Attachement B Filters and Belts by Locations-bldgs-Data Sheets.xlsx
XLSX spreadsheet 690 KB Posted
- Attached to
- 4460--HVAC Filters and Belts
- Solicitation number
- 36C25025Q0919
About this file
This file is an Excel spreadsheet detailing HVAC filters and belts inventory for multiple buildings at the Chillicothe VA Medical Center in Ohio. The document lists specific filter and belt requirements for 14 different buildings, including Buildings 1, 3, 7, 9, 18, 21, 24, 25, 26, 27, 28, 29, 30, 31, 35, 210, 211, and 212, as well as additional structures like the B52 Greenhouse.
The inventory specifies precise measurements, quantities, and replacement frequencies for various HVAC components, with most items requiring quarterly or bi-annual replacement. For example, Building 1 requires 100 fan coil filters sized 8"x 19.75"x1" on a bi-annual basis, while Building 7 needs multiple filter sizes ranging from 24x24x2 to 24x24x12, with corresponding belt replacements. The total requirement encompasses over 7,200 filters and 500 belts of varying sizes and specifications, targeting different air handling units, fan coils, and exhaust systems across the medical center's facilities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment A Table of products Filters and Belts.xlsx | XLSX spreadsheet | |
| 52.225-2 Buy American Certificate.pdf | ||
| 36C25025Q0919.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bldg. 1
| Building HVAC Filters and Belts Inventory Building 1 | STRNAD | ||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| Fan Coil | 8"x 19.75"x1" | FILTER | 100 | BI ANNUAL | |
| Fan Coil | 9 x 19.25" x 1" | FILTER | 22 | BI ANNUAL | |
| Fan Coil | 8.25" x 31.75" x 1" | FILTER | 20 | BI ANNUAL | |
| Fan Coil | 7.5" x 21.5" x 1" | FILTER | 28 | BI ANNUAL | |
| Fan Coil | 8" x 43.75" x 1" | FILTER | 3 | BI ANNUAL | |
| Fan Coil | 8.75" x 23.75" x 1" | FILTER | 2 | BI ANNUAL | |
| Fan Coil | 7.75" x 19.5" x 1" | FILTER | 2 | BI ANNUAL | |
| Fan Coil | 7.5" x 20.5" x 1" | FILTER | 3 | BI ANNUAL | |
| Fan Coil | 7.5" x 31.75" x 1" | FILTER | 4 | BI ANNUAL |
| AHV | 24" x 24" x 2" | PLEATED PRE FILTER | 4 | QUARTERLY |
| AHV | 24" x 24" x 29" | VAVI CELL FILTER | 2 | QUARTERLY |
| AHV | 24" x 24" x 2" | PLEATED PRE FILTER | 6 | QUARTERLY |
| AHV | 20" x 24" x 4" | PLEATED FILTER | 5 | QUARTERLY |
| AHV | 20" x 25" x 2" | PLEATED FILTER | 4 | QUARTERLY |
| AHV | 20" x 25" x 4" | PLEATED FILTER | 4 | QUARTERLY |
| AHV | 20" x 20" x 2" | PLEATED FILTER | 3 | QUARTERLY |
| AHV | 20" x 20" x 4" | PLEATED FILTER | 4 | QUARTERLY |
| AHV | 16" x 20" x 2" | PLEATED FILTER | 5 | QUARTERLY |
| AHV | 16" x 25" x 2" | PLEATED FILTER | 3 | QUARTERLY |
| AHV | 20" x 24" x 2" | PLEATED FILTER | 3 | QUARTERLY |
| BELT | AP 48 | A BELT | 2 | BI ANNUAL |
| BELT | 5VX 490 | B BELT COG | 1 | BI ANNUAL |
| BELT | B 57 | B BELT | 1 | BI ANNUAL |
| BELT | B X 36 | B BELT COG | 1 | BI ANNUAL |
| BELT | A 52 | A BELT | 1 | BI ANNUAL |
| BELT | 3L510R | A BELT | 1 | BI ANNUAL |
Bldg. 3
| Building HVAC Filters and Belts Inventory Building 3 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| AHU | 16" x 20" x 1" | 12 | Quarterly |
| AHU | 17" x 20" x 1" | 12 | Quarterly |
| AHU | 20' x 24" x 2" | 12 | Quarterly |
| BELT | AX-28 | 1 | Quarterly |
| BELT | BX-43 | 1 | Quarterly |
Bldg. 7
| Building HVAC Filters and Belts Inventory Building 7 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Quarterly- Bi-Annual-Annual |
| 7AC-1 | BLDG 7 PENTHOUSE | ||||
| FILTER | 24X24X2 | 8 | Bi-Annual | ||
| FILTER | 24X24X20 | 8 | Bi-Annual | ||
| BELTS | B-68 | 2 MATCH SETS | Bi-Annual |
| 7AC-2 | BLDG 7 PENTHOUSE | |||
| FILTER | 24X24X2 | 8 | Bi-Annual | |
| FILTER | 24X24X29 | 8 | Bi-Annual | |
| BELTS | B-68 | 2 MATCH SET | Bi-Annual |
| POT AND PAN EXHAUST | ROOF | |||
| BELTS | 4L24 | 1 | Quarterly |
| DISH MACH. EXHAUST | ROOF | |||
| BELTS | 4L26 | 1 | Quarterly |
| 7-AH1 | 109A-7 | |||
| FILTER | 24X24X2 | 4 | Quarterly | |
| FILTER | 24X20X2 | 12 | Quarterly | |
| FILTER | 24X24X12 | 6 | Bi-Annual | |
| FILTER | 24X24X12 | 2 | Bi-Annual | |
| BELTS | BX48 | 2 MATCH SET | Bi-Annual |
| 7-AH2 | 109A-7 | |||
| FILTER | 24X24X2 | 3 | Quarterly | |
| FILTER | 24X12X2 | 3 | Quarterly | |
| FILTER | 24X24X12 | 3 | Bi-Annual | |
| FILTER | 24" x 24" x 15' | Pocket Air Filter | 32 | Quarterly |
| FILTER | 24X12X12 | 3 | Bi-Annual | |
| BELTS | B-51 | 1 | Bi-Annual |
| 7-AC4 | 023B-7 | |||
| FILTERS | 24X24X2 | 3 | Bi-Annual | |
| FILTERS | 24X24X29 | 3 | Bi-Annual | |
| BELTS | B-62 | 2 MATCH SET | Bi-Annual |
| CF-1 | B7 2ND FLOOR | |||
| BELTS | BX136 | 2 MATCH SET | Bi-Annual |
| CF-2 | |||
| BELTS | A98 | 2 MATCH SET | Bi-Annual |
| 7-AHU7 | 012-7 | |||
| FILTERS | 24X24X2 | 23 | Quarterly | |
| 24X24X12 | 2 | Bi-Annual | ||
| BELTS | A-27 | 1 | Bi-Annual |
Bldg. 9
| Building HVAC Filters and Belts Inventory Building 9 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| Filter | 20" x 25" x 2" | 8 | Quarterly |
| Filter | 20" x 20" x 2" | 6 | Quarterly |
| Belt | B-54 | 2 | Bi-Annual |
Bldg. 18
| Building HVAC Filters and Belts Inventory Building 18 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| Unit 1 | |||||
| filter | 16" x 25" x 2" | Pleated Pre Filter | 8 | Quarterly |
| Unit 2 | ||||
| filter | 14" x 25' x 2" | Pleated Pre Filter | 11 | Quarterly |
| Unit 3 | ||||
| filter | 24" x 30" x 2" | pleated pre filter | 2 | Quarterly |
| Unit 4 | ||||
| Filter | 24" x 24" x 2" | Pleated Pre Filter | 3 | Quarterly |
| Unit 5 | ||||
| Filter | 24" x 24" x 4" | Pleated Pre Filter | 3 | Quarterly |
| Unit 6 | ||||
| Filter | 24" x 24" x 2" | Pleated Pre Filter | 6 | Quarterly |
| Unit 7 | ||||
| Filter | 20" x 20" x 1" | Pleated Pre Filter | 6 | Quarterly |
| Unit 8 | ||||
| Filter | 20" x 24" x 1" | Pleated Pre Filter | 6 | Quarterly |
Bldg. 21
| Building HVAC Filters and Belts Inventory Building 21 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| furnace filter | 16x20x2 | pleated | 2 | Bi-Annual |
Bldg. 24
| Building HVAC Filters and Belts Inventory Building 24 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| Filter | 24 x 20 x 6 | Pre-Filter | 4 | Quarterly | |
