Attachment 01- 400Hz_Converters_Technical_Requirements_Redacted.pdf

PDF 158 KB Posted

Attached to
400hz 50kw Frequency Converters Federal contract opportunity
Solicitation number
W50S8F-22-R-0007
Issued by
Department of the Army National Guard

About this file

This solicitation requests quotes for three ground mounted 400Hz 50KW solid state frequency converters. Offerors must submit quotes by email no later than noon on September 17th that fully meet the technical requirements in Attachment 01 and acknowledge all solicitation amendments. The government will award a contract to the responsible offeror providing the best value based on meeting the salient characteristics and price. Offerors must be registered in SAM.gov and able to invoice using PIEE. Questions are due by August 30th and must be submitted to the contracting office email provided. The solicitation attachments include the technical requirements, brand name justification, and provisions and clauses.

View the file

Other files for this federal contract opportunity

Other files attached to 400hz 50kw Frequency Converters, newest first.
File Type Posted
W50S8F-22-R-0007-400hz Converters- Q and A log as of 30 August 2022 (For SAM.Gov).pdf PDF
Attachment 03- Provisions and Clauses.pdf PDF
Attachment 02- W50S8F-22-R-0007-Brand Name Justification-400Hz Converters-Qty-3.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NEW JERSEY AIR NATIONAL GUARD

HEADQUARTERS 177TH FIGHTER WING

EGG HARBOR TOWNSHIP

July 21, 2022

MEMORANDUM FOR 177 MSG/EM, 177/CE, 177CES

FROM: AMXSIMXAAF/ALERT

SUBJECT: Technical Requirements - 400HZ 50KW Frequency Conve1ter

The l 7'fh Fighter Wing Alert shelters are required 400hz electrical frequency converters installed in 3 shelters. The 400HZ power has been ran/installed in 6 ACFT shelters. Electrical reels with cords have also been installed.

1. 50KW Frequency Conve1ter Ground Mounted NSN 6130015815332 Qty-3

1.1. Delivery time: 10-12 months

1.2. Wananty 18 months from delivery, 12 month wan-anty from commissioning (Commissioning performed by vendor)

1. 3. Reels and cords previously installed

2. Extemal controls

2.1. On/off push buttons

2.2. Alanns silence

2.3. Alarm reset

2.4. Emergency off

2.5. Input circuit breaker

2.6. Output Contactor

2.7. Output voltage adjust

2. 8. Aircraft Loop

2. 9. Emergency Stop

3. Electrical Power Ratings

3.1. Continuous max 125kVA/100kW

3.2. 62.5kV A/50kW

4. Power ratings

4.1. Input Power Voltage

4.1.1 208vac, 4 wire+/- 10%

4.1.2 380vac, 4 wire+/- 10%

4.1.3 480vac 4 wire+/- 10%

4.1.4 Frequency 60hz +/- 5%, 50hz +/- 5%

4.2. Output Power

4.2.1 Frequency 400.00Hz +/- 0.5%

4.2.2 Voltage 200/115, 4-w

4.2.3 Adjustment+/- 10%

4.2.4 Regulation+/- 0.5%

4.2.5 Transient 5%@ 50% load step

4.2.6 Phase Balance 1 % balanced load 2%, 1/3 balanced load

4.2.7 Overload 110% 60 minutes, 125% 10 minutes, 150% 2 minutes, 200% 20 seconds, 300% 6 seconds

5. Instrumentation 5 .1. Elapsed time

5.2. Voltage digital meter

5.3. CwTent digital meter

5.4. Frequency digital meter

5.5. Panel Illumination

5.6. Incoming Power monitor and indication

5.7. Input breaker closed indication

5.8. Over temp

5.9. Input/output fault indication

5.10. Audible alarm silence indication

5.11. Aircraft interlock bypass

6. Physical/Environmental

6.1. Noise level 72 db, 10ft ventilation redundant fans

6.2. Dimensions 60 inches long, 40 inches wide, 74 inches high

6.3. Weight 1830 LBS

6.4. Stand is fabricated to these dimensions.

7. Delivery Destination

7.1. CPT, 177th FW NJANG 400 Langley Road, Egg Harbor Township, NJ, 08234

File details come from the government source that posted it. Updated .