFFICER.
SALVAGEABLE MATERIALS SHALL BE REMOVED FROM WORK SITE IN A MANNER AND TURNED OVER TO
1.
2.
3.
4.
CONDITIONS AND SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL.
SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD
SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS.
15. FILL EXISTING DUCT AND PIPE HOLE W/ CONCRETE.
16.
RESPONSIBLE FOR REPAIR OR REPLACEMENT OF ACCESS DOOR AND WALL.
THE CONTRACTOR SHALL VERIFY THE NEW EQUIPMENT ACCESS CONDITIONS AT JOB SITE AND WILL BE
17.
18.
19.
AND SPECIFIC NOTES ON THE CONTRACT DRAWINGS.
THE CONTRACTOR SHALL FOLLOW THE CONSTRUCTION WORK AS INDICATED ON THE GENERAL NOTES
20.
CONTRACTOR SHALL SUBMIT ALL MATERIAL & COLOR SAMPLES TO DPW FOR APPROVAL.
COLOR AND PATTERN WHICH MANUFACTURERS STANDARD MUST APPROACH.
MATCH FOR MANUFACTURER COLOR IS NOT REQUIRED. THE SELECTIONS SERVE ONLY TO INDICATE
NOT INTENDED TO LIMIT SELECTIONS TO PRODUCTS OF THE MANUFACTURERS INDICATED. AN EXACT
COLORS AND PATTERNS LISTED BY MANUFACTURES ARE FOR IDENTIFICATION PURPOSES ONLY, AND
CONTRACT DRAWING.
THE CONTRACTING OFFICER. A SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE
CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL TO
5.
INSTALLATION.
DETAILS AND DRAWING SHALL BE APPROVED BY THE C.O. OR HIS COR. BEFORE FABRICATION AND
INSTRUCTIONS. THE CONTRACTOR SHALL PREPARE SHOP DRAWINGS FOR ALL DOOR AND WINDOW
ALL DOORS AND WINDOWS SHALL BE FABRICATED I.A.W. SPECIFICATIONS AND MANUFACTURER’S
CONTRACT.
ACCOMPLISH THE ARCHITECTURAL SCOPE OF WORK AT NO ADDITIONAL COST TO THE PROJECT
AGENCY, KOREA REGION OFFICE" FROM A PART OF THIS PROJECT. THE DETAILS WILL BE UTILIZED TO
PROJECTS, KOREA, NOVEMBER 30, 2015, DEPARTMENT OF THE ARMY INSTALLATION MANAGEMENT
THE ARCHITECTURAL STANDARD DRAWINGS SHOWN IN THE "STANDARD DETAIL DRAWINGS FOR O&MA 5.
6. REMOVE & CLEAN EXISTING FINISH MATERIAL & ADHESIVE BY GRINDING TO RECEIVE VCT & TILE.
7. REMOVE & CLEAN EXISTING PAINT BY SAND PAPER/ GRINDING FOR NEW PAINTING AND COATING.
8.
FREE.
SHEET (MSDS), WRITTEN IN ENGLISH, FROM THE MANUFACTURE SHOWING THE PRODUCT IS LEAD
OF THIS PROJECT. THE CONTRACTOR WILL PROVIDE A CERTIFICATE OR MATERIAL SAFETY DATA
LESS THAN 0.05 PERCENT LEAD BY WEIGHT OF THE NON-VOLATILE SOLIDS) DURING THE EXECUTION
THE CONTRACTOR IS REQUIRED TO USE "LEAD FREE" COATINGS (LIQUID PAINTS OR COATINGS WITH
9.
AND USER.
THE CONTRACTOR SHALL COORDINATE ALL PHASES OF WORK WITH THE CONTRACTING OFFICER
REQUIREMENTS MANUAL EM 385-1-1 LATEST EDITION.
THE CONTRACTOR SHALL PERFORM ALL WORKS IN ACCORDANCE WITH USACE SAFETY AND HEALTH
AND THE ENVIRONMENTAL GOVERNING STANDARDS FOR KOREA, USFK REGULATION 201-1.
ALL DISPOSAL WORK SHALL BE IN ACCORDANCE WITH APPLICABLE KOREAN ENVIRONMENTAL LAWS
CONTRACT, AND SHALL BE RESOLVED BEFORE PROCEEDING WITH THE WORK.
OMISSIONS OR CONFLICTS WHICH PREVENT HIM OR HER FROM FULFILLING THE TERMS OF THE
CONTRACTOR SHALL PROMPTLY NOTIFY THE OWNER’S REPRESENTATIVE OF ANY DISCREPANCIES, WITH THE REQUIRED WORK.
SHALL VERIFY ALL CONDITIONS AND DIMENSIONS RELATING TO THE PROJECT BEFORE COMMENCING
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK OF ALL TRADES AND
WITHOUT WRITTEN APPROVAL OF THE OWNER’S REPRESENTATIVE.
THAT THE PROPER REVISIONS MAY BE MADE. MODIFICATION OF DETAILS SHALL NOT BE MADE
CONFLICT WITH THE DRAWINGS, THEY SHALL BE REPORTED TO THE OWNER’S REPRESENTATIVE SO
BEST PRESENT KNOWLEDGE, BUT WITHOUT GUARANTEE OF ACCURACY. WHERE ACTUAL CONDITIONS
ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS IS GIVEN AS THE
6.
7.
8.
9.
10.
11.
12.
13.
SPECIFIC NOTES MATERIAL NOTES
ARCHITECTURAL
MATERIAL NOTES
SPECIFIC NOTES
GENERAL NOTES
AS SHOWN A001
THROUGH COR.
NEW SURVEY REPORT AND ASBESTOS REMOVAL DOCUMENTATION TO ENVIRONMENTAL OFFICE
THE KOREA ENVIRONMENTAL GOVERNING STANDARD (KEGS). THE CONTRACTOR SHALL PROVIDE THE
PRIOR TO ANY WORK TO ASSURE THAT APPROPRIATE ASBESTOS CONTROL IS IN ACCORDANCE WITH
THE WORK AREA WILL NEED TO BE RESURVEYED AND ASBESTOS MATERIALS SHOULD BE REMOVED
CONTRACTOR SHALL CASE WORK IN THE AFFECTED AREA AND NOTIFY THE CONTRACTING OFFICER.
WORK. HOWEVER, IF SUSPECTED ASBESTOS CONTAINING MATERIAL ARE DISCOVERED, THE
FREE. TESTS HAVE INDICATED THAT ASBESTOS IS NOT PRESENT IN THE AREA AFFECTED BY THIS
OR MSDS, WRITTEN IN ENGLISH, FROM THE MANUFACTURER VERIFYING THE PRODUCT IS ASBESTOS
WEIGHT) DURING THE EXECUTION OF THIS PROJECT. THE CONTRACTOR WILL PROVIDE A CERTIFICATE
THE CONTRACTOR IS REQUIRED TO USE "ASBESTOS FREE" MATERIALS (LESS THAN 1 PERCENT BY
BSF
KIM, CS
PAK, SY
25 APR 24
D - 24 - 22
14.
201-1, ENVIRONMENTAL GOVERNING STANDARD(EGS) CHAPTER 5 & CHAPTER 6.
STORED IN ACCORDANCE WITH THE CODE OF REGULATION 1910 SUBPART H AND USFK REGULATION
ALL HAZARDOUS MATERIAL AND HAZARDOUS WASTE USED/ CREATED DURING THE PROJECT MUST BE
81-00001-3J
BLDG. NO. S-1330
REPAIR DETERIORATED
1 46
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
ARCHITECTURAL
AS SHOWN
BSF
81-00001-3J
A002
SCOPE OF WORK
REMOVE EXISTING ASBESTOS CONTAINING MATERIAL.
REPLACE EXISTING CEILING AND WALL INSULATION WITH CAM-LOCK TYPE INSULATION PANEL SYSTEM.
REPLACE EXISTING CONCRETE FLOOR AND FLOOR FINISH WITH NEW.