| FIlter | 18 x 20" x 2" | Pre-Filter | 24 | Quarterly | |
| AHU | 20 x 20 x 2 | Filter | 24 | Quarterly |
| Air Compressor | |||
| Belt | B-78 | 2 | Bi-Annual |
| AC-1 | |||
| Filter | 20 x 24 x 2 | 2 | Quarterly |
| Filter | 12 x 24 x 2 | 1 | Quarterly |
| AHU-3 | |||
| Belt | 4L490 | 2 | Bi-Annual |
| AC-4 | |||
| Belt | 4L470 | 1 | Bi-Annual |
| Filter | 24 x 24 x 2 | 2 | Quarterly |
| AHU-2 | |||
| Filter | 24 x 20 x 2 | 6 | Quarterly |
| Filter | 12 x 20 x 2 | 6 | Quarterly |
| AC-3 | |||
| Filter | 12 x 24 x 2 | 5 | Quarterly |
| Filter | 24 x 12 x 6 | 10 | Quarterly |
| Attic Exhaust Fan | |||
| Belt | 4L420 | 1 | Bi-Annual |
| Exhaust Fan 10 | |||
| Belt | A-57 | 1 | Bi-Annual |
| Exhaust Fan 11 | |||
| Belt | 4L440 | 1 | Bi-Annual |
| Fan Coils | 8 x 27 3/4 x 1 | 12 | Bi-Annual |
| 8 x 31 3/4 x 1 | 12 | Bi-Annual | |
| 9x42x1 | 12 | Bi-Annual | |
| 8 x 19 3/4 x 1 | 12 | Bi-Annual | |
| 8x331/2x1 | 24 | Bi-Annual |
Bldg. 25
| Building HVAC Filters and Belts Inventory Building 25 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| filters | 24x20x2 | pleated | 18 | Quarterly |
Bldg. 26
| Building HVAC Filters and Belts Inventory Building 26 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| AHU 2 Filter | 24 x 24 x 2 | 2 | Quarterly | ||
| AHU 2 Filter | 24 x 24 x 12 | 2 | Quarterly | ||
| AHU 2 Belt | A-32 | 1 | Bi-Annual |
| AHU 5 Heat Wheel Filter | 20 x 24 x 2 | exhaust | 9 | Quarterly |
| AHU 5 Heat Wheel Filter | 20 x 24 x 2 | make-up | 6 | Quarterly |
| AHU 5 Heat Wheel Filter | 24 x 24 x 2 | make-up | 3 | Quarterly |
| AHU 5 Pre-filters | 24 x 24 x 2 | supply | 6 | Quarterly |
| AHU 5 Pre-filters | 20 x 24 x 12 | supply | 3 | Quarterly |
| AHU 5 final filters | 24 x 20 x 12 | supply | 6 | Quarterly |
| AHU 5 final filters | 24 x 24 x 12 | supply | 3 | Quarterly |
| AHU 3 filter | 20 x 20 x 2 | 4 | Quarterly |
| AHU 3 filter | 24 x 20 x 2 | 4 | Quarterly |
| AHU 3 filter | 20 x 20 x12 | 4 | Quarterly |
| AHU 3 filter | 24 x 20 x 12 | 4 | Quarterly |
| AHU 4 pre filter | 20 x 20 x 2 | 4 | Quarterly |
| AHU 4 pre filter | 24 x 20 x 2 | 4 | Quarterly |
| AHU 4 final filter | 20 x 20 x 12 | 4 | Quarterly |
| AHU 4 final filter | 24 x 20 x 12 | 4 | Quarterly |
Bldg. 27
| Building HVAC Filters and Belts Inventory Building 27 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| AHU 1 belt | B-42 | 1 | Bi-Annual | ||
| AHU 1 pre-filter | 24 x 24 x 2 | 2 | Quarterly | ||
| AHU 1 pre-filter | 12 x 24 x 2 | 1 | Quarterly | ||
| AHU 1 filter | 24 x 24 x 12 | 2 | Quarterly | ||
| AHU 1 filter | 12 x 24 x 12 | 1 | Quarterly |
| AHU 2 belt | B-44 | 2 | Bi-Annual | |
| AHU 2 pre filter | 20 x 24 x 2 | 3 | Quarterly | |
| AHU 2 pre filter | 12 x 24 x 2 | 2 | Quarterly | |
| AHU 2 filter | 24 x 24 x 12 | vera cell | 2 | Quarterly |
| AHU 2 filter | 24 x 12 x 12 | vera cell | 3 | Quarterly |
| AHU 3 belt | B-61 | 1 | Bi-Annual |
| AHU 3 pre filter | 24 x 24 x 2 | 4 | Quarterly |
| AHU 3 bag filter | 24 x 24 x20 | 4 | Quarterly |
| AHU 4 belt | AX-42 | 1 | Bi-Annual |
| AHU 4 filter | 20 x 25 x 2 | 2 | Quaterly |
| AHU 4 Filter | 20 x 20 x 2 | 1 | Quarterly |
Bldg. 28
| Building HVAC Filters and Belts Inventory Building 28 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| TRANE UNIT | OUTSIDE PACKAGE | ||||
| FILTERS | 20X25X2 | 24 | Quarterly | ||
| BELT | BX96 | 1 | Bi-Anuual | ||
| 5 TON UNIT | 102-28 | ||||
| FILTERS | 16X25X1 | 3 | Quarterly | ||
| BELT | 4L490 | 1 | Bi-Annual | ||
| 5 TON UNIT | 103-28 | ||||
| FILTERS | 16X25X1 | 3 | Quarterly | ||
| BELT | 4L490 | 1 | Bi-Annual | ||
| 5 TON UNIT | 13 RETAIL STORE | ||||
| FILTERS | 20 x 25 x 1 | 1 | Quarterly |
Bldg. 29
| Building HVAC Filters and Belts Inventory Building 29 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| AHU | |||||
| Belt | AX 35 | 1EA | Bi-Annual | ||
| Filters | 20 x 25 x 2 | 4 EA | Quarterly |
Bldg. 30
| Building HVAC Filters and Belts Inventory Building 30 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| AHW1 | 16" X 25"X 4" | PLEATED | 2 | Quarterly | |
| 16" X 20"X 4" | PLEATED | 1 | Quarterly | ||
| 20" X 25" X 4" | PLEATED | 4 | Quarterly | ||
| 20" X 20" X 4" | PLEATED | 4 | Quarterly | ||
| 20" X 24" X 22" | HIE | 1 | Quarterly | ||
| 24" X 24" X 22" | HIE | 2 | Quarterly | ||
| 12" X 24" X 22" | HIE | 2 | Quarterly | ||
| 12" X 20" X 22" | HIE | 1 | Quarterly |
| AHW3 | 24" X 24" X 2" | PLEATED | 4 | Quarterly |
| 20" X 24" X 22" | PLEATED | 8 | Quarterly | |
| 24" X 24" X 22" | HIE | 2 | Quarterly |
| BELTS | A-48 | 1 | Bi-Annual |
| AP-45 | 1 | Bi-Annual | |
| B-551 | 2 | Bi-Annual | |
| A-53 | 1 | Bi-Annual | |
| A-32 | 1 | Bi-Annual | |
| AX42 | 1 | Bi-Annual |
| AHU2 | 16" x 20" x 2" | PLEATED | 4 | Quarterly |
| 20" x 20" x 2" | PLEATED | 4 | Quarterly | |
| 16" x 20" x 22" | HIE | 4 | Quarterly | |
| 20" x 20" x 22" | HIE | 4 | Quarterly |
| AHUS | 20" X 28" X 2" | PLEATED | 1 | Quarterly |
| 24" X 24" X 4" | PLEATED | 1 | Quarterly | |
| 24" X 24" X 2" | 55% | 1 | Quarterly |
| AHU4 | 12" X 24" X 22" | PLEATED | 3 | Quarterly |
| 12" X 24" X 22" | HIE | 3 | Quarterly | |
| 16" x 20" x 2" | PLEATED | 8 | Quarterly | |
| 12" X 24" X 12" | MULTI CELL | 1 | Quarterly | |
| 24" X 24" X 12" | MULTI CELL | 1 | Quarterly |
AHU6 20" X 24" X 22" PLEATED 2 Quarterly
| FAN COIL | 8.5" X 34" X 1" | 7 | Quarterly |
| 8.5" X 28" X 1" | 20 | Quarterly | |
| 8.5" X 46" X 1" | 3 | Quarterly | |
| 8.5" X 22" X 1" | 6 | Quarterly | |
| 20.75" X 7.5" X 1" | 4 | Quarterly |
Bldg. 31
| Bi-Annualuilding HVAC Filters and Bi-Annualelts Inventory Bi-Annualuilding 31 | |||||
| Air Handler/Fan Coil | Size | Part numBi-Annualer | Description | Quarterlyuanty Needed | Quarterlyrtly- Bi-Annuali-Annual-Annual |
| A/C 3 | |||||
| Filters | 24x24x2 | 8 | Quarterly | ||
| 24" x 24" x 2" | 4 | Quarterly | |||
| 24" x 24' x 6" | 4 | Quarterly | |||
| 24X24X15 | 2 | Quarterly | |||
| 24X24X30 | 2 | Quarterly | |||
| belts | BX50 | 1 | Bi-Annuali-Annual |
| Liebert | ||||
| Filter | 29" x 30" x 2" | 38 Pleat Space Guard | 1 | Bi-Annual |
| belts | P-38 | 2 | Bi-Annual |
| AHU 2 | ||||
| Filters | 24x24x2 | 5 | Quarterly | |
| 12x24x2 | 5 | Quarterly | ||
| 24x24x15 | 5 | Quarterly | ||
| 12x24x15 | 5 | Quarterly | ||
