ATTACHMENT (1) 20FT MODIFIED SHIPPING CONTAINER SPECIFICATION (10-4-21).pdf
PDF 348 KB Posted
- Attached to
- Equipment Docking Station & Shipping Containers Federal contract opportunity
- Solicitation number
- N4215822QE016
About this file
This document provides specifications for the modification and fabrication of six 20-foot long shipping containers. The containers will be modified with steel framing, spray foam insulation, fire-retardant plywood and laminate on the interior walls, ceiling and floor. A roll-up door, E-track on the walls, and stainless steel clad flooring are required. Exterior steel surfaces must be painted with a Class A fire-rated paint. The contractor must submit design drawings and calculations for approval and conduct all fabrication at their facility. The containers must meet the dimensions in Appendix A and be delivered by the date evaluated in the contractor's submitted transportation plan. This requirement is in support of Solicitation N4215822QE016 issued by the Department of the Navy Naval Sea Systems Command for equipment docking stations and shipping containers.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| ATTACHMENT (1) 10FT Modified Shipping Container Specification.pdf | ||
| Appendix-A 10FT Modified Shipping Container Drawings.pdf | ||
| Appendix-A 20FT Modified Shipping Container Drawings.pdf | ||
| Appendix-A Docking Station Drawings 9-30-21.pdf | ||
| Attachment (1) Docking Station Specifications 9-28-21.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
20’ MODIFIED SHIPPING CONTAINER SPECIFICATION FOR
FABRICATION
REV OI 09/23/2021
1. GENERAL REQUIREMENTS
1.1. Purpose: The purpose of this solicitation is to provide specifications for the design, fabrication, outfitting, and delivery of six modified 20’ long high-cube shipping containers (ISO code 25G0 containers, with one open end). The containers shall be modified such that they comply with the drawings in Appendix (A). Basic construction shall be from carbon steel. The designed maximum gross weight of the containers shall be 26,000lbs.
1.2. The contractor shall submit a completed design package to NNSY for approval prior to any construction, this includes design drawings and necessary calculations. All design calculations shall be stamped by a PE and shall be provided with the design package.
1.3. Construction Site: It is expected that the Contractor shall conduct all fabrication and assembly at the contractor's facility.
1.4. All equipment specified will be procured and installed as shown in Appendix A.
1.5. Delivery/Transportation: To be included in the submission of their design package, the contractor shall evaluate transportation requirements.
1.6. Administrative Deliverables: To be included in the submission of their design package, the contractor shall evaluate the cost of processing administrative deliverables, such as drawings, equipment procurement, and inspection results.
ATTACHMENT (1) DOCUMENT 1308ZN02
2. TECHNICAL REQUIREMENTS
2.1. Materials of Construction:
2.1.1. Frame/Structure: Additional components added to the container shall be made of steel with a standard grade of structural quality or higher. The containers shall remain crane bottom liftable.
2.1.1.1. All member to member joints that are required to make up a required length shall have full penetration welds. All member to member joints that provide weather protection shall be fully welded. Weather protected joints may be constructed according to industry standards.
2.1.1.2. If fasteners are used to attach framing to the container walls, the fasteners shall be selected such that galvanic corrosion is minimized.
2.1.1.3. Any modifications shall not impede the functionality of either corner castings or the fork tunnels.
2.1.2. Walls: Walls should be made of 2”X3” metal studs, spray foam insulation, and 3/4" fire retardant plywood. Interior facing should be a minimum of 0.040” thick fire retardant, shatter resistant laminate, similar to Wilsonart Type 107HW. The interior laminate should be non-glossy white. Flame retardant spray foam shall be applied per manufacturer instructions. Note:
The interior finish of the Modified container shall be a Class A, per NFPA 101.
2.1.2.1. Side and rear wall will be equipped with rows of 5” wide galvanized steel E-track as shown in Appendix A. E-track ends shall be equipped with plastic end caps. E-track shall be installed by utilizing the hardware specified by the manufacturer, utilizing all available mounting holes.
2.1.2.2. All corners and seams shall be covered by appropriate trim.
2.1.3. Ceiling: The ceiling should be made of 2”X3” metal studs, spray foam insulation, and 3/4" plywood. Interior facing should be a minimum of 0.032” thick fire retardant, shatter resistant laminate. The interior laminate should be white. Flame retardant spray foam shall be applied per manufacturer instructions. Note: The interior finish of the Modified container shall be a Class A, per NFPA 101.
2.1.3.1. All corners and seams shall be covered by appropriate trim.
2.1.4. Floor: The flooring must be stainless steel clad and attached using flush mounted stainless steel hardware. Flooring shall be flat and of uniform finish that is easily cleaned. Spray foam insulation or similar (minimum R-15) should be installed below the flooring.
2.2. Dimensions: The modified shipping container shall be of the dimensions as specified in Appendix (A).
2.3. Doors:
2.3.1. Roll Up Door: The roll-up door shall be a custom sized TODCO ArmorPlate roll-up door with a thickness of 1/2". The doors shall be equipped with weather seals at the top, bottom, and sides. The door shall be lockable, and used double-slam locks. Doors shall be ordered using Appendix (B). If door opening dimensions of the container do not match those shown in Appendix (A), View A-2 contact NNSY, as this may affect the fit and finish of the roll-up door.
