Attach A-Excel Sheet Salient Characteristics.xlsx

XLSX spreadsheet 39 KB Posted

Attached to
W023--USP 797/800 Mobile Pharmaceutical Trailer
Solicitation number
36C26221Q0246
Issued by

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Base CLIN Brand Name Brand Name Nomenclature Manufacturer Part Number if Applicable Salient Characteristics Category Salient Characteristic Description Requirement Equivalent Brand Equivalent Nomenclature Equivalent Part Number Equivalent Description Matching Salient Characteristics and/or location of information regarding equal capability Quantity Unit Price Extended Price

1Rooms & AreasUnclassified area separating the main entrance from the anteroomPreferred$ - 0
2Rooms & AreasAnteroomRequired$ - 0
3Rooms & AreasSterile Hazardous Drug (HD) Buffer RoomRequired$ - 0
4Rooms & AreasSterile Non-Hazardous Drug (Non-HD) Buffer RoomRequired$ - 0
5Rooms & AreasSterile Hazardous Drug Storage AreaRequired$ - 0
6Rooms & AreasSelf-Supporting Modular Design inclusive of walls, roof, ceiling, flooring, lighting, electrical & filtering equipmentRequired$ - 0
7Rooms & AreasModular clean room must fit in a 57' L x8'6"L W x 13'6" H DOT approved semi-trailer Modular Clean room seismic intergrity provisions where necessaryPreferred$ - 0
8Rooms & AreasFinishes - Non-pourous and cleanable surfaces, ceilings, walls, and floors with minimal seams and crevices, able to withstand appropriate deactivation, decontamination, disinfecting and cleaning agentsRequired$ - 0
9Equipment - Unclassified AreaSoiled PPE Waste BinRequired$ - 0
10Equipment - Unclassified AreaStainless steel workstationPreferred$ - 0
11Equipment - Unclassified AreaOne (1) data drop with 4 ports (RJ 45)Required$ - 0
12Equipment - Unclassified AreaTwo (2) 120V power outlest with 2 sockets eachRequired$ - 0
13Equipment - AnteromScrub sink with eyewash station and anti-scald device positioned at least 1 meter from the sterile HD buffer room doorRequired$ - 0
14Equipment - AnteromClean Personal Protective Equipment (PPE) Storage Bin$ - 0
15Equipment - AnteromSoiled PPE Waste Bin$ - 0
16Equipment - AnteromStaff Changing Bench$ - 0
17Equipment - AnteromEnvironmental Services Cabinet$ - 0
18AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraEquipment - AnteromTwo (2) ceiling mounted surveillance cameras: AXIS M3045-V Network Camera or equivalentRequired - Equivalent product acceptable$ - 0
19Equipment - Anterom3M™ Avagard™ Hands Free Wall Dispenser$ - 0
20BakerSterilGard e3 Class II Type A2 Biological Safety Cabinet - 4'SG404Equipment - Sterile Hazardous Drug (HD) Buffer RoomTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC) spaced 1 meter apart from each other with 100% Outside Air Supply and ExhaustRequired - Equivalent product acceptable$ - 0
21Equipment - Sterile Hazardous Drug (HD) Buffer RoomInterlocking HEPA filtered Pass-Thru Chamber from AnteroomRequired - Equivalent product acceptable$ - 0
22Equipment - Sterile Hazardous Drug (HD) Buffer RoomStainless Steel WorkstationRequired - Equivalent product acceptable$ - 0
23Thermo ScientificThermo Scientific Refrigerator model TSX3005GATSX3005GAEquipment - Sterile Hazardous Drug (HD) Buffer RoomThermo Scientific Refrigerator model TSX3005GA or equivalentRequired - Equivalent product acceptable$ - 0
24Equipment - Sterile Hazardous Drug (HD) Buffer RoomSoiled PPE Waste BinRequired - Equivalent product acceptable$ - 0
25Equipment - Sterile Hazardous Drug (HD) Buffer RoomStorage Cabinet for compounded sterile hazardous drugsRequired - Equivalent product acceptable$ - 0
26Equipment - Sterile Hazardous Drug (HD) Buffer RoomMobile Solid stainless-steel shelving with lockable casters and a minimum of 4 shelvesRequired - Equivalent product acceptable$ - 0
27Equipment - Sterile Hazardous Drug (HD) Buffer RoomOne (1) data drop with 4 ports (RJ 45)Required - Equivalent product acceptable$ - 0
28Equipment - Sterile Hazardous Drug (HD) Buffer RoomThree (3) 120V power outlets with two sockets eachRequired - Equivalent product acceptable$ - 0
29Gai-TronicsClean Phone® Analog Telephone (Wall-Mount) - UL295-001WEquipment - Sterile Hazardous Drug (HD) Buffer RoomA wall mounted Clean Phone® or similar (GAI-Tronics 295-001W)Preferred - Equivalent product acceptable$ - 0
30AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraEquipment - Sterile Hazardous Drug (HD) Buffer RoomTwo (2) ceiling mounted surveillance cameras: AXIS M3045-V Network Camera or equivalentRequired - Equivalent product acceptable$ - 0
31Equipment - Sterile Hazardous Drug (HD) Buffer Room3M™ Avagard™ Hands Free Wall Dispenser (Government furnished, contractor installed)Required - Equivalent product acceptable$ - 0
32Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC)$ - 0
33Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomInterlocking HEPA Filtered Pass-Thru Chamber from Anteroom or Unclassified AreaRequired - Equivalent product acceptable$ - 0
34Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomStainless Steel WorkstationRequired - Equivalent product acceptable$ - 0
35Thermo ScientificThermo Scientific Refrigerator model TSX3005GATSX3005GAEquipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomThermo Scientific Refrigerator model TSX3005GA or equivalentRequired - Equivalent product acceptable$ - 0
36Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomNon-Hazardous Drug Storage CabinetRequired - Equivalent product acceptable$ - 0
37Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomMobile Solid stainless-steel shelving with lockable casters and a minimum of 4 shelvesRequired - Equivalent product acceptable$ - 0
38Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomOne (1) data drop with 4 ports (RJ 45)Required - Equivalent product acceptable$ - 0
39Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomThree (3) 120V power outlets with two sockets eachRequired - Equivalent product acceptable$ - 0
40Gai-TronicsClean Phone® Analog Telephone (Wall-Mount) - UL295-001WEquipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomA wall mounted Clean Phone® or similar (GAI-Tronics 295-001W)Preferred - Equivalent product acceptable$ - 0
41AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraEquipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomTwo (2) ceiling mounted surveillance cameras: AXIS M3045-V Network Camera or equivalentRequired - Equivalent product acceptable$ - 0
42Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer Room3M™ Avagard™ Hands Free Wall Dispenser (Government furnished, contractor installed)$ - 0
43Environmental ControlsAll facility & engineering controls compliant with USP 797/800 standards.Required$ - 0
44Environmental ControlsTrailer should be able to maintain appropriate internal temperature, humidity and pressure requirements while located in Long Beach, CA, which has a Mediterranean-type, coastal climate. Temperature extremes may range from 20°F – 112°F with a relative humidity up to 100%.Required$ - 0
45Environmental ControlsThe trailer must have fire alarm system that is completely independent and compliant with the NFPA requirement and has the capability to alert and automatically dial out when the fire alarm system is activated.Required$ - 0
46Environmental ControlsPhysically separated Anteroom and Sterile Hazardous Drug Buffer Room and Sterile Non-Hazardous Drug Buffer Room.Required$ - 0
47BakerSterilGard e3 Class II Type A2 Biological Safety Cabinet - 4'SG404Environmental Controls - Primary Engineering ControlsTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC) in Sterile HD Buffer Room with 100% Outside Air Supply and ExhaustRequired$ - 0
48BakerSterilGard e3 Class II Type A2 Biological Safety Cabinet - 4'SG404Environmental Controls - Primary Engineering ControlsTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC) in Sterile Non-Hazardous Buffer RoomRequired$ - 0
49Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomPositive pressure with greater than or equal to 0.02-inch Water ColumnRequired$ - 0
50Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomMinimum of 35 Air Exchanges Per Hour (ACPH) compliant with USP 797 and USP 800 and VA HVAC Design ManualRequired$ - 0
51Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomHigh Efficiency Particulate Air (HEPA) filtered supply airRequired$ - 0
52Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomHigh Efficiency Particulate Air (HEPA) filtered exhaust airRequired$ - 0
53Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomRoom temperature shall be between 15 degrees Celsius and 20 degrees CelsiusRequired$ - 0
54Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomHumidity level shall be between 30% and 60%Required$ - 0
55Environmental Controls - Secondary Engineering Controls - ISO 7 Anteroom24/7 Real-time Environmental Room Monitor providing: Room temperature, Humidity,Differential pressureRequired$ - 0
56Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomNegative pressure between 0.01-inch Water Column to 0.03-inch Water ColumnRequired$ - 0
57Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomMinimum of 35 Air Exchanges Per Hour (ACPH) compliant with USP 797 and USP 800 and VA HVAC Design ManualRequired$ - 0
58Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer Room100% Outside Supply Air (into room)Required$ - 0
59Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomHigh Efficiency Particulate Air (HEPA) filtered supply airRequired$ - 0
60Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomZero recirculation of HD Buffer Room airRequired$ - 0
61Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomEach compounding hood has a dedicated external exhaust that is HEPA-filtered directly to outsidemRequired$ - 0
62Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomBuffer room has a dedicated and HEPA-filtered external exhaust that is 100% of air exhausted directly to outsideRequired$ - 0
63Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomRoom temperature shall be between 15 degrees Celsius and 20 degrees CelsiusRequired$ - 0
64Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomHumidity level shall be between 30% and 60%Required$ - 0
65Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer Room24/7 Real-time Monitoring Refrigerator interior temperature to ensure drug safety. The interior temperature for the refrigerator shall be between 2 degrees Celsius and 8 degrees Celsius.Required$ - 0
66Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer Room24/7 Real-time Environmental Room Monitor providing: Room temperature, Humidity,Differential pressureRequired$ - 0
67Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomPositive pressure with greater than or equal to 0.02-inch Water ColumnRequired$ - 0
68Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomMinimum of 35 Air Exchanges Per Hour (ACPH) compliant with USP 797 and USP 800 and VA HVAC Design ManualRequired$ - 0
69Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer Room100% Outside Supply Air (into room)Required$ - 0
70Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomHigh Efficiency Particulate Air (HEPA) filtered supply airRequired$ - 0
71Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomBuffer room has High Efficiency Particulate Air (HEPA) filtered exhaust/return airRequired$ - 0
72Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomEach compounding hood has built-in HEPA filter.Required$ - 0
73Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomRoom temperature shall be between 15 degrees Celsius and 20 degrees CelsiusRequired$ - 0
74Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomHumidity level shall be between 30% and 60%Required$ - 0
75Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer Room24/7 Real-time Monitoring of refrigerator interior temperature to ensure drug safety. The interior temperature for the refrigerator shall be between 2 degrees Celsius and 8 degrees Celsius.Required$ - 0
76Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer Room24/7 Real-time Environmental Room Monitor providing: Room temperature, Humidity,Differential pressureRequired$ - 0
77Mechanical RoomBack-up Emergency Generator(s) with Automatic Transfer SwitchRequired$ - 0
78Mechanical RoomOn-board freshwater tank and an on-demand electric water pump to provide running water for a sink and eyewashRequired$ - 0
79Mechanical RoomGray water holding tankRequired$ - 0
80Mechanical RoomThe pharmacy cleanroom will arrive completely plumbed, ready for use via holding tanksRequired$ - 0
81Mechanical RoomHVAC system to utilize R410A refrigerantPreferred$ - 0
82Mechanical RoomAll cameras, card readers and data ports will be prewired with 400 ft of CAT6a cable. Excess cable will be bundled and exit the trailer on the front-right side of the trailer closest to the utility pedestal as shown on the site-prep design.Required$ - 0
83Utility RequirementsElectrical: 208V 3-Phase 200 AmpsRequired$ - 0
84Utility RequirementsWater: 3/4" Potable Water LineRequired$ - 0
85Utility RequirementsSewer: 3" Standard Sewer LineRequired$ - 0
86Utility RequirementsCables and conductors must be in conduits that are built for outside uses. All connections must be water proof and tightly sealed.Required$ - 0
87Services - InstallationInstallation and set-up of the Pharmacy Sterile Compounding Trailer, including connections for electrical, water, sewer and data.Required$ - 0
88Services - InstallationThe data cables shall be pulled through the utility pedestal conduit and connected to the appropriate switches in the IT closet in Building 164, Room 189.Required$ - 0
89Services - InstallationThe security camera and badge reader data cables shall be pulled through the utility pedestal conduit and connected to the appropriate switches in the security closet in Building 164, Room 137.Required$ - 0
90Services - InstallationThe vendor must perform on site utility connections.Required$ - 0
91Services - Annual MaintenanceFull maintenance and repair services shall be required for a period of one (1) year after the Pharmacy Sterile Compounding Trailer is fully certified and in operation with two (2) additional option years.Required$ - 0
92Services - Annual MaintenanceFor emergency calls, contractor is required to respond on-site within 3 hours, and by the next business day for non-emergency calls.Required$ - 0
93Services - Annual MaintenanceAll repairs and maintenance services shall be performed after hours or during weekends so that the impact to the Medical Center operations is minimized.Required$ - 0
94Services - MonthlyChange HVAC pre-filters.Required$ - 0
95Services - MonthlyExercise and test emergency generators in accordance with SCAQMD requirements and other federal and state requirements.Required$ - 0
96Services - MonthlyRefuel generators and fuel tank as necessary.Required$ - 0
97Services - MonthlyAdd water treatment to grey water tank. Grey water tank shall be emptied on regular basis or when it is 80% full by the contractor.Required$ - 0
98Services - QuarterlyLubricate direct drive motors on exhaust fansRequired$ - 0
99Services - QuarterlyCheck pressure on all tires of the pharmacy trailer and put in more air as necessaryRequired$ - 0
100Services - Semi AnnuallyCETA certification in compliance with USP 797 and USP 800Required$ - 0
101Services - Semi AnnuallyChange HEPA filters in ceiling diffusers for both supply and exhaust and/or returnRequired$ - 0
102Services - Semi AnnuallyChange filters in BSCs as neededRequired$ - 0
103Services - Semi AnnuallyChange HEPA filters in pass-thru windowsRequired$ - 0
104Services - Semi AnnuallyAirborne particle count for all three rooms (anteroom, non-HD buffer room, and HD buffer room)Required$ - 0
105Additonal RequirementsCETA Certification within 6 months or less is required as part of proof.Required$ - 0
106Additonal RequirementsGuarantee that product will meet USP 797 and USP 800 standards, and VHA Directives 1108.06 and 1108.12.Required$ - 0
107Additonal RequirementsInstallation of aluminum access ramp and emergency exit stairs. Access ramp to pharmacy sterile compounding trailer must have a configurable orientation to meet installation site needs and must have an alternative stairs pathway to the main entry door of the pharmacy sterile compounding trailer. One (1) set of emergency exit stairs shall be provided in case of emergency.Required$ - 0
108AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraAdditonal RequirementsFour (4) security cameras (Model AXIS Q3515-LVE Network Camera or similar) to be mounted on the external walls of the trailer at each corner, all capable of viewing the main entrance to the trailer or the emergency exit. As mentioned above, cameras to be wired with 400 ft of CAT6a cable. Upon installation, contractor to pull wires through the conduit provided at the site prep to the security closet in building 164.Required - Equivalent product acceptable$ - 0
109HirschScrambleSmartProxDS47L-SSP-TSAdditonal RequirementsTrailer main entrance to be secured via Hirsch ScrambleSmartProx Reader. Reader to be wired with 400 ft CAT6a cable. Upon installation, contractor to pull wire through the conduit provided at the site prep to the security closet in building 164.Required - Equivalent product acceptable$ - 0