| 24x24x30 | 5 | Quarterly | ||
| 12x24x30 | 5 | Quarterly | ||
| 20" x 20" x 6" | 8 | Quarterly | ||
| 20" x 24" x 6" | 16 | Quarterly | ||
| 20" x 20" x 2" | 8 | Quarterly | ||
| 20" x 24" x 2" | 16 | Quarterly | ||
| belts | P79 | Matching Set | 2 | Bi-Annual |
| A/C 1 | ||||
| Filters | 24x24x2 | 5 | Quarterly | |
| 12x24x2 | 5 | Quarterly | ||
| 24x24x5 | 5 | Quarterly | ||
| 12x24x5 | 5 | Quarterly | ||
| 24x24x30 | 5 | Quarterly | ||
| 12x24x30 | 5 | Quarterly | ||
| belts | P83 | Matching Set | 2 | Bi-Annual |
| Carrier unit | ||||
| Filters | 24x24x2 | 1 | Quarterly | |
| 12x24x2 | 1 | Quarterly | ||
| 24x24x12 | 1 | Quarterly | ||
| 12x24x12 | 1 | Quarterly | ||
| belts | A48 | Matching Set | 2 | Bi-Annual |
| A/C 5 AAON | |||
| Filters | 16x25x4 | 4 | Quarterly |
| 20x25x4 | 5 | Quarterly | |
| belts | A-50 | 1 | Bi-Annual |
| A/C 1 | ||||
| Filters | 24x24x2 | 3 | Quarterly | |
| 12x24x2 | 3 | Quarterly | ||
| 24x24x15 | 3 | Quarterly | ||
| 12x24x15 | 3 | Quarterly | ||
| 24x24x30 | 3 | Quarterly | ||
| 12x24x30 | 3 | Quarterly | ||
| 20x24x2 | 2 | Quarterly | ||
| 20x24x30 | 2 | Quarterly | ||
| belt | P85 | Matching Set | 3 | Bi-Annual |
| Ac 2 | ||||
| Filters | 24x24x2 | 5 | Quarterly | |
| 12x24x2 | 5 | Quarterly | ||
| 24x24x30 | 5 | Quarterly | ||
| 12x24x30 | 5 | Quarterly | ||
| belt | P64 | Matching Set | 3 | Bi-Annual |
| Roof Top | ||||
| Filters | 24x24x12 | 65% | 12 | Quarterly |
| 24x24x12 | 95% | 12 | Quarterly | |
| belts | BX 112 | Matching Set | 2 | Bi-Annual |
| 5VX 1060 | Matching Set | 2 | Bi-Annual |
| Xray AH61 | |||
| Filters | 24x24x2 | 6 | Quarterly |
| 24x24x12 | 6 | Quarterly | |
| Belts | P85 | 1 | Bi-Annual |
| AX 78 | 1 | Bi-Annual |
| Xray Liebert | |||
| Filters | 29x30x2 | 1 | Quarterly |
| Belt | B-38 | 1 | Bi-Annual |
| Fan Coils | |||
| Filters | 19 1/2x8x1 | 59 | Quarterly |
| 20 1/2 x9x1 | 3 | Quarterly | |
| 44 1/2 x9x1 | 7 | Quarterly | |
| 30 1/2 x9x1 | 2 | Quarterly | |
| 31 1/2x9x1 | 4 | Quarterly | |
| 31 1/2x8x1 | 1 | Quarterly | |
| 16x25x1 | 1 | Quarterly |
| Exhaust | |||
| Bi-Annual belts | AX-24 | 1 | Bi-Annual |
| AP-77 | 4 | Bi-Annual | |
| Bi-AnnualP-90 | 1 | Bi-Annual | |
| A-84 | 1 | Bi-Annual | |
| AP-82 | 1 | Bi-Annual | |
| AP-27 | 1 | Bi-Annual | |
| Bi-AnnualP-85 | 2 | Bi-Annual | |
| Bi-Annual-60 | 1 | Bi-Annual |
Bldg. 35
| Building HVAC Filters and Belts Inventory Building 35 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| Filter | 24" x 24" x 15" | Pocket Air Filter | 36 | Quarterly | |
| Filter | 7" x 30.5" x 1" | 24 | Quarterly | ||
| Filter | 8" x 19.75" x 1" | 55 | Quarterly | ||
| Filter | 8" x 27.75" x 1" | 24 | Quarterly | ||
| Filter | 8" x 31.75" x 1" | 12 | Quarterly | ||
| Filter | 9" x 20 7/8" x 1" | 4 | Quarterly | ||
| Filter | 9" x 33.75" x 1" | 1 | Quarterly | ||
| Filter | 9" x 34" x 1" | 3 | Quarterly | ||
| Filter | 9" x 42" x 1" | 1 | Quarterly | ||
| Filter | 7.5" x 21.5" x 1" | 7 | Quarterly | ||
| Filter | 7.5" x 25.5" x 1" | 12 | Quarterly | ||
| Filter | 7.5" x 31.5" x 1" | 12 | Quarterly |
| Belt | B-62 | 1 | Bi-Annual |
| Belt | B-83 | 2 | Bi-Annual |
| Belt | B-51 | 1 | Bi-Annual |
| Belt | B-54 | 2 | Bi-Annual |
| Belt | BX-47 | 3 | Bi-Annual |
| Belt | 3VX425 | 1 | Bi-Annual |
Bldg. 210
| Building HVAC Filters and Belts Inventory Building 210 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| AH#1 Belt | BX54 | SA | 6 | Bi-Annual | |
| AH#1 Belt | BX78 | RA | 7 | Bi-Annual | |
| AH#1 Belt | A52 (4L540) | EX | 8 | Bi-Annual | |
| AH#2 Belt | B66 | SA | 20 | Bi-Annual | |
| AH#2 Belt | BX86 | RA | 8 | Bi-Annual | |
| AH#2 Belt | A63 (4L650) | EX | 4 | Bi-Annual | |
| AH#3 | 5VX582 | SA | 2 | Bi-Annual | |
| AH#3 | BX67 | RA | 1 | Bi-Annual | |
| AH#3 | A52 (4L540) | EX | 1 | Bi-Annual | |
| AH#4 | 5VX570 | SA | 2 | Bi-Annual | |
| AH#4 | BX66 | RA | 2 | Bi-Annual | |
| AH#4 Belt | A47 (4L490) | EX | 8 | Bi-Annual | |
| AH#5 Belt | 5VX470 | SA | 8 | Bi-Annual | |
| AH#5 Belt | BX63 | RA | 8 | Bi-Annual | |
| AH#5 | A47 (4L490) | EX | 1 | Bi-Annual | |
| Belt | 5VX-580 | 8 | Bi-Annual | ||
| Belt | BX-61 | 4 | Bi-Annual | ||
| Belt | 5VX-570 | 16 | Bi-Annual |
| Filter | 20" x 20" x 2" | Pleated Pre Filter | 48 | Quarterly |
| Filter | 20" x 20" x 15" | Bag Filter | 48 | Quarterly |
| Filter | 24" 12" X 2" | Pleated Pre FIlter | 12 | Quarterly |
| Filter | 24" x 12" x 15" | Bag Filter | 12 | Quarterly |
| Filter | 24" x 20" x 2" | Pleated Pre Filter | 24 | Quarterly |
| Filter | 24" x 20" x 15" | Bag Filter | 24 | Quarterly |
Bldg. 211
| Building HVAC Filters and Belts Inventory Building 211 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| AH #1 | BX 74 | SA | 2 | Bi-Annual | |
| AH#1 | BX 70 | RA | 1 | Bi-Annual | |
| EF#1 | A65 (4L670) | EX | 1 | Bi-Annual | |
| AH#3 | 5VX660 | SA | 1 | Bi-Annual | |
| AH#3 | B62 | RA | 1 | Bi-Annual | |
| EF#3 | A70 (4L720) | EX | 1 | Bi-Annual | |
| AH#2 | SVX830 | SA | 3 | Bi-Annual | |
| AH#2 | BX77 | RA | 2 | Bi-Annual | |
| EF#2 | A61(4l630) | EX | 1 | Bi-Annual | |
| AH#4 | BX 63 | SA | 2 | Bi-Annual | |
| AH#4 | BX 54 | RA | 1 | Bi-Annual | |
| EF#4 | A34(4L360) | EX | 1 | Bi-Annual | |
| AH#5 | 5v630 | SA | 1 | Bi-Annual | |
| AH#5 | BX53 | RA | 1 | Bi-Annual | |
| EF#5 | A67 (4L690) | EX | 1 | Bi-Annual | |
| AH#6 | B44 | SA | 2 | Bi-Annual | |
| AH#6 | A40 (4L420) | RA | 1 | Bi-Annual | |
| AH#7 | BX43 | SA | 2 | Bi-Annual | |
| AH#7 | BX47 | RA | 1 | Bi-Annual | |
| AH#8 | B68 | SA | 4 | Bi-Annual | |
| ah#8 | BX65 | RA | 3 | Bi-Annual | |
| LIBRARY | BX60 | SA | 1 | Bi-Annual | |
| LIBRARY | BX42 | RA | 1 | Bi-Annual | |
| 24" x 18" x 2" | Pleated Pre-Filter | 12 | Quarterly | ||
| 24" x 24"x 2" | Pleated Pre-Filter | 24 | Quarterly | ||
| 24" x 24" x 15" | Filter | 24 | Quarterly | ||
| 24" x 12" x 2" | Pleated Pre-Filter | 24 | Quarterly | ||
| 24" x 12" x 15" | Filter | 24 | Quarterly | ||
| 20" x 20" x 2" | Pleated Pre-Filter | 12 | Quarterly | ||
| 20" x 20" x 15" | Filter | 12 | Quarterly | ||
| 24" x 20 " x 2" | Pleated Pre-Filter | 28 | Quarterly | ||
| 24" x 24" x 15" | Filter | 48 | Quarterly | ||
| 20" x 16" x 2" | Pleated Pre-Filter | 12 | Quarterly | ||
