This document is a set of contract drawings for a federal contract opportunity to replace the Granular Activated Carbon (GAC) filter at the water treatment plant located at Building #1050, THAAD Site.
The key details include:
- The contractor shall replace 1,200-liters of activated carbon filter and 1,000-liters of cation water softener resin filter per the technical requirements.
- The contractor shall provide verification sampling results for the carbon filter media and obtain certification for the suitability of the filters.
- The contractor shall properly dispose of the used filters and construction debris in accordance with applicable regulations.
- The contractor shall perform an operational test, inject chlorine for sterilization, and provide microbiological test results after the filter replacement.
- The contractor shall provide a one-year warranty on the replaced filters.
- The solicitation number is W90VN924R0128, and it is a non-work plan task order request for proposal (RFP) under an existing MATOC contract for Area IV.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation W90VN924R0128.pdf | ||
| Attachment 2 - Manifest Template.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNIT #15746, APO AP 96218-5746
DATE:
NOT TO SCALE
ESTIMATION Br.
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
BUSINESS AND OPERATIONS INTERGRATION DIVISION, ESTIMATION Br.
PROJECT LOCATION PLAN
PARCEL 1-B
PARCEL 1-A
PARCEL 2
50925093
WATER TREATMENT
PRIMARY WASTE
WATP
1020FSTA
GEN
RTWL
H20-00037-4J
THAAD SITE
REPLACE GAC FILTER FOR WATER TREATMENT PLANTPROJECT LOCATION PLAN
Soseong 2-gil, Chojeon-myeon,Seongju-gun, Gyeongsangbuk-do,Korea
THIS PROJECT
THAAD SITE
WATER TREATMENT PLANT, B1050
B1050
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNIT #15746, APO AP 96218-5746
DATE:
NOT TO SCALE
ESTIMATION Br.
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
BUSINESS AND OPERATIONS INTERGRATION DIVISION, ESTIMATION Br.
H20-00037-4J
TANK
BRINE
WELL
COLLECTING
65A CHECK VALVE
65A BUTTERFLY VALVE
PRESSURE GAUGE
WELL
COLLECTING
GROUND WATER
THAAD SITE
REPLACE GAC FILTER FOR WATER TREATMENT PLANT
WATER TREATMENT PLANT FLOOR PLAN
WATER TREATMENT PLANT FLOOR PLAN
FILTER
SOFTENER
FILTER
CARBON
ENTRANCE WAY
A C D
1,0800 x 1,460H
INDEX
G
1,3600 x 1,830H 1,3600 x 1,830H
CATION ION RESIN: 1,000 LIT ACTIVATED CARBON: 1,200
GRAVEL & SAND: 300 LIT GRAVEL & SAND: 300LIT
ENLARGED FLOOR PLAN
CARBON
FILTER
CONTROL
PANEL
IIGTED STATES MNf GMAllllt DflEGU
DIIECfORIIIITEIFPl&.ICIIJRICS 9JIIIEl8MIICl'EMTIINIIIITEIIIIMTIDMOJVIBIIW,EITDMTIOM ...
lltlT "19741.N'D•'1121B•ll748
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNIT #15746, APO AP 96218-5746
DATE:
NOT TO SCALE
ESTIMATION Br.
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
BUSINESS AND OPERATIONS INTERGRATION DIVISION, ESTIMATION Br.
H20-00037-4J
THAAD SITE
REPLACE GAC FILTER FOR WATER TREATMENT PLANT
SCOPE OF WORK (1)
SCOPE OF WORK(1)
[WATER FILTER REPLACEMENT WORK]
- BLEACHING OF METHYLENE BLUE: EQUAL TO OR MORE THAN 150 ML/G.
- ABS: EQUAL TO OR LESS THAN 50.
- PHENOL: EQUAL TO OR LESS THAN 25.
- ZINC: EQUAL TO OR LESS THAN 50 MG/KG.
- CADMIUM: EQUAL TO OR LESS THAN 1 MG/KG.
- LEAD: EQUAL TO OR LESS THAN 10MG/KG.
- ARSENIC: EQUAL TO OR LESS THAN 2 MG/L.
- CHLORIDE: EQUAL TO OR LESS THAN 0.5%.
NOTICE NO. 2017-190 FOR ANALYSIS BELOW.
