Attachment 02 Radioisotope Processing Facility Conceptual Design Floor Plan.pdf
PDF 12 MB Posted
- Solicitation number
- Not on record
- Issued by
-
Department of Energy
About this file
This document is a comprehensive set of architectural drawings for the Radioisotope Processing Facility (RPF) at Oak Ridge National Laboratory, a nonreactor nuclear facilities division project. The drawings depict detailed construction plans for a specialized laboratory building designed to house radioisotope processing operations, material handling corridors, and associated support spaces.
The facility includes multiple functional areas: a mission lobby entry, personnel corridors, hot cell operations with specialized shielding, laboratory casework areas, and a material handling/truck bay corridor. The building features a two-level design with a total height to parapet of approximately 47 feet, incorporating insulated metal panel exterior walls in light and dark gray tones, black anodized aluminum storefront assemblies with low-emissivity glazing, and brake metal coping caps at all parapets. Key architectural elements include a material entry canopy with lift hanger doors and sliding telescopic doors, removable aluminum access platforms, solar array installations on the roof, and specialized HVAC systems with exhaust stacks. The structural design utilizes steel framing with concrete slabs, tegular acoustic ceiling systems, and reinforced concrete construction in critical areas. Interior finishes include lab casework, insulated metal panel clean room assemblies, and specialized environmental controls for radioisotope handling. The drawings span site plans, floor plans for first and second levels, multiple elevation views (north, south, east, and west), building sections, and detailed cross-sections of critical areas including the mission lobby corridor and personnel corridor, along with 3D renderings depicting pedestrian views of the entry, corridors, truck bay, and hot cell areas.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
wkk Callout Transloading Hot Cell
(TYP 9)
wkk Callout Processing Hot Cell
(TYP 23)
123456
C
A
B
D
E
F
G
H
12345678
C
A
B
D
E
F
G
H
CHK DR TL
NO REPRESENTATION OR WARRANTY EXPRESSED OR
MPLIED, IS MADE AS TO THE ACCURACY, COMPLETENESS OR
USEFULNESS OF THE INFORMATION OR STATEMENTS
CONTAINED IN THESE DRAW NGS OR THAT THE USE OR
DISCLOSURE OF ANY INFORMATION APPARATUS METHOD OR
PROCESS DISCLOSED IN THESE DRAW NGS MAY NOT
NFRINGE PRIVATE RIGHTS OF OTHERS. NO LIAB LITY IS
ASSUMED WITH THE RESPECT TO THE USE OF OR FOR
DAMAGES RESULTING FROM THE USE OF ANY INFORMATION,
APPARATUS METHOD OR PROCESS DISCLOSED IN THESE
DRAWINGS. DRAW NGS MADE AVA LABLE FOR NFORMATION
TO BIDDER ARE NOT TO BE USED FOR OTHER PURPOSES,
AND ARE TO BE RETURNED UPON REQUEST OF THE
FORWARDING CONTRACTOR.
REVDO NOT REVISE MANUALLY
THIS DRAWING
PRODUCED IN REVIT
THIS DOCUMENT CONTROLLED BY
NNFD - SAFETY, ENGINEERING & SUPPORT
DESCRIPTION
REVISION OR ISSUE PURPOSE
BY DSNR ESDH REQ FAC DATE SR1 SR2 SR3 SR4 QR
DEFAULT STANDARDS
UNLESS OTHERWISE SPECIFIED
REVISION APPROVALS
ALL DIMENSIONS ARE IN INCHES
WHENEVER A MANUFACTURER'S NAME OR CATALOG NUMBER IS
INDICATED, AN APPROVED EQUAL MAY BE SUBSTITUTED
THIS DRAWING CREATED IN ACCORDANCE WITH
ANSI Y14.5M-1994
DRAWN BY
DESIGNER
CHECKER
