Attachment 0001 Concrete Mtg Pads.pdf
PDF 623 KB Posted
- Attached to
- Concrete Pads Federal contract opportunity
- Solicitation number
- W519TC25Q2183
About this file
This document is a detailed set of technical drawings for concrete mounting pads at the Rock Island Arsenal Joint Manufacturing and Technology Center (RIA JMTC). The drawings, dated 21-JAN-25, provide comprehensive plans for six different laser and tube mounting pads in Building B299, including general locations, layout, demolition/cut plans, and elevation/construction specifications.
Key technical details include: mounting pads for North, Middle, and South Flat Lasers; North and South Tube Lasers; and an FTV Mounting Pad. The concrete specifications require 5000 PSI concrete, #5 rebar mesh 4" from top and bottom surfaces, 6" dowel embedment, and a 3/4" expansion joint. The plans specify careful installation procedures, including maintaining elevation within 1/4" deviation, avoiding disturbance to existing building columns and footings, and using precise cutting and demolition techniques for pad installation.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 25Q2183 Amendment 0001.pdf | ||
| 25Q2183.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL LOCATIONS
CONCRETE MOUNTING PADS
PLANT ENGINEERING
ROCK ISLAND ARSENAL JMTC
21-JAN-25
DRAWN
SCALE DATE
APPROVED
NO.
DRAWING
TARA-LGC
PLANT ENGINEERING DIVISION
ROCK ISLAND ARSENAL
CONCRETE MOUNTING PADS
SHEET 1 OF 6B. McCLURE B. NILES
NONE
ELEVATION/CONSTRUCTION PLAN...6
DEMOLITION/CUT PLAN
LOCATION/LAYOUT PLAN
CONTRACTOR SECURITY NOTES
GENERAL NOTES
GENERAL LOCATIONS
INDEX
DISTRIBUTION STATEMENT A: Approved for public release; distribution is unlimited.
X
X
X
X
X
X
X
X X
X
X X
X
X
X
X
M I S S
I P P
I R
I V E R
LOCATIONS ON ROCK ISLAND ARSENAL
X
X
X
X
X
X
X X
X X
X
X X
X
X X X X X X X X X X X
X X
X
X
X
X X X
X
X
X
X
X X
X
X
X
X
X
X X
X
X X
X
X
21 29
30-G
70-G
2-G 3-G
4-G
6-G
50 52
62 64
102 104
157120144
301-G
314 312
220210
332333
204203
R O
C K
IS
L
A N
D
U .S . G
O V
E R
N M
E N
T
B R I D
G E
PARKING
RODMAN
D A V E N P
O R T
G
IL
L E
S P
IE
KINGSBURY
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
TERRACE
PARKING PARKING PARKING
HEDGE
LANE
SOUTH AVENUE
NORTHAVENUE
PARKING
PARKING
PARKING
PARKING
E A
S T
RODMAN
DRIVE
BECK
SYLVAN
AV
EN
U E
KING
DRIVE
SHED
B L U
N T
R O
A D
PROSPECT
DRIV
E
D R
IV
E
C E
M E T E R
Y
D R
IV
E
DYKE
ROAD
R O
D M
AN
BLUNT
PARKING
PARKING
PARKING
PARKING
PARKING
79 83
S Y
V N
R
IV
E
AVE
BAUMBECK AVENUE
216212
LO
C
K
AND
DAM
NO
. 1
BETTENDORF
DAVENPORT
MOLINE
ROCK ISLAND
C A N A L
M
O
L
I N
E
S L O U G H
E. RIVER DR. GRANT ST.
2ND ST.
4TH ST.
3RD ST.
STATE ST.
PC
X
XX
X
X
X
X
X
X X
X
X X
X
X X
X X
X
X
X
X
X
X X
X
B299-FIRST FLOOR ZONE-8
GUARD RAIL GUARD RAIL GUARD RAIL GUARD RAIL
WINDOW WINDOW
RIA#35073
1 1082 3 4 5 6 7 9 11 12 13 14 15 16 17
A
B
C
D
E
F
G
H
K
L
DN
DN
DN
DN DN
E L
E C
T R
IC
A
L G
E A
R
E L
E C
T R
IC
A
L G
E A
R
NORTH FLAT LASER MTG PAD
MIDDLE FLAT LASER MTG PAD
SOUTH FLAT LASER MTG PAD
FTV MTG PAD
NORTH TUBE LASER MTG PAD
SOUTH TUBE LASER MTG PAD
bradley.niles Rectangle bradley.niles Rectangle bradley.niles Rectangle bradley.niles Rectangle bradley.niles Rectangle
GENERAL NOTES
PLANT ENGINEERING
ROCK ISLAND ARSENAL JMTC
21-JAN-25
DRAWN
SCALE DATE
APPROVED
NO.
