This is a Statement of Work for the replacement of two inoperable geothermal heating and cooling units at the Sabine District Office, located at 5050 TX 21, Hemphill, TX 85948.
The contractor must replace two 5-ton, closed-loop dual inline pump geothermal heat pumps (TRANE model GEVE06011G01ATR0010000100000000000) that are more than 10 years old and no longer functional. Replacement units must match or exceed the existing tonnage and salient characteristics, including performance and capacity. The new units must include a 2-stage scroll compressor in an upflow configuration, a dual flow pump center for water flow and serviceability, and new programmable controls. The units shall not have electric resistance heat. The contractor is responsible for system balancing, connecting to existing air distribution and water circulation systems, purging geothermal system lines, commissioning the system, and ensuring 100 percent operational status prior to demobilization. Additional work includes installing new polymer drain pans plumbed to drain outside the building, removing and disposing of existing units from government property, and providing pleated air filtration (minimum MERV 8 rating). Existing ducting and supply/return piping must not be significantly altered from current configuration. The contractor must provide manufacturer specifications documenting that quoted geothermal units meet or exceed existing unit characteristics as an attachment to the quote. Warranty requirements include a minimum 5-year manufacturer warranty for compressor, parts, and labor, effective from the date of government acceptance and final payment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 12445126Q0016.pdf | ||
| Attachment 0002 - Schedule Of Items.pdf | ||
| EO CLAUSE UPDATE INSERT.pdf | ||
| Attachment 0003 - SCA WD.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK FOR: SABINE DISTRICT OFFICE HVAC REPAIRS
DESCRIPTION:
The existing two units, #1 and # 4, are inoperable and are more than 10 years old and shall be replaced.
Below are the characteristics of the existing unit and are the minimum requirements for replacements:
EXISTING HVAC UNITs:
Replacement unit must match or exceed existing tonnage and salient characteristics to include performance and capacity. Current inoperable units are (2) 5 Ton, closed loop dual inline pump Geothermal Heat Pumps; TRANE, model number:
GEVE06011G01ATR0010000100000000000.
*** All quoted geothermal units shall provide the Manufacturer's salient features that meet or exceed those characteristics by attaching the manufacturers' specifications as an attachment to your quote. ***
• The New units shall have a 2 stage scroll compressor, up flow unit
• The New units shall have a dual flow pump center for water flow and serviceability.
• The New geothermal heat pump shall not have electric resistance heat.
• The New units shall be installed with new programmable controls.
• Additional Work:
o Contractor shall be responsible for any system balancing work and also but not limited to:
connecting to existing air distribution system and water circulation system and power.
o Existing ducting and/or supply/ return pipe shall not be significantly altered from its current configuration.
o Contractor shall purge geothermal system lines for adequate operation of the geothermal field and shall be responsible to commission system.
o The contractor shall be responsible for installing the new unit to the existing location to include the existing control system and verify operation. Unit shall be 100% operational prior to any demobilization.
o Install new polymer drain pan(s) with each new unit, plumbed to drain unobstructed to outside the building.
o Contractor shall remove and dispose of existing units from government property.
o Contractor shall provide pleated air filtration needed for new units. Minimum quality of filtration is a MERV 8, pleated filter.
WARRANTY:
Contractor shall provide a manufacturer warranty for any unit that is to be installed.
Adequate documentation providing such a warranty for compressor (5 year min), parts and labor (5 year min) and will be present and verified by the COR prior to the installation of the new unit. The warranty shall be effective from date of acceptance and final payment by the US Govt
CharlesCotton Cross-Out
CharlesCotton Highlight
Unit Pictures from Attic space:
UNIT #1
UNIT #4
Unit #4 evaporator and blower.
Circulation pumps in red. Typical of 2 pumps per unit.
Reference Maps (3):
5050 TX 21, Hemphill, TX 85948
Sabine Ranger District Office
File details come from the government source that posted it. Updated .