REPLACE EXISTING GUARD POST WITH NEW.
REPLACE EXISTING FLOOR INSULATION WITH SPRAY IN TYPE RIGID INSULATION INCLUDING VAPOR BARRIER.
REPLACE EXISTING CEILING SYSTEM WITH NEW.
REPLACE EXISTING INSULATED DOOR SYSTEM INCLUDING AIR CURTAIN WITH NEW.
BLOCK-UP EXISTING OPENING AND REPLACE EXISTING LOUVER.
REPLACE EXISTING AIR CURTAIN WITH NEW.
PROVIDE NEW GUARD POST.
KIM, CS
PAK, SY
25 APR 24
D - 24 - 22
1. SEE GENERAL REQUIREMENTS ON DRAWING REF. NO. A001.
#1. REPAIR / MAINTENANCE : K - WORK
#2. GENERAL REQUIREMENTS
SCOPE OF WORK
PAINT INTERIOR AND EXTERIOR SURFACE. (WORKING AREA ONLY)
BLDG. NO. S-1330
REPAIR DETERIORATED
2 46
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
UP
2970H
30’-0"
20’-0"
10’-0"
10’-0"
20’-0"
26’-0"
5’-9"
11169
36’-8"
20’-0"
11100
36’-5"
10617
34’-10"
10617
34’-10"
11100
36’-5"
20’-0"
11227
36’-10"
1’
36779
120’-8"
1’-1"
78029
256’-0" 115145
377’-9"
15’-8"
30’-0"
101AD
4’-8"
11’-4"
23’-3"
10’-7"
104 112
ELEC
FREEZER
FREEZER
MECH
CHILLROOM
CHILLROOM
CHILLROOM
CHILLROOM
FREEZER
FREEZER
CORRIDOR
VEST
REMOVE EXST SINGLE SLIDING DOOR SYSTEM WITH AIR CURTAIN
REMOVE EXST DOUBLE SLIDING DOOR SYSTEM WITH AIR CURTAIN
REMOVE EXST SINGLE / DOUBLE DOOR SYSTEM WITH AIR CURTAIN
REMOVE EXST WINDOW / LOUVER
EXST / REMOVAL PLAN
REMOVE EXST MECH. RM. WITH STORAGE
AD101
ARCHITECTURAL
AS SHOWN
BSF
81-00001-3J
N
SCALE : 1 / 200
FLOOR REMOVAL NOTE:
REMOVE EXST CONCRETE FLOOR WITH FLOOR FOAMGLASS INSUL. / SPRAYED INSUL. SYSTEM
VEST
FREEZER
CORRIDOR
CORRIDOR
CORRIDOR
FREEZER
FREEZER
FREEZER
VEST
MECH
LOCKER RM
TOILET
KITCHEN
OFFICE
FREEZER
FREEZER
FREEZER
VEST
CORRIDOR
FREEZER
VEST
CORRIDOR
CORRIDOR
EXST / REMOVAL PLAN
KIM, CS
PAK, SY
25 APR 24
D - 24 - 22
SANDING EXST CONC FLOOR (SEE FLOOR REMOVAL NOTE 6.)
1.
2.
3.
4.
5.
6.
- REPAIR LARGE OR DEEP SURFACE IRREGULARITIES WITH A RAPID SETTING PATCHING COMPOUND.
- NON-MOVING CRACKS AND SAW CUT, CONTROL JOINTS ARE TO BE ROUTED, AND CLEANED.
- ALL SEALER, PAINT, WAX, COATINGS, FLOOR COVERING AND THEIR MASTIC, AS WELL AS ANY SURFACE CONTAMINANTS SUCH AS OIL OR FOOD SPILLS MUST BE REMOVED.
PREPARATION OF EXISTING FLOOR TO INSTALL CONCRETE DENSIFIER
THE CONTRACTOR SHOULD NOT REMOVE ANY COMPONENTS OF THE EXISTING STRUCTURE THAT ARE NOT INDICATED ON THE DRAWINGS.
REMOVE EXST 5" TO 6" SPRAYED INSUL. SYSTEM AT THE BOTTOM OF TOP SLAB.
REMOVE EXST 2-3" OR 2-4" LAYERS OF FOAMGLASS INSUL. SYSTEM AT THE BOTTOM OF TOP SLAB.
REMOVE EXST 4" TO 5" THK. APPROX. CONCRETE TOP SLAB.
REMAIN STRUCTURAL CONCRETE SLAB.
L E G E N D
INSULATION PANEL (REMAIN ONLY CMU & CONCRETE WALL AND STRUCTURAL COMPONENTS)
WD SHEATHING AND PLYWOOD / PROTECTIVE BARRIER / WAINSCOT WITH RIGID INSUL. /
REMOVE EXST CORK BD. INSUL. / SPRAYED INSUL. WITH CHICKEN WIRE / STUD AND RUNNER WITH
REMOVE EXST RAIL GUARDS, RESTORE DOCK SURFACE FINISH
BLDG. NO. S-1330
REPAIR DETERIORATED
3 46
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
AD
UP
30’-0"
20’-0"
10’-0"
10’-0"
20’-0"
26’-0"
5’-9"
11169
36’-8"
20’-0"
11100
36’-5"
10617
34’-10"
10617
34’-10"
11100
36’-5"
20’-0"
11227
36’-10"
1’
36779
120’-8"
1’-1"
78029
256’-0" 115145
377’-9"
15’-8"
30’-0"
VEST
FREEZER
CORRIDOR
CORRIDOR
CORRIDOR
FREEZER
FREEZER
FREEZER
VEST
MECH
LOCKER RM
TOILET
KITCHEN
OFFICE
FREEZER
FREEZER
FREEZER
VEST
CORRIDOR
FREEZER
VEST
CORRIDOR
CORRIDOR
ELEC
FREEZER
FREEZER
MECH
CHILLROOM
CHILLROOM
CHILLROOM
CHILLROOM
FREEZER
FREEZER
CORRIDOR
VEST
REMOVE EXST SUSPENDED CEILING INSULATED PANEL SYSTEM
AD102
ARCHITECTURAL
AS SHOWN
BSF
81-00001-3J
N
SCALE : 1 / 200
CEILING REMOVAL PLAN
(REMAIN ONLY ROOF STRUCTURAL COMPONENTS)
WD SHEATHING AND PLYWOOD
REMOVE EXST CORK BD. INSUL. / SPRAYED INSUL. WITH CHICKEN WIRE / STUD AND RUNNER WITH
CEILING REMOVAL NOTE:
CEILING REMOVAL PLAN
KIM, CS
PAK, SY
25 APR 24
D - 24 - 22
H=6500
H=4700
L E G E N D
THE CONTRACTOR SHOULD NOT REMOVE ANY COMPONENTS OF THE EXISTING STRUCTURE THAT ARE NOT INDICATED ON THE DRAWINGS.
REMOVE EXST SPRAYED INSUL. SYSTEM WITH VAPOR BARRIER.
REMOVE EXST CORKBOARD INSUL. SYSTEM WITH AL. FOIL VAPOR BARRIER.
REMOVE EXST CEILING JOIST WITH BLOCKING AND PLYWOOD CEILING BOARD.
REMAIN EXISTING ROOF STRUCTURAL COMPONENTS.1.
2.
3.
4.
5.