| 25" x 16" x 2" | Pleated Pre-Filter | 12 | Quarterly |
Bldg. 212
| Building HVAC Filters and Belts Inventory Building 212 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| filter | 14" x 14' x 2" | 24 | Quarterly |
| filter | 14" x 20" x 2" | 12 | Quarterly |
| filter | 14" x 25" x 2" | 14 | Quarterly |
| filter | 20" x 20" x 2" | 12 | Quarterly |
Bldg. 247
| Building HVAC Filters and Belts Inventory Building 247 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| AHU #1 | |||||
| Filters | 24 x 24 x 2 | 6 | Quarterly | ||
| Filters | 24 x 24 x 15 Sock | 6 | Quarterly | ||
| Belt | B-57 | 1 | Bi-Annual |
| AHU #2 | |||
| Filter | 24 x 24 x 2 | 2 | Quarterly |
| Filter | 24 x 24 x 12 | 2 | Quarterly |
| Belt | A-33 | 1 | Bi-Annual |
| AHU #3 | |||
| Filter | 16 x 20 x 2 | 2 | Quarterly |
| Filter | 24 x 24 x 2 | 1 | Quarterly |
| Filter | 20 x 20 x 2 | 6 | Quarterly |
| Filter | 24 x 24 x 2 | 6 | Quarterly |
Bldg. 252
| Building HVAC Filters and Belts Inventory Building 252 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| AH-1 | |||||
| Belt | B-51 | SA | 1EA | Bi-Annual | |
| filter | 16 x 25 x 2 | 24 | Quarterly | ||
| filter | 14 x 25 x 2 | 12 | Quarterly |
Bldg. 259
| Building HVAC Filters and Belts Inventory Building 259 | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| filter | 14x25x2 | pleated | 2 | Quarterly | |
| filter | 14x20x2 | pleated | 2 | Quarterly |
Bldg 60
| Building HVAC Filters and Belts Inventory Building 60 Mace House | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| furnace filter | 20 x 20 x 1 | 2 | Bi-Annual |
B52 Greenhouse
| Building HVAC Filters and Belts Inventory Building B52 Greenhouse | |||||
| AHU/Belt/Fan Coil | Size | Part number | Description | Quanty Needed | Qrtly- Bi-Annual-Annual |
| furnace filter | 20 x 20 x 1 | 1 | Bi-Annual |
AHU Data Sheet
| ATTRIBUTE | ANIMAL RESEARCH | ATRIUM | AUDITORIUMS AND THEATERS | AUTOPSY SUITE | CARDIOVASCULAR LAB SERVICE | COMMUNITY LIVING CENTER | CENTRAL LAUNDRY FACILITY | DENTAL CLINIC SPACES | DIALYSIS TREATMENT SPACES | DIGESTIVE DISEASES ENDOSCOPY SUITE | DINING AREA (CAFETERIA) | DOMICILIARY | ELECTROENCEPHALOGRAPHY LABORATORY (EEG) SPACES | EMERGENCY CARE UNIT | EYE CLINIC SPACES | GYMNASIUM | IMAGING SERIES | INFECTIOUS ISOLATION ROOMS / PROTECTIVE ENVIRONMENTS | KITCHEN (FOOD PRODUCTION) | PATHOLOGY & LABORATORIES | MAIN ENTRANCE LOBBY | INPATIENT MENTAL HEALTH UNIT | MENTAL HEALTH REHABILITATION TREATMENT PROGRAM FACIILITY | OUTPATIENT MENTAL HEALTH SERVICES | NURSING WING | OIT MAIN COMPUTER ROOM | OIT SATELLITE | PATIENT CARE AREAS | PHARMACY SERVICE | POLYTRAUMA REHABILITATION CENTER INPATIENT NURSING UNIT | POLYTRAUMA OUTPATIENT UNIT | PULMONARY MEDICINE SERVICE | SPINAL CORD INJURY/DISORDERS CENTER | STANDALONE SMOKING FACILITY | STERILE PROCESSING SERVICES (SPS) | SURGICAL SUITE | MINIMUM VENTILATION AIR | NON-PATIENT CARE AREAS | |
| Air Handling Type | Dedicated Medium Pressure Constant Volume (paragraphs 3.2.3 and 6.2) | Dedicated (paragraph 6.2). Constant or Variable Air Volume | Dedicated (paragraph 6.2). Constant or Variable Air Volume | Dedicated Medium Pressure Constant Volume (paragraphs 3.2.3 and 6.2) | Dedicated Variable Air Volume or Medium Pressure Constant Volume (paragraphs 3.2.3 and 6.2) | Non-dedicated (Par 6.3) Variable Air Volume | |||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.3 and 6.4) | Dedicated (paragraph 6.2). Constant Volume / Variable Volume | Dedicated Variable Air Volume | |||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.2 and 6.4) | Non-dedicated Variable Air Volume | ||||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.3 and 6.4) | Dedicated Variable Air Volume or Medium Pressure Constant Volume | ||||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.3 and 6.4) | Dedicated (paragraph 6.2) Variable Air Volume | Non-dedicated Variable Air Volume | |||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.3 and 6.4) | Non-dedicated (Par 6.3) Variable Air Volume | Dedicated Variable Air Volume | |||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.2 and 6.4) | Non-dedicated (Par 6.3) Variable Air Volume | Dedicated (Par 6.2) Constant Volume | Dedicated Variable Air Volume | ||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.2 and 6.4) | Non-dedicated Variable Air Volume or Medium Pressure Constant Volume (paragraphs 3.2.3, 6.3 and 6.4) | Dedicated Constant Volume | |||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.2 and 6.4) | Dedicated (Par 6.2) Variable Air Volume | Dedicated Variable Air Volume | |||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.2 and 6.4) | Non-dedicated Variable Air Volume | ||||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.3 and 6.4) | Non-dedicated (Par 6.3)Variable Air Volume | Non-dedicated (Par 6.3) Variable Air Volume | Dedicated Variable Air Volume | ||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.2 and 6.4) | Dedicated (Par 6.2) Constant Volume | Dedicated or Non-Dedicated (Par 6.2 and 6.3), Constant Volume or Variable Volume | Non-dedicated (Par 6.3) Variable Air Volume | Dedicated (paragraph 6.2) Variable Air Volume | Dedicated Variable Air Volume | ||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.2 and 6.4) | Non-dedicated (Par 6.3) Variable Air Volume or Constant Volume | Non-dedicated (par 6.3) Variable Air Volume | Dedicated Variable Air Volume | ||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.2 and 6.4) | Dedicated (Par 6.2) Constant Volume | Dedicated (Par 6.2) Variable Air Volume | Dedicated Variable Air Volume | ||||||||||||||||||||||||||||||||||||
| (paragraphs 3.2.3, 6.2 and 6.4) | Non Dedicated (Par 6.3) Constant Volume | Non-dedicated (Par 6.3) Variable Air Volume | |||||||||||||||||||||||||||||||||||||
| Indoor Design Temperature - Cooling | Room Data Sheets | 75 F [24 C] | 75 F [24 C] | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 75 F [24 C] | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 75 F [24 C] | Room Data Sheets | Room Data Sheets | 78 F [26 C] | Room Data Sheets | 75 F [24 C] | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 77 F [25 C] | Room Data Sheets | Room Data Sheets | Not Applicable | Room Data Sheets | |