DRAWING
TARA-LGC
PLANT ENGINEERING DIVISION
ROCK ISLAND ARSENAL
CONCRETE MOUNTING PADS
SHEET 2 OF 6B. McCLURE B. NILES
NONE
MANUAL PROCESSES.
ACCESS WITH COMMERCIAL CONCRETE PUMPING OR POWER DOLLY OR
10. THE CONTRACTOR WILL BE RESPONSIBLE FOR COORDINATING WORK SITE
OR TRUCK AGITATORS HALL BE ACCORDING TO THE FOLLOWING:
THE MAXIMUM HAUL TIME FOR CONCRETE TRANSPORTED IN TRUCK MIXERS
DISCHARGING.
WITHOUT THE ADDITION OF WATER OR WATER AND CEMENT PRIOR TO
WORKABLE CONDITION, SATISFACTORY FOR PLACEMETN IN THE WORK
SHALL BE DELIVERED TO THE SITE OF THE WORK IN A PLASTIC AND
9. CONCRETE TRANSPORTED IN TRUCK MIXERS OR TRUCK AGITATIORS
SATURDAYS. FRAMING, TYING REBAR AND POURING WITH BE DAY SHIFT.
ON 2ND SHIFT STARTING FROM 2:30 TO 11:00 AT NIGHT OR
8. DEMOLITION/JACK HAMMERING/REMOVAL WILL BE PERFORMED
SHALL BE BASF SONOLASTIC SL-1 OR EQUAL.
RIGID FOAM INSULATION FOR VIBRATION ISOLATION. JOINT SEALANT
CLEAN UP IS COMPLETE, LINE MOUNTING PADS AND CAPS WITH 3/4"
7. EXPANSION JOINT MATERIAL UP TO 84" DEEP TYPICAL. AFTER
SHALL BE A MINIMUM OF 5000-PSI.
6. NEW CONCRETE FOR MACHINE MOUNTING PADS AND CAPS
CONVERTER ON ALL DIESEL ENGINES.
USED ARE GAS ENGINES. CONTRACTOR SHALL HAVE CATALYTIC
5. CONTRACTOR SHALL VENT EXHAUST OUTSIDE IF EQUIPMENT
REGULATIONS.
CONCRETE AND REBAR FROM RIA IN ACCORDANCE WITH LOCAL
BOLTS, CANS, BEAMS, CONDUIT, PLATES, PIPES, WOOD BLOCKS,
4. THE CONTRACTOR SHALL REMOVE ALL DEBRIS SUCH AS
OR THE UNDERLYING SOIL CAUSED BY THE CONSTRUCTION.
3. THE CONTRACTOR SHALL REPAIR ANY DAMAGE TO FLOOR
PRESENT MUST BE CUT OFF EVEN WITH SAW CUTS.
2. WHEN SAW CUTTING AROUND THE WORK AREA, REBAR
DUST DURING ENTIRE DEMOLITION AND CONSTRUCTION.
1. THE CONTRACTOR WILL USE WATER TO ELIMINATE DUST
OF DISCHARGE deg-F (deg-C)
CONCRETE TEMPERATURE AT POINT
HAUL TIME
HOURS MINUTE
50-64 (10-17.5)
65-90 (18-32) - WITHOUT RETARDER
1 30
1 3065-90 (18-32) - WITH RETARDER
21. DRAWING NOT TO SCALE.
RIA REPRESENTATIVES IMMEDIATELY.
SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF
20. ANY DISCREPANCIES IN PLANS, OR BETWEEN PLANS AND
OTHER EMBEDDED ITEMS AND INTO FORMS.
SO THAT CONCRTE IS WORKED AROUND REINFORCING AND
VIBRATING EQUIPMENT WITH HAND RODDING AND TAMPING
19. CONSOLIDATE PLACED CONCRETE USING MECHANICAL
PERFORMED BY COMPETENT, EXPERIENCED, QUALIFIED WORKMEN.
(AISC) STANDARDS AND SPECIFICATIONS. ALL WORK SHALL BE
COMPLY WITH LATEST AMERICAN INSTITUTE OF STEEL CONSTRUCTION
18. FABRICATION AND INSTALLATION OF STRUCTURAL STEEL SHALL
OF THE EXISTING CONCRETE.
DOWELS WILL BE DRILLED A MINIMUM OF 6" INTO THE VERTICAL FACE
BOTTOM SURFACE AND HAVE A MINIMUM OF 2 RODS IN EACH DIRECTION.