REMOVE EXST SUSPENDED CEILING SYSTEM
BLDG. NO. S-1330
REPAIR DETERIORATED
4 46
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
AD
N
UP
30’-0"
20’-0"
10’-0"
10’-0"
20’-0"
26’-0"
5’-9"
11169
36’-8"
20’-0"
11100
36’-5"
10617
34’-10"
10617
34’-10"
11100
36’-5"
20’-0"
11227
36’-10"
1’
36779
120’-8"
1’-1"
78029
256’-0" 115145
377’-9"
15’-8"
30’-0"
VEST
FRREEZER
CORRIDOR
CORRIDOR
CORRIDOR
FRREEZER
FRREEZER
FRREEZER
VEST
MECH
LOCKER RM
TOILET
KITCHEN
OFFICE
FRREEZER
FRREEZER
FRREEZER
VEST
CORRIDOR
FRREEZER
VEST
CORRIDOR
CORRIDOR
ELEC
FRREEZER
FRREEZER
MECH
CHILLROOM
CHILLROOM
CHILLROOM
CHILLROOM
FRREEZER
FRREEZER
CORRIDOR
VEST
SPRAY-ON COATING (GRAY)
TRANSITE BOARD
LEGEND
CHRYSOTILE 25%
CHRYSOTILE 3%
CONDITION
PHYSICAL
ASBESTOS
TYPE OF
DESCRIPTION
ACM
GOOD
GOOD
FRIABILITY
NON-FRIABLE
NON-FRIABLE
AD103
ARCHITECTURAL
AS SHOWN
BSF
81-00001-3J
ASBESTOS REMOVAL PLAN
SCALE : 1 / 200
ASBESTOS REMOVAL PLAN
KIM, CS
PAK, SY
25 APR 24
D - 24 - 22
"https://zotapro.com/asbestos-training/" "https://www.envtlmgmt.org/courses-and-registration/asbestos-training" "http://www.baos.com/training_category.php?aCategoryID=1" "https://www.zackacademy.com/class/asbestos-certification/asbestos-inspector" "https://www.epa.gov/asbestos/state-asbestos-contacts" SEE OMA SPEC. SECTION 02 82 14.00 10. AND THE BELOW URLs (INTERNET ADDRESSES).
WHO COMPLETED AN EPA-APPROVED TRAINING COURSE WITH EPA-APPROVED MAP PROGRAM.
8. ASBESTOS REMOVAL WORK SHALL BE SUPERVISED BY THE TRAINED AND ACCREDITED ASBESTOS PROFESSIONAL
THAT HAS CONDUCTED THE ASBESTOS INSPECTION OF THE RELEVANT FACILITY.
7. CLEAN UP, DISPOSAL AND REMOVAL OF ASBESTOS SHALL NOT BE CONDUCTED BY THE INSTITUTION
REMOVAL, CLEAN UP AND DISPOSAL WORK.
6. CONTRACTOR / SUPERVISOR SHALL THROUGHLY MANAGE AND SUPERVISE THE ENTIRE PROCESS OF ASBESTOS
WITH THEIR ASBESTOS RELATED DUTIES.
5. CONTRACTOR SHALL BE QUALIFIED AND MAINTAIN US EPA AHERA ACCREDITATION COMMENSURATE
ASBESTOS CONTAINING MATERIALS (ACM) THAT WAS REMOVED.
4. CONTRACTOR SHALL SUBMIT A REPORT SHOWING THE NATURE, LOCATION, AND QUANTITY OF THE
AND DISPOSAL, AND AIR MONITORING.
CONTAINING MATERIALS (ACM), AND THE PROCEDURES OF WORKER PROTECTION, ACM REMOVAL
DESCRIPTION OF WORK THAT WILL BE PERFORMED INCLUDING LOCATIONS, TYPES, AND QUANTITIES OF ASBESTOS BY INDIVIDUALS WHO HAVE CURRENT ACCREDITATIONS. THE SITE SPECIFIC WORK PLAN SHALL PROVIDE DETAILED
3. WORK PLAN THAT WILL BE REVIEWED BEFORE ANY WORK MAY BEGIN. THE WORK PLAN SHALL BE PREPARED
MATERIALS (ACM) SHALL BE PROPERLY DISPOSED IN ACCORDANCE WITH APPLICABLE R.O.K REGULATIONS.
REMOVAL AND PROTECTION OF WORKERS AND ENVIRONMENT. THE DISPOSAL OF ASBESTOS CONTAINING
2. CONTRACTOR SHALL COMPLY WITH ENVIRONMENTAL GOVERNING STANDARDS (EGS) REGARDING HANDLING,
- R.O.K OCCUPATIONAL SAFETY AND HEALTH LAWS, AND ENVIRONMENTAL LAW.
- U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA).
- UNITED STATE FORCES KOREA(USFK) ENVIRONMENTAL GOVERNING STANDARD (EGS, USFK REGULATION 201-1).
1. REGULATORY REQUIREMENT
ASBESTOS REMOVAL, CLEAN UP AND DISPOSAL WORK
BLDG. NO. S-1330
REPAIR DETERIORATED
5 46
AE101
ARCHITECTURAL
AS SHOWN
BSF
UP
30’-0"
20’-0"
10’-0"
10’-0"
20’-0"
26’-0"
5’-9"
11169
36’-8"
20’-0"
11100
36’-5"
10617
34’-10"
10617
34’-10"
11100
36’-5"
20’-0"
11227
36’-10"
36779
120’-8"
1’-1"
78029
256’-0" 115145
377’-9"
15’-8"
30’-0"
1’
N
101AE SCALE : 1 / 200
NEW FLOOR PLAN
L E G E N D
RAIL GUARDS / POST
SINGLE SLIDING DOOR SYSTEM WITH AIR CURTAIN
DOUBLE SLIDING DOOR SYSTEM WITH AIR CURTAIN
SINGLE / DOUBLE OVER-LAP DOOR SYSTEM WITH AIR CURTAIN
AL LOUVER
VEST
FREEZER
CORRIDOR
CORRIDOR
CORRIDOR
FREEZER
FREEZER
FREEZER
VEST
MECH
LOCKER RM
TOILET
KITCHEN
OFFICE
FREEZER
FREEZER
FREEZER
VEST
CORRIDOR
FREEZER
VEST
CORRIDOR
CORRIDOR
ELEC
FREEZER
FREEZER
MECH
CHILLROOM
CHILLROOM
CHILLROOM
CHILLROOM
FREEZER
FREEZER
CORRIDOR
VEST
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
D1 D1
D1 D1
D1
D1
D6 D6 D6 D6 D6 D6
NEW FLOOR PLAN
AE 102
XX
BLDG. PHOTO VIEW
KIM, CS
PAK, SY
25 APR 24
D - 24 - 2281-00001-3J
D1D2
D4D4
D4 D4
D4 D4 D4 D4
D3D3
D5 D5
D5 D5 D5 D5
D5 D5
D7
D8
D9
CMU WALL (H=2740mm)
21’-3"
10’-7"
AE 201
: RM#103 TO #110
EXISTING INSULATION WALL PANEL USING AREA
1.
2.
3.
4.
5.
6.
CAM-LOCK TYPE PIR INSULATION PANEL SYSTEM
THE CONTRACTOR SHALL CLEAN THE EXISTING PANELS THOROUGHLY AFTER COMPLETING CONSTRUCTION.
THE BUILDING, ARE INSTALLED.
THE CONTRACTOR SHALL INSTALL SUFFICIENT INSULATION BETWEEN THE WALL WHERE DOORS "D6" AND "D8", WHICH ARE CONNECTING PARTS OF
THE CONTRACTOR SHALL REPLACE OR REPAIR THE INSULATION MATERIAL ABOVE THE INSULATION PANEL CEILING THAT IS DAMAGED DURING WORK.
THE CONTRACTOR SHALL PERFORM PANEL REINFORCEMENT WORK NECESSARY FOR THE REPLACEMENT PART OF THE SLIDING DOOR.
PANEL REMAINS.
THE CONTRACTOR SHALL INSULATE AND PROPERLY FINISH ANY EXISTING OPENINGS OR DAMAGED AREAS IN THE SECTION WHERE THE EXISTING
THE CONTRACTOR SHALL ENSURE THAT THE EXISTING INSULATION PANEL IS NOT DAMAGED DURING THE CONSTRUCTION PERIOD.