DESIGN REVIEW
TASK LEADER
ENGINEERING SUPPORT DEPARTMENT HEAD
REQUESTOR
FAC LITY MANAGER / DESIGNEE
SPECIAL REVIEW
DRAWING APPROVALS
SPECIAL REVIEW
SPECIAL REVIEW
SPECIAL REVIEW
DATE
SCALE
TYPE
CLASS
REVDRAWING NUMBER
BUILDING:PLANT5049481
UEM3
D
NONREACTOR NUCLEAR FACILITIES DIVISION
OAK RIDGE NATIONAL LABORATORY
SHEET NAME:
FL SHEET OF
REFERENCE DRAWING DWG NUM
1 1
A3E017177A005
RPFORNL
RPF
ARCHITECTURAL
BUILDING EXTERIOR 3D RENDERINGS
BUILDING EXTERIOR 3D RENDERING
T. GENTRY
06/08/23
06/08/23
06/08/23
06/08/23
SEE REFERENCE NOTES
D. QUINLEY
Z. BEACH
T. GENTRY
NOT TO SCALE
VIEW OF SOUTH-EAST FACADEVIEW OF NORTH-EAST FACADE
VIEW OF SOUTH-WEST FACADEVIEW OF NORTH-WEST FACADE
INITIAL RELEASE FOR CDR0
Appendix Z
TOC FIRST FLOOR
0"
TOC 2ND FLOOR
22' - 0"
TO PARAPET
47' - 0"
H G FJLQ
DX PLATFORM RAILING & EQUIP BEYOND
MATERIAL ENTRY CANOPY
BLACK ANNODIZED ALUMINUM STOREFRONT
ASSEMBLY W/ LOW-E GLAZING (TYP)
DX PENTHOUSE BEYOND
LIGHT GRAY VERTICAL INSULATED METAL
PANELS
DARK GRAY METAL PANELS (TYP @
STAIR TOWERS)
WHITE HORIZONTAL INSULATED
METAL PANELS
DARK GRAY HORIZONTAL
INSULATED METAL PANELS (TYP AT
PEDESTRIAN CORRIDOR)
BLACK ANNODIZED ALUMINUM STOREFRONT ASSEMBLY (TYP)
TO STAIRWELL PARAPET
32' - 8"
M E B
TO MISSION LOBBY
18' - 0"
TO PED. CORRIDOR
15' - 6"
LIGHT GRAY VERTICAL INSULATED
METAL PANELS
DARK GRAY VERTICAL INSULATED METAL
PANELS (TYP ABOVE & BELOW WINDOW
ASSEMBLY)
BRAKE METAL COPING CAP - COLOR TO MATCH
WALL PANEL (TYP AT ALL PARAPETS)
BLACK ANNODIZED ALUMINUM & GLAZING STOREFRONT DOOR
BUILDING SIGNAGE
HOLLOW METAL DOOR (TYP AT
EXTERIOR)
EXHAUST STACK
OPEN TO BEYOND
ALUMINUM AWNING
BEYOND - SEE PLAN
COLLECTOR BOX & DOWNSPOUT (COLOR TO
MATCH WALL PANEL, TYP)
ADP N K C
ALUMINUM GUTTER &
DOWNSPOUT
TOC FIRST FLOOR
0"
TOC 2ND FLOOR
22' - 0"
TO PARAPET
47' - 0"
HGF J L Q
EXHAUST STACK BEYOND
MATERIAL ENTRY CANOPY
LIGHT GRAY VERTICAL INSULATED
METAL PANELS
BRAKE METAL COPING CAP - COLOR TO
MATCH WALL PANEL (TYP AT ALL
PARAPETS)
TO STAIRWELL PARAPET
32' - 8"
MEB
TO MISSION LOBBY
18' - 0"
TO PED. CORRIDOR
15' - 6"
DX PENTHOUSE BEYOND
DARK GRAY METAL PANELS (TYP @
STAIR TOWERS)
WHITE HORIZONTAL
INSULATED METAL
PANELS
HOLLOW METAL DOOR (TYP AT
EXTERIOR)
BLACK ANNODIZED ALUMINUM
STOREFRONT ASSEMBLY W/ LOW-E
GLAZING (TYP)
DARK GRAY VERTICAL INSULATED METAL
PANELS (TYP ABOVE & BELOW WINDOW
ASSEMBLY)
BLACK ANNODIZED ALUMINUM STOREFRONT ASSEMBLY (TYP)
BLACK ANNODIZED ALUMINUM & GLAZING STOREFRONT DOOR
MATERIAL ENTRY LIFT
HANGER DOOR
MATERIAL ENTRY SLIDING
TELESCOPIC DOORS (EA
SIDE)
A D PNKC
STACK ACCESS PLATFORM
BEYOND (TBD)
COLLECTOR BOX &
DOWNSPOUT (COLOR TO
MATCH WALL PANEL, TYP)
123456
C
A
B
D
E
F
G
H
12345678
C
A
B
D
E
F
G
H
CHK DR TL
NO REPRESENTATION OR WARRANTY EXPRESSED OR
MPLIED, IS MADE AS TO THE ACCURACY, COMPLETENESS OR
USEFULNESS OF THE INFORMATION OR STATEMENTS
CONTAINED IN THESE DRAW NGS OR THAT THE USE OR
DISCLOSURE OF ANY INFORMATION APPARATUS METHOD OR
PROCESS DISCLOSED IN THESE DRAW NGS MAY NOT
NFRINGE PRIVATE RIGHTS OF OTHERS. NO LIAB LITY IS
ASSUMED WITH THE RESPECT TO THE USE OF OR FOR
DAMAGES RESULTING FROM THE USE OF ANY INFORMATION,
APPARATUS METHOD OR PROCESS DISCLOSED IN THESE
DRAWINGS. DRAW NGS MADE AVA LABLE FOR NFORMATION
TO BIDDER ARE NOT TO BE USED FOR OTHER PURPOSES,
AND ARE TO BE RETURNED UPON REQUEST OF THE
FORWARDING CONTRACTOR.