| Indoor Design Temperature - Heating | Room Data Sheets | 70 F [21 C] | 70 F [21 C] | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 70 F [21 C] | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 70 F [21 C] | Room Data Sheets | Room Data Sheets | 70 F [21 C] | Room Data Sheets | 70 F [21 C] | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 70 F [21 C] | Room Data Sheets | Room Data Sheets | Not Applicable | Room Data Sheets | |
| Indoor Design Relative Humidity - Dehumidification | Room Data Sheets | 60% | 60% | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 60% | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 60% | Room Data Sheets | Room Data Sheets | 60% | Room Data Sheets | 60% | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 60% | Room Data Sheets | Room Data Sheets | 60% RH | Room Data Sheets | |
| Indoor Design Relative Humidity - Humidification | Room Data Sheets | 20% | Optional (20%) | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Optional (20%) | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Optional | Room Data Sheets | Room Data Sheets | Not Required | Room Data Sheets | Optional (20%) | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Not Required | Room Data Sheets | Room Data Sheets | 20% RH | Room Data Sheets | |
| Minimum Total Air Changes Per Hour | Room Data Sheets | 4 | 4 | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 6 | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 6 | Room Data Sheets | Room Data Sheets | 10 | Room Data Sheets | 6 | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Based on Unit Capacity | Based on Unit Capacity | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | 6 | Room Data Sheets | Room Data Sheets | Not Applicable | Room Data Sheets | |
| Minimum Outdoor Air Changes Per Hour | 100% | 2 | Chapter 2 and Room Data Sheets | 100% | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 | 100% | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | ASHRAE Standard 62.1 - 2016 or latest approved edition. | ASHRAE Standard 62.1-2016 or latest approved edition. | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | Chapter 2 and Room Data Sheets | |
| Return Air Permitted | No | Yes (Normal Mode) | Yes | No | Yes | Yes (Normal Mode) | Room Data Sheets | Yes (Normal Mode) | Yes (Normal Mode) | Yes (Normal Mode) | Yes | Yes (Normal Mode) | Yes | Yes (Normal Mode) | Yes | Yes | Yes (Normal Mode). Also, see Room Data Sheets | Yes (Normal Mode). Also, see Room Data Sheets | Yes (Normal Mode) | No | Yes (Normal Mode) | Yes (Normal Mode) | Yes | Yes | Yes (Normal Mode) | Yes | Yes | Yes | Yes | Yes (Normal mode) | Yes | Yes | Yes (Normal Mode) | Yes | No | Yes (Normal Mode) | No | Yes | |
| Exhaust Air Required | Yes | Yes (Smoke Evacuation Mode) | No | Yes | No | Yes (Emergency Mode) | Room Data Sheets | Yes (Emergency Mode). Also, see Room Data Sheets | Yes (Emergency Mode). Also, see Room Data Sheets | Yes (Emergency Mode). Also, see Room Data Sheets | Yes | Yes (Emergency Mode) | See Room Data Sheets | Yes (Emergency Mode) | See Room Data Sheets | No | Yes (Emergency Mode). Also, see Room Data Sheets | Yes (Emergency Mode). Also, see Room Data Sheets | Yes | Yes | Yes (Emergency Mode). Also, from Selected Spaces) | Yes (Emergency Mode) | No | No | Yes (Emergency Mode) | No | No | No | Yes | Yes (Emergency mode) | No | No | Yes (Emergency Mode) | Yes (Intermittently) | Yes | Yes (Emergency Mode) | Yes | No | |
| Air Economizer Cycle Required | Not Applicable | ASHRAE Standard 90.1 - 2016, or latest approved edition. | ASHRAE Standard 90.1 - 2016, or latest approved edition. | Not Applicable | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | Generally No- ASHRAE 90.1-2016, or latest approved edition | No | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | ASHRAE Standard 90.1 - 2016, or latest approved edition | No | ASHRAE Standard 90.1 - 2016, or latest approved edition | Not Applicable | ASHRAE Standard 90.1 - 2016, or latest approved edition | |
| Energy Recovery System Required | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. Also, see Note 2 | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | No | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | See paragraph 3.6.4 ENERGY RECOVERY SYSTEMS. | |
| Filtration - Pre-Filters (PF-1 and PF-2) | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 14 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | Manufacturer's Standard | Manufacturer’s Standard | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF 1 = MERV 7 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 11 | PF-1 = MERV 7 and PF-2 = MERV 14 | |
| Filtration - After-Filters (AF) | AF = MERV 14 | None | None | None | AF = MERV 14 (Normal Mode) | ||||||||||||||||||||||||||||||||||
| AF = MERV 16A (Emergency Mode) | None | None | AF = MERV 14 | AF = MERV 14 | AF = MERV 14 | None | None | AF = MERV 14 (Normal Mode) | |||||||||||||||||||||||||||||||
| AF = MERV 16A (Emergency Mode) | AF = MERV 14 | AF = MERV 14 (Normal Mode) | |||||||||||||||||||||||||||||||||||||
| AF = MERV 16A (Emergency Mode) | None | AF = MERV 14 | AF = MERV 14 | None | None | None | AF = MERV 14 | AF = MERV 14 (Normal Mode) | |||||||||||||||||||||||||||||||
| AF = MERV 16A (Emergency Mode) | AF = MERV 14 (Normal Mode) | ||||||||||||||||||||||||||||||||||||||
| AF = MERV 16A (Emergency Mode) | AF = MERV 14 (See Note 4 below) | None | None | AF = MERV 14 (Normal Mode) | |||||||||||||||||||||||||||||||||||
| AF = MERV 16A (Emergency Mode) | None | AF = MERV 14 | AF = MERV 14 (Normal Mode) | ||||||||||||||||||||||||||||||||||||
| AF = MERV 16A (Emergency Mode) | AF = MERV 14 (Normal Mode) | ||||||||||||||||||||||||||||||||||||||
| AF = MERV 16A (Emergency Mode) | AF = MERV 14 | None | AF = MERV 14 | AF = MERV 14 | None | None | |||||||||||||||||||||||||||||||||
| Filtration - Final-Filter (FF) | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | FF = MERV 14 (Normal Mode) | ||||||||||
| FF = MERV 16A (Emergency Mode) | None | None | None | None | None | None | See Note 10 | None | None | ||||||||||||||||||||||||||||||