BLDG. NO. S-1330
REPAIR DETERIORATED
6 46
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
AE201
ARCHITECTURAL
AS SHOWN
BSF
81-00001-3J
AE 201
SCREW BOLT 3/8"
SEALANT
FASTENER @ 1500
38x28x2T
AL ANGLE
CON’C FILL
SET ANCHOR 3/8"
WELDED WITH SET ANCHOR
STL ANGLE 50x50
SEALANT
AL HOOK MOLD
CONC WALL BASE / WHEEL STOP
SEALANT
SEALANT
AL HOOK MOLD
CONC WALL BASE / WHEEL STOP
CON’C FILL
FASTENER @ 1500
SCREW BOLT 3/8"
SEALANT
SEALANT
AL HOOK MOLD
/ WHEEL STOP
CONC WALL BASE
PIR INSULATION PANEL SYSTEM
CAM-LOCK TYPE 125mm THK.
PIR INSULATION PANEL SYSTEM
CAM-LOCK TYPE 125mm THK.
SEALANT
STORAGE STORAGE
STORAGESTORAGE
PIR INSULATION PANEL SYSTEM
CAM-LOCK TYPE 125mm THK.
PIR INSULATION PANEL SYSTEM
CAM-LOCK TYPE 125mm THK.
SEALANT
38x28x2T
AL ANGLE
SEALANT
SEALANT
38x28x2T
AL ANGLE
SEALANT
SEALANT
AL HOOK MOLD
CONC WALL BASE / WHEEL STOP
SET ANCHOR 3/8"
WELDED WITH SET ANCHOR
STL ANGLE 50x50 SET ANCHOR 3/8"
WELDED WITH SET ANCHOR
STL ANGLE 50x50
1A
WALL / CEILING PANEL PARTIAL DETAILS
1B 1C
PARTITION DETAIL
FASTENER (-) FASTENER (+)
SEALANT
FASTENER (+) FASTENER (-)
PIR INSULATION PANEL SYSTEM
CAM-LOCK TYPE 125mm THK.SEALANT
PANEL JOINT DETAIL PIR INSULATION PANEL DETAIL
1D 1E
STEEL SHEET 0.5T
SILICON POLYESTER COATED
PIR INSULATION 125T
STEEL SHEET 0.5T
SILICON POLYESTER COATED
H-BEAM
75x25x3.2T
C-CHANNEL
GALVANIZED
WELDING
ARC
WALL REINFORCING DETAIL
1F 1G
CEILING DETAILS
CONCRETE STEEL
EYE BOLT
CLIP
50x100x5T
STL PLATE
GALVANIZED
BRACKET
75x25x3.2T
C-CHANNEL
GALVANIZED
6mm
WIRE ROPE
C CHANNEL
CLIP
75x25x3.2T
C-CHANNEL
GALVANIZED
50x100x5T
STL PLATE
GALVANIZED
BRACKET
DOUBLE NUT
NOT TO SCALE
KIM, CS
PAK, SY
25 APR 24
D - 24 - 22
AE 201 NOT TO SCALE
CAM-LOCK TYPE PIR INSULATION PANEL SYSTEM (TYP)
10WINDOW / ETC
REMOVE EXST LOUVER /
NEW LOUVER
SEE MECH DWG FOR
PHOTO VIEW
PHOTO VIEW
PIR INSULATION PANEL SYSTEM (TYP)
CAM-LOCK TYPE
2-PLY 0.03mm THK. VINYL
URETHAN SPRAY 125mm AVG. THK. MIN.
CONCRETE FLOOR W/ WWF
CONCRETE DENSIFIER
2-PLY 0.03mm THK. VINYL
URETHAN SPRAY 125mm AVG. THK. MIN.
CONCRETE FLOOR W/ WWF
CONCRETE DENSIFIER
2-PLY 0.03mm THK. VINYL
URETHAN SPRAY 125mm AVG. THK. MIN.
CONCRETE FLOOR W/ WWF
CONCRETE DENSIFIER
1.
2.
INSULATION PANEL SYSTEM
DETAILS OF THE INSULATION PANEL SYSTEM TO DPW FOR APPROVAL.
THE CONTRACTOR SHALL SUBMIT FACTORY PRODUCTION DRAWINGS AND INSTALLATION
THIS BUILDING OVER THE PAST TEN(10) YEARS.
AS FOOD, LOGISTICS WAREHOUSES, AND DISTRIBUTION STORES SIMILAR FUNCTIONS TO
WHO HAS EXPERIENCE IN CONSTRUCTING MORE THAN HUNDRED(100) FACILITIES SUCH
COLD STORAGE INSULATION PANEL SYSTEM SHALL BE INSTALLED BY THE CONTRACTOR
BLDG. NO. S-1330
REPAIR DETERIORATED
7 46
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
REMARKS
HDW
SET
NOTHICK
NOS
TYPE
DOOR
WIDTH HEIGHT MATL
DOOR
LOUVER
FRAME
MATL
GLAZING
THE CONTRACTOR SHALL PREPARE SHOP DRAWINGS FOR ALL DOORS AND ALUMINUM WINDOWS
AS ACTUAL SIZE, AND DRAWINGS SHALL BE APPROVED BY THE CONTRACTING OFFICER BEFORE
FABRICATION AND INSTALLATION.
MANUFACTURERS LISTED ARE FOR IDENTIFICATION PURPOSES ONLY AND ARE NOT INTENDED TO LIMIT
SELECTIONS OF PRODUCTS. AN EXACT MATCH OF THE MANUFACTURERS FUNCTION, GRADE, COLOR &
QUALITY ARE NOT REQUIRED. BUT CONTRACTOR SHOULD INSTALL HIGH QUALITY AND GRADE PRODUCTS
WITH APPROVAL TO COR.
1. ALL DOORS AND WINDOWS SHALL BE FABRICATED IN ACCORDANCE WITH SPECIFICATIONS.
2.
3. ALL WOOD FLUSH DOORS SHALL BE FINISHED FACTORY COATED NATURAL COLOR FINISH.
( FINISH TO BE DETERMINED BY ARCH.)
4. FIRE DOORS AND FRAMES SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 80 FIRE DOORS AND
FIRE WINDOWS ASTM E119.
5. ELECTRONIC NETWORKED LOCKSET SHALL BE "SALTO" OR APPROVED EQUAL.
6. ALL LOCKS EXCEPT ELECTRONIC LOCKSET SHALL BE INTERCHANGEABLE CORE, "BEST-LOCK"
OR APPROVED EQUAL.
7. THE CONTRACTOR SHALL BE PREPARE SHOP DRAWINGS FOR SINGLE MASTER KEYING SYSTEM
DIAGRAM AND SHALL BE APPROVED BY THE COR. BEFORE APPLICATION.
8.
9. WINDOWS IN ALL AREAS WHERE FUNCTIONALLY WARRANTED SHALL BE EQUIPPED WITH HORIZONTAL
10.
THE CONTRACTOR SHALL PREPARE THREE (3) EACH OR MORE KEYING FOR EXTRA.
MINI BLINDS. COLOR SHALL BE WHITE OR LIGHT BEIGE TO MAXIMIZE REFLECTANCE AND MINIMIZE HEAT.
