This document is a DRAFT Technical Specification Sheet for a 20-Ton Industrial Water Chiller required by the Department of the Air Force Materiel Command Test Center. The chiller must have a minimum cooling capacity of 239,756 BTU/hr, be rated for continuous usage within an ambient temperature range of +14°F to +113°F, and use water as a medium with a minimum flow rate of 50 GPM. The chiller must have a self-contained 55-gallon stainless steel reservoir and be portable on a movable skid/frame. Electrical requirements are 460V, 3-phase, 60Hz with a maximum of 60 amps. The chiller must fit within the specified dimensions of 45" wide, 100" long/deep, and 90" height, and not exceed 1,650 lbs. This Technical Specification Sheet is associated with a Sources Sought Notice for the 20-Ton Industrial Water Chiller, which will be delivered to Arnold AFB in Tennessee.

View the file

Other files

File Type Posted
Sources Sought Notice.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Technical Specification Sheet 20 Ton Industrial Water Chiller

1.General & Operational Data/Specifications
a.Must be rated for continuous usage
b.Ambient working limits: Minimum requirements are +14 ᴼF through +113 ᴼF
c.Cooling capacity (Capacity based on 45 ᴼF water outlet temp.: 10 ᴼF delta t @ 95 ᴼF ambient temperature):
i.20 tons, minimum capacity
ii.239,756 BTU/hr, minimum capacity
d.Must be designed to use water as a medium
e.Cooling Water flow rate: 50 gpm, minimum flow rate
f.Head Pressure: 50 psi at a flow rate of 46 gal/min
g.Refrigerant: Type/Qty: R410A
h.Noise rating: Not to exceed 69 db at 10 ft
2.Reservoir/Self-Contained Water Tank: `
a.55 gal. minimum capacity
b.Chiller is to only operate using water contained in reservoir/self-contained tank. This means an external water supply IS NOT required except to fill the reservoir/self-contained tank.
c.Tank is to be stainless steel.
3.Interfaces:
a.Power Supply:
i.Volts: 460V
ii.Phase: 3
iii.Hertz: 60
iv.FLA: Maximum of 60 amps
b.Fluid Connections
i.System water supply: MPT 2”
ii.System water return: MPT 2”
c.Filling reservoir/self-contained tank with drain:
4.Weight & Dimensions: System must fit within below dimensions. Note: Reservoir/Self-Contained water tank is to be included in these measurements
a.Dry Weight: Not to exceed 1650 lbs
b.Width: Not to exceed 45 inches
c.Length/Depth: Not to exceed 100 inches
d.Height: Not to exceed 90 inches
5.Portability
a.Portability must be maintained while meeting all requirements in this spec
b.System must be self-contained on a movable skid/frame
c.Skid/frame is to have lifting hole to allow forklift to move system
d.Only items to be disconnected to allow system to be moved are:
i.Power Source identified in 3.a.iv
ii.Fluid connections identified in 3.b.i and 3.b.ii
e.Drain reservoir/self-contained tank of water
6.Clearance Spacing: The following states how much space must be provided between the system and an obstacle
a.Side Clearances: Required clearance for any side of unit is not to exceed 6.5 ft
b.Top Clearance: Required clearance for top of unit is not to exceed 10 ft