SPACING. REBAR SHOULD BE A MINIMUM OF 4" AWAY FROM TOP OR
17. DOUBLE TIED LAYERS OF #5 REBAR MESH (5/8"). 12" X-W
COMPLETION OF THE PROJECT.
16. CONTRACTOR SHALL CLEAN UP THE WORKSITE AFTER
SITE UNDER CONSTRUCTION.
15. CONTRACTOR SHALL PROVIDE BARRICADES AROUND JOB
PEDESTRIAN INTERACTIONS.
WITHIN THE BUILDING TO ENSURE SAFE TRAFFIC AND
EQUIPMENT/TRUCKS GOING IN/OUT OF THE BUILDING AND
14. CONTRACTOR WILL PROVIDE SPOTTER/GROUND MAN FOR
GRADE TO ALLOW FOR PROPER GROUNDING OF MACHINE.
INTO MOUNTING PADS AND LEFT EXPOSED 6-INCHES ABOVE
13. CONTRACTOR WILL PROVIDED ONE GROUND ROD DRIVEN
UTILIZE PROPER PPE.
SAFETY RULES OF THE TRAD AND ENSURE ALL PERSONNEL
12. CONTRACTOR WILL FOLLOW AND APPLY ALL STANDARD
REPRESENTATIVE FOR GATE PASS AND FUNCTIONALITY.
11. CONTRACTOR WILL COORDINATE WITH CONTRACTING OFFICER
DISTRIBUTION STATEMENT A: Approved for public release; distribution is unlimited.
The RAMP program is discussed in the RIA-JMTC AT training.
Department.
Contractors will comply with any instructions given by the Rock Island Arsenal Police installation RAMP security program (e.g. vehicles searches, wearing of ID badges, etc.).
Contractor personnel working on Rock Island Arsenal are subject to participation in change.
The COR will keep the contractors informed on the current FPCON or any possible FPCON
The FPCON descriptions will be provided in the RIA-JMTC AT training.
threat. Services will resume when FPCON level is reduced to level Bravo or lower.
During FPCONs Charlie and Delta, services may be discontinued/postponed due to higher iWATCH program. The iWATCH training will be provided in the RIA-JMTC AT training.
The Contractor and all associated subcontractors shall brief all employees on the local support of any future contract.
Contractors who routinely fail to return these items will not be issued them in placed in a drop box at a RIA-JMTC access point.
within 24 hours of no longer being needed. Items will returned to the COR or
RIA-JMTC electronic keys and access passes are accountable items and will be returned contractor5#32s employment.
IF00015 IF00015 at the end of the contract or the last day of an individual
Cards, installation badges, and/or access passes. Use FAR 52.204-9 or PADDS Clause
Contractor will acquire and need to return all issued U.S. Government Common Access thru the RIA Directorate of Emergency Services.
will provide guidance to complete the Access Control Records Check request Form security policies and procedures (provided by government representative). The COR
(Army Directive 2014-05/AR 190-13), applicable installation, facility access and local identification Index (NCIC-III) and Terrorist Screening Database (TSDB) standards and procedures using the National Crime Information Center interstate
Contractor and all associated subcontractor employees shall comply with adjudication training will be provided in the RIA-JMTC AT training.
all employees on the local iWATCH program. The iWATCH
The Contractor and all associated subcontractors shall brief be issued them in support of any future contract.
Contractors who routinely fail to return these items will not box at a RIA-JMTC access point.
needed. Items will returned to the COR or placed in a drop items and will be returned within 24 hours of no longer being
RIA-JMTC electronic keys and access passes are accountable individual contractor�s employment.
IF00015 at the end of the contract or the last day of an access passes. Use FAR 52.204-9 or PADDS Clause IF00015 Government Common Access Cards, installation badges, and/or Contractor will acquire and need to return all issued U.S.
Form thru the RIA Directorate of Emergency Services.
guidance to complete the Access Control Records Check request (provided by government representative). The COR will provide facility access and local security policies and procedures Directive 2014-05/AR 190-13), applicable installation, Index (NCIC-III) and Terrorist Screening Database (TSDB) (Army National Crime Information Center interstate identification comply with adjudication standards and procedures using the Contractor and all associated subcontractor employees shall require changes in contractor security matters or processes.
individual facility or installation change, the Government may contract, should the Force Protection Condition (FPCON) at any changes otherwise authorized by the change clause of this directed by DoD, HQDA, and/or local policy. In addition to the Personal Identity Verification of Contractor Personnel) as identity verification requirements (FAR clause 52.204-9, The contractor workforce must comply with all personal the installation Director of Emergency Services.
to meet installation access requirements to be accomplished by shall provide all information required for background checks The contractor and all associated subcontractors employees access pass being issued.