NOTES
D O O R S C H E D U L E
D - 24 - 22
ARCHITECTURAL
D1 A 2400 2700 MFR 100 MFR
--2400 2700 MFR 100 MFR
--B 2400 2700 MFR 100 MFR
--C 1200 2100 MFR 100 MFR
(LEVER TYPE) WITH AIR CURTAIN
INSULATED AUTOMATIC DOUBLE SLIDING DOOR
(LEVER TYPE) WITH AIR CURTAIN
INSULATED AUTOMATIC DOUBLE SLIDING DOOR
(LEVER TYPE) WITH AIR CURTAIN
INSULATED AUTOMATIC SINGLE SLIDING DOOR
WITH AIR CURTAIN
INSULATED MANUAL SINGLE OVER-LAP DOOR
--D 2400 2700 MFR 100 MFR
WITH AIR CURTAIN
INSULATED MANUAL DOUBLE OVER-LAP DOOR
MFR
MFR
MFR
MFR
MFR
--- EXST EXST EXST
WITH NEW AIR CURTAIN
EXST STEEL DOOR, DOOR FRAME
7’-8" 9’-0"
BY DR MFR
BY DR MFR
BY DR MFR
BY DR MFR
STRUCTURAL STEEL SUPPORT IS REQUIRED TO INSTALL SLIDING DOOR
BY DR MFR
--- EXST EXST
WITH NEW AIR CURTAIN
EXST COOLER SWING DOOR, DOOR FRAME
3’-0" 7’-0" -EXST
A
D O O R T Y P E S
B
(LEVER TYPE) WITH AIR CURTAIN
DOUBLE SLIDING DOOR
INSULATED AUTOMATIC
(LEVER TYPE) WITH AIR CURTAIN
SINGLE SLIDING DOOR
INSULATED AUTOMATIC
C
WITH AIR CURTAIN
SINGLE OVER-LAP DOOR
INSULATED MANUAL
WITH AIR CURTAIN
DOUBLE OVER-LAP DOOR
INSULATED MANUAL
D
BY MFR
BY MFR
AIRCURTAIN AIRCURTAIN AIRCURTAIN AIRCURTAIN
AIRCURTAIN AIRCURTAINAIRCURTAIN
--A 2400 2700 MFR 100 MFR
(LEVER TYPE) WITH AIR CURTAIN
INSULATED AUTOMATIC DOUBLE SLIDING DOOR
MFR
FLOOR HEATER (500L x 2400W)
BY DR MFR
AE301
BSF
KIM, CS
PAK, SY
25 APR 24
81-00001-3J
INSULATION : PIR INSULATION
DOOR FRAME : AL PROFILE
POWER : SINGLE PHASE, 220V, 2KW
SST SURFACE FINISH
INSULATION : PIR INSULATION
DOOR FRAME : AL PROFILE
POWER : SINGLE PHASE, 220V, 1KW
SST SURFACE FINISH
INSULATION : PIR INSULATION
LEVER : SST LEVER
DOOR : PVC+AL PROFILE
DOOR FRAME : AL PROFILE
OPERATION TYPE : TIMING BELT
MOTER : DC 150W
POWER : SINGLE PHASE, 220V, 3KW
STS 304 SURFACE FINISH
INSULATION : PIR INSULATION
LEVER : SST LEVER
DOOR : PVC+AL PROFILE
DOOR FRAME : AL PROFILE
OPERATION TYPE : TIMING BELT
MOTER : DC 150W
POWER : SINGLE PHASE, 220V, 3KW
STS 304 SURFACE FINISH
D2
D4
A
D3
--2400 2700 MFR 100 MFR MFR
FLOOR HEATER (500L x 2400W)
BY DR MFR
D5
(LEVER TYPE) WITH AIR CURTAIN
INSULATED AUTOMATIC SINGLE SLIDING DOOR
B
D6
D7
D8
D9
NOTE
DOOR SCHEDULE , DOOR TYPES
BLDG. NO. S-1330
REPAIR DETERIORATED
8 46
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
MATL
CEILING
FNSH COLOR HGT
REMARKS
MATL
FLOOR
ROOM
COLORFNSHMATLFNSH FNSH MATL
BASE WALL
FLOOR MATERIAL / COLOR
MATERIAL COLOR SCHEDULE
FINISH
REMARKSSURFACE
ROOF
WALL
FLASHING
METAL
STEELDOOR/ DOOR FRAME
MATERIAL
SOFFIT
FASCIA
CEILING
COLOR
CLG
CLR
CONC CONCRETE
HARDENER
HGT
VINYL COMPOSITION TILE
VINYL COVE BASEMECH MECHANICAL
MATERIALMATL
VCT
VCB
HEIGHT
HDR
FINISHFNSH
GCWT GLAZED CERAMIC WALL TILEACST ACOUSTICAL TILE
P PAINT
WALL TILEWT
CONCRETE MASONRY UNITCMU
GYPSUM WALL BOARDGWB
PLASTIC LAMINATEPL
WOODWD
RUBBER COVE BASERCB
CPT CARPET
EP EPOXY
VARIOUSVAR
MRL METAL ROOF LINER
CT CERAMIC TILE
SAWP
SLM SELF-LEVELING MORTAR
SOUND ABSORBTION WALL PANEL
1.
NOTE
AS APPROVED BY DPW.
SHALL BE IN ACCORDANCE WITH CAMP / INSTALLATION EXTERIOR COLOR SCHEME
SELECTION OF EXTERIOR PAINT AND APPLIED FACTORY COLORS
ABBREVIATION
ARCHITECTURAL
AS SHOWN
GENERAL NOTES
ABBREVIATION , NOTE
MATERIAL COLOR SCHEDULE
INTERIOR & EXTERIOR FINISH SCHEDULE
EXST PROTECTED
NO.
ROOM
NAME
MECH. ROOM
ELEC. ROOM EXST CONC
EXST CONC
EXST CONC -
EXST
EXST
EXST
EXST
VAR.
VAR.
CORRIDOR
FREEZER
FREEZER
FREEZER
FREEZER
CHILLROOM
CHILLROOM
CHILLROOM
CHILLROOM
VESTIBULE - - PNL FF - FF - 4064
NEW PNL
EXST PNL /
EXST CMU /
NEW PNL
NEW PNL FF - 4064
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST CONC
EXST PNL
FF
CLEANING /
PAINT /
CLEANING -
-CLEANINGEXST PNL
-CLEANINGEXST PNL
-CLEANINGEXST PNL
-CLEANINGEXST PNL
-CLEANINGEXST PNL
-CLEANINGEXST PNL
-CLEANINGEXST PNL
EXST PNL CLEANING -
-CLEANINGEXST PNL
-CLEANINGEXST PNL
-CLEANINGEXST PNL
-CLEANINGEXST PNL
-CLEANINGEXST PNL
-CLEANINGEXST PNL
-CLEANINGEXST PNL
VEST113
FREEZER114
CORRIDOR115
116 FREEZER
117 VEST
118 FREEZER
NEW CONC HDR
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
NEW CONC
NEW CONC
NEW CONC
NEW CONC
NEW CONC
NEW CONC
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF FF
FF
FF
FF
FF
FF NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF FF
FF
FF
FF
FF
FF
119 MECH. ROOM
120 LOCKER ROOM
121 TOILET
122 KITCHEN
123 OFFICE
EXST
EXST
EXST
EXST
EXST -
EXST -
EXST
EXST -
EXST -
EXST
EXST
EXST PAINT
124 FREEZER
VEST125
FREEZER126
CORRIDOR127
128 FREEZER
129 VEST
130 FREEZER
131 FREEZER
132 CORRIDOR
133 CORRIDOR
134 CORRIDOR
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
HDRNEW CONC
NEW CONC
NEW CONC
NEW CONC
NEW CONC
NEW CONC
NEW CONC
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF FF
FF
FF
FF
FF
FF NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF FF
FF
FF
FF
FF
FF 4500
NEW CONC
NEW CONC
NEW CONC
NEW CONC
NEW CONC
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF FF
FF
FF
FF
FF NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF
NEW PNL FF FF
FF
FF
FF
FF 4500
135 CORRIDOR HDRNEW CONC NEW CONC NEW PNL FF FF NEW PNL FF FF
WALL MATERIAL / COLOR
: PAINT, ALKYD, SEMI-GLOSS
PT-1
PT-2
OR APPROVED EQUAL
AMS-STD-595C, #27880
OR APPROVED EQUAL
2800ACST-1-ACST
2700PAINT
PAINT
PAINT
PAINT, ALKYD, SEMI-GLOSS
OR APPROVED EQUAL
AMS-STD-595C, #27925
:PT-3
PAINT
AMS-STD-595C, #27880
PAINT
EXST PT-3
PT-3
PT-3
PT-3
PT-1
PT-2
PT-1
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
PT-4
/ HDR
SANDING
/ HDR
SANDING
/ HDR
SANDING
/ HDR
SANDING
/ HDR
SANDING
/ HDR
SANDING
/ HDR
SANDING
/ HDR
SANDING
/ HDR
SANDING
/ HDR
SANDING
PAINT, LATEX / EGGSHELL
/ SLM
EXST CONC
OR APPROVED EQUAL
EPOXY, GLOSS
MPI 77
SELF LEVELING MORTAR
SIKA KOREA
25 CEMENTITIOUS SELF SMOOTHING
INDUSTRIAL SUB-FLOOR SCREED
OR APPROVED EQUAL
EP :SLM :
MATCH WITH EXST COLOR
INSULATION PANLE SYSTEM
PNL PANEL
:PNL
THERMAL CONDUCTIVITY - 0.023W/mK OR UNDER
DENSITY - 35Kg/CM OR ABOVE
OR APPROVED EQUAL
SAMSUNG PANEL PLANT
:PT-4
SLM
EXST CONC/
EXST
METAL
EXST / NEW PROTECTED
EXST CMU AND CONC / NEW CMU
CANOPY STRU. WOOD / STEEL STRU.
