Attachment 1 – CRAC Unit Specifications

Building 859

Liebert Model number VS053ADA0EI or equivalent

Factory Startup (Civil Engineer will remove and install new unit) after installation

1 year warranty

Upflow Airflow distribution

Return flow through front of unit

Centrifugal blower minimum 8,000

MERV 8 rated filters

15 Ton Nominal cooling capacity

Dual refrigeration circuits

Liquid line filters dryers, sight glasses, expansion valves, and liquid line solenoids

R407C refrigerant

Air Cooled cooling type

Dual condenser with variable speed fans 460v 3 ph 60 Hz

Condenser surge protection

60” condenser legs

2 Digital Scroll compressors

Minimum 14 gauge welded frame

460V 3 ph 60 Hz

Forward curved fan blower

3 stage electric reheat minimum 85,000 BTUH

Humidifier minimum 22 lbs/hr

Supply air temperature sensor

Insulated exterior panels

ICOM control with touchscreen display with Ethernet port and RS‐485 port

Dimensions 102” X 42” X 82”