Attach. 1 - Salient Characteristics.pdf
PDF 1 MB Posted
- Attached to
- Storm Water Pump (Brand Name or Equal) Federal contract opportunity
- Solicitation number
- FA462026QA212
About this file
This is a Salient Characteristics document for a federal contract opportunity to procure a replacement storm water lift station pump at Fairchild Air Force Base in Washington State. The procurement is identified as FA462026QA212 and is scheduled for March 2026.
The government seeks a Cornell Model #6NHTA-VM-7.5-8 brand name or equal storm water lift station pump to replace an inoperative unit (Serial Number: 65771 11.12) serving the SERE side of the base. The pump must feature an 11.12" impeller, all iron materials of construction, heat treated 420SS wear rings, 316SS shaft sleeve, tangential volute with counter-clockwise/left-hand rotation, single mechanical shaft seal faces, vertical close coupled configuration, and a 7.5HP/900rpm/200-208V/3 phase/60hz motor rated for premium industrial-grade efficient inverter-ready operation with standard enamel paint. One unit is required for delivery to 610 Twinning Avenue, Suite 380, Fairchild AFB, WA 99011. The document includes data plates from the existing inoperative pump (manufactured by Marathon Electric with specifications showing 7.5HP, 860 RPM, and 208V operation) and the Cornell pump for reference, establishing the baseline specifications for acceptable equivalent proposals.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 26QA212 Combo.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SALIENT CHARACTERISTICS
FOR
Storm Water Pump
March 2026
FA462026QA212
Attach. 1 - Salient Characteristics
Salient Characteristics For
Storm Water Pump
Fairchild AFB, WA
1. BACKGROUND: All storm water on the SERE side of Fairchild Air Force Base is collected and pumped out of the lift station. The current pump that serves that lift station is inoperative.
2. OBJECTIVES: To procure a new storm water lift station pump that is Brand Name or Equal in salient characteristics to the existing pump (Serial Number: 65771 11.12)
3. REQUIREMENTS: Contractor shall provide and deliver a Cornell Model #6NHTA-VM-7.5-8 BRAND NAME OR EQUAL new Storm Water Lift Station Pump with the following salient characteristics:
a) 11.12” impeller
b) All iron materials of construction
c) Heat treated 420SS wear rings
d) 316SS shaft sleeve
e) Tangential volute w/ CCW/LH rotation
f) Single mechanical shaft seal faces
g) Vertical close coupled configuration
h) 7.5HP/900rpm/200-208V/3 phase/60hz/wp-1 motor
i) Premium industrial grade efficient inverter ready
j) Standard enamel paint
4. DELIVERY: 610 Twinning Ave, Suite 380 Fairchild AFB WA 99011
5. PARTS LIST:
PART NUMBER OR EQUAL DESCRIPTION OR EQUAL QUANTITY
Cornell Model #
6NHTA-VM-7.5-8
11.12” impeller; all iron materials of construction;
heat treated 420SS wear rings; 316SS shaft sleeve;
tangential volute w/ CCW/LH rotation; single mechanical shaft seal faces; vertical close coupled configuration; 7.5HP/900rpm/200-208V/3 phase/60hz/wp-1 motor; premium industrial-grade efficient inverter ready; standard enamel paint
APPENDIX 1: Data Plates
Motor Data Plate
Pump Data Plate
File details come from the government source that posted it. Updated .