| Cooling Source | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water, DX, Evap Cooling | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water or DX | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water or DX | Chilled Water or DX | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water | Chilled Water or DX | Chilled Water | Chilled Water | Chilled Water | Chilled Water | |
| Heating Source | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Hot Water or Steam | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Hot Water | Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water, Electric | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | Steam and/or Hot Water | |
| Humidification Source | Plant Steam or "Clean" Steam | Plant or "Clean" Steam | Plant or "Clean" Steam | Plant or "Clean" Steam | Plant Steam or "Clean Steam" | Plant or "Clean" Steam | Plant Steam or "Clean Steam" | Plant or "Clean" Steam | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant or "Clean" Steam | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant or "Clean" Steam | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Not Required | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or Clean Steam | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Not Required | Plant Steam or "Clean Steam" | Plant Steam or "Clean Steam" | Plant or "Clean" Steam | Plant or "Clean" Steam | |
| General Exhaust System Required | Yes | No | Yes | Yes | No | Yes | Yes | Room Data Sheets | Room Data Sheets | Yes | Yes | Yes | Room Data Sheets | Yes | Room Data Sheets | Yes | Yes | No | Yes | Yes | Yes | Yes | Yes | Yes | Yes | No | No | Yes | Yes | No | No | Yes | Yes | Yes | Yes | Yes | Yes | ||
| Special Exhaust System Required | Yes | Yes (Smoke Evacuation Mode) | No | Yes | No | Room Data Sheets | Yes | Room Data Sheets | Room Data Sheets | No | Yes | Room Data Sheets | Room Data Sheets | Yes (Emergency Mode) | Room Data Sheets | No | Yes | Yes | Yes | Yes | No | No | No | No | Yes (Emergency Mode) | No | No | No | Yes | Yes (Emergency mode) | No | No | No | No | Yes | Yes (Emergency Mode) | No | Room Data Sheets | |
| Emergency Power Required | Yes | Yes (Smoke Evacuation System) | No | Yes (Exhaust System Only) | No | Yes | No | No | No | No | No | Yes | No | Yes | No | No | MRI Unit, Emergency Exhaust Fan, Associated Controls | Yes - Equipment Branch | No | Yes | No | No | No | No | Yes | Yes For Unit and Controls | Yes For Unit and UPS for Controls | No | Yes | Yes | No | No | Yes | No | Yes | Yes | No | Yes | |
| Individual Room Temperature Control Required | Room Data Sheets | Yes | Yes | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Yes | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Yes | Room Data Sheets | Room Data Sheets | Yes | Room Data Sheets | Yes | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Yes | Yes | No | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Yes | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | |
| Room Air Balance | Room Data Sheets | Positive (+) (Normal Mode) , Negative (-) (Smoke Evacuation) | Positive (+) | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Negative (-) | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Neutral (o) | Room Data Sheets | Room Data Sheets | Negative (-) | Room Data Sheets | Positive (+) | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Positive (+) | Positive | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | Negative (-) | Room Data Sheets | Room Data Sheets | Room Data Sheets | Room Data Sheets | |
| Compliance | AAALAC and NIH DRM | AAALAC and NIH DRM | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | None | NFPA 96 | NFPA 45 and 99 | None | None | None | None | None | None | None | USP <797> and USP <800> | None | None | None | None | None | None | NFPA 99 | None | None | ||
| Note 1 | Note 1 - Listed Rooms and Their Names | ||||||||||||||||||||||||||||||||||||||
| In RDS Sheets. Since current VA design guides are a not available the listed rooms, their names, and the design conditions are based on research for compliance with the American Association for Accreditation of Laboratory Animal Care (AAALAC) and the National Institute of Health Design Requirement Manual (NIH DRM). | Note 1 - HVAC System | ||||||||||||||||||||||||||||||||||||||
| Based on Atrium configuration and air distribution arrangement, evaluate using a variable air volume HVAC system in lieu of a constant volume system. | Note 1 - HVAC System | ||||||||||||||||||||||||||||||||||||||
| Based on Auditorium and Theater air distribution arrangement and extent of conditioned air volume, evaluate using a variable air volume HVAC system in lieu of a constant volume system. | Note 1 - Dedicated Air-Handling Unit | ||||||||||||||||||||||||||||||||||||||
| A dedicated air-handling unit for the Autopsy Suite is NOT required if a 100% OA air-handling unit in the vicinity can meet the requirements of the hours of operation and filtration. | Note 1 - General | ||||||||||||||||||||||||||||||||||||||
| Depending on the size of the Cardiovascular Lab Service area, the space may be served by a non-dedicated air handling unit as long as the unit meets all the minimum requirements described herein. | Note 1 - VAV Air-Handling Units | ||||||||||||||||||||||||||||||||||||||
| The all-air VAV system describe here can also be used for applicable spaces such as offices, lobbies, classrooms, examination rooms, conference rooms, etc. The number of air handling units shall be determined by practical design considerations such as available mechanical room spaces, available above ceiling space for ductwork, functional space grouping, occupancy schedules etc. Spaces requiring constant volume shall be served by constant volume air terminals. | Note 1 - Listed Rooms and Their Names In RDS Sheets | ||||||||||||||||||||||||||||||||||||||
| Since a current VA design guides are a not available the listed rooms, their names, and the design conditions are based on research for compliance with ASHRAE, American Conference of Governmental Industrial Hygienists Industrial Ventilation Manual and past VA HVAC Design Manual. | Note 1 - Emergency Epidemic Air-Handling Unit | ||||||||||||||||||||||||||||||||||||||