PAINT
INTERIOR FINISH SCHEDULE
EXTERIOR FINISH SCHEDULE
AE302
BSF
KIM, CS
PAK, SY
25 APR 24
81-00001-3J
OR APPROVED EQUAL
HDR :
LATICRETE
D - 24 - 22
CONCRETE DENSIFIER
YELLOW & BLACK , 45 ANGLE DIAGONAL LINE, W=150mm
FOR GUARDPOST, CONCRETE BASE AND BUMPER
FF
PT-2 /
EP EP
PAINT
PAINT /
6500 /
L&H SEAL HARD (2-COATS FINISH)
EXST GWB
CONC /
SLM ON DAMAGED/ REMOVED FLOOR SURFACE.
*GWB
*GWB
*GWB
*GWB -12.5T WATER RESISTANT TYPE
*GWB -12.5T WATER RESISTANT TYPE
*GWB -12.5T WATER RESISTANT TYPE
WORKING AREA ONLY
(PIR : SEMI-NON-COMBUSTIBLE), 125mm THK.
CAM-LOCK(FASTENER OR HOOK) TYPE URETHAN PANEL
BLDG. NO. S-1330
REPAIR DETERIORATED
9 46
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
SCALE : 1 / 5
14 14 14 14
1A 1B 1C 1D 1E 1F 1G
1J
1C
1G
1A
1B
1D 1E
1J
1H
AT WALL AT MAIN TEE AT CROSS TEE AT LIGHTING FXTR AT LIGHTING FXTR I S O M E T R I C
MAIN TEE & CROSS
TEE ISOMETRIC
SEISMIC
LOCKING PIN
AT HANGER
SPLICES AND INTERSECTIONS OF
RUNNERS SHALL BE ATTACHED
WITH MECHANICAL INTER
LOCKING CONNECTORS SUCH
AS POP RIVETS, SCREWS, PINS,
PLATES WITH BENT TABS, OR
OTHER APPROVED CONNECTORS.
DESIGN CONNECTORS FOR 2 X
DESIGN LOAD OR ULTIMATE AXIAL
TENSION OR COMPRESSION
(MINIMUM 120 POUNDS)
TYPICAL
12GA WIRE
HANGER
LOC.
SEISMIC
SWAY
BRACE
WIRES(12GA)
PERPENDICULAR
WITH MAIN TEE
45(MAX) IN LINE
WITH MAIN TEE
Fp ZIp
C p
Wp
3 TURNS
MIN
SEISMIC
SWAY
BRACE
WIRES(12GA)
IN LINE WITH
MAIN TEE
PERPENDICULAR
WITH MAIN TEE
Fp = ZIp Cp Wp
SPLICE
MAIN TEE.
1 EA PER EDGE
(TOTAL 4 EA)
a) FOR 610 x 610 PANEL :
(TYPICAL)
ACOUSTICAL TILE
610x610
FOR CLARITY,
ARE NOT SHOWN
ADDITIONAL HANGER
WIRE FOR LIGHTING
FIXTURE WHERE
REQUIRED (TYP.)
METAL
MOULDING
CROSS TEE
HOLD DOWN
CLIP (TYP)
610mm L
OR 1219mm L
MAIN TEE
CROSS
TEE
MAIN
TEE
(@ ATC PANELS)
MAIN
RUNNER
CROSS
RUNNER
HANGER
WIRE
SEISMIC
LOCKING
PIN
38mm MAIN TEE
@ 610mm O.C.
LIGHTING
FIXTURE
ATC PANEL
PER SPEC
38mm MAIN TEE
@ 610mm O.C.
32mm x 610mm L
OR 1219mm L
CROSS TEE
@ 610mm O.C.
LIGHTING
FIXTURE
ATC PANEL
PER SPEC
32mm x 610mm L OR
1219mm L CROSS TEE
@ 610mm O.C.
ATC PANEL
PER SPEC
BOT OF STRUCTURE
10mm EXP BOLT &
SHIELD OR APPROVED
EQUAL @ CONC.
38mm x 38mm x 3mm x 50mm LG STEEL "L" CLIP
APPROVED SCREW
ATTACHMENT @
METAL FRAMING
WIRE HANGERS
@ 1219mm O.C.
32mm x 610mm L OR
1219mm L CROSS TEE
@ 610mm O.C. W/ HOLD
DOWN CLIP
SWAY BRACE
WIRES (12GA)
38mm MAIN TEE
@ 610mm O.C.
203 MAX (W/O SEISMIC WIRES)
1828 MAX (W/ SEISMIC WIRES)
FACE OF WALL
32mm x 610mm L
OR 1217mm L
CROSS TEE
@ 610mm O.C.
ATC PANEL
PER SPEC
24mm x 24mm METAL MOULDING
W/ 5mm DIA. TOGGLE BOLTS
OR SCREW @ 406mm O.C.
(SEE NOTE 2)
QTY OF HOLD DOWN CLIPS
REQUIRED PER PANELAT LIGHTING
FIXTURES 610
CROSS TEES OR
1219 MAIN TEES
GENERAL NOTE: (TYPICAL)
NOTE:
LOCKING CLIP TO FASTEN CROSS
RUNNER TO MAIN RUNNER :
3A
2A 2B 2C 2D 2E 2FAT WALL AT FURRING AT FURRING AT CONTROL JOINT AT LIGHTING FIXTURE AT WALL(PLASTER, CMU)
WIRE HANGER
12 PLUS OR
MINUS 6 (TYP)
25 MIN
150 MAX
GYPSUM BOARD
CASING TRIM
FLEXIBLE DUST
MEMBRANCE
WIRE HANGER
@ 1219 O.C.
GYPSUM BOARD
CHANNEL
@1219 O.C.
TAPE JOINT
TREATMENT
CHANNEL
CHANNEL
JOINT
COMPOUND
METAL CONTROL
JOINT TRIM SUPPLEMENTARY
FRAMING
TROFFER
TROFFER SUSPENSION
BRACKET
WIRE MESH SCREEN
ABOVE FIXTURE
CASING TRIM
ROD
HANGER
WIRE
HANGER
SWAY BRACE
WIRES (12GA)
TIE
WIRES EXP BOLT
EXP BOLT
STEEL ANGLE
CLIP
CEILING IN EITHER DIRECTION.
WHERE PERIMETER BREAK DOES NOT EXIST AROUND
IN CASES WHERE PERIMETER BREAK EXIST AND 40 FT.
CEILING CONTROL JOINTS SHALL NOT EXCEED 30FT.
CONTROL JOINT SHALL BE PROVIDED WHERE CEILING
FRAMING OR FURRING CHANGES DIRECTION. EXPANSION
AND COTRACTION JOINTS SHALL BE INSTALLED IN
CEILINGS IN EXCEEDING 2,500 SQ. FT. INTERVAL BETWEEN
WIRE HANGER
@ 1219 O.C.
