This document is a Bill of Materials for a shore power cable procurement by the US Department of Transportation Maritime Administration. The specification requires 3,000 feet of 2 AWG 3/C 15KV type MP-GC power cable with specific technical characteristics, including class B copper conductors, Ethylene Propylene Rubber insulation, copper tape shield, ground and ground check, and an orange Chlorinated Polyethylene jacket. The cable must be MSHA approved and meet ASTM B3, ASTM B8, and ICEA S-75-381/NEMA WC 58 standards.
The cable is intended for underwater service in shallow water (maximum 36-foot depth) and must be delivered as one continuous length on a single spool with a length variance of +/-2%. Prior to proceeding, the contractor must submit the manufacturer's catalog data and drawing for acceptance. After manufacturing, the cable must be tested in accordance with specified standards, with test reports and a certificate of testing required before shipment. The delivery location is the Suisun Bay Reserve Fleet in Benicia, California, with Luis A. Martinez Jr. as the point of contact.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bill of Materials 3,000’ Shore Power Cable
Provide 3,000 feet of 2 AWG 3/C 15KV type MP-GC power cable with class B copper conductors, Ethylene Propylene Rubber (EPR) 133% insulation level, copper tape shield, with ground and ground check, and mold cured Chlorinated Polyethylene (CPE) jacket
(jacket color Orange).
Cable must be MSHA approved and meet the following specifications:
• ASTM B3 Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• ICEA S-75-381/NEMA WC 58 Portable and Power Feeder Cables for use in
Mines and Similar Applications
Prior to receiving a notice to proceed, provide the cable manufacturer’s catalog data and drawing for the cable being offered, for acceptance.
Cable is to be tested in accordance with ICEA S-75-381 section 4.10 and applicable sections of section 6. Provide the manufacturer’s test reports and a certificate of cable testing after the electrical cable is manufactured. The electrical cable will be shipped after acceptance of the testing results.
Cable is intended to be used for underwater service in shallow water (max 36-foot depth).
Cable to be provided as one continuous length on one spool, with an acceptable length variance of
+/-2%.