REVDO NOT REVISE MANUALLY
THIS DRAWING
PRODUCED IN REVIT
THIS DOCUMENT CONTROLLED BY
NNFD - SAFETY, ENGINEERING & SUPPORT
DESCRIPTION
REVISION OR ISSUE PURPOSE
BY DSNR ESDH REQ FAC DATE SR1 SR2 SR3 SR4 QR
DEFAULT STANDARDS
UNLESS OTHERWISE SPECIFIED
REVISION APPROVALS
ALL DIMENSIONS ARE IN INCHES
WHENEVER A MANUFACTURER'S NAME OR CATALOG NUMBER IS
INDICATED, AN APPROVED EQUAL MAY BE SUBSTITUTED
THIS DRAWING CREATED IN ACCORDANCE WITH
ANSI Y14.5M-1994
DRAWN BY
DESIGNER
CHECKER
DESIGN REVIEW
TASK LEADER
ENGINEERING SUPPORT DEPARTMENT HEAD
REQUESTOR
FAC LITY MANAGER / DESIGNEE
SPECIAL REVIEW
DRAWING APPROVALS
SPECIAL REVIEW
SPECIAL REVIEW
SPECIAL REVIEW
DATE
SCALE
TYPE
CLASS
REVDRAWING NUMBER
BUILDING:PLANT5049481
UEM3
D
NONREACTOR NUCLEAR FACILITIES DIVISION
OAK RIDGE NATIONAL LABORATORY
SHEET NAME:
FL SHEET OF
REFERENCE DRAWING DWG NUM
1 1
1/8" = 1'-0" A3E017177A006
RPFORNL
RPF
ARCHITECTURAL
BUILDING EAST & WEST ELEVATIONS
BUILDING EAST & WEST ELEVATIONS
SCALE: 1/8" = 1'-0"A EAST EXTERIOR ELEVATION
SCALE: 1/8" = 1'-0"B WEST EXTERIOR ELEVATION
T. GENTRY
06/08/23
06/08/23
06/08/23
06/08/23
40 8 16 FEET
GRAPHIC SCALE
1/8" = 1'-0"
SEE REFERENCE NOTES
D. QUINLEY
Z. BEACH
T. GENTRY
TOC 2ND FLOOR
22' - 0"
TO PARAPET
47' - 0"
R1R2 789101112131415
M
AT
C H
L
IN
E
10' - 0"
LIGHT GRAY VERTICAL INSULATED
METAL PANELS
DARK GRAY METAL PANELS (TYP @
STAIR TOWERS)
DARK GRAY HORIZONTAL INSULATED
METAL PANELS (TYP AT PEDESTRIAN
CORRIDOR)
BLACK ANNODIZED ALUMINUM
STOREFRONT ASSEMBLY (TYP)
BRAKE METAL COPING CAP - COLOR TO
MATCH WALL PANEL (TYP AT ALL
PARAPETS)
DX PENTHOUSE BEYOND
ALUMINUM AWNING
BLACK ANNODIZED ALUMINUM
STOREFRONT ASSEMBLY (TYP)
EXHAUST STACK BEYOND
TO STAIRWELL PARAPET
32' - 8"
TO MISSION LOBBY
18' - 0"
TO PED. CORRIDOR
15' - 6"
DARK GRAY HORIZONTAL
INSULATED METAL PANELS
LIGHT GRAY VERTICAL INSULATED
METAL PANELS
ALUMINUM AWNING W/ TIE
BACK RODS & INTEGRAL
GUTTER
BLACK ANNODIZED ALUMINUM
STOREFRONT ASSEMBLY (TYP)
DARK GRAY METAL PANELS (TYP @
STAIR TOWERS)
BUILDING SIGNAGE
CAST ALUMINUM
SOLAR ARRAY BEYOND - SEE PLAN
DARK GRAY HORIZONTAL INSULATED METAL
PANELS (TYP AT PEDESTRIAN CORRIDOR)
WHITE HORIZONTAL INSULATED METAL PANELS
STACK ACCESS
PLATFORM BEYOND (TBD)
COLLECTOR BOX &
DOWNSPOUT (COLOR TO
MATCH WALL PANEL, TYP)
AWNING DOWNSPOUT
TOC FIRST FLOOR
0"
TOC 2ND FLOOR
22' - 0"
TO PARAPET
47' - 0"
34 2567
M
AT
C H
L
IN
E
10' - 0"
LIGHT GRAY VERTICAL INSULATED
METAL PANELS
DARK GRAY HORIZONTAL INSULATED
METAL PANELS (TYP AT PEDESTRIAN
CORRIDOR)
BLACK ANNODIZED ALUMINUM
STOREFRONT ASSEMBLY (TYP)
BRAKE METAL COPING CAP - CLOR TO
MATCH WALL PANELS (TYP AT ALL
PARAPETS)
TO STAIRWELL PARAPET
32' - 8"
TO PED. CORRIDOR
15' - 6"
BLACK ANNODIZED ALUMINUM &
GLAZING STOREFRONT DOOR
SOLAR ARRAY BEYOND - SEE PLAN
COLLECTOR BOX &
DOWNSPOUT (COLOR TO
MATCH WALL PANEL, TYP)
123456
C
A
B
D
E
F
G
H
12345678
C
A
B
D
E
F
G
H
CHK DR TL
NO REPRESENTATION OR WARRANTY EXPRESSED OR
MPLIED, IS MADE AS TO THE ACCURACY, COMPLETENESS OR
USEFULNESS OF THE INFORMATION OR STATEMENTS
CONTAINED IN THESE DRAW NGS OR THAT THE USE OR
DISCLOSURE OF ANY INFORMATION APPARATUS METHOD OR
PROCESS DISCLOSED IN THESE DRAW NGS MAY NOT
NFRINGE PRIVATE RIGHTS OF OTHERS. NO LIAB LITY IS
ASSUMED WITH THE RESPECT TO THE USE OF OR FOR
DAMAGES RESULTING FROM THE USE OF ANY INFORMATION,
APPARATUS METHOD OR PROCESS DISCLOSED IN THESE
DRAWINGS. DRAW NGS MADE AVA LABLE FOR NFORMATION
TO BIDDER ARE NOT TO BE USED FOR OTHER PURPOSES,
AND ARE TO BE RETURNED UPON REQUEST OF THE
FORWARDING CONTRACTOR.