REGISTRATION ISSUED BY EITHER ROK CITY MAYOR OR A ROK LOCAL PROVINCE GOVERNOR IN ACCORDANCE WITH ROK MINISTRY OF ENVIRONMENT
AND VALID MEASURING AGENCY BUSINESS
B. THE CONTRACTOR SHALL PERFORM CARBON FILTER MEDIA?S VERIFICATION SAMPLING RESULTS FROM THE LABORATORY WHICH HAS CURRENT
ASSOCIATION (AWWA) B604 WITH IODINE NUMBER MINIMUM 1,000MG/G.
A. THE CONTRACTOR SHALL PROVIDE VERIFICATION SAMPLING RESULTS OF CARBON FILTER MEDIA IN ACCORDANCE WITH AMERICAN WATER WORKS
REQUIREMENTS.
4. THE CONTRACTOR SHALL OBTAIN VERIFICATION OF THE SUITABILITY OF THE CARBON FILTER SUPPLIED THROUGH THE COR PER THE TECHNICAL
INSTITUTE (NSF/ANSI) 60 BY AN ANSI ACCREDITED CERTIFICATION ORGANIZATION.
P. DISINFECT CHEMICALS SHALL BE CERTIFIED, LISTED, AND LABELED TO NATIONAL SANITATION FOUNDATION/AMERICAN NATIONAL STANDARDS O. WATER QUALITY ASSOCIATION GOLD SEAL VALIDATED TO CONFORM TO NSF/ANSI STANDARD 61.
N. WEIGHT: APPROX. 50 LBS PER FT3.
M. PH RANGE: 0 TO 14.
L. MAXIMUM FEED TEMPERATURE: 120?C (248.0?F).
K. RECOMMENDED BED DEPTH: 30-36 INCHES.
J. TYPICAL FREEBOARD: 50%.
I. BACKWASH FLOW RATE: 5-6 GPM/FT2.
H. FLOW DIRECTION: DOWNWARD FLOW.
G. RECOMMENDED SERVICE FLOW RATE: 5-7.5 GPM/FT3.
F. REGENERANT: SODIUM OR POTASSIUM CHLORIDE.
E. IONIC FORM AS SHIPPED: SODIUM.
D. FUNCTIONAL GROUPS: SULFONIC ACID.
C. PHYSICAL FORM / APPEARANCE: GOLDEN YELLOW SPHERICAL BEADS.
B. POLYMER STRUCTURE: POLYSTYRENE / MIN 8% CROSS-LINKED.
A. CATION WATER SOFTENER RESIN FILL: 1,000-LITERS.
POLYSTYRENE, AND THE CATION WATER SOFTENER RESIN FILTER SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS.
3. CATION WATER SOFTENER RESIN FILTER SUPPLIED UNDER THE CONTRACT SHALL BE VIRGIN GRANULAR MATERIALS MANUFACTURED FROM
INSTITUTE (NSF/ANSI) 60 BY AN ANSI ACCREDITED CERTIFICATION ORGANIZATION.
F. DISINFECT CHEMICALS SHALL BE CERTIFIED, LISTED, AND LABELED TO NATIONALSANITATION FOUNDATION/AMERICAN NATIONAL STANDARDS
E. IODINE NUMBER: MINIMUM 1,000 MG/G.
TYPICALLY REQUIRED).
D. EFFECTIVE PARTICLE SIZE: 0.55-0.90MM (THIS PARAMETER DOES NOT APPLY TO EXTRUDED CARBONS WHERE THE CYLINDRICAL DIAMETER IS
C. UNIT WEIGHT (APPARENT DENSITY OR DENSE PACKING): 27-34 LBS./FT 39/64 .
B. ACTIVATED CARBON FILTER SIZE: 12X30 MESH PRODUCTS.
A. ACTIVATED CARBON FILL: 1,200-LITERS.
COAL OR COCONUT SHELLS, AND THE ACTIVATED CARBON FILTER SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS.
2. ALL ACTIVATED CARBON FILTER SUPPLIED UNDER THE CONTRACT SHALL BE VIRGIN GRANULAR MATERIALS MANUFACTURED FROM BITUMINOUS
A. THE ACTIVATED CARBON FILTER AND CATION WATER SOFTENER RESIN FILTER ARE INSTALLED IN EACH TANK AT THAAD SITE.
CARBON SYSTEM).