| Refer to Par 6.4 DESIGNATED EMERGENCY EPIDEMIC AIR-HANDLING UNITS for additional specific requirements, including 100% OA delivery during emergency mode. | Note 1 - Dedicated Air-Handling Unit | ||||||||||||||||||||||||||||||||||||||
| A dedicated air-handling unit is required if the AHU serving Dialysis Treatment and other spaces is not capable of operating at 100% OA during emergency epidemic mode, or if the AHU does not meet the requirements of the hours of operation and filtration. If warranted for other reasons the dialysis clinic may be provided with its own dedicated air handling unit. | Note 1 - Dedicated Air-Handling Unit | ||||||||||||||||||||||||||||||||||||||
| A dedicated air-handling unit is required if the AHU serving Digestive Health and other spaces is not capable of operating at 100% OA during emergency epidemic mode, or if the AHU does not meet the requirements of the hours of operation and filtration. | Note 1 - Kitchen Make-Up Air | ||||||||||||||||||||||||||||||||||||||
| Estimate the make-up air requirement for the adjoining kitchen (if any) and transfer room air to the kitchen. Maintain the dining or cafeteria under positive air balance with respect to the kitchen. | Note 1 - VAV Air-Handling Units. The all-air VAV system describe here can also be used for applicable spaces such as offices, lobbies, classrooms, examination rooms, conference rooms, etc. The number of air handling units shall be determined by practical design considerations such as available mechanical room spaces, available above ceiling space for ductwork, functional space grouping, occupancy schedules etc. Spaces requiring constant volume shall be served by constant volume air terminals. | Note 1 - General. A separate air handling unit is not required and not prohibited. Any air handling unit used must meet the minimum requirements listed. If warranted for other reasons the EEG Laboratory may be provided with its own dedicated air handling unit. | Note 1 - Listed Rooms and Their Names. Room name and criteria shown in attached Room Data Sheets (RDS) are based on VA PG 18-9 Space Planning Criteria, dated October 3, 2016. | Note 1 - General |
A separate air handling unit is not required and not prohibited. Any air handling unit used must meet the minimum requirements listed. If warranted for other reasons the Eye Clinic may be provided with its own dedicated air
| handling unit. | Note 1 - Demand-Controlled Ventilation |
| Incorporate demand-controlled ventilation sequence, if feasible, to control outdoor air based on carbon-dioxide concentration. Follow requirements of ASHRAE Standard 62.1 - 2016 or latest approved edition. | Note 1 - Listed Rooms and Their Names |
Room names shown in the attached Room Data Sheets are based on the VA Radiology Service Design Guide, April 2008; the VA MRI Design Guide, April 2008; the VA Radiation Therapy Service Design Guide, April 2008; and the VA Nuclear Medicine Design Guide April 2008. See other sections of Chapter 6 for the miscellaneous and support rooms, such as, Housekeeping Aide's Closet (HAC), Attic Space, Crawl Space (Pipe Basement), Exterior Stairs,
| Mechanical/Electrical Rooms, etc. | Note 1 - Emergency Epidemic Air-Handling Unit |
| Refer to Par 6.4 DESIGNATED EMERGENCY EPIDEMIC AIR-HANDLING UNITS for additional specific requirements, including 100% OA delivery during emergency mode | Note 1 - Space Air Balance |
| Minimum room air changes can be increased to meet the exhaust requirements of the range hood and canopy hoods. Conversely, room air can be returned back to the air-handling unit if the system air balance shows surplus air after accounting for the hood exhaust requirement and the use of the return air is economically viable. Transfer air from the exit corridor may be used to maintain negative air balance in the space. | Note 1 - Air-Handling Unit |
| A dedicated air-handling unit with 100% outdoor air is required when a group of laboratories, forming a full-fledged department is in the project scope. One or two laboratories, in the outpatient clinic or similar facilities, can be served by an air-handling unit with minimum outdoor air shown in the Room Data Sheets (Reference: ASHRAE Standard 170-2016 or latest approved edition) and meeting the filtration requirements. | Note 1 - Areas Served |
| The air-handling unit may serve adjoining spaces, such as, Gift Shop, Barber's Shop, Chapel, Public Toilets, and Waiting and Admitting. See Non Patient Room Data Sheets, for additional information on these spaces. | Note 1 - Emergency Epidemic Air-Handling Unit |
| Refer to Par 6.4 DESIGNATED EMERGENCY EPIDEMIC AIR-HANDLING UNITS for additional specific requirements, including 100% OA delivery during emergency mode. | Note 1 - General |
| A separate air handling unit is not required and not prohibited. Any air handling unit used must meet the minimum requirements listed. The air handling unit must operate 24 hours per day, 7 days per week. | Note 1 - General |
| A separate air handling unit is not required and not prohibited. Any air handling unit used must meet the minimum requirements listed. The air handling unit must operate 24 hours per day, 7 days per week. | Note 1 - Listed Rooms and Their Names |
| The space types listed in this manual reflect the terminology and functions used in the VA Medical/Surgical Inpatient Units and Intensive Care Nursing Unit Design Guide dated November 29, 2011. | Note 1 - Standby Capacity |
| Provide N+1 computer room air-conditioning units. N = Number of units in operation required to meet the load and 1 is the standby unit of capacity equal or greater than the largest of the N units. | Note 1 – General |
| HVAC for telephone and satellite OIT spaces shall be provided by systems adjacent to the space if they are systems capable of providing cooling 24/7 365 per year. Systems that do not operate 24/7 or which switch to heating a times during the year cannot be used. In such cases provide local cooling by the most practical method. | Note 1 - General |