REVDO NOT REVISE MANUALLY
THIS DRAWING
PRODUCED IN REVIT
THIS DOCUMENT CONTROLLED BY
NNFD - SAFETY, ENGINEERING & SUPPORT
DESCRIPTION
REVISION OR ISSUE PURPOSE
BY DSNR ESDH REQ FAC DATE SR1 SR2 SR3 SR4 QR
DEFAULT STANDARDS
UNLESS OTHERWISE SPECIFIED
REVISION APPROVALS
ALL DIMENSIONS ARE IN INCHES
WHENEVER A MANUFACTURER'S NAME OR CATALOG NUMBER IS
INDICATED, AN APPROVED EQUAL MAY BE SUBSTITUTED
THIS DRAWING CREATED IN ACCORDANCE WITH
ANSI Y14.5M-1994
DRAWN BY
DESIGNER
CHECKER
DESIGN REVIEW
TASK LEADER
ENGINEERING SUPPORT DEPARTMENT HEAD
REQUESTOR
FAC LITY MANAGER / DESIGNEE
SPECIAL REVIEW
DRAWING APPROVALS
SPECIAL REVIEW
SPECIAL REVIEW
SPECIAL REVIEW
DATE
SCALE
TYPE
CLASS
REVDRAWING NUMBER
BUILDING:PLANT5049481
UEM3
D
NONREACTOR NUCLEAR FACILITIES DIVISION
OAK RIDGE NATIONAL LABORATORY
SHEET NAME:
FL SHEET OF
REFERENCE DRAWING DWG NUM
1 1
1/8" = 1'-0" A3E017177A007
RPFORNL
RPF
ARCHITECTURAL
BUILDING NORTH ELEVATION
BUILDING NORTH ELEVATION
SCALE: 1/8" = 1'-0"A NORTH EXTERIOR ELEVATION
SCALE: 1/8" = 1'-0"B NORTH EXTERIOR ELEVATION
T. GENTRY
06/08/23
06/08/23
06/08/23
06/08/23
40 8 16 FEET
GRAPHIC SCALE
1/8" = 1'-0"
SEE REFERENCE NOTES
D. QUINLEY
Z. BEACH
T. GENTRY
TOC 2ND FLOOR
22' - 0"
TO PARAPET
47' - 0"
3 42 5 6 7
M
AT
C H
L
IN
E
10' - 0"
BRAKE METAL COPING CAP -
COLOR TO MATCH WALL PANEL
(TYP AT ALL PARAPETS)
HOLLOW METAL DOOR (TYP AT
EXTERIOR)
DARK GRAY HORIZONTAL
INSULATED METAL PANELS (TYP
AT PEDESTRIAN CORRIDOR)
TO PED. CORRIDOR
15' - 6"
BLACK ANNODIZED ALUMINUM & GLAZING STOREFRONT DOOR
BLACK ANNODIZED ALUMINUM STOREFRONT ASSEMBLY (TYP)
LIGHT GRAY VERTICAL INSULATED
METAL PANELS
TOC FIRST FLOOR
0"
TOC 2ND FLOOR
22' - 0"
TO PARAPET
47' - 0"
R1 R27 8 9 10 11 12 13 14 15
M
AT
C H
L
IN
E
10' - 0"
BRAKE METAL COPING CAP - COLOR TO
MATCH WALL PANEL (TYP AT ALL PARAPETS)
EXHAUST STACK SHOWN DASHED
FOR CLARITY
LIGHT GRAY VERTICAL INSULATED
METAL PANELS
BLACK ANNODIZED ALUMINUM
STOREFRONT ASSEMBLY (TYP)
DARK GRAY HORIZONTAL INSULATED
METAL PANELS (TYP AT PEDESTRIAN
CORRIDOR)
MATERIAL ENTRY CANOPY
MATERIAL ENTRY LIFT
HANGER DOOR
TO PED. CORRIDOR
15' - 6"
MATERIAL ENTRY SLIDING TELESCOPIC
DOORS (EA SIDE)
SHOWN OPEN FOR
CLARITY
HOLLOW METAL DOOR (TYP AT
EXTERIOR)
BLACK ANNODIZED ALUMINUM &
GLAZING STOREFRONT DOOR
DX PENTHOUSE BEYOND
COLLECTOR BOX & DOWNSPOUT
(COLOR TO MATCH WALL PANEL, TYP)
STACK ACCESS PLATFORM (RAILING
HIDDEN FOR CLARITY)
MATERIAL ENTRY SLIDING TELESCOPIC
DOORS (EA SIDE)
123456
C
A
B
D
E
F
G
H
12345678
C
A
B
D
E
F
G
H
CHK DR TL
NO REPRESENTATION OR WARRANTY EXPRESSED OR