2.4. Windows: The modified shipping container shall not have any windows.
2.5. Painting: Applications of all coatings shall be in accordance with the manufacturer’s instructions.
2.5.1. Interior carbon steel surfaces, including steel members behind insulation, shall be painted with a Class A paint. Paint should meet low VOC (<340g/L) requirements and also be certified asbestos free, similar to Rust-oleum 7400 series paint.
2.5.2. Exterior surfaces shall be painted with an appropriate primer. Exterior Surfaces will be painted with a DTM marine grade paint. Exterior paint shall be Haze Gray.
2.6. MARKINGS: Application of all adhesive markings shall be in accordance with the manufacturer’s instructions. All markings shall be of a durable, UV resistant construction, and of a material suitable for sustained outdoor use. All markings shall be of conspicuous size.
2.6.1. Reflective high-cube height warning tape shall be applied to the top edge of the door opening end of the container.
2.6.2. A warning decal shall be applied to the right side of the roll-up door that reads “Warning High Trailer.”
2.6.3. Decals shall be applied to the right side of the roll-up door that indicates the tare weight of the container rounded up to the nearest 100lb, as indicated in Section 3.
2.6.4. Decals shall be applied to the right side of the roll-up door that indicates the net weight of the container. The net weight of the container shall be 26,000lbs minus the tare weight of the container.
2.6.5. Decals shall be applied to the right side of the roll-up door that indicates the maximum gross weight of the container. The gross weight of the container shall be 26,000lbs.
2.6.6. As viewed from either of the longitudinal sides of the container, paint the bottom left casting yellow with a 3” tall “L” directly above the casting. Paint should be of a similar quality as the exterior paint used on the exterior of the container.
2.6.7. As viewed from either of the longitudinal sides of the container, paint the bottom right casting red with a 3” tall “R” directly above the casting. Paint should be of a similar quality as the exterior paint used on the exterior of the container.
3. QUALITY CONTROL
3.1. Weighing of Structures: The modified containers must be weighed after all work is complete and painted.
3.1.1. The modified container must be rigged using contractor provided rigging.
3.1.2. The final weight of the modified shipping container (shall be rounded up to the next 100 pounds) must be recorded (do not include the weight of the rigging gear in the final weight). Stencil the final weight on the web of lower beam. Stenciled weight is to be on each side of structure.
3.2. Final Inspection: Final acceptance of the modified shipping container shall be made at the contracting agent within 15 days after completed assembly.
Acceptance shall be based on satisfactory completion of the examination.
3.3. Vendor shall provide a Certificate of Compliance that certifies that all requirements of this contract have been met. Certificate of Compliance and all other submitted documentation shall be traceable to the contract number under which this enclosure is provided.
3.4. Vendor shall provide at least a one year warranty on all components of the enclosure.
4. OUTFITTING
4.1. Outfitting of the containers shall be in accordance with Appendix A, View A-10.
4.2. The following equipment shall be outfitted as shown in Appendix A, View A-10.
EQUIPMENT
CALL OUT MANUFACTURER PART
NUMBER
OPTIONAL
FEATURES
REQUIRED
IMAGE
21-3/8DX45W
(VIDMAR)
EXTRA-WIDE
SHALLOW
DEPTH
VIDMAR RP2151AL
1. Lista Dynamic Handles
2. Formed Stainless
Steel Work Top
3. 4-Way Pallet Base
4. Label Holders
5. Slip Resistant
Drawer Liners
6. 30” Surface Mount Frames
7. Under-Shelf Task
Light
8. Backstop and Sidestops
9. 36”Wx15”Dx19”H
Overhead Cabinet W/Recessed Door
21-3/8DX30W
(VIDMAR)
SHALLOW
DEPTH
VIDMAR RP3503AL
2. Formed Stainless
Steel Work Top
3. 4-Way Pallet Base
4. Label Holders
5. Slip Resistant
6. Backstop and Sidestops
28DX30W
(VIDMAR)
ROLLING
TOOLBOX
VIDMAR SEP3203AL
2. Side Push Bar
3. Cabinet Top Tray
4. 5” Hard Rubber
Wheels
5. Label Holders
6. Slip Resistant
24DX48W
SHELVING UNIT U-LINE H-3913 N/A
24DX36W
SHELVING UNIT U-LINE H-4857 N/A
E-TRACK
RATCHET
STRAP
U-LINE H-7064
Yellow or magenta straps are not acceptable
5. REFERENCES
a) American Welding Society Manual D1.1; Structural Welding Code-Steel
b) AISC Manual of Steel Construction
c) ASCE/SEI 7 Minimum Design Loads for Buildings and Other Structures
d) NFPA 801: Standard for Fire Protection for Facilities Handling Radioactive
Materials
e) NFPA 101: Life Safety Code
f) Appendix A: Modified 20’ Shipping Container Drawing Set
g) Appendix B: TODCO Roll-Up Door Order Form
File details come from the government source that posted it. Updated .