110Additonal RequirementsContractor must be able to deliver and install pharmacy sterile compounding trailer within 6 months of awarding of contract.Required$ - 0
111Additonal RequirementsThe pharmacy sterile compounding trailer shall have back-up emergency power with Automatic Transfer Switch. The emergency generator(s) shall provide 100% coverage for the entire trailer and have the capacity to fully power the entire trailer for at least 72 continuous hours in case of normal power outage.Required$ - 0
112Additonal RequirementsThe trailer shall have fully functional, complete, and independent fire alarm compliant with NFPA 72 and NFPA 13 requirements respectively.Required$ - 0
113Additonal RequirementsIf required by South Coast Air Quality Management District (SCAQMD) and applicable federal, state and local regulations, obtain permit to construct and permit to operate from SCAQMD for emergency generators for the pharmacy sterile compounding trailer.Required$ - 0
Total$ - 0

2. Option 1 CLIN Brand Name Brand Name Nomenclature Manufacturer Part Number if Applicable Salient Characteristics Category Salient Characteristic Description Requirement Equivalent Brand Equivalent Nomenclature Equivalent Part Number Equivalent Description Matching Salient Characteristics and/or location of information regarding equal capability Quantity Unit Price Extended Price

1Rooms & AreasUnclassified area separating the main entrance from the anteroomPreferred$ - 0
2Rooms & AreasAnteroomRequired$ - 0
3Rooms & AreasSterile Hazardous Drug (HD) Buffer RoomRequired$ - 0
4Rooms & AreasSterile Non-Hazardous Drug (Non-HD) Buffer RoomRequired$ - 0
5Rooms & AreasSterile Hazardous Drug Storage AreaRequired$ - 0
6Rooms & AreasSelf-Supporting Modular Design inclusive of walls, roof, ceiling, flooring, lighting, electrical & filtering equipmentRequired$ - 0
7Rooms & AreasModular clean room must fit in a 57' L x8'6"L W x 13'6" H DOT approved semi-trailer Modular Clean room seismic intergrity provisions where necessaryPreferred$ - 0
8Rooms & AreasFinishes - Non-pourous and cleanable surfaces, ceilings, walls, and floors with minimal seams and crevices, able to withstand appropriate deactivation, decontamination, disinfecting and cleaning agentsRequired$ - 0
9Equipment - Unclassified AreaSoiled PPE Waste BinRequired$ - 0
10Equipment - Unclassified AreaStainless steel workstationPreferred$ - 0
11Equipment - Unclassified AreaOne (1) data drop with 4 ports (RJ 45)Required$ - 0
12Equipment - Unclassified AreaTwo (2) 120V power outlest with 2 sockets eachRequired$ - 0
13Equipment - AnteromScrub sink with eyewash station and anti-scald device positioned at least 1 meter from the sterile HD buffer room doorRequired$ - 0
14Equipment - AnteromClean Personal Protective Equipment (PPE) Storage Bin$ - 0
15Equipment - AnteromSoiled PPE Waste Bin$ - 0
16Equipment - AnteromStaff Changing Bench$ - 0
17Equipment - AnteromEnvironmental Services Cabinet$ - 0
18AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraEquipment - AnteromTwo (2) ceiling mounted surveillance cameras: AXIS M3045-V Network Camera or equivalentRequired - Equivalent product acceptable$ - 0
19Equipment - Anterom3M™ Avagard™ Hands Free Wall Dispenser$ - 0
20BakerSterilGard e3 Class II Type A2 Biological Safety Cabinet - 4'SG404Equipment - Sterile Hazardous Drug (HD) Buffer RoomTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC) spaced 1 meter apart from each other with 100% Outside Air Supply and ExhaustRequired - Equivalent product acceptable$ - 0
21Equipment - Sterile Hazardous Drug (HD) Buffer RoomInterlocking HEPA filtered Pass-Thru Chamber from AnteroomRequired - Equivalent product acceptable$ - 0
22Equipment - Sterile Hazardous Drug (HD) Buffer RoomStainless Steel WorkstationRequired - Equivalent product acceptable$ - 0
23Thermo ScientificThermo Scientific Refrigerator model TSX3005GATSX3005GAEquipment - Sterile Hazardous Drug (HD) Buffer RoomThermo Scientific Refrigerator model TSX3005GA or equivalentRequired - Equivalent product acceptable$ - 0
24Equipment - Sterile Hazardous Drug (HD) Buffer RoomSoiled PPE Waste BinRequired - Equivalent product acceptable$ - 0
25Equipment - Sterile Hazardous Drug (HD) Buffer RoomStorage Cabinet for compounded sterile hazardous drugsRequired - Equivalent product acceptable$ - 0
26Equipment - Sterile Hazardous Drug (HD) Buffer RoomMobile Solid stainless-steel shelving with lockable casters and a minimum of 4 shelvesRequired - Equivalent product acceptable$ - 0
27Equipment - Sterile Hazardous Drug (HD) Buffer RoomOne (1) data drop with 4 ports (RJ 45)Required - Equivalent product acceptable$ - 0
28Equipment - Sterile Hazardous Drug (HD) Buffer RoomThree (3) 120V power outlets with two sockets eachRequired - Equivalent product acceptable$ - 0
29Gai-TronicsClean Phone® Analog Telephone (Wall-Mount) - UL295-001WEquipment - Sterile Hazardous Drug (HD) Buffer RoomA wall mounted Clean Phone® or similar (GAI-Tronics 295-001W)Preferred - Equivalent product acceptable$ - 0
30AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraEquipment - Sterile Hazardous Drug (HD) Buffer RoomTwo (2) ceiling mounted surveillance cameras: AXIS M3045-V Network Camera or equivalentRequired - Equivalent product acceptable$ - 0
31Equipment - Sterile Hazardous Drug (HD) Buffer Room3M™ Avagard™ Hands Free Wall Dispenser (Government furnished, contractor installed)Required - Equivalent product acceptable$ - 0
32Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC)$ - 0
33Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomInterlocking HEPA Filtered Pass-Thru Chamber from Anteroom or Unclassified AreaRequired - Equivalent product acceptable$ - 0
34Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomStainless Steel WorkstationRequired - Equivalent product acceptable$ - 0