| In general, the patient care areas in the Room Data Sheets (RDS) which follow do not require a separate air handling unit. However, if other reasons such as energy, economics, building layout or other similar concerns make a separate air handling unit advantageous, a separated dedicated air handling unit may be provided. Any air handling unit used must meet the minimum requirements listed. | Note 1 - Listed Rooms and Their Names |
| Room names shown in the attached Room Data Sheets are based on Chapter 268: Pharmacy Service in PG-18-9 Space Planning Criteria dated March 2008 and revised October 3, 2016. Since the VA Pharmacy Design Guide Currently in the TIL dates back to 1998 which predates space codes and the current versions of USP 797 and USP 800 that document was not referenced for this HVAC Design Manual. See other tables in chapter 6 for general support areas such as staff and patient toilets and housekeeping aid closets (HAC), locker rooms, lounges, etc. | Note 1 - General - Handling Unit |
| Provide a dedicated air-handling unit where the Polytrauma Rehabilitation Center is constructed as a standalone entity or full-fledged department. The air-handling unit can also serve the Polytrauma Transitional Rehabilitation Program unit (PTRP) unit if located in the same building. The air handling unit shall be served by equipment branch of emergency power. | Note 1 - General |
| A separate air handling unit is not required and not prohibited. Any air handling unit used must meet the minimum requirements listed. The air handling unit must operate on the same schedule as the outpatient unit. | Note 1 - General |
| A separate air handling unit is not required and not prohibited. Any air handling unit used must meet the minimum requirements listed. | Note 1 - General |
| Provide a dedicated air-handling unit where the Spinal Cord Injury/Disorders Center (SCI) is constructed as a standalone entity or full-fledged department. The air-handling unit can also serve the SCI Long Term Care unit if located in the same building. The air handling unit shall be served by equipment branch of emergency power. | Note 1 - VHA Directive |
| Per VHA Directive (2003-035 dated July 1, 2003), smoking is permitted for long term care patients and mental health patients. Indoor smoking must not interfere with the safety of non-smokers. | Note 1 - Listed Rooms and Their Names |
| Room names and criteria shown in the attached Room Data Sheets are based on the VA Design Guide for Logistics Service and Sterile Processing Services dated October 1, 2015 on Chapter 285: Sterile Processing Service in PG-18-9 Space Planning Criteria dated March 2008 and revised October 3, 2016; and on VHA Directive 1116 dated March 23, 2016. See other sections of Chapter 6 for the miscellaneous and support rooms, such as, Housekeeping Aide's Closet (HAC), Attic Space, Crawl Space (Pipe Basement), Exterior Stairs, Mechanical/Electrical Rooms, etc. | Note 1 - Listed Rooms and Their Names |
| Listed rooms, their names, codes, and design conditions found in the RDS sheets that follow this air handling unit are based on the VA Surgical Service Design Guide dated April 2016. See other RDS sheets for general purpose support and clinical spaces found in multiple areas of medical facilities. | Note 1 - Application |
| The minimum ventilation air unit is used when spaces are served by heating and cooling terminal units, such as, fan coil units, ground source heat pumps, etc. | Note 1 - VAV Air-Handling Units |
The all-air VAV system describe here can be used for applicable spaces such as offices, lobbies, classrooms, examination rooms, conference rooms, etc. The number of air handling units shall be determined by practical design considerations such as available mechanical room spaces, available above ceiling space for ductwork, functional space grouping, occupancy schedules etc. Spaces requiring constant volume shall be served by constant volume air terminals.
Note 2 Note 2 - Number of Air-Handling Units
(a) Provide two separate air-handling units, one to meet the lower indoor design temperature, 65 F [18 C], for the Animal Surgical Suite and Rabbit Holding Area and another unit to serve the Animal Holding Areas and Associated Spaces for which the indoor design temperature ranges from 72 F [22 C] to 77 F [25 C].
(b) Due to the lower space temperatures and humidity requirements in the animal surgery room a separate unit or supplemental cooling may be required. The supply temperature of chilled water (if connecting to an existing plant) shall be considered to ensure surgery conditions can be maintained.
| (c) For smaller facilities with few spaces requiring lower (65 F [18 C]) indoor temperature, dedicated, re-circulatory terminal cooling units can provide supplementary cooling in lieu of a dedicated air-handling unit. | Note 2 - Smoke Evacuation System |
| Design the smoke evacuation system per NFPA 101 and its associated documents. VA has opted to follow NFPA 101 with the understanding that the provisions of NFPA 101 may be at variance with the IBC. The design calculations shall be performed by a fire protection professional engineer and reviewed by an independent fire protection professional engineer. The VA fire protection engineer may serve as the independent reviewer. | Note 2 - Demand Control Ventilation |
| Incorporate demand-controlled ventilation sequence, if feasible, to control outdoor air based on carbon-dioxide concentration. Follow ASHRAE Standard 62.1 - 2016 (or latest approved edition) requirements for demand control ventilation. | Note 2 - Dedicated General Exhaust System |
(a) Exhaust System and Discharge Requirement. Provide a dedicated exhaust system to serve the Autopsy Suite. Locate the exhaust fan on the roof with the fan discharging above the highest point of the building. Provide a stack of sufficient height (minimum 10 ft. [3 m]) to discharge air at 3,500 fpm [18 m/s]. Follow the recommendations of the dispersion analysis to ensure that exhaust air does not enter outside air intakes, operable windows and other openings. Mount the fan bearings outside the airstream and monitor the fan status at the ECC.
This is the start of the file's text. The full file is on GovTribe.