MPLIED, IS MADE AS TO THE ACCURACY, COMPLETENESS OR
USEFULNESS OF THE INFORMATION OR STATEMENTS
CONTAINED IN THESE DRAW NGS OR THAT THE USE OR
DISCLOSURE OF ANY INFORMATION APPARATUS METHOD OR
PROCESS DISCLOSED IN THESE DRAW NGS MAY NOT
NFRINGE PRIVATE RIGHTS OF OTHERS. NO LIAB LITY IS
ASSUMED WITH THE RESPECT TO THE USE OF OR FOR
DAMAGES RESULTING FROM THE USE OF ANY INFORMATION,
APPARATUS METHOD OR PROCESS DISCLOSED IN THESE
DRAWINGS. DRAW NGS MADE AVA LABLE FOR NFORMATION
TO BIDDER ARE NOT TO BE USED FOR OTHER PURPOSES,
AND ARE TO BE RETURNED UPON REQUEST OF THE
FORWARDING CONTRACTOR.
REVDO NOT REVISE MANUALLY
THIS DRAWING
PRODUCED IN REVIT
THIS DOCUMENT CONTROLLED BY
NNFD - SAFETY, ENGINEERING & SUPPORT
DESCRIPTION
REVISION OR ISSUE PURPOSE
BY DSNR ESDH REQ FAC DATE SR1 SR2 SR3 SR4 QR
DEFAULT STANDARDS
UNLESS OTHERWISE SPECIFIED
REVISION APPROVALS
ALL DIMENSIONS ARE IN INCHES
WHENEVER A MANUFACTURER'S NAME OR CATALOG NUMBER IS
INDICATED, AN APPROVED EQUAL MAY BE SUBSTITUTED
THIS DRAWING CREATED IN ACCORDANCE WITH
ANSI Y14.5M-1994
DRAWN BY
DESIGNER
CHECKER
DESIGN REVIEW
TASK LEADER
ENGINEERING SUPPORT DEPARTMENT HEAD
REQUESTOR
FAC LITY MANAGER / DESIGNEE
SPECIAL REVIEW
DRAWING APPROVALS
SPECIAL REVIEW
SPECIAL REVIEW
SPECIAL REVIEW
DATE
SCALE
TYPE
CLASS
REVDRAWING NUMBER
BUILDING:PLANT5049481
UEM3
D
NONREACTOR NUCLEAR FACILITIES DIVISION
OAK RIDGE NATIONAL LABORATORY
SHEET NAME:
FL SHEET OF
REFERENCE DRAWING DWG NUM
1 1
1/8" = 1'-0" A3E017177A008
RPFORNL
RPF
ARCHITECTURAL
BUILDING SOUTH ELEVATION
BUILDING SOUTH ELEVATION
SCALE: 1/8" = 1'-0"B SOUTH EXTERIOR ELEVATION
SCALE: 1/8" = 1'-0"A SOUTH EXTERIOR ELEVATION
T. GENTRY
06/08/23
06/08/23
06/08/23
06/08/23
40 8 16 FEET
GRAPHIC SCALE
1/8" = 1'-0"
SEE REFERENCE NOTES
D. QUINLEY
Z. BEACH
T. GENTRY
BO LAB CLG
12' - 0"
TOC 2ND FLOOR
22' - 0"
TOC 2ND FLOOR
22' - 0"
TO PARAPET
47' - 0"
TO PARAPET
47' - 0"
HGF J L
BO HOT CELL CLG
19' - 0"
BO HOT CELL CLG
19' - 0"
TOS 2ND FLOOR
21' - 6"
TOS 2ND FLOOR
21' - 6"
ME
WALL BEYOND
STRUCTURAL FRAME - SEE
STRUCTURAL DWGS
42" H TEMPORARY REMOVABLE
GUARDRAIL - TYP EA SIDE
STRUCTURAL FRAMING - SEE
STRUCTURAL DWGS
ROLL UP DOOR - SEE
PLAN
SOG - SEE STRUCTURAL
DWGS
LAB CASEWORK, TYP - SEE
PLAN
MAN DOOR - SEE PLAN
HOTCELL - SEE
PLAN
MAN DOOR - SEE PLAN
WALL BEYOND
WALL BEYOND
WALL BEYOND
MAN DOOR BEYOND -
SEE PLAN
VERTICAL INSULATED
METAL PANELS
PERSONNEL CORRIDOR
PERSONNEL CORRIDOR
VERTICAL INSULATED METAL
PANELS - SEE PLAN
PARAPET - SEE DETAILPARAPET - SEE DETAIL