CARBON, THE ENCLOSED SPACE/LOW OXYGEN LEVEL PROCEDURE MUST BE FOLLOWED (REFERENCE #1; O&M MANUAL FOR GRANULAR ACTIVATED INSTRUCTIONS. IF THE OPERATOR IS REQUIRED TO ENTER THE TANK CONTAINING WET ACTIVATED
IN ACCORDING TO THE ATTACHED
1. THE CONTRACTOR SHALL REPLACE 1,200-LITERS ACTIVATED CARBON FILTER AND 1,000-LITERS CATION WATER SOFTENER RESIN FILTER
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNIT #15746, APO AP 96218-5746
DATE:
NOT TO SCALE
ESTIMATION Br.
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
BUSINESS AND OPERATIONS INTERGRATION DIVISION, ESTIMATION Br.
H20-00037-4J
THAAD SITE
REPLACE GAC FILTER FOR WATER TREATMENT PLANT
SCOPE OF WORK (2)
SCOPE OF WORK(2)
FOR WATER TREATMENT AGENTS)
- ROK MINISTRY OF ENVIRONMENT NOTICE NO. 2017-190 (CRITERIA, SPECIFICATIONS AND MARKING CRITERIA
STANDARDS (EGS), 2020
- CHAPTER 6. HAZARDOUS WASTE AND DESIGNATED WASTE, USFK REGULATION 201-1,ENVIRONMENTAL GOVERNING
- CHAPTER 3. DRINKING WATER, USFK REGULATION 201-1, ENVIRONMENTAL GOVERNING STANDARDS (EGS), 2020
PURIFICATION FILTERS, 2018
- UNIFIED FACILITIES GUIDE SPECIFICATIONS (UFGS)-43 31 13. 13 10, ACTIVATED CARBON GAS AND LIQUID GRANULAR ACTIVATED CARBON AND C653-20; DISINFECTION OF WATER TREATMENT PLANTS,2020
- APPROVED AMERICAN NATIONAL STANDARD/AMERICAN WATER WORKS ASSOCIATION (ANSI/AWWA) B604;
- OPERATION AND MAINTENANCE MANUAL FOR THAAD SITE, 2018
[REFERENCE]
REQUIREMENTS) TO THE COR WITHIN 15 CALENDAR DAYS OF DISPOSAL.
ACCORDANCE WITH APPLICABLE REGULATION (AWWA OR REPUBLIC OF KOREA MINISTRY OF ENVIRONMENT
2. THE CONTRACTOR SHALL PROVIDE CERTIFICATE OF DISPOSAL AFTER PROPERLY DISPOSING WASTE FILTERS IN
WITH LOCAL LAWS AND REGULATIONS.
1. THE CONTRACTOR SHALL REMOVE AND DISPOSE WASTE FILTERS AND CONSTRUCTION DEBRIS LOCATED OUTSIDE OF THE COMPOUND IN ACCORDANCE
[DISPOSAL OF CONSTRUCTION WASTE RUBBLE]
SOFTER IN MEETING URANIUM, PFOS/PFOA CONCENTRATION RESULTS FOR ACCEPTANCE CRITERIA.
9. THE CONTRACTOR SHALL PROVIDE ONE (1) YEAR WARRANTY RELATED TO THE QUALITY OF THE REPLACED ACTIVATED CARBON FILTER AND
- METALS, URANIUM, AND PHYSICAL PARAMETERS: USFK REG. 201-1, ENVIRONMENTAL GOVERNING STANDARDS (EGS), CHAPTER 3.
- PFOS/PFOA: COMPLETELY REMOVE TOTAL PFOS/PFOA CONCENTRATIONS BELOW THE ANALYTICAL DETECTION LIMIT (~5 TO 7 PPT.)
D. COMPLIANCE STANDARD
REGISTRATION ISSUED BY EITHER ROK CITY MAYOR OR A ROK LOCAL PROVINCE GOVERNOR.
- PHYSICAL PARAMETERS: NELAP CERTIFIED LABORATORY OR LABORATORY WHICH HAS CURRENT AND VALID MEASURING AGENCY BUSINESS
ENVIRONMENTAL LABORATORY ACCREDITATION PROGRAM (NELAP) CERTIFIED LABORATORY.
- PFOS/PFOA. URANIUM AND METALS: US DOD CERTIFIED LABORATORY OR NATIONAL
C. LABORATORY QUALIFICATION
CYANIDE, MERCURY, LEAD, COPPER, SELENIUM, THALLIUM AND URANIUM.
- ANALYSIS: ANTIMONY, ARSENIC, BARIUM, BERYLLIUM, BORON, CADMIUM, CHROMIUM,
- TWO VALVES AT INFLUENT EFFLUENT OF FILTER TANKS.