CHANNEL
@1219 O.C. WIRE HANGERS
@ 1219 O.C.
CHANNEL
@1219 O.C.
GYPSUM
BOARD
1.5THK 40x40
METAL CONT
W/ 60 TOGGLE
BOLTS OR EXP
BOLTS OR CONC
NAIL @1200 O.C.
50x50x3THK
ANGLE CLIP
NOTE:
3B ROD HANGER
TYPICAL HANGER DETAILS
SCALE : 1 / 5SCALE : 1 / 5
GYPSUM BOARD CEILING DETAILS
SCALE : 1 / 5
CHANNEL @
1219MM O.C.
HINGE
(CONTINUOUS)
WIRE HANGER
@ EACH CORNER
STL PLATE FRAME
BOLT & NUT
GWB OR
CPL CLG
CAM LATCH
& KEY
CEILING ACCESS
SCALE : 1 / 5
CEILING ACCESS (ATC)
HINGE
(CONTINUOUS)
WIRE HANGER
@ EACH CORNER
STL PLATE FRAME
BOLT & NUT
ATC
CAM LATCH
& KEY
(FINISH MATCH TO CEILING)
L 51 x 51 x 16GA FRAME (FINISH MATCH TO CEILING)
(LIGHT WEIGHT METAL)
STEEL ACCESS PANEL
(FINISH MATCH TO CEILING)
L 51 x 51 x 16GA FRAME
(FINISH MATCH TO CEILING)
(LIGHT WEIGHT METAL)
STEEL ACCESS PANEL
VARIOUSVARIOUS
22mm FURRING 22mm FURRING
38mm RUNNER
38mm RUNNER
38mm CHANNEL
38mm RUNNER
38mmx38mmx
3mmx50mm
10mmx60mm
STRUCTURE
EXISTING
STRUCTURE
EXISTING
x50LG STEEL
10mmx60mm
38mm RUNNER 6mm DIA.
51mm PIANO
76mm x 16GA THK
51mm PIANO
6mm DIA.
76mm x 16GA THK
SEMI-EXPOSED GRID ACOUSTICAL TILE CEILING DETAILS (TYP)
AE
AE
AE
AE
AE
ARCHITECTURAL
AS SHOWN
CEILING DETAILS (TYP)
AE303
BSF
KIM, CS
PAK, SY
25 APR 24
D - 24 - 22
303 303
303 303 81-00001-3J
BLDG. NO. S-1330
REPAIR DETERIORATED
10 46
LEGEND AND ABBREVIATIONS
SCH
SA
SAN
QTY
R12, R22
RA
RDTR
RPM
RT
PG
PH
POC
POL
PPM
PRV
QT
OA
OAIL
OD
OS&Y
Pa
NTS
BUTTERFLY
CUBIC METER PER HOUR
AIR CONDITION (-ING,-ED)
AIR CONDITION UNIT (S)
AIR COOLED CONDENSING UNIT
CHILLED/HOT WATER RETURN
CHILLED/HOT WATER SUPPLY
REFRIGERANT LIQUID
CAP CAPACITY
CUBIC METER
COMPRESSOR
CONTINUE
CONNECTION
CPRSR
CU M
CONT
CONN
COUNTER CLOCKWISE
COEFFICIENT
CIRCUIT
CAST IRON PIPE
CHILLED WATER
CKT
CMH
COEF
CHW
CCW
CIP
ALARM CHECK VALVEACV
AVG AVERAGE
BAROMETER(-TRIC)
CENTIGRADEC
BARO
AMPERE(AMP, AMPS)
ALUMINUM
APPROX
AMP
AIR COND
AHU
AL
AIR COOLED
ACU
ACLD
ACCU
CHWS
CHWR
CHR
CHS
D
RL
DRAIN
KILOCALORIE PER HOUR
KILOGRAM PER SQ. CENTIMETER
KILOGRAM
THERMAL CONDUCTIVITY
IRON PIPE SIZE
ISOMETRIC
DIAMETER, INSIDE
FACE AREA OR FRESH AIR
EXTERNAL STATIC PRESSURE
EVAPORAT (-E,-ING,-ED,-OR)
ENTERING WATER TEMP
FIRE HOSE CABINET
EXPLOSION PROOF
FHC
FA
ESP
EVAP
EWT
EFF
ENT
EQPT
EP
EFFICIENCY
ENTERING
EQUIPMENT
KG
K
IPS
ISO
ID
NIC
N.O.
NO
MPS
N.C.
N/A
MM
MPH
MIN
MAX
NOT IN CONTRACT
NORMALLY OPEN
NUMBER
NORMALLY CLOSED
METERS PER SECOND
METERS PER HOUR
MINIMUM OR MINUTE
NOT APPLICABLE
MILLIMETER
MAXIMUM
HERTZ
HOSE BIBB
HEAD
HORSEPOWER
HOUR(S)
HOT WATER
HOT WATER HEATER
HORIZONTAL
FIBERGLASS REINFORCED PLASTIC
FREQUENCY
FLUSH VALVE
FEED WATER PUMP
FIXTURE
GAGE OR GAUGE
GALVANIZED STEEL
FUEL OIL
FEMALE PIPE THREAD
CIRCULATING WATER PUMPCWP
FRP
DECIBEL OR DRY BULB
DRY BULB TEMPERATURE
ENTERING AIR TEMPERATURE
DRY PIPE VALVE
DIRECT EXPANSION
DO DIESEL OIL
EAT
DPV
DX
DIV
DIAG
DIFF
DB
DBT
DIVISION
DIAMETER
DIAGRAM
DIFFERENCE
DEGREE
HR
HZ
HW
HWH
HORIZ
HB
HD
HP
GA
GALVS
FV
FWP
FXTR
CLOCKWISE OR COLD WATERCW
PLUG VALVE
THREE WAY
FREQ
FO
FPT
GATE, GLOBE
GATE, ANGLE
GLOBE
CONTROL
GATE
M
LPS
LWT
LT
LPH
LPD
LL
LG
LBS
LAT
LAV
L
KWH
KW
LITERS PER SECOND
LITERS PER HOUR
LEAVING WATER TEMPERATURE
METERS
LAUNDRY TRAY
LITERS PER DAY
LIQUID LINE
LEAVING AIR TEMPERATURE
POUNDS
LAVATORY
LENGTH
KILOWATT HOUR
KILOWATT
LITERS
P
STRAINER, BLOW OFF
STRAINER
PUMP (INDICATE USE)
KG/ SM KILOGRAM PER SQ. METER
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
PIPE TO BE REMOVED
MEDIUM TEMPERATURE HOT WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
RS
RD
(NAME)
(NAME)E EXISTING PIPE
HWR
HWS
MTWR
MTWS
CR
CS
PIPING
SANITARY DRAIN
CHECK, SWING
PIPE SLEEVE WITH FIRE STOPPING
VENT THRU ROOF
BFP
PLAN
HOSE BIBB
BALL
ELEV.