STRUCTURAL FRAMING - SEE
STRUCTURAL DWGS
HOT CELL - SEE PLAN
/A A3E017177A017
REMOVABLE ALUMINUM ACCESS
PLATFORM TO ATTACH TO BEAM
SYSTEM - SEE PLAN
/A A3E017177A017
SOLAR ARRAY - SEE PLAN
ROOF TOP CHORD BRG
42' - 8"
TEGULAR ACT CLG
INSULATED METAL PANEL CLEAN
ROOM ASSEMBLY - SEE PLAN
COLLECTOR BOX &
DOWNSPOUT (COLOR TO
MATCH WALL PANEL, TYP)
1/4" / 1'-0"
1/4" / 1'-0"
D PNK
A3E017177A017 B
S M
A3E017177A017 B
SIM OH
DUCTWORK - SEE MECHANICAL DWGS
123456
C
A
B
D
E
F
G
H
12345678
C
A
B
D
E
F
G
H
CHK DR TL
NO REPRESENTATION OR WARRANTY EXPRESSED OR
MPLIED, IS MADE AS TO THE ACCURACY, COMPLETENESS OR
USEFULNESS OF THE INFORMATION OR STATEMENTS
CONTAINED IN THESE DRAW NGS OR THAT THE USE OR
DISCLOSURE OF ANY INFORMATION APPARATUS METHOD OR
PROCESS DISCLOSED IN THESE DRAW NGS MAY NOT
NFRINGE PRIVATE RIGHTS OF OTHERS. NO LIAB LITY IS
ASSUMED WITH THE RESPECT TO THE USE OF OR FOR
DAMAGES RESULTING FROM THE USE OF ANY INFORMATION,
APPARATUS METHOD OR PROCESS DISCLOSED IN THESE
DRAWINGS. DRAW NGS MADE AVA LABLE FOR NFORMATION
TO BIDDER ARE NOT TO BE USED FOR OTHER PURPOSES,
AND ARE TO BE RETURNED UPON REQUEST OF THE
FORWARDING CONTRACTOR.
REVDO NOT REVISE MANUALLY
THIS DRAWING
PRODUCED IN REVIT
THIS DOCUMENT CONTROLLED BY
NNFD - SAFETY, ENGINEERING & SUPPORT
DESCRIPTION
REVISION OR ISSUE PURPOSE
BY DSNR ESDH REQ FAC DATE SR1 SR2 SR3 SR4 QR
DEFAULT STANDARDS
UNLESS OTHERWISE SPECIFIED
REVISION APPROVALS
ALL DIMENSIONS ARE IN INCHES
WHENEVER A MANUFACTURER'S NAME OR CATALOG NUMBER IS
INDICATED, AN APPROVED EQUAL MAY BE SUBSTITUTED
THIS DRAWING CREATED IN ACCORDANCE WITH
ANSI Y14.5M-1994
DRAWN BY
DESIGNER
CHECKER
DESIGN REVIEW
TASK LEADER
ENGINEERING SUPPORT DEPARTMENT HEAD
REQUESTOR
FAC LITY MANAGER / DESIGNEE
SPECIAL REVIEW
DRAWING APPROVALS
SPECIAL REVIEW
SPECIAL REVIEW
SPECIAL REVIEW
DATE
SCALE
TYPE
CLASS
REVDRAWING NUMBER
BUILDING:PLANT5049481
UEM3
D
NONREACTOR NUCLEAR FACILITIES DIVISION
OAK RIDGE NATIONAL LABORATORY
SHEET NAME:
FL SHEET OF
REFERENCE DRAWING DWG NUM
1 1
1/4" = 1'-0" A3E017177A016
RPFORNL
RPF
ARCHITECTURAL
BUILDING SECTION
BUILDING SECTION
SCALE: 1/4" = 1'-0"
A3E017177A001
A BUILDING SECTION
06/08/23
06/08/23
06/08/23
06/08/23
L. BLACKWELL
0 2 4 8 FEET
GRAPHIC SCALE
1/4" = 1'-0"
SEE REFERENCE NOTES
D. QUINLEY
Z. BEACH
T. GENTRY
REFERENCE NOTES:
REFERENCE DRAWINGS:
A3E017177A001 RPF, ARCHITECTURAL, FIRST LEVEL - FLOOR PLAN
A3E017177A017 RPF, ARCHITECTURAL, BUILDING ENLARGED SECTIONS
BO LAB CLG
12' - 0"
BO HOT CELL CLG
19' - 0"
LAB CASEWORK - SEE
PLAN