B. METALS SAMPLING LOCATIONS AND ANALYTES
TWO VALVES AT INFLUENT EFFLUENT OF FILTER TANKS.
A. PFOS/PFOA (PERFLUOROALKYL AND POLYFLUOROALKYL SUBSTANCES) SAMPLING LOCATIONS
CONCENTRATION UNDER THE ANALYSIS DETECTION LIMIT (~5 TO 7 PPT.)
ONCE PH (POTENTIAL OF HYDROGEN) HAS STABILIZED AFTER CONDUCTING INITIAL SAMPLING TO COMPLETELY REMOVE THE TOTAL PFOS/PFOA
8. THE CONTRACTOR SHALL PROVIDE PFOS (PERFLUOROOCTANESULFONIC) / PFOA(PERFLUOROOCTANNOIC ACID) / METAL SAMPLING RESULTS, CONTRACTOR?S EXPENSE. THIS DETERMINATION SHALL BE MADE BY THE GOVERNMENT.
OUT OF COMPLIANCE WITH DRINKING WATER COMPLIANCE STANDARDS SHALL BE REPLACED WITH NEW ACTIVATED CARBON FILTER AT THE REPLACED. THE REPLACED ACTIVATED CARBON FILTER THAT IS FOUND TO RELEASE ANY CONTAMINANTS OR CAUSE THE TREATED WATER TO BE A. THE USING AGENCY MAY COLLECT INFLUENT AND EFFLUENT SAMPLES WITHIN ONE (1) WEEK AFTER VIRGIN ACTIVATED CARBON FILTER IS
REPORT.
ALSO, THE OPERATIONAL TEST PLAN AND RESULT REPORT SHALL BE SUBMITTED TO THE COR WITHIN 30 CALENDAR DAYS FOR WATER ANALYSIS
7. THE CONTRACTOR SHALL PERFORM OPERATING TEST AND MONITOR INFLUENT AND EFFLUENT SAMPLES ONCE WATER FILTER REPLACEMENT
TO PROVIDE MICROBIOLOGICAL TEST RESULTS PER AMERICAN WATER WORKS ASSOCIATION (AWWA) C653-20 TO MEET APPLICABLE REQUIREMENTS.
6. THE CONTRACTOR SHALL INJECT A RESIDUAL AMOUNT OF CHLORINE INTO THE TANK FOR STERILIZATION AND CONDUCT A BACTERIAL TEST
5. THE CONTRACTOR SHALL REMOVE THE USED FILTERS FROM TANK IN ACCORDANCE WITH THAAD SITE WATER FILTER O&M MANUAL.
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNIT #15746, APO AP 96218-5746
DATE:
NOT TO SCALE
ESTIMATION Br.
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
BUSINESS AND OPERATIONS INTERGRATION DIVISION, ESTIMATION Br.
H20-00037-4J
THAAD SITE
REPLACE GAC FILTER FOR WATER TREATMENT PLANT
SCOPE OF WORK (3)
ASCOPE OF WORK(3)
PROPER MATERIAL HANDING METHODS.
1. THE CONTRACTOR SHOULD COORDINATE ANY SALVAGEABLE AND RECYCLABLE MATERIALS WITHIN PROJECT LIMIT WITH COR CAREFULLY TO DETERMINE
[GENERAL WORK]
1. THE CONTRACTOR SHALL ASSIGN SAFETY GUARD AROUND WORKING AREA.
[SAFETY]
Te ch ni ca l Ex hi bi t
W at er
Tr ea tm en t
Pl an t
3 1 ni ca l Ex hi bi t
W tm en t
Pl an ni ca l Ex hi bi t
W tm en t
Pl an ni ca l Ex hi bi t
W tm en t
Pl an
Techni cal Exhibit 3 - W ater Treatm ent Plant
Techni cal Exhibit 3 - W ater Treatm ent Plant
Technical Exhibit 3 - Water Treatment Plant
| FOS B1050 FLOOR-Model-000 |
| Encl #5_H20-00037-4J_Applicable Contract Drawings |
| 1FOS B1050 FLOOR-Model-000 |
| 2FOS B1050 FLOOR-Model-000 |
| 3FOS B1050 FLOOR-Model-000 |
| 4FOS B1050 FLOOR-Model-000 |
| 5FOS B1050 FLOOR-Model-000 |
| 6FOS B1050 FLOOR-Model-000 |
File details come from the government source that posted it. Updated .