PIPE SLEEVE
BACKFLOW PREVENTER
FLOOR DRAIN
FLOOR CLEANOUT
FD
FCO
FLEXIBLE CONNECTOR
ANCHOR, INTERMEDIATE
ANCHOR, MAIN
EXPANSION JOINT
EXPANSION LOOP
EJ
RELIEF
SAFETY
HOSE END DRAIN
LOCK SHIELD
NEEDLE
PRESSURE REDUCING
CONTROL, PNEUMATIC-ELECTRIC
CONTROL, ELECTRIC-PNEUMATIC
CHECK, NON-SLAM
S
R
EP
PE
COLD WATER
VENT
AD FD
QUANTITY
TEMPERATURE DIFFERENCE
TONS OF REFRIGERATION
SCHEDULE
SUPPLY AIR
SANITARY
REFRIGERANT (12, 22, ETC)
RETURN AIR
REVOLUTIONS PER MINUTE
REFRIGERATION TON
RADIATOR
TYP TYPICAL
UNIT HEATER
URINAL
UH
UR
SYMBOL
TEMPERATURE
THICKNESS
TONS
THK
TEMP
SYM
TD
OUTSIDE AIR INTAKE LOUVER
PRESSURE REDUCING VALVE
PHASE (ELECTRIC)
PETROLEUM, OIL AND LUBRICANTS
POINT OF CONNECTION
PARTS PER MILLION
PERCENT/
QUART
PRESSURE GAGE
DIAMETER, OUTSIDE
OUTSIDE SCREW & YOKE
PASCAL
POLE
SPR SPRINKLER
STAINLESS STEEL
SQUARE
STEAM
STANDARD
STEEL
ST
STD
STL
SQ
SST
SPECIFICATION
SQUARE METER
STATIC PRESSURE
SPEC
SP
SM
OUTSIDE AIR
NOT TO SCALE
SECONDSEC
VAV VARIABLE AIR VOLUME
WATER CLOSET
VENTILATION
W/
WT
WC
WD
WITH
WEIGHT
WIDTH
W
WB
VOL
VEL
VENT
VERT
WATT
WET BULB
VOLUME
VELOCITY
VERTICAL
SMOKE DAMPER (PROVIDE ACCESS DOOR)
MANUAL VOLUME DAMPER
VAC
V
VACUUM
VOLT
SPLITTER DAMPER
AD
SD
VD
TEE, SINGLE SWEEP
TEE, OUTLET DOWN
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
ELBOW, TURNED DOWN
UNION, FLANGED
UNION, SCREWED
TEE, OUTLET UP
TEE
LATERAL
ELBOW, TURNED UP
CONNECTION, TOP
CONNECTION, BOTTOM
BUSHING
CAP
FIRE DAMPER (PROVIDE ACCESS DOOR)
BDD
TURNING VANES
TRANSITION
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FC
DUCT WORK
A B B R E V I A T I O N S
L E G E N D
PG
TM
AAV
FOS
3-WAY VALVE (MOTORIZED)
PRESSURE GAUGE
THERMOMETER
AUTOMATIC AIR VENT
GATE VALVE
CHECK VALVE
FUEL OIL SUPPLY
FLEXIBLE JOINTFJ
& STRAINER
M
CS
SD
SHOWER DRAIN
DEG
DIA or o
CEAT CONDENSER ENTERING AIR TEMP
LCWT LEAVING CHILLED WATER TEMP
FAIL FRESH AIR INTAKE LOUVER
EXPANSION JOINTEXPJT
EXST EXISTING
A / C AIR CONDITIONING
APPROXIMATELY
ARCH ARCHITECTURAL
BLDG BUILDING
CONC CONCRETE
DWG DRAWING
EA EACH
F.C.U. FAN COIL UNIT
MECH MECHANICAL
KCAL/ HR
KG/ SQ CM
HOT WATER SUPPLY
HOT WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
V
DOMESTIC HOT WATER SUPPLY
DOMESTIC HOT WATER RETURN
AAV
ED EXHAUST DUCT
AUTOMATIC AIR VENT
AIR HANDLING UNIT
GROUND LEVELGL
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
SUPPLY AIR GRILLE OR
(200mm NECK DIAMETER)
CEILING DIFFUSER, ROUND TYPE
REGISTER, CEILING
EXHAUST AIR GRILLE OR
GRILLES, REGISTERS AND DIFFUSERS
SQUARE TYPE
CEILING DIFFUSER,
EG
ER
SG
SR
SG
SR
RG
RR
CD
200mm NCD
COWL, (GOOSENECK) AND FLASHING
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN810mm x 400mm
M
ELECTRIC MOTOR OPERATED DAMPER
S
MOTORIZED DAMPER
MD
SUPPLY AIR DUCT RISER
RETURN OR EXHAUST AIR DUCT RISER
SUPPLY AIR DUCT SECTION
RETURN AIR DUCT SECTION
GATE, GLOBE OR BALL VALVE
CHECK VALVE (FLOW)
ANGLE VALVE
STRAINER
DRIP CHECK VALVE
RESTRICTED ORIFICE
FILL CUP
PRESSURE GAUGE
SOLENOID VALVE
ECCENTRIC REDUCER
CONCENTRIC REDUCER
FLEXIBLE PIPE CONNECTION
RELAY
HOSE VALVE
TEST HEADER
SMOKE DAMPER
R
SD
S
: WATER MOTER ALARM GONG
SPRINKLER SYSTEM
: UP-RIGHT TYPE SPRINKLER
: PENDENT TYPE SPRINKLER
: SIDE WALL TYPE SPRINKLER
REMOVAL WORK
RELOCATED WORK
SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
SA
RA
EA
DEMPERS
VALVES, SPECIAL DUTY
HEATING
AIR CONDITIONING & REFRIGERATION
PLUMBING
VALVES : (for selective actuators)
BACK DRAFT DAMPER
CIRCUIT SETTER
POINT OF CONNECTIONPOC
POR POINT OF REMOVAL
TcH THERMOSTAT HEATING/COOLING
THERMOSTAT OF HEATING
REGISTER, CEILING
RETURN AIR GRILLE OR
Th
REDUCER, CONCENTRIC
11 46
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-1
D - 24 - 22
G
CHONG, CHANG NAK
NAM, TAE CHIN
25 APR 24
BSF
81-00001-3J
BLDG. NO. S-1330
GENERAL NOTES
DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH THE ADJACENT SURFACE OR AREA.
4. ALL WALL / FLOOR / ROOF OPENINGS RESULTING FROM THE REMOVAL OF PIPING AND
AS DIRECTED BY THE CONTRACTING OFFICER.
EXISTING AREAS CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS
5. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO
CEILING, ROOF, EQUIPMENT, PIPE, DUCT AND ELECTRICAL ITEMS.
PREVENTION SYSTEM WITH NO ADDITIONAL COST TO THE GOVERNMENT SUCH AS WALLS,
ITEMS TO MAKE WAY FOR THE INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE
18. THE CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE AND REINSTALL THE OBSTRUCTED
SPECIFICATIONS.
CONTRACT DRAWINGS SHALL BE SUBMITTED FOR APPROVAL AS REQUIRED BY THE CONTRACT
OF THE ACTUAL PROPOSED CONTROL SYSTEM WHICH MAY DEVIATE FROM THAT SHOWN ON
SYSTEM TO SATISFY ALL FUNCTIONAL REQUIREMENTS SHOWN ON DRAWING. SHOP DRAWINGS
17. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND WORKABLE CONTROL
9. ANY PIPES THAT PENETRATE FIRE RATED WALLS (EXISTING/ NEW) SHALL BE SEALED PER SPEC.
TO ENSURE PROPER OPERATION, AS ORIGINALLY INTENDED.
EQUIPMENT. THE CONTRACTOR SHALL TEST, ADJUST AND BALANCE EQUIPMENT AS REQUIRED
14. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY START-UP AND TESTING OF THE NEW
AND SHALL BE VERIFIED AT THE JOB SITE.
2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC, ARE APPROXIMATE
PRIOR TO COMMENCING CONSTRUCTION FOR APPROVAL.
ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE CONTRACTING OFFICER
FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR
3. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACTLY TO THE
CONTRACTING OFFICER’S APPROVAL.
REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER CORRECTIONS FOR
IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING OFFICER’S
PRIOR TO COMMENCING ANY CONSTRUCTION OR REPAIR.
EQUIPMENT, DUCTWORK, PIPING, DIMENSIONS AND ETC. UNDER THE SUPERVISION OF C.O.R
1. THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFYING ALL EXISTING CONDITION,
A SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
10. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWING.
THE REQUIREMENTS OF SEAL CLASS C.
TO SMACNA STATIC PRESSURE CONSTRUCTION CLASS 500PA AND DUCTWORK SHALL MEET
7. THE SUPPLY, RETURN…