INSULATED METAL PANEL CLEAN
ROOM ASSEMBLY - SEE PLAN
BLACK ANNODIZED ALUMINUM
STOREFRONT ASSEMBLY W/ BLUE
TINT DOUBLE PANE LOW-E GLAZING
(TYP)
TOS 2ND FLOOR
21' - 6"
SOG - SEE STRUCTURAL
DWGS
ANNODIZED ALUMINUM
STOREFRONT
LIGHT GRAY VERTICAL INSULATED
METAL PANELS
TO STOREFRONT
8' - 6"
E
TO PED. CORRIDOR
15' - 6"
TEGULAR ACT CLG
DARK GRAY HORIZONTAL
INSULATED METAL PANELS (TYP
AT PEDESTRIAN CORRIDOR)
MEMBRANE ROOFING W/ 5" RIGID INSULATION ON MTL DECK -
SEE STRUCTURAL DWGS
BRAKE METAL COPING CAP - COLOR TO
MATCH WALL PANEL
6" MTL STUD - SEE
STRUCTURAL DWGS
6" MTL STUD W/ 5/8" GYP
BOARD - EXTEND FINISH 1'-0"
ABOVE CLG (TYP)
STRUCTURAL FRAMING - SEE
STRUCTURAL DWGS
TO PED. CLG
10' - 0"
" P
AR
AP
ET
M
IN
TEGULAR ACT CLG
COLLECTOR BOX &
DOWNSPOUT (COLOR TO
MATCH WALL PANEL, TYP)
D
TOC FIRST FLOOR
0"
TOC 2ND FLOOR
22' - 0"
TO PARAPET
47' - 0"
TOS 2ND FLOOR
21' - 6"
SOG - SEE STRUCTURAL
DWGS
SPANDREL GLAZING
CONCRETE SLAB - SEE STRUCTURAL
DWGS
BLACK ANNODIZED ALUMINUM STOREFRONT
ASSEMBLY W/ BLUE TINT DOUBLE PANE
LOW-E GLAZING (TYP)
ALUMINUM AWNING
BRAKE METAL COPING CAP - COLOR
TO MATCH WALL PANEL
(2) 2X6 P.T. TOP PLATE
MEMBRANE ROOFING ON EXTERIOR GRADE
SHEATHING
5" RIGID INSULATION
STEEL FRAMING ASSEMBLY - SEE STRUCTURAL DWGS
MTL PARAPET STUD - SEE
STRUCTURAL DWGS
E
TO MISSION LOBBY
18' - 0"
TO PED. CORRIDOR
15' - 6"
TO WINDOW
30' - 2"
TO WINDOW
13' - 0"
TO CORRIDOR CLG
10' - 1"
ALUMINUM AWNING W/ TIE
BACK RODS
BRAKE METAL COPING CAP -
COLOR TO MATCH WALL PANEL
LIGHT GRAY VERTICAL
INSULATED METAL PANELS
DARK GRAY HORIZONTAL
INSULATED METAL PANELS
WHITE HORIZONTAL
INSULATED METAL PANELS
BEYOND
BLACK ANNODIZED ALUMINUM
STOREFRONT ASSEMBLY W/ BLUE TINT
DOUBLE PANE LOW-E GLAZING (TYP)
VISION GLAZING
MEMBRANE ROOFING W/ 5" RIGID
INSULATION ON MTL DECK - SEE
STRUCTURAL DWGS
ROOF TOP CHORD BRG
42' - 8"
DC
123456
C
A
B
D
E
F
G
H
12345678
C
A
B
D
E
F
G
H
CHK DR TL
NO REPRESENTATION OR WARRANTY EXPRESSED OR
MPLIED, IS MADE AS TO THE ACCURACY, COMPLETENESS OR
USEFULNESS OF THE INFORMATION OR STATEMENTS
CONTAINED IN THESE DRAW NGS OR THAT THE USE OR
DISCLOSURE OF ANY INFORMATION APPARATUS METHOD OR
PROCESS DISCLOSED IN THESE DRAW NGS MAY NOT
NFRINGE PRIVATE RIGHTS OF OTHERS. NO LIAB LITY IS
ASSUMED WITH THE RESPECT TO THE USE OF OR FOR
DAMAGES RESULTING FROM THE USE OF ANY INFORMATION,
APPARATUS METHOD OR PROCESS DISCLOSED IN THESE
DRAWINGS. DRAW NGS MADE AVA LABLE FOR NFORMATION
TO BIDDER ARE NOT TO BE USED FOR OTHER PURPOSES,
AND ARE TO BE RETURNED UPON REQUEST OF THE
FORWARDING CONTRACTOR.
