Attachment 1 - 36 MXS Mobile Inflatable Paint Booth Salient Characteristics.pdf

PDF 323 KB Posted

Attached to
36 MXS Mobile Inflatable Paint Booth Federal contract opportunity
Solicitation number
FA524025QM162
Issued by
Department of the Air Force Pacific Air Forces

About this file

The document is a Salient Characteristics specification for a Mobile Inflatable Paint Booth for the 36th Maintenance Squadron (36 MXS) at Andersen Air Force Base in Guam. The portable paint booth must have interior dimensions of 40'L × 23'W × 12'H, be constructed of flame-retardant, antistatic PVC with glass-clear panels, and include features such as a pressurized airlock entry system, emergency exit handles, and a fully removable door. The booth requires four 120V blower fans capable of delivering 800-2800 CFM, a three-stage exhaust filtration system with a charcoal bed filter, and activated carbon filters for VOC and odor control.

Key technical requirements include 99.87% emissions capture efficiency, compliance with EPA, OSHA, and NESHAP standards, explosion-proof lighting providing 1000 lux at working height, and an electric air compressor pump that can inflate/deflate the booth in under 10 minutes. The booth must operate on standard 120V power and be suitable for on-site repair of aircraft parts and Aerospace Ground Equipment. Delivery is specified to 36 MXS/MXMFS, Unit 14012, APO AP 96543-4012 at Andersen Air Force Base, Guam.

View the file

Other files for this federal contract opportunity

Other files attached to 36 MXS Mobile Inflatable Paint Booth, newest first.
File Type Posted
Attachment 2 - Amendment MFR FA524025QM162 - 36 MXS Mobile Inflatable Paint Booth.pdf PDF
RFI Sources Sought - FA524025QM162.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA524025QM162 - 36 MXS Mobile Inflatable Paint Booth

Salient Characteristics

36 MXS Mobile Inflatable Paint Booth, Andersen AFB, Guam

REQUIREMENT DESCRIPTION WITH SALIENT CHARACTERISTICS

1. Quantity & General Requirements

A minimum of one (1) Portable Paint Booth is required.

Must be suitable for on-site repair of aircraft parts and Aerospace Ground Equipment

(AGE).

2. Dimensions & Structure

Interior dimensions must be 40 feet (L) × 23 feet (W) × 12 feet (H).

Must be free-standing and not require continuous inflation to maintain structure.

Must include tie-downs and floor anchors for securing the booth in outdoor environments.

Booth structure must be made of flame-retardant, antistatic PVC with glass-clear panels for visibility.

Structural base material must be heavy-duty PVC-coated polyester.

All closures must be splash-proof 8mm coil-type zippers or equivalent.

All panels, doors, zippers, windows, floor sections, and filters must be installed using similar fastener components and be replaceable.

3. Access & Safety Features

Must include a fully removable door for unobstructed access.

Must include a personnel door with replaceable zippers.

Must feature emergency exit pull handles on interior side windows located on both sides.

Must include a pressurized airlock entry system to prevent contamination during ingress/egress.

Must meet all applicable OSHA standards for confined spaces.

4. Ventilation & Airflow

Must include a minimum of four (4) 120V blower fans, each capable of delivering airflow between 800–2800 CFM.

Fans must be multi-speed, rated at 1 HP, and compatible with 120V/230V and 50Hz operation.

Must provide complete air changes every 3 minutes to maintain a clean working environment.

Must utilize High Volume Low Pressure (HVLP) airflow to minimize overspray and improve capture efficiency.

FA524025QM162 - 36 MXS Mobile Inflatable Paint Booth

Salient Characteristics

5. Filtration System

Must meet EPA and NESHAP standards for air filtration and all relevant aerospace safety/environmental regulations.

Must include:

o Replaceable pre-stage filters on the inlet side wall.

o A three-stage exhaust filtration system, with the final stage being a charcoal bed filter.

o Activated carbon filters using Carbotec RT20 foam or equivalent for VOC and odor control.

Filter surface area must include:

o Input filters: Minimum 3.85 m² using G4 synthetic media.

o Exhaust filters: Minimum 10.77 m² of synthetic paint arrestor media.

o Carbon filters: Minimum 2.39 m².

6. Lighting & Visibility

Must include windows that allow external visibility of painting operations.

Lighting system must be explosion-proof, with sufficient brightness to meet 1000 lux at working height.

7. Inflation & Compressor System

Must include an electric air compressor pump with a built-in monitor to auto-adapt pressure and manage inflation/deflation.

Booth must inflate/deflate in under 10 minutes and be operationally ready within 1 hour.

Must not rapidly deflate or lose pressure once inflated.

8. Power Requirements

All powered components must operate on standard 120V electrical power.

9. Environmental & Safety Compliance

Must demonstrate 99.87% capture efficiency for emissions.

Must visibly demonstrate compliance with EPA, OSHA, and NESHAP standards for mobile aerospace painting operations.