35Thermo ScientificThermo Scientific Refrigerator model TSX3005GATSX3005GAEquipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomThermo Scientific Refrigerator model TSX3005GA or equivalentRequired - Equivalent product acceptable$ - 0
36Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomNon-Hazardous Drug Storage CabinetRequired - Equivalent product acceptable$ - 0
37Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomMobile Solid stainless-steel shelving with lockable casters and a minimum of 4 shelvesRequired - Equivalent product acceptable$ - 0
38Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomOne (1) data drop with 4 ports (RJ 45)Required - Equivalent product acceptable$ - 0
39Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomThree (3) 120V power outlets with two sockets eachRequired - Equivalent product acceptable$ - 0
40Gai-TronicsClean Phone® Analog Telephone (Wall-Mount) - UL295-001WEquipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomA wall mounted Clean Phone® or similar (GAI-Tronics 295-001W)Preferred - Equivalent product acceptable$ - 0
41AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraEquipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomTwo (2) ceiling mounted surveillance cameras: AXIS M3045-V Network Camera or equivalentRequired - Equivalent product acceptable$ - 0
42Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer Room3M™ Avagard™ Hands Free Wall Dispenser (Government furnished, contractor installed)$ - 0
43Environmental ControlsAll facility & engineering controls compliant with USP 797/800 standards.Required$ - 0
44Environmental ControlsTrailer should be able to maintain appropriate internal temperature, humidity and pressure requirements while located in Long Beach, CA, which has a Mediterranean-type, coastal climate. Temperature extremes may range from 20°F – 112°F with a relative humidity up to 100%.Required$ - 0
45Environmental ControlsThe trailer must have fire alarm system that is completely independent and compliant with the NFPA requirement and has the capability to alert and automatically dial out when the fire alarm system is activated.Required$ - 0
46Environmental ControlsPhysically separated Anteroom and Sterile Hazardous Drug Buffer Room and Sterile Non-Hazardous Drug Buffer Room.Required$ - 0
47BakerSterilGard e3 Class II Type A2 Biological Safety Cabinet - 4'SG404Environmental Controls - Primary Engineering ControlsTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC) in Sterile HD Buffer Room with 100% Outside Air Supply and ExhaustRequired$ - 0
48BakerSterilGard e3 Class II Type A2 Biological Safety Cabinet - 4'SG404Environmental Controls - Primary Engineering ControlsTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC) in Sterile Non-Hazardous Buffer RoomRequired$ - 0
49Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomPositive pressure with greater than or equal to 0.02-inch Water ColumnRequired$ - 0
50Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomMinimum of 35 Air Exchanges Per Hour (ACPH) compliant with USP 797 and USP 800 and VA HVAC Design ManualRequired$ - 0
51Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomHigh Efficiency Particulate Air (HEPA) filtered supply airRequired$ - 0
52Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomHigh Efficiency Particulate Air (HEPA) filtered exhaust airRequired$ - 0
53Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomRoom temperature shall be between 15 degrees Celsius and 20 degrees CelsiusRequired$ - 0
54Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomHumidity level shall be between 30% and 60%Required$ - 0
55Environmental Controls - Secondary Engineering Controls - ISO 7 Anteroom24/7 Real-time Environmental Room Monitor providing: Room temperature, Humidity,Differential pressureRequired$ - 0
56Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomNegative pressure between 0.01-inch Water Column to 0.03-inch Water ColumnRequired$ - 0
57Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomMinimum of 35 Air Exchanges Per Hour (ACPH) compliant with USP 797 and USP 800 and VA HVAC Design ManualRequired$ - 0
58Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer Room100% Outside Supply Air (into room)Required$ - 0
59Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomHigh Efficiency Particulate Air (HEPA) filtered supply airRequired$ - 0
60Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomZero recirculation of HD Buffer Room airRequired$ - 0
61Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomEach compounding hood has a dedicated external exhaust that is HEPA-filtered directly to outsidemRequired$ - 0
62Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomBuffer room has a dedicated and HEPA-filtered external exhaust that is 100% of air exhausted directly to outsideRequired$ - 0
63Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomRoom temperature shall be between 15 degrees Celsius and 20 degrees CelsiusRequired$ - 0
64Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomHumidity level shall be between 30% and 60%Required$ - 0
65Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer Room24/7 Real-time Monitoring Refrigerator interior temperature to ensure drug safety. The interior temperature for the refrigerator shall be between 2 degrees Celsius and 8 degrees Celsius.Required$ - 0
66Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer Room24/7 Real-time Environmental Room Monitor providing: Room temperature, Humidity,Differential pressureRequired$ - 0
67Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomPositive pressure with greater than or equal to 0.02-inch Water ColumnRequired$ - 0
68Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomMinimum of 35 Air Exchanges Per Hour (ACPH) compliant with USP 797 and USP 800 and VA HVAC Design ManualRequired$ - 0
69Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer Room100% Outside Supply Air (into room)Required$ - 0
70Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomHigh Efficiency Particulate Air (HEPA) filtered supply airRequired$ - 0
71Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomBuffer room has High Efficiency Particulate Air (HEPA) filtered exhaust/return airRequired$ - 0
72Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomEach compounding hood has built-in HEPA filter.Required$ - 0
73Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomRoom temperature shall be between 15 degrees Celsius and 20 degrees CelsiusRequired$ - 0
74Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer RoomHumidity level shall be between 30% and 60%Required$ - 0
75Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer Room24/7 Real-time Monitoring of refrigerator interior temperature to ensure drug safety. The interior temperature for the refrigerator shall be between 2 degrees Celsius and 8 degrees Celsius.Required$ - 0
76Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile Non-HD Buffer Room24/7 Real-time Environmental Room Monitor providing: Room temperature, Humidity,Differential pressureRequired$ - 0
77Mechanical RoomBack-up Emergency Generator(s) with Automatic Transfer SwitchRequired$ - 0
78Mechanical RoomOn-board freshwater tank and an on-demand electric water pump to provide running water for a sink and eyewashRequired$ - 0
79Mechanical RoomGray water holding tankRequired$ - 0
80Mechanical RoomThe pharmacy cleanroom will arrive completely plumbed, ready for use via holding tanksRequired$ - 0
81Mechanical RoomHVAC system to utilize R410A refrigerantPreferred$ - 0
82Mechanical RoomAll cameras, card readers and data ports will be prewired with 400 ft of CAT6a cable. Excess cable will be bundled and exit the trailer on the front-right side of the trailer closest to the utility pedestal as shown on the site-prep design.Required$ - 0
83Utility RequirementsElectrical: 208V 3-Phase 200 AmpsRequired$ - 0
84Utility RequirementsWater: 3/4" Potable Water LineRequired$ - 0
85Utility RequirementsSewer: 3" Standard Sewer LineRequired$ - 0
86Utility RequirementsCables and conductors must be in conduits that are built for outside uses. All connections must be water proof and tightly sealed.Required$ - 0
87Services - InstallationInstallation and set-up of the Pharmacy Sterile Compounding Trailer, including connections for electrical, water, sewer and data.Required$ - 0
88Services - InstallationThe data cables shall be pulled through the utility pedestal conduit and connected to the appropriate switches in the IT closet in Building 164, Room 189.Required$ - 0
89Services - InstallationThe security camera and badge reader data cables shall be pulled through the utility pedestal conduit and connected to the appropriate switches in the security closet in Building 164, Room 137.Required$ - 0
90Services - InstallationThe vendor must perform on site utility connections.Required$ - 0
91Services - Annual MaintenanceFull maintenance and repair services shall be required for a period of one (1) year after the Pharmacy Sterile Compounding Trailer is fully certified and in operation with two (2) additional option years.Required$ - 0
92Services - Annual MaintenanceFor emergency calls, contractor is required to respond on-site within 3 hours, and by the next business day for non-emergency calls.Required$ - 0
93Services - Annual MaintenanceAll repairs and maintenance services shall be performed after hours or during weekends so that the impact to the Medical Center operations is minimized.Required$ - 0
94Services - MonthlyChange HVAC pre-filters.Required$ - 0
95Services - MonthlyExercise and test emergency generators in accordance with SCAQMD requirements and other federal and state requirements.Required$ - 0
96Services - MonthlyRefuel generators and fuel tank as necessary.Required$ - 0
97Services - MonthlyAdd water treatment to grey water tank. Grey water tank shall be emptied on regular basis or when it is 80% full by the contractor.Required$ - 0
98Services - QuarterlyLubricate direct drive motors on exhaust fansRequired$ - 0
99Services - QuarterlyCheck pressure on all tires of the pharmacy trailer and put in more air as necessaryRequired$ - 0
100Services - Semi AnnuallyCETA certification in compliance with USP 797 and USP 800Required$ - 0
101Services - Semi AnnuallyChange HEPA filters in ceiling diffusers for both supply and exhaust and/or returnRequired$ - 0
102Services - Semi AnnuallyChange filters in BSCs as neededRequired$ - 0
103Services - Semi AnnuallyChange HEPA filters in pass-thru windowsRequired$ - 0
104Services - Semi AnnuallyAirborne particle count for all three rooms (anteroom, non-HD buffer room, and HD buffer room)Required$ - 0
105Additonal RequirementsCETA Certification within 6 months or less is required as part of proof.Required$ - 0
106Additonal RequirementsGuarantee that product will meet USP 797 and USP 800 standards, and VHA Directives 1108.06 and 1108.12.Required$ - 0
107Additonal RequirementsInstallation of aluminum access ramp and emergency exit stairs. Access ramp to pharmacy sterile compounding trailer must have a configurable orientation to meet installation site needs and must have an alternative stairs pathway to the main entry door of the pharmacy sterile compounding trailer. One (1) set of emergency exit stairs shall be provided in case of emergency.Required$ - 0
108AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraAdditonal RequirementsFour (4) security cameras (Model AXIS Q3515-LVE Network Camera or similar) to be mounted on the external walls of the trailer at each corner, all capable of viewing the main entrance to the trailer or the emergency exit. As mentioned above, cameras to be wired with 400 ft of CAT6a cable. Upon installation, contractor to pull wires through the conduit provided at the site prep to the security closet in building 164.Required - Equivalent product acceptable$ - 0
109HirschScrambleSmartProxDS47L-SSP-TSAdditonal RequirementsTrailer main entrance to be secured via Hirsch ScrambleSmartProx Reader. Reader to be wired with 400 ft CAT6a cable. Upon installation, contractor to pull wire through the conduit provided at the site prep to the security closet in building 164.Required - Equivalent product acceptable$ - 0
110Additonal RequirementsContractor must be able to deliver and install pharmacy sterile compounding trailer within 6 months of awarding of contract.Required$ - 0
111Additonal RequirementsThe pharmacy sterile compounding trailer shall have back-up emergency power with Automatic Transfer Switch. The emergency generator(s) shall provide 100% coverage for the entire trailer and have the capacity to fully power the entire trailer for at least 72 continuous hours in case of normal power outage.Required$ - 0
112Additonal RequirementsThe trailer shall have fully functional, complete, and independent fire alarm compliant with NFPA 72 and NFPA 13 requirements respectively.Required$ - 0
113Additonal RequirementsIf required by South Coast Air Quality Management District (SCAQMD) and applicable federal, state and local regulations, obtain permit to construct and permit to operate from SCAQMD for emergency generators for the pharmacy sterile compounding trailer.Required$ - 0
Total$ - 0

3. Option 2 CLIN Brand Name Brand Name Nomenclature Manufacturer Part Number if Applicable Salient Characteristics Category Salient Characteristic Description Requirement Equivalent Brand Equivalent Nomenclature Equivalent Part Number Equivalent Description Matching Salient Characteristics and/or location of information regarding equal capability Quantity Unit Price Extended Price

1Rooms & AreasUnclassified area separating the main entrance from the anteroomPreferred$ - 0
2Rooms & AreasAnteroomRequired$ - 0
3Rooms & AreasSterile Hazardous Drug (HD) Buffer RoomRequired$ - 0
4Rooms & AreasSterile Non-Hazardous Drug (Non-HD) Buffer RoomRequired$ - 0
5Rooms & AreasSterile Hazardous Drug Storage AreaRequired$ - 0
6Rooms & AreasSelf-Supporting Modular Design inclusive of walls, roof, ceiling, flooring, lighting, electrical & filtering equipmentRequired$ - 0
7Rooms & AreasModular clean room must fit in a 57' L x8'6"L W x 13'6" H DOT approved semi-trailer Modular Clean room seismic intergrity provisions where necessaryPreferred$ - 0
8Rooms & AreasFinishes - Non-pourous and cleanable surfaces, ceilings, walls, and floors with minimal seams and crevices, able to withstand appropriate deactivation, decontamination, disinfecting and cleaning agentsRequired$ - 0
9Equipment - Unclassified AreaSoiled PPE Waste BinRequired$ - 0
10Equipment - Unclassified AreaStainless steel workstationPreferred$ - 0
11Equipment - Unclassified AreaOne (1) data drop with 4 ports (RJ 45)Required$ - 0
12Equipment - Unclassified AreaTwo (2) 120V power outlest with 2 sockets eachRequired$ - 0
13Equipment - AnteromScrub sink with eyewash station and anti-scald device positioned at least 1 meter from the sterile HD buffer room doorRequired$ - 0
14Equipment - AnteromClean Personal Protective Equipment (PPE) Storage Bin$ - 0
15Equipment - AnteromSoiled PPE Waste Bin$ - 0
16Equipment - AnteromStaff Changing Bench$ - 0
17Equipment - AnteromEnvironmental Services Cabinet$ - 0
18AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraEquipment - AnteromTwo (2) ceiling mounted surveillance cameras: AXIS M3045-V Network Camera or equivalentRequired - Equivalent product acceptable$ - 0
19Equipment - Anterom3M™ Avagard™ Hands Free Wall Dispenser$ - 0
20BakerSterilGard e3 Class II Type A2 Biological Safety Cabinet - 4'SG404Equipment - Sterile Hazardous Drug (HD) Buffer RoomTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC) spaced 1 meter apart from each other with 100% Outside Air Supply and ExhaustRequired - Equivalent product acceptable$ - 0
21Equipment - Sterile Hazardous Drug (HD) Buffer RoomInterlocking HEPA filtered Pass-Thru Chamber from AnteroomRequired - Equivalent product acceptable$ - 0
22Equipment - Sterile Hazardous Drug (HD) Buffer RoomStainless Steel WorkstationRequired - Equivalent product acceptable$ - 0
23Thermo ScientificThermo Scientific Refrigerator model TSX3005GATSX3005GAEquipment - Sterile Hazardous Drug (HD) Buffer RoomThermo Scientific Refrigerator model TSX3005GA or equivalentRequired - Equivalent product acceptable$ - 0
24Equipment - Sterile Hazardous Drug (HD) Buffer RoomSoiled PPE Waste BinRequired - Equivalent product acceptable$ - 0
25Equipment - Sterile Hazardous Drug (HD) Buffer RoomStorage Cabinet for compounded sterile hazardous drugsRequired - Equivalent product acceptable$ - 0
26Equipment - Sterile Hazardous Drug (HD) Buffer RoomMobile Solid stainless-steel shelving with lockable casters and a minimum of 4 shelvesRequired - Equivalent product acceptable$ - 0
27Equipment - Sterile Hazardous Drug (HD) Buffer RoomOne (1) data drop with 4 ports (RJ 45)Required - Equivalent product acceptable$ - 0
28Equipment - Sterile Hazardous Drug (HD) Buffer RoomThree (3) 120V power outlets with two sockets eachRequired - Equivalent product acceptable$ - 0
29Gai-TronicsClean Phone® Analog Telephone (Wall-Mount) - UL295-001WEquipment - Sterile Hazardous Drug (HD) Buffer RoomA wall mounted Clean Phone® or similar (GAI-Tronics 295-001W)Preferred - Equivalent product acceptable$ - 0
30AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraEquipment - Sterile Hazardous Drug (HD) Buffer RoomTwo (2) ceiling mounted surveillance cameras: AXIS M3045-V Network Camera or equivalentRequired - Equivalent product acceptable$ - 0
31Equipment - Sterile Hazardous Drug (HD) Buffer Room3M™ Avagard™ Hands Free Wall Dispenser (Government furnished, contractor installed)Required - Equivalent product acceptable$ - 0
32Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC)$ - 0
33Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomInterlocking HEPA Filtered Pass-Thru Chamber from Anteroom or Unclassified AreaRequired - Equivalent product acceptable$ - 0
34Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomStainless Steel WorkstationRequired - Equivalent product acceptable$ - 0
35Thermo ScientificThermo Scientific Refrigerator model TSX3005GATSX3005GAEquipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomThermo Scientific Refrigerator model TSX3005GA or equivalentRequired - Equivalent product acceptable$ - 0
36Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomNon-Hazardous Drug Storage CabinetRequired - Equivalent product acceptable$ - 0
37Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomMobile Solid stainless-steel shelving with lockable casters and a minimum of 4 shelvesRequired - Equivalent product acceptable$ - 0
38Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomOne (1) data drop with 4 ports (RJ 45)Required - Equivalent product acceptable$ - 0
39Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomThree (3) 120V power outlets with two sockets eachRequired - Equivalent product acceptable$ - 0
40Gai-TronicsClean Phone® Analog Telephone (Wall-Mount) - UL295-001WEquipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomA wall mounted Clean Phone® or similar (GAI-Tronics 295-001W)Preferred - Equivalent product acceptable$ - 0
41AXISAXIS M3045-V Network CameraAXIS M3045-V Network CameraEquipment - Sterile Non-Hazardous Drug (Non-HD) Buffer RoomTwo (2) ceiling mounted surveillance cameras: AXIS M3045-V Network Camera or equivalentRequired - Equivalent product acceptable$ - 0
42Equipment - Sterile Non-Hazardous Drug (Non-HD) Buffer Room3M™ Avagard™ Hands Free Wall Dispenser (Government furnished, contractor installed)$ - 0
43Environmental ControlsAll facility & engineering controls compliant with USP 797/800 standards.Required$ - 0
44Environmental ControlsTrailer should be able to maintain appropriate internal temperature, humidity and pressure requirements while located in Long Beach, CA, which has a Mediterranean-type, coastal climate. Temperature extremes may range from 20°F – 112°F with a relative humidity up to 100%.Required$ - 0
45Environmental ControlsThe trailer must have fire alarm system that is completely independent and compliant with the NFPA requirement and has the capability to alert and automatically dial out when the fire alarm system is activated.Required$ - 0
46Environmental ControlsPhysically separated Anteroom and Sterile Hazardous Drug Buffer Room and Sterile Non-Hazardous Drug Buffer Room.Required$ - 0
47BakerSterilGard e3 Class II Type A2 Biological Safety Cabinet - 4'SG404Environmental Controls - Primary Engineering ControlsTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC) in Sterile HD Buffer Room with 100% Outside Air Supply and ExhaustRequired$ - 0
48BakerSterilGard e3 Class II Type A2 Biological Safety Cabinet - 4'SG404Environmental Controls - Primary Engineering ControlsTwo (2) ISO 5 Class II Type A2 Biological Safety Cabinets (BSC) in Sterile Non-Hazardous Buffer RoomRequired$ - 0
49Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomPositive pressure with greater than or equal to 0.02-inch Water ColumnRequired$ - 0
50Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomMinimum of 35 Air Exchanges Per Hour (ACPH) compliant with USP 797 and USP 800 and VA HVAC Design ManualRequired$ - 0
51Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomHigh Efficiency Particulate Air (HEPA) filtered supply airRequired$ - 0
52Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomHigh Efficiency Particulate Air (HEPA) filtered exhaust airRequired$ - 0
53Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomRoom temperature shall be between 15 degrees Celsius and 20 degrees CelsiusRequired$ - 0
54Environmental Controls - Secondary Engineering Controls - ISO 7 AnteroomHumidity level shall be between 30% and 60%Required$ - 0
55Environmental Controls - Secondary Engineering Controls - ISO 7 Anteroom24/7 Real-time Environmental Room Monitor providing: Room temperature, Humidity,Differential pressureRequired$ - 0
56Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomNegative pressure between 0.01-inch Water Column to 0.03-inch Water ColumnRequired$ - 0
57Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomMinimum of 35 Air Exchanges Per Hour (ACPH) compliant with USP 797 and USP 800 and VA HVAC Design ManualRequired$ - 0
58Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer Room100% Outside Supply Air (into room)Required$ - 0
59Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomHigh Efficiency Particulate Air (HEPA) filtered supply airRequired$ - 0
60Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomZero recirculation of HD Buffer Room airRequired$ - 0
61Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomEach compounding hood has a dedicated external exhaust that is HEPA-filtered directly to outsidemRequired$ - 0
62Environmental Controls - Secondary Engineering Controls - ISO 7 Sterile HD Buffer RoomBuffer room has a dedicated and HEPA-filtered external exhaust that is 100% of air exhausted directly to outsideRequired$ - 0