REVDO NOT REVISE MANUALLY
THIS DRAWING
PRODUCED IN REVIT
THIS DOCUMENT CONTROLLED BY
NNFD - SAFETY, ENGINEERING & SUPPORT
DESCRIPTION
REVISION OR ISSUE PURPOSE
BY DSNR ESDH REQ FAC DATE SR1 SR2 SR3 SR4 QR
DEFAULT STANDARDS
UNLESS OTHERWISE SPECIFIED
REVISION APPROVALS
ALL DIMENSIONS ARE IN INCHES
WHENEVER A MANUFACTURER'S NAME OR CATALOG NUMBER IS
INDICATED, AN APPROVED EQUAL MAY BE SUBSTITUTED
THIS DRAWING CREATED IN ACCORDANCE WITH
ANSI Y14.5M-1994
DRAWN BY
DESIGNER
CHECKER
DESIGN REVIEW
TASK LEADER
ENGINEERING SUPPORT DEPARTMENT HEAD
REQUESTOR
FAC LITY MANAGER / DESIGNEE
SPECIAL REVIEW
DRAWING APPROVALS
SPECIAL REVIEW
SPECIAL REVIEW
SPECIAL REVIEW
DATE
SCALE
TYPE
CLASS
REVDRAWING NUMBER
BUILDING:PLANT5049481
UEM3
D
NONREACTOR NUCLEAR FACILITIES DIVISION
OAK RIDGE NATIONAL LABORATORY
SHEET NAME:
FL SHEET OF
REFERENCE DRAWING DWG NUM
1 1
3/4" = 1'-0" A3E017177A017
RPFORNL
RPF
ARCHITECTURAL
BUILDING ENLARGED SECTIONS
BUILDING ENLARGED SECTIONS
SCALE: 3/4" = 1'-0"
A3E017177A001
B PERSONNEL CORRIDOR SECTION
T. GENTRY
06/08/23
06/08/23
06/08/23
06/08/23
SCALE: 3/4" = 1'-0"
A3E017177A001
A MISSION LOBBY CORRIDOR SECTION
0 1 2 3 FEET
GRAPHIC SCALE
3/4" = 1'-0"
SEE REFERENCE NOTES
D. QUINLEY
Z. BEACH
T. GENTRY
REFERENCE NOTES:
REFERENCE DRAWINGS:
A3E017177A001 RPF, ARCHITECTURAL, FIRST LEVEL - FLOOR PLAN
123456
C
A
B
D
E
F
G
H
12345678
C
A
B
D
E
F
G
H
CHK DR TL
NO REPRESENTATION OR WARRANTY EXPRESSED OR
MPLIED, IS MADE AS TO THE ACCURACY, COMPLETENESS OR
USEFULNESS OF THE INFORMATION OR STATEMENTS
CONTAINED IN THESE DRAW NGS OR THAT THE USE OR
DISCLOSURE OF ANY INFORMATION APPARATUS METHOD OR
PROCESS DISCLOSED IN THESE DRAW NGS MAY NOT
NFRINGE PRIVATE RIGHTS OF OTHERS. NO LIAB LITY IS
ASSUMED WITH THE RESPECT TO THE USE OF OR FOR
DAMAGES RESULTING FROM THE USE OF ANY INFORMATION,
APPARATUS METHOD OR PROCESS DISCLOSED IN THESE
DRAWINGS. DRAW NGS MADE AVA LABLE FOR NFORMATION
TO BIDDER ARE NOT TO BE USED FOR OTHER PURPOSES,
AND ARE TO BE RETURNED UPON REQUEST OF THE
FORWARDING CONTRACTOR.
REVDO NOT REVISE MANUALLY
THIS DRAWING
PRODUCED IN REVIT
THIS DOCUMENT CONTROLLED BY
NNFD - SAFETY, ENGINEERING & SUPPORT
DESCRIPTION
REVISION OR ISSUE PURPOSE
BY DSNR ESDH REQ FAC DATE SR1 SR2 SR3 SR4 QR
DEFAULT STANDARDS
UNLESS OTHERWISE SPECIFIED
REVISION APPROVALS
ALL DIMENSIONS ARE IN INCHES
WHENEVER A MANUFACTURER'S NAME OR CATALOG NUMBER IS
INDICATED, AN APPROVED EQUAL MAY BE SUBSTITUTED
THIS DRAWING CREATED IN ACCORDANCE WITH
ANSI Y14.5M-1994
DRAWN BY
DESIGNER
CHECKER
DESIGN REVIEW
TASK LEADER
ENGINEERING SUPPORT DEPARTMENT HEAD
REQUESTOR
FAC LITY MANAGER / DESIGNEE
SPECIAL REVIEW
DRAWING APPROVALS
SPECIAL REVIEW
SPECIAL REVIEW
SPECIAL REVIEW
DATE
SCALE
TYPE
CLASS
REVDRAWING NUMBER
BUILDING:PLANT5049481
UEM3
D
NONREACTOR NUCLEAR FACILITIES DIVISION
OAK RIDGE NATIONAL LABORATORY
SHEET NAME:
FL SHEET OF
REFERENCE DRAWING DWG NUM
1 1
A3E017177A019
RPFORNL
RPF
ARCHITECTURAL
BUILDING PEDESTRIAN 3D RENDERINGS
BUILDING PEDESTRIAN 3D RENDERINGS
T. GENTRY
06/08/23
06/08/23
06/08/23
06/08/23
VIEW OF MATERIAL HANDLING CORRIDORVIEW OF MISSION LOBBY ENTRY
VIEW OF HOT CELLVIEW OF TRUCK BAY
SEE REFERENCE NOTES
D. QUINLEY
Z. BEACH
T. GENTRY
NOT TO SCALE
File details come from the government source that posted it. Updated .