Operations Center prior to a RIA-JMTC electronic keys and contractor employee and subcontractor employee to the RIA-JMTC The contractor shall sign a Memorandum of Record for each completed.
Level I awareness training and assuring the training is training. The COR will be provided a copy of the RIA-JMTC AT controlled access areas shall complete AT Level I awareness requiring access to Army installations, facilities, or All contractor employees,including subcontractor employees, SECURITY NOTES
CONCRETE MOUNTING PADS
PLANT ENGINEERING
ROCK ISLAND ARSENAL JMTC
21-JAN-25
DRAWN
SCALE DATE
APPROVED
NO.
DRAWING
TARA-LGC
PLANT ENGINEERING DIVISION
ROCK ISLAND ARSENAL
CONCRETE MOUNTING PADS
SHEET 3 OF 6B. McCLURE B. NILES
NONE
B299 LAYOUT
PLANT ENGINEERING
ROCK ISLAND ARSENAL JMTC
21-JAN-25
DRAWN
SCALE DATE
APPROVED
NO.
DRAWING
TARA-LGC
PLANT ENGINEERING DIVISION
ROCK ISLAND ARSENAL
CONCRETE MOUNTING PADS
SHEET 4 OF 6B. McCLURE B. NILES
NONE
DISTRIBUTION STATEMENT A: Approved for public release; distribution is unlimited.
GUARD RAIL GUARD RAIL GUARD RAIL GUARD RAIL
WINDOW WINDOW
RIA#35073
DN
DN
DN
DN DN
E L
E C
T R
IC
A
L G
E A
R
T
Y P
T
Y P
64' TYP
TYP
20'
T
Y P
18'
SOUTH FLAT LASER
MIDDLE FLAT LASER
NORTH FLAT LASER
S O
U T
H T
U B
E L
A S
E R
N O
R T
H T
U B
E L
A S
E R
F T
V
3'
2' TYP
bradley.niles Rectangle bradley.niles Rectangle bradley.niles Rectangle bradley.niles Rectangle bradley.niles Rectangle
CURRENT VIEW CUT LINE VIEW
1" EXPANSION JOINT
4"-8" EXISTING CONCRETE 4"-8" EXISTING CONCRETE
NEW MOUNTING PAD
DEMO AS NEEDED TO INSTALL
DISTURBED.
COLUMNS AND FOOTINGS WILL BE AVOIDED AND NOT
THICK WITH A 3/4" THICK EPOXY COATING. BUILDING
EXISTING CONCRETE FLOORS THAT ARE BETWEEN 4" AND 8"
NOTE: LASER MOUNTING PADS WILL REQUIRE REMOVAL OF
B299 DEMOLITION/CUT PLAN
CONCRETE MOUNTING PADS
PLANT ENGINEERING
ROCK ISLAND ARSENAL JMTC
21-JAN-25
DRAWN
SCALE DATE
APPROVED
NO.
DRAWING
TARA-LGC
PLANT ENGINEERING DIVISION
ROCK ISLAND ARSENAL
CONCRETE MOUNTING PADS
SHEET 5 OF 6B. McCLURE B. NILES
NONE
B299 ELEVATION/CONSTRUCTION PLAN
PLANT ENGINEERING
ROCK ISLAND ARSENAL JMTC
21-JAN-25
DRAWN
SCALE DATE
APPROVED
NO.
DRAWING
TARA-LGC
PLANT ENGINEERING DIVISION
ROCK ISLAND ARSENAL
CONCRETE MOUNTING PADS
SHEET 6 OF 6B. McCLURE B. NILES
NONE
DISTRIBUTION STATEMENT A: Approved for public release; distribution is unlimited.
4"-8" EXISTING CONCRETE
LAYERS. 6" DOWEL EMBEDMENT STANDARD.
#5 REBAR MESH 4" FROM TOP AND BOTTOM SURFACES
" CA6
3/4" EXPANSION JOINT MATERIAL - SL-1 OR EQUIVALENT
ELEVATION.
THE FINAL 12" CAN BE SLOPED TO MEET THE EXISTING
OVER 10'. IF THIS CANNOT MEET EXISTING CONCRETE
MUST MAINTAIN NO GREATER THAN 1/4" DEVIATION
ALWAYS BE THE SAME ELEVATION. MOUNTING PADS
AREA SURROUNDING MOUNTING PADS WILL NOT
NOTE:
5000 PSI CONCRETE
File details come from the government source that posted it. Updated .