This document is a DRAFT Technical Specification Sheet for a 20-Ton Industrial Water Chiller required by the Department of the Air Force Materiel Command Test Center. The chiller must have a minimum cooling capacity of 239,756 BTU/hr, be rated for continuous usage within an ambient temperature range of +14°F to +113°F, and use water as a medium with a minimum flow rate of 50 GPM. The chiller must have a self-contained 55-gallon stainless steel reservoir and be portable on a movable skid/frame. Electrical requirements are 460V, 3-phase, 60Hz with a maximum of 60 amps. The chiller must fit within the specified dimensions of 45" wide, 100" long/deep, and 90" height, and not exceed 1,650 lbs. This Technical Specification Sheet is associated with a Sources Sought Notice for the 20-Ton Industrial Water Chiller, which will be delivered to Arnold AFB in Tennessee.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sources Sought Notice.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Specification Sheet 20 Ton Industrial Water Chiller
| 1. | General & Operational Data/Specifications |
| a. | Must be rated for continuous usage |
| b. | Ambient working limits: Minimum requirements are +14 ᴼF through +113 ᴼF |
| c. | Cooling capacity (Capacity based on 45 ᴼF water outlet temp.: 10 ᴼF delta t @ 95 ᴼF ambient temperature): |
| i. | 20 tons, minimum capacity |
| ii. | 239,756 BTU/hr, minimum capacity |
| d. | Must be designed to use water as a medium |
| e. | Cooling Water flow rate: 50 gpm, minimum flow rate |
| f. | Head Pressure: 50 psi at a flow rate of 46 gal/min |
| g. | Refrigerant: Type/Qty: R410A |
| h. | Noise rating: Not to exceed 69 db at 10 ft |
| 2. | Reservoir/Self-Contained Water Tank: ` |
| a. | 55 gal. minimum capacity |
| b. | Chiller is to only operate using water contained in reservoir/self-contained tank. This means an external water supply IS NOT required except to fill the reservoir/self-contained tank. |
| c. | Tank is to be stainless steel. |
| 3. | Interfaces: |
| a. | Power Supply: |
| i. | Volts: 460V |
| ii. | Phase: 3 |
| iii. | Hertz: 60 |
| iv. | FLA: Maximum of 60 amps |
| b. | Fluid Connections |
| i. | System water supply: MPT 2” |
| ii. | System water return: MPT 2” |
| c. | Filling reservoir/self-contained tank with drain: |
| 4. | Weight & Dimensions: System must fit within below dimensions. Note: Reservoir/Self-Contained water tank is to be included in these measurements |
| a. | Dry Weight: Not to exceed 1650 lbs |
| b. | Width: Not to exceed 45 inches |
| c. | Length/Depth: Not to exceed 100 inches |
| d. | Height: Not to exceed 90 inches |
| 5. | Portability |
| a. | Portability must be maintained while meeting all requirements in this spec |
| b. | System must be self-contained on a movable skid/frame |
| c. | Skid/frame is to have lifting hole to allow forklift to move system |
| d. | Only items to be disconnected to allow system to be moved are: |
| i. | Power Source identified in 3.a.iv |
| ii. | Fluid connections identified in 3.b.i and 3.b.ii |
| e. | Drain reservoir/self-contained tank of water |
| 6. | Clearance Spacing: The following states how much space must be provided between the system and an obstacle |
| a. | Side Clearances: Required clearance for any side of unit is not to exceed 6.5 ft |
| b. | Top Clearance: Required clearance for top of unit is not to exceed 10 ft |